A4G4a
VEDANTA 4X600 MW IPP, JHARSUGUDA,
steag
PERMIT NO: 171693
Check List For LAVT W.0. NO: 44542
DATE: 16-07-2013
SLNO JOB DESCRIPTION STATUS REMARKS,
1 [Cleaning and terminal tightness of LAV |Work completed
2 [Cleaning of insulators —___|Work completed -
3 |Primary side busbar tightness checking _ [Work completed
4 |Cleaningand terminal tightness of VT 5.4 completed
secondary terminals |
Cleaning and terminal tightness of VT
5 |secondary terminals in the main PT Work completed
terminal box
R Phase:
1VT=1240,2VT=1230,3VT=1230 ;
™ \Y Phase:
6 |PT fuses resistance measurement Work completed AVT=1200,2VT=1240,3VT=1240 ;
|B Phase:
AVT=1220,2VT=1250,3VT=1250 ;
7 [Applying petroleum jelly in the contacts w.5 completed
of LAVT
| eee NEI ORV welnd ing Te cance Work completed ‘Values are in test report
ratio test , IR value
STEAG ENGINEER
wv H Gocndhaay
Name
SEL.
sien f\nal,
Opn
Sign f. ll [Ii ha
Name Jruié (uw Name ¢. Manosvere