You are on page 1of 8

Slot Tech Feature Article PRINT ME

SAVE AS

Understanding Harmonic
Suppression Systems
Get a Handle on Wasted Energy and Excess Heat

A typical casino will have vide enough current to power


thousands of switched-mode the machines and we have By Michael Lowenstein and Jonathan Piel
power supplies on-line, the place wired properly so
twenty-four hours a day, the current is distributed and These nefarious culprits are
seven days a week, 365 days the loads are balanced cor- called “harmonic currents”
a year. A typical slot machine rectly, it’s all good, right?” and it’s up to the White
will have at least two and Knights of technology to elimi-
likely three or more. There’s Well, yes and no. Sure, it all nate them from your gaming
the SMPS for the monitor (re- works correctly but there are property forever. Problems
gardless of whether it’s a CRT hidden, insidious forces at caused by harmonic currents
or an LCD), the power supply work when you have so many include overheated trans-
for the game’s logic and often switched-mode power sup- formers and wiring, random
a separate power supply for plies in operation at the same circuit breaker tripping and
the bill validator. Possibly time. These evil forces are reduced useable system ca-
added to the mix will be a dropping the efficiency of your pacity.
power supply for a hopper, system and likely causing you
ticket printer and/or SMIB. to spend thousands of extra Our White Knight is some-
dollars each year, not only for thing called "harmonic sup-
Multiply that by 2000 ma- electric power but also for the pression." Harmonic suppres-
chines or more, add in all of air-conditioning required to sion systems can be installed
the computers for the back- cool your casino. to eliminate the flow of the
end system (including all of
the DCUs, etc.) as well as
each and every office com-
puter and its associated moni-
tor along with the display
monitors scattered around
the casino floor, in the sur-
veillance room and, if you
have a hotel, all of the televi-
sion sets in the guest rooms
and you begin to see that
your casino has thousands of
switched-mode power sup-
plies in operation at this very
moment.

“So what’s the big deal about


Figure 1. Here's our first problem: Although the AC volt-
that?” you ask. “As long as
age is a sine wave, the rectifier draws its current in spikes.
the power company can pro-
Page 18 Slot Tech Magazine August 2004
most troublesome of these
bad boys, the "third har-
monic" currents. Economic
benefits of installing such
systems include increased
capacity (good if you’re in
California where Governor
Arnold Schwarzenegger has
just signed an agreement al- The input circuit of an SMPS is a bridge rectifier that changes the 120
lowing unlimited slot ma- volt AC input to DC. A capacitor smoothes this DC to eliminate voltage
chines) increased component ripples and the resultant DC bus has a voltage of about 170 volts.
lifetime and reduced down
time. Later in this discus- do not provide power to the Harmonic Current Flow in
sion, you’ll see how it is now SMPS, but they do take up a Wye Distribution System
possible to measure the en- distribution system capacity.
ergy savings obtained when The principal harmonic cur- When SMPS loads are con-
excessive harmonic current rent is the 3rd (180 Hz) and nected as shown in Figure 2,
flow is eliminated in an elec- the amplitude of this current each phase wire carries both
trical system. These savings can be equal to or even greater the 60Hz fundamental cur-
are due to reduced I2R losses than that of the fundamental rent that supplies power to
in transformers and wiring current. the SMPS and the harmonic
and reduced air conditioning currents that are there be-
costs. cause of the way the SMPS
draws its current. While most
Harmonic Currents

Harmonic currents are a di-


rect result of the way in which
a switched-mode power sup-
ply (SMPS) draws current
from the system. The input
circuit of an SMPS is a bridge
rectifier that changes the 120
volt AC input to DC. A capaci-
tor smoothes this DC to elimi-
nate voltage ripples and the
resultant DC bus has a volt-
age of about 170 volts when
the AC rms input is 120 volts.
Although the AC voltage is a
sine wave, the rectifier draws
its current in spikes as shown
in Figure 1. These spikes re-
quire that the AC supply sys-
tem provide harmonic cur-
rents, primarily 3rd, 5th and
7th. These harmonic currents

