Bo see after efter fort feecr rer UTTAR DAKSHIN HARYANA SLILI VITRAN WIGAM devi Hen a Specification No. CSC- 99/UH/DH/P&D/2015-16 TECHNICAL SPECIFICATIONS FOR M TYPE TOWER FOR 33 KV & 11 KV OVERHEAD TRANSMISSION LINE NETWORKS Issue Month: Oct. 2015 Common Specification Committee (CSC Approval dae 04.08.2015 ) UHBVN & DHBVN 10f9 see =faror Bfrerow frat forerror ferorr UTTAR DAKSMIN HARYANA SULI VITRAN NIGAM ‘SVN M TYPE TOWER FOR 33 KV & 11 KV NETWORKS. INTRODUCTION:- Single pole supports — RS joists, PSC poles and Tubular poles are use normally for 33 KV and 11 KV transmission lines. These single pole supports are provided with guys, Stays and struts at line deviation angle points, road crossing, inhabited areas so as to ensure stability of supports. The guys stays or struts occupy space. It is difficult to get Necessary corridor in urban areas and inhabited localities. The extent to which the stays are to be tightened depends on the unbalanced force (or pull) on the pole. The stay is to be erected in the proper direction and tightened optimally so as to counter the unbalanced force on the pole. It is often difficult to access this force and its direction of action. The PSC poles and RS joists are not expandable vertically. These single pole Supports cannot therefore provide necessary electrical clearances over structures, dwellings, huts and vegetation in urban and other inhabited areas. For negotiating railway crossings, and road crossings, it is obligatory to erect self supporting latticed towers. Itis in this context that the use of self supporting latticed towers has become an important option for erection of 33 KV and 11 KV lines in urban areas and at special locations. These towers are expandable vertically in four stages each 3m, 6m, 9m and 12m extensions. The towers with extensions facilitate obtain necessary clearances at railway crossings and other obligatory locations. In this manual, M type of 33 KV large angle/ dead end double circuit is described. This manual consists of designs of tower with extension and foundation thereof. The construction activities related to erection of lines are also described. Single line diagram, structural drawing and foundation drawing are also furnished in this manual. These drawings may be issued for ‘fabrication of tower parts lying of foundation and erection of tower at site’. 2 see sffror efenow for feraor ferorer UTTAR DAKSHIN HARYANA BLT VITRAN NIGAM ‘SVN M TYPES POWER ADVANTAGES ARE AS FOLLOWS:- + The M type tower is supposed to carry electrical power lines voltage exceeding of 33 KV. * The height of M type tower is supported 22m clearance above the ground level for straining of line. + The M type towers can be used for stringing of double circuit lines and provisions for street light cable crossings available. + The M type tower span (road & river crossings) can be support length exceeding 100m. ‘* These clearances have been fixed taking into consideration the overall height of vehicles and the statutory provisions of the Indian electricity rules. ‘* More feeders can be carried by the same tower 2HT, 2LT, HT/LT, HT/2LT may cross the road in the same location. + The solution reduces the no. of crossings, and also in future additional new crossing may be avoided. The span length between the towers may be increased and there is no need of intermediate pole along the road corridor. * The vertical clearance with the live line to the road corridor could accommodate additional feeder crossing on the same location 33 KV LARGE ANGLE / DEAD END DOUBLE CIRCUIT TOWER TYPE M:- The type of tower to be erected at any location depends on the angle of deviation of line. It also depends on whether the location is to negotiate a railway crowing of state of central highways. The tower extensions are designed for M type. The tower extensions are to be used to obtain the statutory electrical clearances while crossing railway tracks, highways or any structures along the route of the line The M type tower is narrow based and width or tower is chosen as 0.750m. for the purpose of designing the 33 KV double circuit towers, the characteristics of DOG ACSR are considered. 