HORIZONTAL SPLIT CASE FIRE PUMP SYSTEM
DIESEL ENGINE DRIVEN
1. Fuel Tank, Diesel Engine 7. Discharge Pressure Gauge 13. Jockey Pump Controller
2. Isolation Gate Valve (suction) 8. Enclosed Waste Cone with Sight Glasses 14. Jockey Pump
3. Compound Suction Gauge 9. Main Relief Valve 15. Isolation Valves
4. Automatic Air Release Valve 10. Low Suction Pressure Shutoff Valve 16. Ball Drip Valve
5. Diesel Engine Drive 11. Fire Pump Controller 17. Test Valve Manifold with Hose Valves,
6. Horizontal Split Case Fire Pump 12. System Check Valve Caps & Chains
Pump: Horizontal split case, double-suction, UL Listed, FM Approved, mounted on a common base with and flexibly
coupled to a diesel engine. Pump sized for rated capacity and head. Also must be capable of producing 150% rated flow
at not less than 65% rated head and not to exceed 140% rated head at a shutoff or no-flow condition.
Diesel Engine: UL Listed or FM Approved diesel engine adequately sized so as to not overload at any point on the pump
hydraulic curve. Consideration must be given and de-rates applied based on job site elevation and ambient temperature.
Engines must be specifically designed for fire protection service.
Coupling: Flexible type, sized to transmit the horsepower requirements of the pump. Coupling shall be furnished with an
OSHA-design coupling guard.
Base: Fabricated steel design base capable of adequately supporting the weight of the pump and driver. After pump has
been fully piped and accurately aligned with the engine, the base should be fully grouted into place.
Controller: Diesel engine controller starts the engine automatically on a loss of system pressure. System pressure is
monitored via a sensing line from the system side of the check valve. Controller can also be manually started. Controllers
are UL Listed and FM Approved specifically for fire pump service.
Standard Pump Accessories: Accessories furnished with the fire pump system include: suction and discharge gauges
and automatic air release valve. Other accessories commonly furnished as part of the fire pump package include: hose
valve manifold with hose valves, caps and chains, flowmeter, main relief valve and enclosed waste cone, ball drip valve,
eccentric suction reducer, concentric discharge increaser.
Standard Engine Accessories: Accessories furnished with the diesel engine include: engine starting batteries, battery
rack, battery cables, engine exhaust flexible connector and silencer.
Jockey Pump: Jockey pump keeps pressure in the system to prevent the main fire pump from operating to maintain
system pressure. Jockey pumps are generally a few gallons per minute sized to overcome small system leaks and
typically sized for 10 PSI greater than the rated pressure of the main fire pump. Jockey pumps are not required to be
UL Listed or FM Approved.
Jockey Pump Controller: Starts the jockey pump across the line by sensing the system pressure via a sensing line from
the system side of the check valve. This sensing line must be independent from the main fire pump controller sensing line.
Controller is sized per the jockey pump motor horsepower and voltage. Jockey pump controllers are UL Listed specifically
for this service.
HORIZONTAL SPLIT CASE FIRE PUMP SYSTEM
ELECTRIC MOTOR DRIVEN
Pump: Horizontal split case, double-suction, UL Listed, FM the application. Common types of controllers include:
Approved, mounted on a common base with and flexibly across-the-line, primary resistor, part-winding, wye-delta,
coupled to an electric motor. Pump sized for rated capacity auto-transformer, and soft start. Controllers are UL Listed
and head. Also must be capable of producing 150% rated and FM Approved specifically for fire pump service.
flow at not less than 65% rated head and not to exceed
140% rated head at a shutoff or no-flow condition. Standard Accessories: Accessories furnished with the
fire pump system include: suction and discharge gauges,
Electric Motor: UL Listed or FM Approved motor sized so casing relief valve and automatic air release valve. Other
as to not overload at any point on the pump hydraulic curve accessories commonly furnished as part of the fire pump
as per NFPA #20. Motors are open-drip proof type with a package include: hose valve manifold with hose valves,
1.15 service factor wound for the correct voltage. Motor caps and chains, flowmeter, main relief valve and enclosed
to be compatible with the type of controller (i.e., starting waste cone, ball drip valve, eccentric suction reducer,
characteristics). concentric discharge increaser.
