Professional Documents
Culture Documents
All electrical equipments have their rated power. It is called overload when
they surpass the rated power, and protection to the status is called
called no-voltage protection. When there is power failure, circuit with the
will not start automatically when power is supplied next time. the purpose
automatically next time when there is power and thus cause accidents.
confronted with damages, load short circuit or wiring errors, short troubles
will come into being. Transient fault current generated when there is short
due to short circuit current can damage, generate arc and even cause fire.
Short circuit protection requires to shut off power in a short time after
voltage circuit breaker. Action current of low voltage circuit is 1.2 times of
Overcurrent protection
smaller than short circuit current and within 6 times of the rated current.
circuit, especially when electric motor switches on and has positive and
value can get right before the maximum allowable temperature rise,
current caused by over current will damage electric motor and the
current reaches to the setting value, over current relay operates. And the
the contactor coil is to shut off contractor coil. Then, shut off the main
contact of the contactor in the main circuit to shut off electric motor in
time.
Overload protection
motor surpasses the rated current but smaller than 1.5 times of the rated
current. And the running state is within the range of running state of over
long time, temperature rise of the winding will surpass the allowable value
motor or short circuit current, and thus thermal relay is usually used as
thermal relay operates, heating elements of the thermal relay can have
been burned out. Therefore, when using thermal relay for overload
Calculating Short-Circuit
Current
One of the most fundamental calculations made on a power
distribution system is that which yields available short-circuit current.
The September – October 2012 issue of IAEI magazine included an
article titled “Going to Basics, Maximum Fault Current” which spoke to
this topic but did not get into the math. I have received many requests
ever since to get into the math. I trust this article will satisfy inquiring
minds with details around calculating available fault current and
provide some equations for the student to explore.
The assumptions for the transformer that will be used as part of the
example for this article will include that which follows. This information
should be available when reading the nameplate of the transformer.
The assumption is for the utility available short-circuit current. For this
exercise 50,000 amps will be used. Before a study is conducted, the
utility is contacted to obtain this information. They may provide the
available fault current in one of a few different ways. The most
straightforward and probably most seen data from the utility will be an
available fault current in kA. Some utilities may provide the data as
short-circuit MVA instead. This article will provide equations to
accommodate both forms of input but cater to a utility available short-
circuit current of 50 kA.
The very first step of this process is the calculation of full-load amps
(FLA) for the transformer. Yet another basic calculation that an
electrical professional will have to perform at some point in their career
and that some perform many times a day. The equations for
calculating FLA are included below:
(√3)×(kVsec)
This 1500 kVA transformer has a secondary FLA of 1,804 amps. This
parameter is necessary to select the secondary conductors for this
transformer. Based on this FLA and the use of Table 310.15(B)(16)
from NEC 2014, the conductors used on the secondary of the
transformer will be a quantity of 5-500 MCM conductors per phase.
Calculating Short-Circuit Current On Secondary of Main
Transformer
There are two ways to approach calculating the available fault current
at the secondary of a transformer. We can calculate the maximum
amount that the transformer will let through, as if the power
generation facility was hooked directly to the line side of the
transformer, or we can calculate the available fault current considering
the provided available fault current from the utility. The former
approach which results in the maximum amount of fault current that a
transformer will let through is referred to as an “infinite bus”
calculation. The circuit of figure 2 can be re-drawn to include zero
impedance for the utility which will reduce the overall impedance of the
circuit and so increase the value of calculated short-circuit current.
Figure 3 will yield the maximum available fault current that a
transformer can supply.
Figure 3.
Infinite Bus equivalent circuit diagram
Using the information stated above for the example 1500 kVA
transformer for this example, the maximum available fault current that
this specific transformer will let through is 31,378 amps and is
calculated as follows:
What this tells us is that the secondary of the transformer cannot see
any more fault current than what we have calculated. There are NO
changes on the utility side that can impact this available fault current
to a point where it would be greater than 31,378 amps. The only way
this service would see more than 31,378 amps would be if we changed
the transformer and the new transformer which would presumably be
the same in all other characteristics, has a different % impedance.
Figure 4 is a table that includes the results of varying the impedance of
the subject transformer +/- 20% in increments of 5% as compared
with the 5.75% impedance value used in this example. This illustrates
how a change in transformer impedance will impact the maximum
available fault current that it can let through.
Below, are two equations that address when kA is available and when
Short-Circuit MVA is available. For this example, we will use the
equation below that assumes the utility has provided you with an
available fault current in kA.
The circuit diagram now looks like that shown in figure 5.
Figure 5.
Circuit diagram that includes both transformer and utility source impedance.
The first step required is to convert the utility provided available fault
current information (50 kA) into a source impedance.
When kA is provided by the utility:
For a given utility available fault current of 50 kA, the %Z of the utility
is calculated as follows
Inserting all of the known variables, the new available fault current is
calculated as follows:
If we compare the infinite bus calculation and that which included the
source impedance of the utility (available fault current of 50,000
amps) we see that the available short-circuit current dropped from
31,378 amps to 29,259 amps, a 6.8% reduction in available fault
current (2,119 amps).
Figure 7. Impact of
varying utility available fault currents on the power distribution system
Just to recap where we are in this discussion, the available fault
currents are as in figure 7a.
The data needed for this example is retrieved from the National
Electrical Code. From Table 9 of NEC 2014 for a 500 MCM conductor in
steel conduit, the Xl (reactance) is found to be 0.048 Ohms/1000ft. For
this example, as stated earlier, we are only using the reactance value
which will result in slightly higher short-circuit current values and make
the math for this publication more palatable. For a 1500 kVA
transformer with 1,804 full load amps, we will need 5- 500MCM
conductors in parallel per phase. The calculation is made as follows:
As can be seen here, including more details reduces the available fault
current. In this case the fault current was reduced from 31,378 amps
to 26,566 amps, approximately 15.3%.
Figure
8. Summary of calculations and comparison with other tools to calculate available
fault current.
Final Calibration
Again, none of the examples shown above and included in this article
considers motor contribution. This was an exercise meant to provide
some background to the discussion of short-circuit currents and so
simplicity was our friend. Motor contribution can be very important for
these calculations. From a math and/or system circuit perspective,
when you include motor contribution the impedance is in parallel with
the utility source impedance, transformer impedance and the
conductor impedance. This acts to reduce the overall impedance in the
circuit of figure 2 and hence increasing the calculated short-circuit
current. The reset is left to the student. (I’ve always wanted to say
that.)
Closing Remarks
As always, keep safety at the top of your list and ensure you and those
around you live to see another day.