30f9 CONDUC" sea efor efenon frac feeror fret UTTAR DAKSHIN HARYANA SLILI VITRAN NIGAM iBYN M type tower is a large angle tower, which can take line deviation upto an angle of 60 degrees. This tower can also be erected as a dead end/ terminal tower. This tower is erected as a straight line cut point at obligatory locations of road crossings, railway crossings, canal crossing and locations of longer spans. The M type tower is a double circuit tower designed to be strung with DOG. ACSR or equivalent AAAC. This is narrow based tower with straight alignment. This leg member of the towers are butt jointed. There are two insulator strings for each phase conductor. Each sting consists of three 11 KV ball and socket type porcelain disc insulators. Alternatively silicon rubber insulators are also used. The hardware sets for each phase conductor consists of one strain plate(common), two D shackles or another shackles, Two ball-eyes, two socket-eyes and two tension clamps. Ground wire peak is not provided. One of the four legs of each tower is to be connected to pipe earthing provided at tower location. TOR CHARACTERISTICS:- 33 KV lines are strung with DOG ACSR or equivalent all aluminum alloy conductor. This conductor is standardized for use on all 33 KV lines in India. The important Characteristics of these conductors are indicated in the table below:- Sr. No. Characteristics DOG ACSR Equivalent AAC 1 | Conductor size and standing 64.72 #77187 Steal__| T/A. 26mm 2 | Nominal Al. Sq. mm 405 ‘Ai Eq. 100 3 ‘Area of cross section Sq. mm 118.5 . 100 4 | Overall diameter (4) mm 74.48mm 12.78 mm 5 | Weight of conductor Kg/im 0.394 0.273 6 | Modulus of Elasticity (E) kg -mm 7750 6324 i OMe Coefficient of expansion per degree C__| 19.80 x10" 23.00x10" 40f9 e see efor efenow firor® fereaor fren UTTAR DAKSHIN HARYANA BLLI VITRAN NIGAM ‘SVN Ufimate Tensile strength (UTS)Ko. | 3305 2984 ‘9 | Current carrying capacity Amps. [324 214 70 _| Resistance Ohm/km 0.278 0.339 GEOMETRY OF TOWER TYPE 33 KV DOUBLE CIRCUIT ANGLE TOWER TYPE-M:- The 33 KV Double Circuit Angle Tower type M is a narrow based tower to be erected at line derivations point with angle of deviation less than 60 Degrees and at termination point under dead end conditions. The following data and parameters are considered or determining the geometry or of the tower. Height of Tower Type “M” Tower Width = Calculated value of maximum sag at 65 degrees C and no wind Ground clearance from bottom conductor (statutory) Height of bottom cross arm from G.L. Minimum vertical spacing between two = conductors on the support (Statutory) Provision for swing of jumpers = Vertical spacing between the cross arm = Tower Top Total height of M type tower = Width of Cross Arm: Width of tower = From centre line of tower = Minimum clearance from earth/ towers body (in = closed areas like sub stations)(Statutory) Additional clearance for outdoor transmission = Provision for swig of jumpers = 50f9 0.780 m 1.720 m 5.200 m 5.200 + 1.720 6.920 m or say 7.000m 1.320m 0.180 m 1.500 M 0.300 M 7.000+1.500+1.500+0.300m 0.750 m 0.375 m 0.400 0.200 m 0.100 m r) see efor sfenow fort fererror ferorer UTTAR DAKSHIN HARYANA SULI VITRAN NIGAM ‘SVN Distance between conductor support point to = 0.100 m edge of cross arm = 1.175 m or say 1.200 m Length of cross arm from center line of tower = 1.200 m OUTLINE DIAGRAM OF 33 KV DOUBLE CIRCUIT TOWER TYPE M:- ‘The basic dimensions of tower type M as worked above are considered for preparation of outline diagram of M type tower. The outline diagram is shown in fig (1) annexed. These dimensions of towers are taken into consideration for calculation of loads on towers design of superstructure DESIGN OF 33 KV DOUBLE CIRCUIT ANGLE TOWER TYPE M- PARAMETERS CONSIDERED:- The various loading on the tower type M are calculated as per IS 802 and CBIP transmission manual. The tower is to be erected as double circuit angle tower strung with DOG ACSR The tower is designed for the deviation upto 60 degrees angle and for dead end conditions. Calculated value of wind pressure of 130 Kg / Sq. m on full protected area of tower members is considered for calculation of wind load on towers. Calculated value of wind pressure of 45 kg per Sq. m full projected area of conductor is considered for calculation of load on tower due to wind on conductor. The conductor tension at 32 degrees C and no wind is taken as 400 kgs. This value is less than 25% of UTS of DOG ACSR Calculated value of tension of the conductor at 32 degrees C and full wind