M E D I U M VO LTAG E P R O D U C T S

KEVA C
Indoor voltage sensors
2 K E VA C I N D O O R V O LTA G E S E N S O R S

— UP
01 Resistive divider Parameters for Application Value
principle
Rated primary voltage of up to 24 kV
— application
02 IED and sensor
R2
Sensor Parameters Value Us = Up
Rated primary voltage, Upn 22/√3 kV R1 + R2
Highest voltage for equipment, Um 24 kV

Rated power frequency withstand 50 kV


voltage US
Rated lightning impulse withstand 125 kV
voltage —
01
Rated transformation ratio, K n 10 000:1
for voltage measurement
Voltage accuracy class 0.5/3P In all cases, the transmitted output signal repro-
duces the actual waveform of the primary voltage
Length of cable 2.5; 5; 8; 10 m
signal.

Sensor principles
Protection and control IEDs (Intelligent Elec-
Electronic Instrument Transformers (Sensors) of-
tronic Devices)
fer an alternative way of making the voltage mea-
Protection and control IEDs incorporate the func-
surement needed for the protection and monitor-
tions of a traditional relay, as well as allow new
ing of medium voltage power systems. Sensors
additional functions. The information transmit-
based on alternative principles have been intro-
ted from the sensors to the IED is very accurate,
duced as successors to conventional instrument
providing the possibility of versatile relay func-
transformers in order to significantly reduce size,
tionality.
increase safety, and to provide greater rating
standardization and a wider functionality range. However, the IED must be able to operate with
These well known principles can only be fully uti- sufficient accuracy at a sensor’s low input signal
lized in combination with versatile electronic re- level. Modern IEDs (such as ABB’s 615 series re-
lays. lays) are designed for such sensor use.

Modern digital apparatuses (microprocessor


Sensor characteristics based relays) allow protection and measurement
Construction of ABB’s voltage sensors is done functions to be combined. They fully support volt-
without the use of a ferromagnetic core. This fact age sensing realized by the single sensor with
results in several important benefits for the user double the accuracy class designation (e.g.: volt-
and the application. age sensing with combined accuracy class
0.5/3P).
The main benefit is that the behavior of the sen-
sor is not influenced by non-linearity and width of
hysteresis curve, which results in a highly accu-
rate and linear response over a wide dynamic
range of measured quantities. A linear and highly
accurate sensor characteristic in the full operat-
ing range enables the combination of metering
and protection classes in one device.

Voltage sensor —
02
Voltage measurement in KEVA C sensors is based
on the resistive divider principle. The output volt-
age is directly proportional to the input voltage:
3


03 KEVA C application Sensor applications Sensor variants
The voltage sensors type KEVA C are intended for
use in voltage measurement in gas insulated me- Sensor type Metal coated Picture
designation (conductive
dium voltage switchgear. The voltage sensors are surface)
designed as easy replacement of originally used
insulating plugs in the cable connectors. Due to
their compact size and optimized design sensors KEVA 24 Cxy
can be used for retrofit purposes as well as in new
installations.

KEVA 24 Cxyc

Tab. 1. Sensor design variants (with and without conductive surface)

Note: Voltage sensor KEVA 24 C30 is available


only in sensor design variant without conductive
surface.


03

Sensor type Cable connectors


designation Manufacturer Type Connecting screw for sensor
400 TB/G, K400 TB/G
440 TB/G, K440 TB/G
400 PB/G, K400 PB/G
Nexans-Euromold 400 PB-xSA (for x= up to 24kV)
400 BE/G-E, K400 BE/G-E
944 TB/G, K944 TB/G
KEVA 24 C10 400 TE/G, K400 TE/G
M16
KEVA 24 C10c Cellpack CTS-S 630A
FMCTs-400
FMCTs-400/1250 (C/D)
Prysmian
FMCTXs-630/C
MSCT/EC-630-C
SEHDT 13, 23
Südkabel
MUT 33
CSE-A 12630, CSE-A 24630
KEVA 24 C21 CSEP-A 12630, CSEP-A 24630
ABB Kabeldon M16
KEVA 24 C21c SOC 630 (older)
CSAP-A 6/12/24 kV
CB 12-630, CB 24-630
CC 12-630, CC 24-630
NKT CBC 40,5 630 (max for 24 kV)
KEVA 24 C22
CSA M12, CSA M16 M12
KEVA 24 C22c
CB 36-400 (for max 24 kV)
RSTI L56xx
TE connectivity
RSTI-CC L56xx
RSTI 58xx/39xx
TE connectivity RSTI-CC 58xx/39xx
RSTI LCxx/LAxx (older) M16
KEVA 24 C23 (For use in NKT connectors with
CB 12-630, CB 24-630
KEVA 24 C23c M16 screw shall be used the 
CC 12-630, CC 24-630 correct screw)
NKT
CBC 40,5 630 (max for 24 kV)
CSA M12, CSA M16
4 K E VA C I N D O O R V O LTA G E S E N S O R S