Coupling: Flexible type, sized to transmit the horsepower Jockey Pump: Jockey pump keeps pressure in the system
requirements of the pump. Coupling shall be furnished with to prevent the main fire pump from operating to maintain
an OSHA-design coupling guard. system pressure. Jockey pumps are generally a few gallons
per minute sized to overcome small system leaks and
Base: Fabricated steel design base capable of adequately typically sized for 10 PSI greater than the rated pressure
supporting the weight of the pump and driver. After pump of the main fire pump. Jockey pumps are not required to be
has been fully piped and accurately aligned with the motor, UL Listed or FM Approved.
the base should be fully grouted into place.
Jockey Pump Controller: Starts the jockey pump across
Controller: Electric motor controller starts the motor the line by sensing the system pressure via a sensing line
automatically on a loss of system pressure. System from the system side of the check valve. This sensing line
pressure is monitored via a sensing line from the system must be independent from the main fire pump controller
side of the check valve. Controller can also be manually sensing line. Controller is sized per the jockey pump motor
started. The type of motor starting, and therefore the type horsepower and voltage. Jockey pump controllers are UL
of controller, varies depending upon the specifics of Listed specifically for this service.
APPROVED CONTROLLER STARTING METHODS
STARTING
STARTING
CURRENT
TORQUE
(% MOTOR TYPE
TYPE STARTING CHARACTERISTICS ADVANTAGES RESTRAINTS (% LOCKED
FULL LOAD TRANSITION
ROTOR
STARTING
TORQUE)
CURRENT)
Across-the-line Connects motor directly to power * Least expensive * High inrush current 600% 100% Not applicable
source. Full voltage applied to motor * Highest starting torque
when controller is actuated.
* Low maintenance
* Standard motor used
Primary When controller is actuated, a * Smooth starting * High power loss through resistors 300% 25% Closed
Resistance resistance is connected to each * Low shock to motor * Must dissipate heat
Reduced Voltage phase. Resistors are by-passed after
* Standard motor used * Low torque per ampere input
a time delay and motor then runs at
full voltage. * Medium relative cost
* Not recommended for transfer
switch applications
Part Winding Motor starts on one winding. After * Low relative cost * Not recommended for frequent 390% 42% Closed
a time delay, second winding is * Low starting torque starting
connected in parallel to the line. * Low starting torque
* Low maintenance
* Special motor required
Wye-Delta On controller activation, motor windings * Moderate to low relative cost * Medium starting torque 200% 33% Open
Open-Transition wye-connected for starting. After a time * Low motor stress * Special motor required for 200V
delay, automatically converts to delta
* Low starting current * Power line transients
connection for running, applying full
voltage to motor windings. Most often * Can affect other equipment
used with transfer switch/emergency sharing same power source.
generator applications.
Wye-Delta Same sequence as Open Transition. * Moderate to high relative cost * Medium starting torque 200% 33% Closed
Closed-Transition Connected to resistors in each phase * Low motor stress * Special motor may be required
during transition from wye to delta. for 200V
* Low starting current
* No line transients
Auto Starters supply reduced voltage * Good for heavy starting loads * High relative cost Closed
Transformer starting at motor terminals through use * Highest starting torque
Reduced Voltage of tapped, 3-phase autotransformer.
* Standard motor used
A timing relay causes transfer of motor
w/50% tap from reduced voltage start to line voltage * Low starting current 150% 25%
w/65% tap operation without disconnecting motor * Starting torque adjustable 252% 42%
w/80% tap from power source. 384% 64%
Soft Start/Stop Reduces inrush current to motor with * Low inrush current * High relative cost Adjustable Varies Closed
adjustable ramp time. Stop sequence * Adjustable ramp time 50% - 500%
reduces possibility of surges occurring
* Reduces system surges
in the system.