is 648 kgs. Transverse component of conductor tension = 2T sin @/2 i conductor Tension = 648 Kgs. 2 Angle of deviation = 60 degrees Transverse component of tension acting at each cross arm = 2x648xsing (60/2) x648x0.5 = 648 Kgs. The M type tower is designed to be erected as dead end towers at terminal points. Longitudinal forces of 648 Kgs. Act at each of the six cross arms. 60f9 a y 2 see aftror efenow fwrorf fereror frerer UTTAR DAKSIIN HARYANA SLILI VITRAN MIGAM ‘SVN LEV * The tower is designed for critical value of transverse loads, vertical loads and longitudinal load (Under normal conditions) ‘© The loading diagram of tower type M is shown in fig. (2) annexed. Based on the loading pattern, the stresses in the tower members are worked out and suitable steel sections selected. © The M type tower is expandable by adding 3 m extensions to the first panel of the tower to gain required ground clearance over any structure/ object/ vegetation along with line alignment. © The tower design and the foundation design hold good for normal tower with 3 m extension and normal tower with 6 m extension (3m +3m extensions). However, if 9 m and 12m extension are to be erected, the following steps may be taken. a) “M" type tower may be erected as a straight line cut point. b) The span may be limited to 80m. * One of the four legs of the tower is connected to pipe earthing provided separately at the tower location. © The super structure of tower type M and 3 m extension thereof are designed as per the data/ parameters indicated above. * Single line diagrams of normal tower and 3 m extension are shown in fig. (3) annexure. Steel sections proposed for the tower parts and dimensions are indicated in the diagrams. DESIGN OF FOUNDATION OF 33 KV DOUBLE CIRCUIT ANGLE / DEAD END TOWER TYPE ‘M’ - DESIGN PARAMETERS:- The foundation of the tower is designed based on the following data and calculated values. © The four stubs of “M” type towers are extended upto first panel of the tower. This arrangement facilities laying of tower foundation without using stub template. © The Stubs are provided with clear of size 45x30x5mm section 200 mm long for each stub. * The contact resistance between cement concrete and steel = 10 kg Sq. cm. © Weight of earth (Normal day) = 1440 kg/ Cu. M © Bearing strength of earth = 25000 kg/ Sq/m © Weight of 1:2:4 mix concrete = 2000 kg/Cu. M * Angle of repose of soil = 30 degrees * Ultimate compression of GL = 92780 Kg. © Ultimate uplift at GL = 89100 Kg 70f9 Py see STRUCTURE DRAWING OF TOWER TYPE ‘M’:- The structural drawings of normal ‘M’ type tower and plus 3 m extension are shown in fig. (5) annexed. These drawings may be used for fabrication tower parts and for erection of towers. The structure drawing as shown in fig. (5) annexed. BILL OF QUANTITIES OF ‘M’ TYPE POWER:- The steel sections proposed and their quantities are worked out as per the single line diagram of tower type M. the statement of bill of quantities is furnished in annexure (A). CONSTRUCTION OF TOWER LINE FOR 33 KV AND 11 KV NETWORKS — GUIDELINES:- * New 33 KV and 11 KV lines are proposed after carrying out necessary studies on ()) load Growth (ii) Voltage profile (ii) Adequacy of existing 33 KV and 11 KV networks (jv) Location of 33/11 KV Sub Stations (existing/ planned) and (v) Availability of corridors. Technical and economic viability is also examined before selecting the route. * Survey is conducted on the proposed route alignment as detailed below: a) The proposed alignment is drawing on survey of India map. Obligatory angle location are marked and walk though is conducted, b) It may be considered that at least one angle point may be introduced for line length of ten spans. All the angle points selected above may be marked on the route map. ©) Details of ground levels along the route may be noted and tower extensions to be erected may be decided based on detailed survey. ) Nature of soil along there route may be noted. If the soil is soft, the tower grounding will be affective. Otherwise altemate arrangement is to be made. e) If canal bed or river bed locations become obligatory special river bed foundations have to be designed for towers. * The sub transmission and HV line normally pass through plain areas or undulated terrain with marginal steepness. If the lines are to cross tall structures