Professional Documents
Culture Documents
a r t i c l e i n f o a b s t r a c t
Article history: Faulty phase recognition under single-line-to-ground (SLG) fault condition is critical for some arc suppres-
Received 14 December 2017 sion methods in medium voltage (MV) networks. Traditional methods usually assume that the distributed
Received in revised form 5 March 2018 parameters of the network are symmetrical, thus are unsuitable for the asymmetrical networks, espe-
Accepted 28 March 2018
cially when the ground-fault resistance is relatively high. In this paper, the trajectory of the zero-sequence
voltage with the change of ground-fault conductance is analyzed in detail. The magnitude and phase
Keywords:
angle variation rules of the voltage under different asymmetry ratios are presented. Then, the ranges
Distribution power system
of their unique variation rules on SLG fault for each phases are separately and strictly discussed both
Single-phase-to-ground fault
Faulty phase recognition
for the under-compensated and over-compensated grounding conditions. Furthermore, a faulty phase
High-resistance ground fault recognition method is proposed based on the variation rules of zero-sequence voltage on faulty condition.
Distribution network asymmetry Simulation results verify the concluded variation rules and validate the effectiveness of the proposed fault
Zero-sequence voltage phase recognition method, which ensures exact recognition of faulty phase in asymmetrical network and
high-resistance ground fault condition.
© 2018 The Author(s). Published by Elsevier B.V. This is an open access article under the CC
BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
https://doi.org/10.1016/j.epsr.2018.03.024
0378-7796/© 2018 The Author(s). Published by Elsevier B.V. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/
4.0/).
18 J. Meng et al. / Electric Power Systems Research 161 (2018) 17–25
ratio also increases as the grounding method changes to resistive 3.1. Magnitude variation rules
grounding. Therefore, the zero-sequence voltage can be written to
Expression (11) shows the magnitude of ground-fault ratio. It
jra cos ˛ − ra sin ˛ + GEs indicates that the sign of detuning ratio has no impact on M(K),
U 0A = −E A = −E A K. (6)
j + d + GEs which means the variation rules of M(K) apply for both under-
GEs is the standardized ground-fault conductance by the admit- compensated and over-compensated grounding methods.
tance of the overall distributed capacitance, i.e., GE /(ωC ). The
Fig. 5. Integrated zero-sequence voltage magnitude and phase angle variation rules
Fig. 3. Zero-sequence voltage magnitude variation region with different asymmetry when SLG fault happens on phase A ( = +10%, d = 4%, ra = 3.5%).
ratio phases when SLG fault happens on phase A ( = +10%, d = 4%, ra = 3.5%; Curve I:
˛ = 270◦ ; Curve II: ˛ = 45◦ ).
rises after GEs reaches the root specified by (19) as GEs increases
from 0 to infinite. The corresponding range is shown by the blue
arc in Fig. 4, which is ˛ ∈ (−72.4◦ , 72.4◦ ) for the specified net-
work parameters. Zero-sequence voltage curves as ˛ is at the
two boundaries (I and III) are particularly displayed, from which
it can be seen that the intersection points of the curves and U00
circle are just the tangent points from the origin to the curves.
Thus,the boundariescorrespond to the phase shift points.
2) ˛ ∈ arccos 2ra 2 , 2 . This condition ensures that the roots of
+d
(18) are two positive reals. Therefore, the curve of P(K) has firstly
a rise, then a fall and finally a rise as GEs increases. Particularly,
the roots of (18) are equal when ˛ is /2, thus the fall and rise
Fig. 4. Zero-sequence voltage phase variation region with different asymmetry ratio simultaneously
happen origin point (see curve II in Fig. 4).
at the
phases when SLG fault happens on phase A ( = +10%, d = 4%, ra = 3.5%; Curve I: 3) ˛ ∈ 2
, 2 − arccos 2ra 2 . On this condition the roots of (18)
+d
˛ = 287.56◦ , Curve II: ˛ = 90◦ , Curve III: ˛ = 72.44◦ ). are either negative or imaginary, which means P(K) monotoni-
cally increases as GEs increases.
zero-sequence voltage tends to decrease firstly, followed by an
increase. This again verifies the aforementioned rules as ˛ is out
of the monotonically increasing range. 3.3. Integrated variation rules
3.2. Phase angle variation rules For practical network parameters, the following inequalities
stand.