Slot Tech Magazine August 2004 Page 19


Figure 2. 208/120 Wye distribution sys-
tem with phase-neutral computer loads

of the harmonic currents can- Larger conduit must be in- 1. All distribution systems
stalled to handle more or
cel in the neutral wire, just as are rms current limited. For
the 60Hz currents do, the 3rd larger wires. (Although the instance, a 150 kVA 208/
harmonic current and other code permits downsized 120 wye transformer is rated
currents divisible by three areneutrals if the system is not for 416 rms amps per phase.
additive in the neutral wire. powering non-linear loads, The more harmonic current
Thus, if the 3rd harmonic language in NEC 310. flowing, the less fundamen-
current were 100 amps in 15(B)(4)(b, c) (2002) requires tal current can be supplied.
each phase, the 3rd harmonic neutral conductors to be con- Since the harmonic current
current returned to the X0 sidered current-carrying con- does not deliver any power,
transformer connection by ductors when nonlinear its presence uses up system
the common neutral wire (SMPS) loads are present. It capacity and reduces the
would be 300 amps. should be noted that there is number of loads that can be
no code requirement for powered. Either the system
This fact has implications for double neutrals, only that the must be de-rated or a larger
system design, since the en- neutrals be properly sized for system, that can only be par-
tire electrical system must the expected current. ) tially utilized, must be in-
meet the national electrical stalled.
code specifications for wire System Problems Caused by
and conduit size. If it is ex- 3rd Harmonic Currents 2. Harmonic currents flow-
pected that SMPS loads will ing through the system wir-
cause high neutral currents, The effect of current distor- ing cause increased I2R heat
wires must be sized for the tion on distribution systems losses. This heating can in-
anticipated load. Instead of can be serious, primarily due crease the temperature of
downsizing neutral wires, to the increased current flow- wires and switchgear to the
once common practice for a ing throughout the system. point that erratic operation
system supporting only lin- Following are some of the or even fires can occur. One
ear loads, now neutral wires problems that must be con- study found that 33% of tele-
must be oversized or doubled. sidered. communication fires were

Page 20 Slot Tech Magazine August 2004


caused by failures of power of transformer failure due to the transformer to the loads
systems or components. overheating, special trans- still carry all the harmonic
formers, known as “k-rated,” currents and double neutral
3. Balanced 3rd harmonic have been designed to handle wires are recommended.
currents cannot flow out of a high harmonic loading, in-
delta primary. Therefore, they cluding 3rd harmonic cur- Problems with Accommo-
circulate in the primary of rents circulating in the delta dation Methods
the transformer where they primary. The k-rated trans-
are dissipated as heat, Fig. 2. former will survive overheat- While accommodation meth-
The current circulating in the ing when subjected to high ods enable the electrical sys-
transformer delta primary harmonic loading, but the tem to survive harmonic cur-
winding contributes to the harmonic currents are still rents, they have a number of
load on the winding, but does present in the system. shortcomings.
not flow through the primary
circuit breaker protection. 3. Install a zig-zag reactor. 1. Useful system capacity is
Thus the transformer pri- The zig-zag reactor contains not changed. Harmonic cur-
mary winding can be over- special windings connected rents still flow throughout the
loaded and the breaker that so as to present a low imped- system wiring and rms cur-
is expected to protect the ance to 3rd harmonic cur- rent is not decreased.
transformer will not do so. rents and a high impedance
to 60 Hz currents. When a 2. Heating of wires and
4. Heat dissipated by trans- zig-zag reactor is connected switchgear is not reduced.
formers, switchgear, and wir- between the phases and neu- Although the temperature of
ing represents wasted energy. tral of a wye system, the 3rd transformers may be reduced,
Energy losses, brought about harmonic currents are di- harmonic currents still flow
by harmonic current flow, can verted through the device. throughout the system wir-
result in significant increases These currents no longer flow, ing.
in operating costs. from the point where the zig-
zag is connected in the sys- 3. Energy losses due to I2R
Alternatives for tem, upstream to the trans- heating are not reduced.
Harmonic Mitigation former. However, the phase Since the harmonic currents
and neutral wires from the still flow throughout the sys-
Accommodation Methods zig-zag toward the loads still tem wiring, energy is still
carry all the harmonic cur- wasted. In fact, studies have
Traditional methods used to rents including the 3rd, and shown that the installation of
mitigate the effects of har- double neutral wires are rec- certain accommodation
monic currents involve “ac- ommended. methods may actually in-
commodation” of the currents crease energy losses. The typi-
after they are in the system. 4. Install a zig-zag trans- cal impedance of zig-zag
former. A “zig-zag” trans- transformers and k-rated
1. Overbuild the system to former can be used to replace transformers is lower than
handle the extra current. the standard transformer in a that of a standard trans-
Double-sized neutral wires, system. This device has the former. Likewise, an oversized
oversized switchgear, and special windings of the zig- transformer typically shows
transformers de-rated to less zag reactor built into the a lower impedance than a
than their full capacity are transformer secondary so that smaller transformer. Since
examples of system over- the 3rd harmonic currents transformer impedance is
building. are cancelled in the second- lower, harmonic current flow
ary and do not circulate in the throughout the system is ac-
2. Install a k-rated trans- primary winding. Again, the tually increased. A recent
former. To reduce the chance phase and neutral wires from study shows that a signifi-
Slot Tech Magazine August 2004 Page 21
the flow of the fundamental
60Hz current. Application of
the HSS is shown in Figure 3.