* Standard motor used
Long established as a leading fire pump manufacturer, Fairbanks Morse Pump offers a broad range of
horizontal split case, vertical in-line and vertical turbine designs over a wide range of rated capacities
and pressures…pumps for every fire pump application. Split case and vertical turbine pumps have
the option of being driven via either an electric motor or diesel engine, and are furnished as a
complete package with controller, jockey pump and its controller, as well as standard fire pump system
accessories.
Units are Underwriters Laboratories Listed and Factory Mutual Approved specifically for fire pump
service continually meeting their stringent inspection, testing and record-keeping standards. Split case
rated capacities range from 250 GPM through 5000 GPM, vertical in-line rated capacities range from
50 GPM through 750 GPM, and vertical turbine fire pumps cover 250 GPM through 4500 GPM, all with
a wide range of rated pressures.
The Fairbanks Morse Pump sales family includes highly qualified distributors and representatives well
versed in fire pump systems, who provide prompt and accurate quotations, submittals and acceptance
testing as required. These sales professionals stand ready to address and meet your fire pump needs,
and are backed by many years of factory knowledge and experience.
RATED RATED
CAPACITY HEAD
250 GPM 40 – 167 PSI
500 GPM 40 – 278 PSI
750 GPM 40 – 266 PSI
1000 GPM 40 – 244 PSI
1250 GPM 43 – 236 PSI
1500 GPM 40 – 228 PSI
2000 GPM 53 – 210 PSI
2500 GPM 50 – 213 PSI
3000 GPM 60 – 165 PSI
3500 GPM 94 – 151 PSI
4000 GPM 94 – 223 PSI
4500 GPM 90 – 223 PSI
5000 GPM 88 – 221 PSI
Pump Features:
Pump Features:
VERTICAL TURBINE
RATED RATED
CAPACITY HEAD
250 GPM PSI
500 GPM 100 – 370 PSI
750 GPM 99 – 361 PSI
1000 GPM 96 – 316 PSI
1500 GPM 98 – 320 PSI
2000 GPM 98 – 198 PSI
2500 GPM 100 – 187 PSI
3000 GPM 100 – 189 PSI
3500 GPM 101 – 180 PSI
4000 GPM 120 – 189 PSI
4500 GPM 120 – 181 PSI
Pump Features:
• Bronze impellers
• Cast iron bowl (multi-stage)
• Stainless steel bowl shaft
• Carbon steel open lineshaft
• Steel column pipe
• Cast iron or fabricated steel discharge heads
• Brass suction strainer
• Packed stuffing box
PACKAGED FIRE PUMP SYSTEMS
When the application calls for a completely packaged fire pump system, Fairbanks Morse Pump has the
capability to meet these requirements. Systems include the pump, driver, controller, jockey pump and
jockey pump controller all mounted on a common base. Controller is pre-wired to the driver,
sensing lines are pre-piped from the controllers to the system side of the check valve, and suction and
discharge piping is piped to the edge of the common base. Isolation valves, check valve, and test
header piping (and/or flowmeter piping) can be supplied as required. For diesel engine driven units, the
package would also include the mounting of the fuel tank, piping of fuel lines to the engine and
connection of batteries to the engine.
Should your requirements include the packaged fire pump system to include an enclosure, Fairbanks
Morse Pump can provide the protective structure to house the system. Packaged systems can be
designed for use with horizontal split case, vertical turbine or vertical in-line pump designs.
Programmable Features
·Languages
(English, French, Spanish Standard.
Other languages are available. Consult
factory.)
·Date and Time
·Pressure Start and Stop Points
·Low and High Pressure Alarms
·Stop Mode
Alarm LED's ·Low Suction Shutdown
The controller is supplied with fourteen (14) ·Pressure Recording Parameters
red alarm LED's for the following: ·Run Period Timer Standards & Certification
BATTERY #1 FAILURE
·Weekly Test Timer
CHARGER # 1 FAILURE
BATTERY #2 FAILURE ·Sequential Start Timer The FD120 Diesel Engine Fire Pump Controllers
CHARGER # 2 FAILURE ·AC Failure Alarm meet or exceed the requirements of Underwriters
LOW PRESSURE ·AC Fail to Start Laboratories (UL 218), Underwriters Laboratories
SYSTEM OVER PRESSURE of Canada, Factory Mutual (FM1321 / 1323), the
LOW SUCTION PRESSURE Canadian Standards Association, New York City
LOW FUEL Enclosures building code, are built to NFPA 20 standards and
FAIL TO START meet CE mark requirements.