From Eq. (6), the phase angle of ground-fault ratio can be
dra ra
expressed as (17). < + arcsin 2 < 2 − arccos 2 (20)
⎧
2 + d2 + d2
⎨ arctan ra cos ˛
− arctan , as GEs > ra sin ␣
GEs − ra sin ˛ GEs + d
P(K) = (17) ra dra ra
⎩ + arctan ra cos ˛
− arctan
, as GEs < ra sin ˛ −arccos < −arcsin 2 < arccos 2 (21)
GEs − ra sin ˛ GEs + d 2 + d2 + d2 + d2
Similarly, we can fix the network coefficients and obtain the
derivative of P(K) over ground-fault conductance GEs . The inflection Therefore, the zero-sequence voltage magnitude and phase
point of P(K) is determined by angle variation rules can be integrated in one plane. The ranges
indicating the unique magnitude and phase variation rules of zero-
dP(K) sequence voltage can then be concluded as shown in Table 1.
=0 (18)
dGEs Fig. 5 aims to illustrate the ranges in Table 1. As each range cor-
Assume that the phase angle of asymmetry ratio ˛ is /2 or 3/2, responds to unique zero-sequence voltage magnitude and phase
from (9) and (10) it can be seen that the origin point is on the trace of angle variation rules, the voltage trajectory is predictable if the start
zero-sequence voltage, which means an 180◦ phase change occurs point is specified. Actually, the point is determined by the phase
around the point. This phase shift can also be observed from the angle and magnitude of the asymmetry ratio ra . The rules shown in
roots of (18), which are two equal ones with positive real value. Table 1 specifies the zero-sequence voltage feature of SLG fault on
If ˛ is neither /2 nor 3/2, the roots of Eq. (18) can be expressed phase A. The faulty feature on phase B and C can also be concluded,
as which will be discussed in the next section.
2
tan ˛ + d tan ˛ + d 2 + d2 − ra / cos ˛
GEs = ± + (19)
/(ra cos ˛) − 1 /(ra cos ˛) − 1 /(ra cos ˛) − 1
4. Faulty phase recognition method
The variation rules of P(K) with ˛ can be concluded as follows.
Typical zero-sequence voltage traces are shown in Fig. 4 for explicit As the faulty phase corresponds to the specific zero-sequence
explanation. voltage trace and the traces for the three phases never cross each
other, an effective way to recognize the faulty phase is to com-
1) ˛ ∈ −arccos 2ra 2 , arccos 2ra 2 . On this condition, Eq. (18) pare the zero-sequence voltage on SLG fault with that on normal
+d +d
has just one positive real root, which means P(K) falls first, then condition.
J. Meng et al. / Electric Power Systems Research 161 (2018) 17–25 21
Table 1
Zero-sequence voltage magnitude and phase angle variation rules on under-compensated grounding condition.
Range number Asymmetry ratio angle ˛ (˛ + 2/3 Zero-sequence voltage Zero-sequence voltage phase
for phase B; ˛ − 2/3 for phase C) magnitude variation rules angle variation rules
dra ra
I −arcsin , arccos Fall → rise Fall → rise
2 + d2 2 + d2
ra
II arccos 2 , Fall → rise Rise → fall → rise
+ d 2 2
dra
III , + arcsin 2 Fall → rise Rise
2 + d2
dra ra
IV + arcsin 2 , 2 − arccos 2 Rise Rise
+d 2 + d 2
ra dra
V −arccos 2 , −arcsin 2 Rise Fall → rise
+ d2 + d2
Fig. 6. Zero-sequence voltage curves with SLG fault on different phases. ( = +10%,
d = 4%, ra = 3.5%).
Fig. 9. Typical asymmetry ratio angles and the allocation of their corresponding U00 .