The HSS is connected be-


tween the neutral wire and
the transformer X0. All cur-
Table 1. Increase in kW useage due to decrease in rent that flows through the
transformer impedance
phase wires to the load must
return through the neutral.
cant increase in kW usage the disease from occurring. If 3rd harmonic current can-
results from installing a lower The HSS is designed to pre- not flow in the neutral, due to
impedance transformer. Data vent the flow of harmonic cur- the high impedance of the
from this study are shown in rents in the distribution sys- HSS, then no 3rd harmonic
Table 1. tem, rather than treating or current can flow in the phase
accommodating the currents wires. The damaging 3rd
Harmonic Suppression after they are there. harmonic current is blocked
throughout the entire distri-
Harmonic suppression sys- The HSS consists of a parallel bution system from the trans-
tems (referred to as HSS) use resistive/inductive/capaci- former out to the furthest
a different approach to miti- tive (RLC) network tuned to load. There is no 3rd har-
gate harmonic currents in the the 3rd harmonic, or 180 Hz monic current circulating in
distribution system. Their for a 60 Hz fundamental fre- the delta transformer primary
application is based on the quency. The electrical char- because there is no 3rd har-
same concept that is used in acteristics of this type of cir- monic current available to
modern medicine, “preventa- cuit are such that it has a circulate. The transformer is
tive action. “Instead of treat- very high resistance to the now fully protected by the
ing the symptoms of a dis- flow of 3rd harmonic current primary circuit breaker
ease, it is far better to keep and a very low resistance to against overloading. Phase

Figure 3. 208/120 Wye distribution system with phase-neutral loads and HSS

Page 22 Slot Tech Magazine August 2004


Figure 4a

wires have more capacity neutral currents greater than ties, are at risk from over-
available to carry useful load the phase currents, facilities, heated wiring leading to fires.
and double neutrals are not and particularly older facili- Transformers with high 3rd
necessary. The neutral, for
code purposes, need no longer
be considered a current car-
rying conductor. Overheat-
ing of transformers,
switchgear, and wiring is
eliminated, increasing the
lifetime of all system compo-
nents.

Benefits of the HSS

Four areas will be discussed:


1) enhanced life safety; 2) in-
creased system capacity; 3)
greater reliability; 4) energy
and operating cost savings.

1) Enhanced Life Safety.


3rd harmonic currents flow-
ing in the system can over-
load transformers,
switchgear, and wiring. With A typical installation
Slot Tech Magazine August 2004 Page 23
Figure 4b

harmonic currents circulat- 3) Greater Reliability. directly in energy bills as in-


ing in the primary, and un- The major cause of failure for creased kW hour charges.
protected against overload- transformers and switchgear Installation of the HSS elimi-
ing, can fail or catch fire. By is overheating. Random nates this wasted energy and
eliminating 3rd harmonic breaker tripping due to har- leads to a direct reduction in
currents from the transformer monic heating is well known. energy costs. One recent
to the furthest outlet, the HSS The elimination of 3rd har- study showed that, depend-
eliminates the risk of over- monic currents reduces heat ing on transformer loading
current caused fires. in all parts of the distribution and the distribution distance
system, thereby reducing the from the transformer, the
2)Increased System Capacity. likelihood that system com- energy saved by eliminating
All electrical distribution sys- ponents will fail or trip off due 3rd harmonic currents
tems are rms current limited. to excessive temperatures. ranged from a minimum of 2.
Harmonic currents carried by The elimination of high neu- 5% to a maximum of 8% of
transformers, switchgear, tral currents lowers neutral- the energy used to power com-
and wiring use up system ground voltages and reduces puters. [3]Another study,
capacity that could be used the likelihood that data er- conducted for the California
to carry 60Hz currents that rors will occur. Energy Commission, mea-
do work. By eliminating 3rd sured realized energy savings,
harmonic currents through- 4) Reduced Energy and Oper- due to the HSS, of from 4 to
out the entire distribution ating Costs. 6%. [4]
system, the HSS provides the Excessive heat in electrical
facility with more useful ca- distribution systems means Energy Estimator
pacity without requiring that wasted energy. The heat is
the electrical system be due to I2R losses in all system An energy savings estimator
upsized. components, and appears is available as a Microsoft

