multi-function, load manager, VAF PF, energy, and dual source meters
Applications Communication
s¬ -ODBUS¬245¬2-Wires, 4800, 9600, 19200, or 38400 baud.
Electrical installation remote monitoring
s¬ Parity: Even, Odd, None, 1 stop bit if parity is Odd or Even,
s¬ Energy accounting and balancing 2 stop bits if None.
s¬ Control panels s¬ $,&¬firmware update through communication port.
s¬ Motor control centres
s¬ Power distribution boards Key features and essential measurements
s¬ Dual or Alternate source power and energy measurement s¬ True RMS, 32 samples/second
(Utility vs. Genset, Utility vs. Solar power, Utility vs. Wind s¬ Voltage, Current, and Power Factor: Average and per-phase
power or combination of any two sources) s¬ Derived neutral current
s¬ Original equipment manufacturers (OEMs) s¬ Power: Active energy (W) with the option of choosing VA or
s¬ Building management system VAR parameter (one power at a time), total and per-phase
s¬ Panel instrumentation s¬ Demand: Configurable to either W, VA, or VAR with maximum
s¬ Energy management system demand reading
s¬ PF improvement panel s¬ Integrated parameters: kWh, kVARh, or kVAh, 2 quadrant
energy, any one energy at a time
Security and data integrity s¬ Separate registers for dual source energy and Run Hrs
s¬ 0ASSWORD¬SETTINGS configurable password from 0000 to s¬ Frequency, % Load, % Unbalance (V&I)
9999 to prevent unauthorised set-up changes or resetting
s¬ Phase angle between V & A, per-phase
stored data (energy and demand).
s¬ On Hours, Run Hours, and power Interrupts
s¬ 4AMPER¬PROOF¬terminal cover with sealing provisions to
protect against tampering of input signals in dual source s¬ Revolution per minute (RPM)
meter. s¬ Total Harmonic Distortion (THD%) for Voltage and Current,
s¬ 0ROTECTION¬COVER¬no risk of dropping screws inside panel or per-phase
enclosure. Suitable for connection with ring type lugs. Protect s¬ Old registers to retrieve last cleared integrated values
against accidental contact with live terminals. (energy and Run Hrs)
s¬ #YBERSECURITY¬enable/disable COM port to protect
against possible misuse, and enhance troubleshooting and Accuracy and standards
maintenance of communication network. s¬ Tested as per IEC 62052-11 requirements
s¬ Active energy: Class 1.0 as per IEC 62053-21 and Class 0.5
Rugged constructions for industrial/commercial and as per IEC 62053-22
residential use, EMI/EMC tested as per IEC 61326-1 s¬ Reactive energy: Class 2.0 as per IEC 62053-24
%MISSION FCC Part 15/Class A/CE s¬ V, I, W, VA: ± 0.5% of reading
%LECTRO¬STATIC¬DISCHARGE IEC 61000-4-2 s¬ VAR: ± 2.0% of reading
2ADIATED¬lLED IEC 61000-4-3 s¬ Power factor: ± 0.01
s¬ Frequency: ± 0.05% for F-nominal 50/60 Hz ± 2, ± 0.2% for
&AST¬TRANSIENT IEC 61000-4-4
frequency range from 30 to 48 Hz, 52 to 58 Hz, and 62 to
)MPULSE¬WAVES IEC 61000-4-5 70 Hz
#ONDUCTED¬IMMUNITY IEC 61000-4-6 s¬ EMI/EMC tested as per IEC 61326-1
-AGNETIC¬lELD IEC 61000-4-8
6OLTAGE¬DIPS IEC 61000-4-11
3AFETY¬CONSTRUCTION Self extinguishable, V0 plastic
)NGRESS¬PROTECTION IP 51 and Rear IP 30
Conzerv EM64xxH series schneider-electric.com 2
multi-function, load manager, VAF PF, energy, and dual source meters
Model Commercial Reference Short Description RS-485 Acc VAF PF W,VA, Wh/ VAh/ % Unbalance ON/ Run Hrs Phase RPM
Reference Class VAR VARh (V&I) Pwr Intr Angle
EM6433H METSEEM6433HCL10RS EM6433H RS CL 1.0 b 1.0 A - - On Hrs, Intr - -
Only one power and energy measurement at a time, selectable through set-up mode.
© 2017 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.