HIGH ENGINE TEMP Ratings
LOW OIL PRESSURE All FD120 controllers come standard with
ENGINE OVER SPEED NEMA 2 enclosures unless otherwise ordered.
ECM SELECTOR IN ALT POSITION Available options include: NEMA 3R, 4, 4X, 12.
FUEL INJECTION MALFUNCTION
Reduced Size N. Y. C.
Statistics A streamlined internal design has allowed the APPROVED
Up to 27 of statistical points are recorded to overall size of the DIESEL Plus controllers to be
provide a quick review of how the system reduced from previous models. See
has been operating. The statistics can be dimensional drawings in this document.
viewed on the main display, saved to a USB
disk drive, or viewed on the embedded
webpage.
Dimensions
Standard Enclosure - Type NEMA 2, 3R, (*4, 4X), 12
19.17 [487]
26.72 [679] 15.00 [381]
7.00 [178]
2.00 [51]
13.11 [333]
34.98 [888]
32.98 [838]
18.00 [457]
10.56 [268]
N. Y. C.
APPROVED
INTERLOCK ON
LOW SUCTION
PUMP START
NOTES:
LOW FUEL
INPUT #10
INPUT #1
INPUT #2
INPUT #3
INPUT #4
INPUT #5
INPUT #6
INPUT #7
INPUT #8
INPUT #9
1. DELUGE VALVE INPUT NORMALLY CLOSED.
REMOVE JUMPER IF USED.
2. ALL RELAY CONTACTS ARE SHOWN IN NO POWER
CONDITION.
3. ALARM CONTACTS RATED FOR 8A/250VAC. ENGINE
RUN CONTACTS RATED 10A/250VAC.
CUSTOMER INPUTS
OPTION RELAY #1
(2 SETS FORM-C)
ENGINE RUN
OPTION RELAY #2
(2 SETS FORM-C)
ENGINE RUN
FUTURE #1
OPTION RELAY #4
(2 SETS FORM-C)
ALARM CONTACTS
FUTURE #2
LOW FUEL
OPTION RELAY #6
(2 SETS FORM-C)
LOW FUEL
OPTION RELAY #7
AUTO MODE (2 SETS FORM-C)
COMMON ALARM
(NORMALLY ENERGIZED)
AUX. ANALOG INPUT (4-20MA)
COMMON ALARM
(NORMALLY ENERGIZED)
90-240VAC
POWER
BATTERY #2 INPUT(+)
BATTERY #1 CRANK
BATTERY #2 CRANK
BATTERIES (-)
BATTERIES (-)
FUEL SOLENOID
ECM IN ALTERNATE
FUEL INJECTOR FAIL
N. Y. C.
APPROVED
Field Connections
Engine Board Terminal Blocks Inputs
90-240VAC
POWER
BATTERY #2 INPUT(+)
BATTERY #1 CRANK
BATTERY #2 CRANK
BATTERIES (-)
BATTERIES (-)
FUEL SOLENOID
ECM IN ALTERNATE
FUEL INJECTOR FAIL
Outputs
I/O Board
Stranded # 14 (1.63 mm) 11, 34-49, 60-95 N. A.
Stranded # 14 (1.63 mm) Option Board Terminals N. A.
Engine Board
Stranded # 14 (1.63 mm) 1-5, 9, 10, 12, 301, 302, L, N, G N. A.
