You are on page 1of 1

2nd FFL

CB RATING
CKT LOAD LOAD
QTY VOLTS AMPS. WIRES/CONDUIT PANEL BOARD
NO. DESCRIPTION (VA) A.T
P KAIC

7 8W WALL MOUNTED LIGHT

35 15W SELECTED PIN LIGHT

4 8W WALL MOUNTED LAMP LIGHT


230 9.64 2 20 5 2 2 M
1 2218 2 -3.5 mm + 1 -2.0 mm Grnd in 1/2" dia. PVC
3 100W CHANDELIER
6 60W PENDANT LIGHT
1 40W TASK LIGHT
31 15W SELECTED PIN LIGHT
4 40W COVE LIGHT
2 2 GFL
2 8 8W WALL MOUNTED LAMP LIGHT 230 905 3.93 2 20 5 2 -3.5 mm + 1 -2.0 mm Grnd in 1/2" dia. PVC

2 8W WALL MOUNTED LIGHT


2 100W CHANDELIER
7.83 2 2
3 10 CONVENIENCE OUTLET 230 1800 2 20 5 2 -3.5 mm + 1 -2.0 mm Grnd in 1/2" dia. PVC
2 2
4 14 CONVENIENCE OUTLET 230 2520 10.95 2 20 5 2 -3.5 mm + 1 -2.0 mm Grnd in 1/2" dia. PVC
2 2
5 10 CONVENIENCE OUTLET 230 1800 7.83 2 20 5 2 -3.5 mm + 1 -2.0 mm Grnd in 1/2" dia. PVC
2 2
6 7 CONVENIENCE OUTLET 230 1260 5.48 2 20 5 2 -3.5 mm + 1 -2.0 mm Grnd in 1/2" dia. PVC
2 2
7 1 ACU (1 HP) 230 1840 8 2 20 5 2 -3.5 mm + 1 -2.0 mm Grnd in 1/2" dia. PVC
2 2
8 1 ACU (1.5 HP) 230 2300 10 2 30 5 2 -5.5 mm + 1 -3.5 mm Grnd in 3/4" dia. PVC
2 2
9 1 WATER HEATER 230 3200 13.91 2 30 5 2 -5.5 mm + 1 -3.5 mm Grnd in 3/4" dia. PVC
230 34.78 2 2 MCB
10 1 RANGE OUTLET 8000 2 50 5 2 -8.0 mm + 1 -5.5 mm Grnd in 1" dia. PVC

11 1 ACU (1 HP) 230 1840 8 2 20 5 2 2


2 -3.5 mm + 1 -2.0 mm Grnd in 1/2" dia. PVC
2 20 2 2 LIGHTING LIGHTING
12 1 ACU (1 HP) 230 1840 8 5 2 -3.5 mm + 1 -2.0 mm Grnd in 1/2" dia. PVC
2 2
13 1 ACU (.75 HP) 230 1587 6.9 2 20 5 2 -3.5 mm + 1 -2.0 mm Grnd in 1/2" dia. PVC
2 2
14 1 ACU (1 HP) 230 1840 8 2 20 5 2 -3.5 mm + 1 -2.0 mm Grnd in 1/2" dia. PVC C.O C.O
2 20 2 2
15 1 ACU (1 HP) 230 1840 8 5 2 -3.5 mm + 1 -2.0 mm Grnd in 1/2" dia. PVC
2 2
16 1 WATER HEATER 230 3200 13.91 2 30 5 2 -5.5 mm + 1 -2.0 mm Grnd in 3/4" dia. PVC C.O C.O
2 2
17 1 WATER HEATER 230 3200 13.91 2 30 5 2 -5.5 mm + 1 -2.0 mm Grnd in 3/4" dia. PVC
2 2
18 1 LAUNDRY WASHING MACHINE 230 1500 6.52 2 20 5 2 -5.5 mm + 1 -2.0 mm Grnd in 3/4" dia. PVC
ACU ACU
21.74 2 2
19 1 5kW LAUNDRY DRYER 230 5000 2 30 5 2 -5.5 mm + 1 -2.0 mm Grnd in 3/4" dia. PVC

20 2 SPARE 2 20
TOTAL 47690 207.33 WH RANGE

GENERAL LOADS/OTHER LOADS 23,480 @40% Demand Factor TOTAL VA = 32,002


9,392 VA
If = 139.14 + [10(HML) x 0.25] = 141.64A
ACU ACU
8000 @80% Demand Factor I = 139.14 + [10(HML) x 1.50] = 154.14A
COOKING LOAD b
6,400 VA
FEEDER SIZE:
ACU ACU
LIGHTING AND ACU LOADS 16,210 @100% Demand Factor 2 2
USE: 2-80mm THHN + 14mm THW (G) Cu wire
16,210 VA in 50mmØ IMC pipe
ACU WH
MCB SIZE:
USE: 175AT, 200AF, 2P, 22KAIC WH LAUNDRY WASHING
MACHINE

LAUNDRY DRYER SPARE

PROJECT TITLE PROJECT OWNER SHEET CONTENT DESIGNED BY : JML DRAWING NO. :

LORENO, JELLAH MAY ROBEL, RUBILYN


A PROPOSE TWO-STOREY VACATION CHECKED BY :
2
A
NEBRIDA, HARRIS
HOUSE
ARCHITECTS AR. T-JAY DENMARK CADETE DRAWN BY : JML

PRC No. LOCATION DATE : AP2021 3


TIN No.
MILO RESIDENCES
AMADEO, CAVITE
APPROVED :
PTR No. DATE PLACE
PSALM 127:1