Fig. 8. Zero-sequence voltage phase variation region with different asymmetry ratio
phases when SLG fault happens on phase A ( = −10%, d = 4%, ra = 3.5%; Curve I:
˛ = 107.56◦ , Curve II: ˛ = 90◦ , Curve III: ˛ = 252.44◦ ).
to deal with the SLG fault with high ground-fault resistance which
is the situation this paper mainly focuses on. As for the low resis-
tance situation, the aforementioned traditional method is precise
enough to find the faulty phase. Then, we calculate the change of the
magnitude and phase angle of the zero-sequence voltage. Finally,
the rule that matches the real variation of the voltage indicates the
corresponding phase to be on fault.
Table 2
Zero-sequence phase angle variation rules on over-compensated grounding condition.
Range number Asymmetry ratio angle ␣ Zero-sequence voltage phase angle variation rules
ra
I , arccos 2 Fall → rise → fall
2 + d2
ra ra
II arccos 2 , 2 − arccos 2 Rise → fall
+d 2
+d 2
ra
III 2 − arccos 2 , Fall
+ d2 2
Table 3
Zero-sequence voltage on phase-A SLG fault ( = +10%, d = 4%, ra = 3.5%).
˛ Corresponding range number GE /S M(U0A )/kV Variation of M(U0A ) P(U0A )/◦ Variation of P(U0A )
Table 4
Zero-sequence voltage on phase-B SLG fault ( = +10%, d = 1.5%, ra = 1.5%).
in Table 5. As to the magnitude variation rules, the monotonically on over-compensated one. The ground-fault resistances are rela-
increasing range as analyzed above is (186.9, 353.1), in which the tively high but practical enough. Take notice that phase A is set
second and third asymmetry ratio angles are included. The results to be in SLG fault on all the conditions. UAX is the line-to-ground
perfectly match the presented rules. voltages of phase X.
The zero-sequence variation rules can be used to recognize the
5.2. Discussion on faulty phase recognition method faulty phase. For condition I, the asymmetry ratio angle corre-
sponds to range I in Table 1 while assuming phase-A SLG fault. The
Four conditions indicating that the traditional faulty phase range changes to III and V while considering SLG faults on phase
recognition criterion is invalid are shown in Table 6. Two of them B and C, respectively. As the zero-sequence voltage magnitude on
are on under-compensated grounding condition and the others are faulty condition decreases from the normal, i.e., M(U0A ) < M(U00 ),
24 J. Meng et al. / Electric Power Systems Research 161 (2018) 17–25
Table 5
Zero-sequence voltage on phase-A SLG fault under over-compensated grounding condition ( = −10%, d = 4%, ra = 3.5%).
Table 6
Conditions when traditional criterion does not stand (d = 4%, ra = 3.5%, Phase A is set to be the faulty phase).
SLG fault on phase-C must not happen. In the same way, as the and phase angle variation rules of zero-sequence voltage with the
zero-sequence voltage angle falls from the normal condition to the change of ground-fault conductance on SLG fault condition for both
faulty one, SLG fault on phase-B must not happen. under-compensated and over-compensated grounding systems are
For condition II, the specified asymmetry ratio angle corre- presented in detail. The ranges for unique magnitude and phase
sponds to range III, IV and V while assuming SLG faults on phase angle variation rules are strictly addressed. A faulty phase recog-
A, B and C, respectively. It is easy to exclude the possibility of SLG nition method based on the rules is proposed and the flowchart
faults on phase B and C as the magnitude of zero-sequence voltage of the method is provided and described in detail. Comparisons
falls from the normal condition to the faulty condition. are made between the proposed method with the traditional one,
The same analysis can be conducted for the over-compensated which indicates the proposed one is immune to the asymmetry
grounding conditions. As to the specified network parameters, and high ground-fault resistance. As the unique ranges of zero-
the ranges for different zero-sequence voltage angle variation in sequence voltage under SLG fault are clearly presented, the method
Table 2 are (90◦ , 107.6◦ ], (107.6◦ , 252.4◦ ] and (252.4◦ , 450◦ ] from is easily to be implemented, especially for digital processors. How-
the top to the bottom. For condition III, as the zero-sequence ever, the SLG fault with low ground-fault resistance should be dealt
voltage angle increases from the normal to faulty condition, with carefully, as a result, the traditional method is recommended
the SLG fault on phase-C must not happen. As the asymme- if the resistance is relatively low.
