INSTRUMENT TRANSFORMERS
CURRENT TRANSFORMER RATING:
PRIMARY: = 1200 A
SECONDARY: = 1A
LINE PARAMETERS
PART- PART- PART-
1 2 3
SS-A SS-B
PART-1
LENGTH= 1.5 KM
TYPE: XLPE
NO OF CONDUCTORS/PHASE: 1 x1200mm2
R= 0.02700 /
X= 0.37275 /
QCHARGING= 2.27908 MVAR
NORMAL RATING= 209 MVA
PART-2
LENGTH= 10 KM
TYPE: ACSR-CONDOR
NO OF CONDUCTORS/PHASE: 2 x402mm2
R= 0.44700 /
X= 3.12800 /
QCHARGING= 0.89661 MVAR
NORMAL RATING= 274 MVA
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670
PART-3
LENGTH= 3.5 KM
TYPE: XLPE
NO OF CONDUCTORS/PHASE: 1 x1200mm2
R= 0.06300 /
X= 0.86975 /
QCHARGING= 5.3178 MVAR
NORMAL RATING= 209 MVA
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670
TOTAL EQUIVALENT PARAMETERS
LENGTH= 15 KM
TYPE: COMPOSITE (UG+OHL)
R1= 0.53700 / (POSITIVE SEQUNCE RESISTANCE)
X1= 4.37050 / (POSITIVE SEQUNCE REACTANCE)
QCHARGING= 8.49349 MVAR
NORMAL RATING= 209 MVA (MINIMUM OF COMPOSITIONS)
ZERO SEQUENCE PARAMETERS (NOT AVAILABLE YET AND THEREFORE WILL BE ASSUME
R0= 3 x R1
R0= 1.61100 / (ASSUMED)
X0= 3 x X1
X0= 13.11150 / (ASSUMED)
GENERAL SETTINGS:
IBase = 1200 A (CORRESPONDING TO MAXIMUM RATED CT PRIMARY)
NoOfTerminals = 2 (NUMBER OF TERMINALS OF PROTECTED CIRCUIT)
Chan2IsLocal = NO (YES IF 11/2 BREAKER CONFIGURATION)
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670
AND IF IT IS DISABLED: IdMin2.5*ICHARGING
IN OUR CASE: ICHARGING = 0.03 A (IN SECONDARY)
THEREFORE WE PROPOSE:
IdMin = 0.25 IBase
IdMinHigh: SETTING USED TO TEMPORARILY DECREASE THE SENSITIVITY IN SITUATIONS WHEN:
1. LINE IS ENERGIZED, 2.FAULT CLASSIFIED AS EXTERNAL.
A SETTING OF 1.00*IBase IS MOST SUITABLE TO COVER BOTH CASES ABOVE.
THEREFORE WE PROPOSE:
IdMinHigh = 1.00 IBase
IntervIdMinHig: TIME THAT IdMinHigh IS ACTIVE. A SETTING OF 1 SECOND IS SUFFICIENT SINCE NO POWER TRANSFORMERS
ARE INCLUDED IN THIS PROTECTION ZONE.
IntervIdMinHig = 1s
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670
IdUnre: RECOMMENDED SETTING IS 120% OF THE HIGHEST THROUGH FAULT CURRENT THAT CAN APPEAR ACROSS
THE PROTECTED LINE.
HIGHEST THROUGH FAULT CURRENT= 20 kA SINCE THERE ARE TWO SIMILAR LINES.
WE PROPOSE: 120% x HIGHEST THROUGH FAULT CURRENT
= 24 kA
= 20 A (SECONDARY)
THEREFORE WE PROPOSE:
IdUnre = 20 IBase
EndSection1: DEFAULT VALUE 1.25*IBase IS RECOMMENDED BY MANUFACTURER.
EndSection1 = 1.25 IBase
EndSection2: DEFAULT VALUE 3.00*IBase IS RECOMMENDED BY MANUFACTURER.
EndSection2 = 3.00 IBase
SlopeSection2: DEFAULT VALUE 40% IS RECOMMENDED BY MANUFACTURER.
SlopeSection2 = 40.0 %
SlopeSection3: DEFAULT VALUE 80% IS RECOMMENDED BY MANUFACTURER.
SlopeSection3: = 80.0 %
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670
SETTING DIRECTIONALITY BOUNDARIES
ArgDir: SETTING FOR THE LOWER BOUNDARY OF THE FORWARD DIRECTIONAL FIGURE 1
CHARACTERISTICS, BY DEFAULT SET TO "-15 DEGREES".(REFER TO FIGURE 1)
ArgNegRes: SETTING FOR THE UPPER BOUNDARY OF THE FORWARD DIRECTIONAL
CHARACTERISTICS, BY DEFAULT SET TO "115 DEGREES".(REFER TO FIGURE 1)
ArgDir = 15 degrees
ArgNegRes = 115 degrees
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670
ZONE 3 = 100 % OF TOTAL PROTECTED LINE IMPEDANCE + 120
PARAMETERS OF NEXT LONGEST LINE ARE NOT YET AVAILABLE, THERFORE WE PROPOSE:
ZONE 3 = 200 % OF TOTAL PROTECTED LINE IMPEDANCE
X1Z3: ZONE 3 POSITIVE SEQUENCE REACTANCE REACH.
X1Z3 = 8.74 ohm/ph
R1Z3: ZONE 3 POSITIVE SEQUENCE RESISTANCE REACH.