Battery Wire
Stranded # 10 (2.59 mm) 6, 8, 11 0 feet to 25 feet (7.62m)
Stranded # 8 (3.26 mm) 6, 8, 11 25 feet to 50 feet (7.62 - 15.24m)
FM-UL-CUL APPROVED
RATINGS BHP/KW
JX6H RATED SPEED
MODEL 1760 2100
UFADF0 460 343 488 364
UFAD60 510 380 525 392
UFADK0 517 385.5 526 392
UFADN0 542 404 575 429
UFADP0 575 429 600 447
UFAD88 617 460
All engine models and ratings are USA EPA emissions
certified Tier 3 per NSPS (40 CFR Part 60 Sub Part IIII)
SPECIFICATIONS
JX6H MODELS
ITEM UFADF0 UFAD60 UFADK0 UFADN0 UFADP0 UFAD88
Number of Cylinders 6
Aspiration TRWA
Rotation* Clockwise (CW)
Weight - lb (kg) 3315 (1500)
Compression Ratio 16.0:1
Displacement - cu. in. (l) 824 (13.5)
Engine Type 4 Stroke Cycle - Inline Construction
Bore & Stroke - in. (mm) 5.20 x 6.50 (132 x 165)
Installation Drawing D - 626
Wiring Diagram AC C07651 (AC Heater Wiring)
Wiring Diagram DC C071360, C071361, C071371
Engine Series John Deere 6090 Series Power Tech Plus
Speed Interpolation N/A Optional N/A
Abbreviations: CW - Clockwise • NA - Naturally Aspirated • T - Turbocharged • TRWA - Turbocharged Raw Water Aftercooled.
*Rotation viewed from Heat Exchanger/Front of engine • Engine intended for indoor use or inside weatherproof enclosure only
† ENGINE RATINGS BASELINES • Note: Engines are not to be used for continuous duty. Engines are to be used
• Engines are rated at standard SAE conditions of 29.61 in. (7521 mm) Hg only for stationary emergency standby fire pump service. According to NFPA 25
barometer and 77˚F (25˚C) inlet air temperature [approximates 300 ft. (91.4 m) engines are to be tested 30 minutes per week at no pump flow and full pump flow
above sea level] by the testing laboratory (see SAE Standard J 1349). once per year.
• A deduction of 3 percent from engine horsepower rating at standard SAE CERTIFIED POWER AT ANY SPEED
conditions shall be made for diesel engines for each 1000 ft. (305 m) altitude above • FM-UL Certified BHP ratings are shown at specific speeds, Clarke engines can
300 ft. (91.4 m). be applied at a single rated RPM setting ±50 RPM. Contact Clarke or your Pump
• A deduction of 1 percent from engine horsepower rating as corrected to stan- OEM representative to obtain details.
dard SAE conditions shall be made for diesel engines for every 10˚F (5.6˚C) above • Engines with optional speed interpolation can be factory set at any intermedi-
77˚F (25˚C) ambient temperature. ate speed, to determine intermediate certified power, make a linear interpolation
from the certified FM-UL certified power curve.
MODELS
One (1) 12V- JX6H-UFADFO JX6H-UFADN0
DC w/2 Start JX6H-UFAD60 JX6H-UFADP0
FIRE PUMP ENGINES Contactors JX6H-UFADK0 JX6H-UFAD88
ENGINE EQUIPMENT
EQUIPMENT STANDARD OPTIONAL
Air Cleaner Direct Mounted, Washable, Indoor Service with Drip Shield Disposable, Drip proof, Indoor Service, Outdoor Type
Alternator 24V-DC, 40 Amps; w/Belt Guard
Exhaust Protection Metal Guards on Manifolds & Turbo