04 Combined accuracy Sensor type Cable connectors
class designation Manufacturer Type Connecting screw for sensor
430 TB/G, K430 TB/G
Nexans-Euromold 300 PBM/G-630A, K300 PBM/G-630A
KEVA 24 C24
300 SA M16
KEVA 24 C24c
FMCEAs 630/400
Prysmian
MSCEA/EC-630-C
CTS 630A 24kV
KEVA 24 C25
Cellpack CTKS 630A 24 kV M16
KEVA 24 C25c
CTKSA
SET 12, 24, SAT 12,24
SEHDK 13.1, 23.1, SAK 12,24
KEVA 24 C26
Südkabel SEHDT 23.1 M16
KEVA 24 C26c
MUT 23, MUT 23.1
AD 23.1 SP
KEVA 24 C30 TE connectivity RICS 51x3, 51x9, 51x7 M16

Tab. 2. Sensor variants and use in cable connectors

Note: For use in alternative cable connectors please contact ABB.

Differences between Sensors and Instrument Rated parameters


Transformers Because the sensors are highly linear within a very
There are some noticeable differences between wide range of voltages, the same single sensor
Sensors and conventional Instrument Transform- can be used for the va­r ious rated voltages associ-
ers: ated with each specific application up to the
specified maximum voltage for equipment. There
Linearity
is no need to specify other parameters such as
Due to the absence of a ferromagnetic core the
burden etc. since they are standard over the de-
sensor has a linear response over a very wide pri-
fined range. To achieve the correct function of the
mary voltage range.
protection and control IED, the selected rated
Example of voltage measurement range for me- voltage as well as the rated transformation ratio,
tering accuracy class 0.5 and protection accuracy must be properly set into the IED.
class 3P:
Correction factors
The accuracy limits are described on the graph
The amplitude and phase error of a voltage sen-
below.
sor is, in practice, constant and independent of
the primary voltage. Due to this fact it is an inher-
ε[%]
+6% ent and constant property of each sensor and it is
not considered as unpredictable and influenced
+3%
Protection accuracy limit class 3P
error. Hence, it can be easily corrected in the IED
by using appropriate correction factors, stated
Metering accuracy limit class 0.5
+0.5% se­parately for every sensor.
Sensor linear characteristic

Values of the correction factors for the amplitude


0.02*Upn 0.8*Upn Upn 1.2*Upn 1.9*Upn Up


and phase error of a voltage sensor are men-
-0.5%
tioned on the sensor label (for more information
-3% please refer to Instructions for installation, use
and maintenance) and should be uploaded with-
-6% out any modification into the IED before the sen-
sors are put into operation (please check avail-

04 able correction in the IED manual). To achieve
required accuracy classes it is recommended to
use both correction factors (Cfs): amplitude cor-
rection factor (aU) and phase error correction
factor (pU) of a voltage sensor.
5


05 Example of a sensor Standards
label
• IEC 60044-7 (1999-12) Instrument transformers
— - Part 7: Electronic voltage transformers
06 Connector RJ-45

Highest voltage for equipment and test voltages


• Highest voltage for equipment, Um: 24 kV
• Rated power frequency test voltage: 50 kV
• Rated lightning impulse test voltage: 125 kV

Voltage sensor, rated values


• Rated primary voltage, Upn: 22/√3 kV
• Rated frequency, fr: 50/60 Hz
• Accuracy class: 0.5/3P
• Rated burden, Rbr: 10 MΩ
• Rated transformation ratio, Kn: 10 000:1
— • Rated voltage factor, ku: 1.9/8h
05

Temperature category
Secondary cables • Operation: -25°C/+80°C
The sensor is equipped with a cable for connec- • Transport and storage: -40°C/+80°C
tion with the IED. The cable connector is type
RJ-45. The sensor accuracy classes are verified up
Cable
to the connector, i.e. considering also its second-
• Length: 2.2; 5; 8; 10 m
ary cable. These cables are intended to be con-
• Connector: RJ-45 (CAT-6)
nected directly to the IED, and subsequently nei-
• Grounding wire length: 0.5 m
ther burden calculation nor secondary wiring is
needed. Every sensor is therefore accuracy tested
when equipped with its own cable and connector.


06

Connector adapters
To provide connectivity between a sensor with a
RJ-45 cable connector and IEDs with Twin-BNC
connectors a group of adapters were designed.
To provide connectivity between current and volt-
age sensors with RJ-45 cable connectors and
IEDs with RJ-45 connector the coupling adapter
was designed.

The use of connector or coupling adapters has no


influence on the current and/or voltage signal and
accuracy of the sensor with the cable.

