Lighting Poles

Item Reference: NSR-5 to NSR-8


a) Type of pole: Octagonal pole
b) Material of Construction: GI
c) Type of Galvanization: Hot dip galvanized
d) Galvanization thickness: min 60 micron
e) Thickness of Pole: min 4.5 mm
f) Height: 6M / 9M / 12M (as per schedule of items)
g) Fixing details: To be fixed upon existing foundation with suitable size base plate, stiffeners &
bolts made up of MS
h) Type of arms: Single / Double (as per schedule of items)
i) Thickness of arm: min 3.6 mm
j) Other details:
 Pole should be finished with adequate size flush door with openable chained cover in lower section
with proper strengthening of cutout of door opening including necessary rubber gasket with two
coats of p.u paint of approved shade, supplying & fixing of suitable size SP MCB , neutral link, earth
stud, heavy duty connector ( suitable for 25 sq.mm terminations).
 Pole should be compatible for the required model of lighting fixture.

Lighting Fixtures & Fans


Item Reference: NSR-9 to NSR-13
Fans
Ceiling fans including their suspension shall conform to relevant Indian Standards. The capacity of a
ceiling fan to meet the requirement of a room with the longer dimension D meters should be about
55 D m3/min. The height of fan blades above the floor should be (3H + W)/4, where H is the height
of the room, and W is the height of the work plane. The minimum distance between fan blades and
the ceiling should be about 0.3 meters. Energy efficient fans with BEE 5 star rating or complying with
IS 374: 1979, shall be used. The minimum service value of fans shall be 3.5 m3/min/W and air
delivery 200 m3/min. All ceiling fans shall be wired to ceiling roses or to special connector boxes,
and suspended from hooks or shackles, with insulators between hooks and suspension rods. There
shall be no joint in the suspension rod. For wooden or steel joists and beams, the suspension shall
consist of GI flat of size not less than 40 mm x 6 mm, secured on the sides of the joists or beams by
means of two coach screws of size not less than 5 cm for each flat. Where there is space above the
beam, a through-bolt of size not less than 1.5 cm dia, shall place above the beam from which the
flats are suspended. In the latter case, the flats shall be secured from movements by means of
another bolt and nut at the bottom of the beam. A hook consisting of In the case of ‘I’ beams, flats
shall be shaped suitably to catch the flanges MS rod of size not less than 1.5 cm dia shall be
inserted between the MS flat through oval holes on their sides. Alternatively, the flats may be bent
inwards to hold tightly between them by means of a bolt and nut, a hook of ‘S’ form and shall be held
together by means of a long bolt and nut for concrete roofs, a 12 mm dia. MS rod in the shape of ‘U’
with their vertical legs bent horizontally at the top at least 19 cm on either side, and bound to the top
of the roof shall be used. In buildings with concrete roofs having a low ceiling height, where the fan
clamp cannot be used, or wherever specified, recessed type fan clamp inside metallic box, shall be
used. Canopies on top of suspension rod shall effectively hide the suspension. The leading in wire
shall be of nominal cross sectional area not less than 1.5sq. mm. and shall be protected from
abrasion. Unless otherwise specified, all ceiling fans shall be hung 2.75 m above the floor. The
metallic body of regulators of ceiling fans shall be connected to earth by protective conductor.

Mirror Light
a) Fixture type :
b) Wiring :
c) Efficacy :
d) Color Temperature :
e) CRI ( Color Rendering Index) :
f) UGR (Unified Glare Ratio) :
g) THD% (Total Harmonic Distortion) :
h) Driver :
i) Dimmable :
j) Housing :
k) Type of Reflector / Diffuser :
l) IP Protection :
m) Input Power :
Supply, installation, testing and commissioning of LED based
2ft. Surface Mounted Luminaire with a nominal system lumen
output of 1150 lumens and a minimum system efficacy of 110
lm/W. The luminaire shall have a rated system lifetime of 25000
burning hours @L70B50. The luminaire shall have a IP20 Rating
with PF>0.9 and an operating Voltage Range of 140 - 270 V. THe
luminare housing should be made of aluminium Extrusion with
Polycarbonate Diffuser . The total power consumption should not
exceed 10 W (including driver). Similar to Philips Make BN 021
LED10S- 6500 PSU GR S1. or approved Equivalent.

Supply, installation, testing and commissioning of wall bracket


decorative light fixture with 20W lamp with B22 base. Housing
made of Metal, synthetics in white color
Philips make cat ref Grace or approved Equivalent.

Supplying installation testing & commissioning of LED BULB 20W


2000lm E27 6500K A67 ,colour temperature 5700 K having
efficacy not less than 80 lm/W, CRI ≥ 70 ,THD ≤ 10%, complete
as required or approved Equivalent.
Supply, installation, testing and commissioning of 3W LED
Emergency Exit signage in sheet steel housing, white powder
coated, non-maintained luminaries suitable for wall / ceiling /
suspension type single / double sided display,EXIT sign
illumination should be GREEN. Environment friendly nickle metal
hydried battery with 3-hour battery back-up including all
accessories complete as required. Make of Crompton/ Bajaj/
Prolite.