minimum clearance of 3.700 m above the structure is to be maintained and appropriate tower extension is to be erected. * Ifthe 33 KV and 11 KV lines have to cross the railway tracks and highway only self supporting latticed type towers are to be erected. The crossing arrangements are to be planned meticulously so as to meet the statutory norms. ay UTTAR DAKSHIN HARYANA SLIT VITRAN NIGAM ‘BYN GB sex efor efferow fort recor freer Detailed proposals are to be prepared for railway crossings and necessary approvals obtained. Statutory approvals from forest. Aviation, Telecom Deptt. Etc. may also be obtained as may be required. While negotiating railway, canal or road crossings etc. route alignment may be planned so as to cross the railway tracks, highways etc. at right angle as far as. possible. Tower schedules may be prepared indicating the following details. a) Reach No : Angle Point to next angle point. b) Location No. : Tower Location No. ©) Span in meter From one location to next location d) Angle of deviation : At Angle points ©) Details of obligatory locations such as railway crossings, road crossings ete. The stubs, super structures, towers extensions may ne got fabricated as per the structural drawings. The foundations may be laid as per the foundation drawings fumished in the manual. The excavation and concrete volumes indicated in the foundation drawings may be adopted for estimate and execution purpose. The tower foundations are designed for normal tower, plus 3 m extension and plus 6 m extension. However if 9 m and 12 m extensions are to be erected the span may be limited to 80m and the angle towers may be erected the span may be limited to 80 m and the angle towers may be erected as straight line cut points. Towers may be erected as per structural drawings. It is considered appropriate to se disc insulators in suspension strings. However if pin insulators are to be used, necessary space may be got provided on the cross arm main members at the time of fabrication of towers. Ys. ‘SE/P&D, DHBVN Cum-member Secretary CSC, UHBVN/DHBVN 90f9 4 panel and S* Panels 6" Panel and 7” Panels Cage ASNASXS 43.000 3.400 40.800 45x30x5 32x1.061 2.800 26,832 || Cross arm Main Members 45x45x5 12x0.906 3.400 36.965 Tie Members 45x30x5 12x0.955 2.800. 32,088 Belt Members 45x45x5 12x0.750 3.400 30,600 Plan Bracings 45x30x5 12x1,061 2.800 12,732 Tower Top ‘A5x4 5x5 4x0.300 3.400 4.080 45x30x5 4x0.750 2.800 8.400 Total 962.177 Bolts & Nuts, Gussets 38.500 plates and cleats (4%) Grand Total ee or say 1000 kg BILL OF QUANTITIES OF 3 M EXTENSION Details Steel Sections | Qtyand Length (MM) | Unit Weight Total | Proposed (mm) Weight 3M Extension Leg 100x100x8 413.000 32,100 [ 145.200 Member, 2ax.250 3.400 | __102.000 acre ae 247.200 Total ae Bolts & Nuts, Gussets plates and cleats (4%) Total weight of 3m Extension _L FIG - 1 ‘ALL DIMENSIONS ARE IN METERS G.L. GROUND LEVEL C.L. CONCRETE LEVEL Drawing No. Win Yeannad hv Cam@ranner ~~ ALL’ LOADS ARE IN KGS. ALL DIMENSIONS ARE IN METERS. teannad hv CamGrannor a it | ab k LT 'S= if a ee pete a FIG-3 ‘STEEL SECTIONS FOR LEG MEMBERS AND BRACING ARE INDICATED IN THE DRAWING. ‘CROSS-ARM MAIN MEMBERS AND BELT MEMBERS ARE 45 X 45 X 5 MM, OTHER MEMBERS OF CROSS - ARMS ARE 45 X 30X 5M. ALL SECTIONS ARE IN MM. ‘8 NOSS 16MM @ BOLTS AND NUTS DOUBLE SHEAR FOR FRST PANEL, 2M AND 6M EXTENSIONS, ‘8NOS 16MM @ BOLTS AND NUTS DOUBLE SHEAR FOR SECOND AND THIRD PANES, ‘6NOS 16MM @ BOLTS AND NUTS DOUBLE SHEAR FOR FOURTH TO SEVENTH PANELS, 4.NOS 164M @ BOLTS AND NUTS DOUBLE SHEAR FOR CAGE. ALL DIAGONALS SHALL HAVE SINGLE BOLT CONNECTIONS. "ALL LEG MEMBERS ARE BUTFIONTED. ALL DIMENSIONS ARE IN METERS. FOUNDATION IS DESIGNED FOR NORMAL TOWER, PLUS 3M AND 6M EXTENSIONS. ‘STUBS EXTENDED UPTO FIRST PANEL. SECTION : 110X 110X 10MM. DIAGONAL BRACINGS OF FIRST PANEL : 45 X 45 X 5 MM. DLEATS WELDED TO STUBS AT BOTTOM : 45 X 30 X 5 MM, 200MM LONG TWO FOR EACH STUB. )NE OF THE FOUR LEGS IS TO BE CONNECTED TO PIPE EARTHING PROVIDED SEPARATELY AT OWER LOCATION. ‘OLUME OF EXCAVATION = 22.308 CULM (WORKING SPACE OF 150 MM ALL AROUND THE BOTTOM PAD) OLUME OF CONCRETE= 4434 CUM, {E FOUNDATION IS SUITABLE FOR NORMAL TOWER, PLUS 3M AND PLUS 6M EXTENSIONS. 1 CAN BE ADOPTED FOR PLUS 9M AND PLUS 12M EXTENSIONS ERECTING THE STRAIGHT LINE CUT POINT AND LIMITING THE SPAN TO 80M,

You might also like