Coupling Bare Flywheel Non Listed Drive Shaft & Guard, JX6H-UFADF0 -
SC2140, UFAD60/K0/N0/P0 -SC2155, UFAD88 - SC2160
Electronic Control Module 24V-DC, Energized to stop, Primary ECM always powered on
Exhaust Flex Connection* SS Flex, 150# Flange 8” SS Flex, 150# Flange, 10”
Flywheel Housing S.A.E. #2
Flywheel Power Take Off 11.5” S.A.E. Industrial Flywheel Connection
Fuel Connections Fire Resistant Flexible, Supply & Return Lines, US Coast Guard
Approved
Fuel Filter Primary Filter w/priming pump
Fuel Injection System Unit Injector
Engine Heater 240V-AC, 2500 Watt 120V-AC, 2500 Watt
Governor, Speed Electronic, Dual Electronic Engine Control Modules
Heat Exchanger Tube & Shell Type, 60 PSI w/NPTF Connections
Instrument Panel Multimeter to Display English & Metric, Tachometer,
Hourmeter, Water Temperature, Oil Pressure & One (1)
Voltmeter with toggle switch, Front Opening
Junction Box Integral with Instrument Panel; For DC Wiring Interconnection
to Engine Controller
Lube Oil Cooler Engine Water Cooled, Plate Type
Lube Oil Filter Full Flow w/By-Pass Valve
Lube Oil Pump Gear Driven, Gear Type
Manual Start Controls On Instrument Panel With Control Position Warning Light
Overspeed Control Electronic w/Reset & Test in Instrument Panel
Raw Water Solenoid Operation Automatic from Engine Controller & from Instrument Panel
Run-Stop Control On Instrument Panel With Control Position Warning Light
Starters One (1) 24V-DC with 2 Start Contactors
Throttle Control Adjustable Speed Control by Increase/Decrease Button,
Tamper Proof
Water Pump Poly-Vee Belt Drive w/Guard
Note: Engine Controller needs 2 additional signals: Injector Failure, Alternate ECM Selected
* JX6H-UFADF0/60/K0/N0/P0/88 All provided with orifice plate mounted in flex exhaust.
®
Fire Protection Products, Inc. ®
UK, Ltd.
3133 E. Kemper Rd., Cincinnati, Ohio 45241 Grange Works, Lomond Rd., Coatbridge, ML5-2NN
United States of America United Kingdom
Tel +1-513-771-2200 Fax +1-513-771-0726 Tel +44-1236-429946 Fax +44-1236-427274
www.clarkefire.com www.clarkefire.com
C132704 2.4 5/09 Specifications and information contained in this brochure subject to change without notice. Printed in U.S.A.
FIRE PUMP MODEL: JX6H-UFADN0
Heat Exchanger Cooled
Raw Water Charge Cooling
Tier 3 Emissions Certified
590
580
575
(429)
570
560
550
542
(404)
540
ENGINE PERFORMANCE:
STANDARD CONDITIONS: (SAE J1349, ISO 3046)
77°F (25°C) AIR INLET TEMPERATURE NAMEPLATE BHP (MAXIMUM PUMP LOAD)
29.61 IN. (751.1MM) HG BAROMETRIC PRESSURE
#2 DIESEL FUEL (SEE C13940)
THIS DRAWING AND THE IN- CREATED DATE CREATED
FORMATION HEREIN ARE OUR 08/14/08
PROPERTY AND MAY BE USED BY
OTHER ONLY AS AUTHORIZED BY
US. UNPUBLISHED -- ALL RIGHTS ENGINE MODEL JX6H-UFADN0
RESERVED UNDER THE DRAWING NO. REV
KEVIN KUNKLER 18AUG08 COPYRIGHT LAWS. C132690 A
CLARKE
Fire Protection Products
JX6H-UFADN0
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer…………..……….……..……….……..……….……..………John Deere Co.