R1Z3 = 1.07 ohm/ph
X0Z3: ZONE 3 ZERO SEQUENCE REACTANCE REACH.
X0Z3 = 26.22 ohm/ph
R0Z3: ZONE 3 ZERO SEQUENCE RESISTANCE REACH.
R0Z3 = 3.22 ohm/ph
RFPPZ3: FAULT RESISTANCE REACH FOR PHASE TO PHASE LOOP
RFPPZ3 = 26.22 ohm/loop
RFPEZ3: FAULT RESISTANCE REACH FOR PHASE TO EARTH LOOP
RFPEZ3 = 39.33 ohm/loop
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670
ZONE 4
ACTIVATION OF ZONE 4 OPERATION (ZM4)
OperationDir = Reverse
Operation PP = ON
Operation PE = ON
SETTING OF ZONE 4 FAULT REACH
ZONE 4 = 25 % OF ZONE-3 REACH (FOR CURRENT REVERSAL LOGIC IN CASE OF PERM
X1Z4: ZONE 4 POSITIVE SEQUENCE REACTANCE REACH.
X1Z4 = 2.19 ohm/ph
R1Z4: ZONE 4 POSITIVE SEQUENCE RESISTANCE REACH.
R1Z4 = 0.27 ohm/ph
X0Z4: ZONE 4 ZERO SEQUENCE REACTANCE REACH.
X0Z4 = 6.56 ohm/ph
R0Z4: ZONE 4 ZERO SEQUENCE RESISTANCE REACH.
R0Z4 = 0.81 ohm/ph
RFPPZ4: FAULT RESISTANCE REACH FOR PHASE TO PHASE LOOP
RFPPZ4 = 6.56 ohm/loop
RFPEZ4: FAULT RESISTANCE REACH FOR PHASE TO EARTH LOOP
RFPEZ4 = 9.83 ohm/loop
ZONE 5
ACTIVATION OF ZONE 5 OPERATION (ZM5)
OperationDir = Non-Directional
Operation PP = ON
Operation PE = ON
SETTING OF ZONE 5 FAULT REACH
ZONE 5 = 100 % OF PROTECTED LINE IMPEDANCE + 100
X1Z5: ZONE 5 POSITIVE SEQUENCE REACTANCE REACH.
X1Z5 = 62.45 ohm/ph
R1Z5: ZONE 5 POSITIVE SEQUENCE RESISTANCE REACH.
R1Z5 = 6.35 ohm/ph
X0Z5: ZONE 5 ZERO SEQUENCE REACTANCE REACH.
X0Z5 = 71.19 ohm/ph
R0Z5: ZONE 5 ZERO SEQUENCE RESISTANCE REACH.
R0Z5 = 7.42 ohm/ph
RFPPZ5: FAULT RESISTANCE REACH FOR PHASE TO PHASE LOOP
RFPPZ5 = 39.33 ohm/loop
RFPEZ5: FAULT RESISTANCE REACH FOR PHASE TO EARTH LOOP
RFPEZ5 = 47.20 ohm/loop
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670
RFFwPP: FAULT RESISTANCE FORWARD REACH FOR PHASE TO PHASE LOOPS
RFFwPP = 19.67 ohm/l (>=1.25 x RFPPZ2)
RFRvPP: FAULT RESISTANCE REVERSE REACH FOR PHASE TO PHASE LOOPS
RFRvPP = 19.67 ohm/l
RFFwPE: FAULT RESISTANCE FORWARD REACH FOR PHASE TO EARTH LOOPS
RFFwPE = 29.50 ohm/l (>=1.25 x RFPEZ2)
RFRvPE: FAULT RESISTANCE REVERSE REACH FOR PHASE TO EARTH LOOPS
RFRvPE = 29.50 ohm/l
IMinOpPP: MINIMUM OPERATE CURRENT FOR PHASE TO PHASE LOOPS
IMinOpPP = 20 %
IMinOpPE: MINIMUM OPERATE CURRENT FOR PHASE TO EARTH LOOPS
IMinOpPE = 10 %
TimerPP = OFF
TimerPE = OFF
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670
SETTING OF ZONES TIMERS
ZONE-1
tPP1 = 0.00 s
tPE1 = 0.00 s
ZONE-2
tPP2 = 0.30 s
tPE2 = 0.30 s
ZONE-3
tPP3 = 0.60 s
tPE3 = 0.60 s
ZONE-4 (USED FOR CURRENT REVERSAL LOGIC)
tPP4 = - s
tPE4 = - s
ZONE-5
tPP5 = 1.00 s
tPE5 = 1.00 s
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670
tW = 0.25 s
tH = 0.8 s
tEF = 3s
tR1 = 0.3 s
tR2 = 2s
IMinOpPE = 10 %
Ibase = 1200 A
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670
SETTING OF CURRENT REVERSAL LOGIC FOR DISTANCE PROTECTION
CurrRev = ON
tPickUpRev = 0.020 s
tDelayRev = 0.050 s
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670
LL BE ASSUMED)
CT PRIMARY)
TED CIRCUIT)
IdMinICHARGING ,
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670
NSATION IS ACTIVATED.
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670
URE 1
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670
% OF NEXT LONGEST LINE
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670
N CASE OF PERMISSIVE OVER REACH TRIP)
RELAY SETTINGS AND CALCULATIONS FOR 132KV LINE DIFFERENTIAL PROTECTION +DISTANCE + DEF, 87L+21+67N
RELAY: ABB RED670