For more information about connector adapters


and coupling adapter refer to Doc. No.
1VLC000710 - Sensor accessories.
6 K E VA C I N D O O R V O LTA G E S E N S O R S

Sensor type Secondary cable length


designation 2.2 m 5m 10 m 8m
KEVA 24 C10 1VL5400061V0101 1VL5400061V0103 1VL5400061V0102 1VL5400061V0104
KEVA 24 C10c 1VL5400061V0201 1VL5400061V0203 1VL5400061V0202 1VL5400061V0204
KEVA 24 C21 1VL5400062V0101 1VL5400062V0103 1VL5400062V0102 1VL5400062V0104
KEVA 24 C21c 1VL5400062V0201 1VL5400062V0203 1VL5400062V0202 1VL5400062V0204
KEVA 24 C22 1VL5400063V0101 1VL5400063V0103 1VL5400063V0102 1VL5400063V0104
KEVA 24 C22c 1VL5400063V0201 1VL5400063V0203 1VL5400063V0202 1VL5400063V0204
KEVA 24 C23 1VL5400064V0101 1VL5400064V0103 1VL5400064V0102 1VL5400064V0104
KEVA 24 C23c 1VL5400064V0201 1VL5400064V0203 1VL5400064V0202 1VL5400064V0204
KEVA 24 C24 1VL5400078V0101 1VL5400078V0103 1VL5400078V0102 1VL5400078V0104
KEVA 24 C24c 1VL5400078V0201 1VL5400078V0203 1VL5400078V0202 1VL5400078V0204
KEVA 24 C25 1VL5400079V0101 1VL5400079V0103 1VL5400079V0102 1VL5400079V0104
KEVA 24 C25c 1VL5400079V0201 1VL5400079V0203 1VL5400079V0202 1VL5400079V0204
KEVA 24 C26 1VL5400080V0101 1VL5400080V0103 1VL5400080V0102 1VL5400080V0104
KEVA 24 C26c 1VL5400080V0201 1VL5400080V0203 1VL5400080V0202 1VL5400080V0204
KEVA 24 C30 1VL5400081V0101 1VL5400081V0103 1VL5400081V0102 1VL5400081V0104

with M16-M12 adapter


KEVA 24 C23 1VL5400064V0301 1VL5400064V0303 1VL5400064V0302 1VL5400064V0304
KEVA 24 C23c 1VL5400064V0401 1VL5400064V0403 1VL5400064V0402 1VL5400064V0404

Tab. 3. Ordering numbers by sensor type and cable length


7

Dimensional Drawings

— Outline drawing numbers:


KEVA 24 C10(c) 2RKA015654A0001 (KEVA 24 C10)
2RKA015654A0002 (KEVA 24 C10c)
Weight: 0.85 kg
8 K E VA C I N D O O R V O LTA G E S E N S O R S

— Outline drawing numbers:


KEVA 24 C21(c) 2RKA017064A0001 (KEVA 24 C21)
2RKA017064A0002 (KEVA 24 C21c)
Weight: 0.85 kg
9

— Outline drawing numbers:


2RKA017065A0001 (KEVA 24 C22)
KEVA 24 C22(c) 2RKA017065A0002 (KEVA 24 C22c)
Weight: 0.85 kg
10 K E VA C I N D O O R V O LTA G E S E N S O R S

— Outline drawing numbers:


KEVA 24 C23(c) 2RKA017066A0001 (KEVA 24 C23)
2RKA017066A0002 (KEVA 24 C23c)
Weight: 0.85 kg
11

— Outline drawing numbers:


KEVA 24 C24(c) 2RKA019520A0001 (KEVA 24 C24)
2RKA019520A0002 (KEVA 24 C24c)
Weight: 0.85 kg
12 K E VA C I N D O O R V O LTA G E S E N S O R S

— Outline drawing numbers:


KEVA 24 C25(c) 2RKA019522A0001 (KEVA 24 C25)
2RKA019522A0002 (KEVA 24 C25c)
Weight: 0.85 kg
13

— Outline drawing numbers:


KEVA 24 C26(c) 2RKA019784A0001 (KEVA 24 C26)
2RKA019784A0002 (KEVA 24 C26c)
Weight: 0.85 kg
14 K E VA C I N D O O R V O LTA G E S E N S O R S

— Outline drawing number:


KEVA 24 C30 2RKA020039A0001 (KEVA 24 C30)
Weight: 0.85 kg
— —
C O N TA C T U S NOTE We reserve all rights in this document and in
1VLC000717 Rev.6, en 2018.11.28

ABB s.r.o. We reserve the right to make technical the subject matter and illustrations con-
EPDS Brno changes or modify the contents of this docu- tained therein. Any reproduction, disclosure
Videnska 117, 619 00 Brno, ment without prior notice. With regard to to third parties or utilization of its contents -
Czech Republic purchase orders, the agreed particulars shall in whole or in parts - is forbidden without
Tel.: +420 547 152 082 prevail. ABB does not accept any responsibil- prior written consent of ABB.
+420 547 152 854 ity whatsoever for potential errors or possi-
Fax: +420 547 152 626 ble lack of information in this document. Copyright© 2018 ABB
E-mail: kontakt@cz.abb.com All rights reserved

www.abb.com