Page 24 Slot Tech Magazine August 2004


Excel spreadsheet as illus- puter manufacturer also are addressed. The bot-
trated in Figures 4a and 4b tom line is that the installa-
on the next page. This esti- The following data were ob- tion of an HSS can pay for
mator allows the user to in- tained for this facility: itself, by energy savings, in
put electrical system param- 1. 3-story office building one to three years.
eters for any system. The dol- 2. 225 kVA transformer 53%
lar savings expected for the loaded For further information,
system when an HSS is in- 3. Neutral current reduced contact:
stalled are quickly calculated. by78% from 301 to 67 amps Dr. Michael Z. Lowenstein
4. 3rd harmonic current re- Harmonics Limited
In addition to the direct waste duced by 98% from 290 to 6 50 Pocono Road
of energy caused by harmonic amps Brookfield, CT 06804
currents, there is a second- 5. rms phase current re- tel.877.437.3688
ary effect. Air conditioners duced by 12% Fax.203.740.3083
must be powered to remove 6. Using energy savings esti- mzl@harmonicslimited.com
this excess heat. Reducing mator, ROI = 26 months
extra operation of air condi-
tioners, necessary because of Case study 3. An internet Michael Z. Lowenstein holds
harmonic generated heat, can hosting facility an A. B. in chemistry from
add another 1-3% to the en- Oberlin College, and an MS
ergy saved by an HSS. The following data were ob- and Ph. D. in physical and
tained for this facility: analytical chemistry and
Case Studies 1. 8-150 kVA k-13 trans- physics from Arizona State
formers University. He spent 13 years
Three case studies are out- 2. Combined neutral current as a College Chemistry Pro-
lined below. In each study, reduced by 76% from 1940 to fessor and 8 years as a Na-
neutral 3rd harmonic cur- 451 amps (average 56 amps) tional Program Manager for
rents were almost totally 3. 3rd harmonic current re- the Solar Energy Research
eliminated and useful load duced by 98% from 1890 to Institute. His experience with
capacity was increased. It was 44 amps (average 5 amps) harmonics includes 15 years
estimated that energy sav- 4. rms phase current re- designing filters for 3-phase
ings due to the HSS would duced by 21% industrial drives. In 1989 he
result in complete payback of 5. Using energy savings esti- founded Harmonics Limited,
the purchase cost in 14. 5 to mator, ROI = 14. 5 months a company devoted to solving
26 months. harmonic problems caused
Conclusions by multiple computer loads.
Case study 1. A major TV He is currently President and
broadcast studio The harmonic suppression Chief Technology Officer of
system is a well-established the company.
The following data were ob- technology. As the case stud-
tained for this facility: ies show, it has been em- Jonnathan K. Piel received a
1. 3-500 kVA UPSs braced by a wide variety of BSEE degree from Michigan
2. Neutral current reduced users, including major com- Technological University. He
by 81% from 1513 to 283 puter manufacturers, banks, is currently the Engineering
amps stock exchanges, educational Manager at Harmonics Lim-
3. 3rd harmonic current re- institutions, insurance com- ited, Milwaukee, Wisconsin,
duced by 96% from 1508 to panies and broadcast facili- where he is responsible for
56 amps ties. In short, any group that power quality-related re-
4. rms phase current re- uses multiple computers search, training, and prod-
duced by 8% (such as a casino) can benefit uct development. His main
5. Using energy savings esti- from this technology. The area of research has been
mator, ROI = 18 months capacity and energy savings single-phase non-linear har-
are well documented and life monic phenomena and solu-
Case study 2. A major com- safety and reliability issues tion applications.

Slot Tech Magazine August 2004 Page 25

You might also like