Ignition Type……….….……..……….……..……….……..……….……..……….… Compression (Diesel)
Number of Cylinders………….……..……….……..……….……..……….……..…6
Bore and Stroke - in.(mm)…………..……..……….……..……….……..……….… 5.20 (132) x 6.50 (165)
Displacement - cu.in.(L)………...…………..……….……..……….……..……….… 824 (13.5)
Compression Ratio…………….……..……….……..……….……..……….…….. 16.0:1
Valves per cylinder - Intake……..……..……….……..……….……..……….…… 2
Exhaust…..……..……….……..……….……..……….……2
Combustion System………….……..……….……..……….……..……….……..…Unit Injection
Engine Type……………..……..……….……..……….……..……….……..………In-Line, 4 Stroke Cycle
Aspiration…………….……..……….……..……….……..……….……..……….…Turbocharged
Firing Order (CW Rotation)………..……..……….……..……….……..……….…1-5-3-6-2-4
Charge Air Cooling Type………….……..……….……..……….……..……….… Raw Water Cooled
Rotation (Viewed from Front) - Clockwise……..……….……..……….……..…… Standard
Counter-Clockwise….……..……….……..…… Not Available
Engine Crankcase Vent System..………………..……….……..……….……..… Open
Installation Drawing…………………..……….……..……….……..……….…….. D-626
Weight - lb (kg)……..……….………..……….………..……….………..……….…3315 (1500)
Electric System - DC
System Voltage (Nominal)…………………..……..……….……..……….……..…24 (Standard)
Battery Capacity for Ambients Above 32°F (0°C)
Voltage (Nominal)………..……..……….……..……….……..……….……. 12
Qty. per Battery Bank…………..……….……..……….……..……….……. 2
SAE size per J537………..……..……….……..……….……..……….…… 8D-900
CCA @ 0°F (-18°C)………..……..……….……..……….……..……….……900
Reserve Capacity - Minutes…………..………..……..……….……..………430
Battery Cable Circuit*, Max Resistance - ohm…...….…..……..……….……..…0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length………………..……….……..……….……..………. 00
121 - 160 in. Circuit* Length……….……..……….……..……….……..……….…000
161 - 200 in. Circuit* Length……….……..……….……..……….……..……….…0000
Charging Alternator Output - Amp…………….…………...……..……….……..…40
Starter Cranking Amps - @ 60°F (15°C)…...………………..……….……..…… 600
*Positive and Negative Cables Combined Length
Fuel System
Fuel Consumption - gal./hr. (L/hr.)………………..……….……..……….……..…… 25.6 (96.6) 29.2 (110.3)
Fuel Return - gal./hr. (L/hr.)…………………..……….……..……….……..……….…
Total Supply Fuel Flow - gal./hr. (L/hr.)……..……….……..……….……..……….…
Fuel Pressure - lb./in.2 (kPa)…………..……..……….……..……….……..……….…70-90 (483-620)
Minimum Line Size - Supply - (in.)……..……….….………….………………….…… .75 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)……..…………..……..…………..………..…… 1.05 (0.41)
Minimum Line Size - Return - (in.)……….……….……..……….……..….………… .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)……..…………..……..…………..………..…… .848 (.033)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20)……..……….……..……….……..……….… 40 (1.02)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m)..... 11.7 (3.6)
Fuel Filter Micron Size……………..……….……..……….……..……….……..…… 2 (Secondary)
Heater System
Jacket Water Heater……..……….……..……….……..……….……..……….…… Standard
Wattage (Nominal)……..……..……….……..……….……..……….……..……2500
Voltage - AC, 1P……..……..……….……..……….……..……….……..……… 230 (+5%, -10%)
Optional Voltage - AC, 1P…………..……..……….……..……….……..…… 115 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40°F (4°C)……………………… 150
Lubrication System
Oil Pressure - normal - lb./in.2 (kPa)…………………..……….……..……….……..… 42 (287) 45 (310)
In Pan Oil Temperature - °F (°C)…………..……..……….……..……….……..…… 239 (115)
Total Oil Capacity with Filter - qt. (L)…………………..……….……..……….……. 44 (41.5)
Oil Capacity - High - qt. (L)………………………………………………………….. 42 (40)
- Low - qt. (L)…………………………………………………………… 40 (38)
Performance
BMEP - lb./in.2 (kPa)………………..……….……..……….……..……….……..…… 296(2040) 263 (1813)
Piston Speed - ft./min. (m/min.)………………..……….……..……….……..……… 1907 (581) 2275 (693)
Mechanical Noise - dB(A) @ 1M……………………………………………………. Consult Clarke
Power Curve…………………..……….……..……….……..……….……..……….… C132690
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)
*** Review For Power Deration If Air Entering Engine Exceeds °77F (25°C)
C132903 revB
DSP 08JUL09