try ratio angle forces the zero-sequence voltage magnitude in
the monotonically increasing region for SLG fault on phase-B, Acknowledgments
i.e., (186.9◦ < ˛ + 120◦ = 196.0◦ < 353.1◦ ), the falling magnitude from
normal to faulty condition makes this type of fault impossible to This research was sponsored in part by the National Natu-
happen. ral Science Foundation of China (Grant Nos. 51407014, 51577014
For condition IV, the asymmetry ratio angle P(U00 ) forces both and 51707013), in part by the Hunan Provincial Natural Science
the zero-sequence voltage angle on phase B and phase C into the Foundation of China (Grant No. 2018JJ2427), and in part by the
third range, i.e., the angle has a monotonically falling nature. How- Key Laboratory of Renewable Energy Electric-Technology of Hunan
ever, as the data of P(U0A ) shows, the zero-sequence voltage angle Province (Grant No. 2017ZNDL004). The authors would like to
just increases from the normal condition. Therefore, the SLG faults acknowledge Ziqiang Sheng, Mingwen Ma and Lingjie Yan for their
on phase-B and phase-C must not happen. help on finding the variation rules of zero-sequence voltage.
6. Conclusion References
[1] W. Wang, L. Yan, X. Zeng, B. Fan, J.M. Guerrero, Principle and design of a
Traditional criterion for faulty phase recognition on SLG fault is single-phase inverter based grounding system for neutral-to-ground voltage
invalid as the asymmetry of the distribution network exists, espe- compensation in distribution networks, IEEE Trans. Ind. Electron. 64 (2)
cially when the ground-fault resistance is high. The magnitude (2017) 1204–1213.
J. Meng et al. / Electric Power Systems Research 161 (2018) 17–25 25
[2] Y. Li, X. Meng, X. Song, Application of signal processing and analysis in [13] Alberto Cerretti, F.M. Gatta, Alberto Geri, Stefano Lauria, M. Maccioni,
detecting single line-to-ground (SLG) fault location in high-impedance Giovanni Valtorta, Grounding fault temporary overvoltages in MV networks:
grounded distribution network, IET Gener. Transm. Distrib. 10 (2) (2016) evaluation and experimental tests, IEEE Trans. Power Deliv. 27 (July (3))
382–389. (2012) 1592–1600.
[3] M. Brenna, E. De Berardinis, L. Delli Carpini, P. Paulon, P. Petroni, G. Sapienza, [14] X. Zeng, Y. Xu, Y. Wang, Some novel techniques for insulation parameters
G. Scrosati, D. Zaninelli, Petersen coil regulators analysis using a real-time measurement and Petersen-coil control in distribution systems, IEEE Trans.
digital simulator, IEEE Trans. Power Deliv. 26 (July (3)) (2011) 1479–1488. Ind. Electron. 57 (April (4)) (2010) 1445–1451.
[4] Q. Wang, M. Cheng, Y. Jiang, W. Zuo, G. Buja, A simple active and reactive [15] Xuxuan Chen, Baichao Chen, Cuihua Tian, Jiaxin Yuan, Yaozhong Liu,
power control for applications of single-phase electric springs, IEEE Trans. Modeling and harmonic optimization of a two-stage saturable magnetically
Ind. Electron. 65 (August (8)) (2018) 6291–6300. controlled reactor for an Arc suppression coil, IEEE Trans. Ind. Electron. 59
[5] X. Xia, Y. Zhou, C. Fu, Z. Zhou, Y. He, Research on high voltage DC transmission (July (7)) (2012) 2824–2831.
system optimal control based on MMC, Int. J. Electr Power Energy Syst. 82 [16] M. Janssen, S. Kraemer, R. Schmidt, K. Winter, Residual current compensation
(November (11)) (2016) 207–212. (RCC) for resonant grounded transmission systems using high performance
[6] A.S. Al-Abdulwahab, K.M. Winter, N. Winter, Decreasing the harmonic voltage source inverter, IEEE PES Transm. Distrib. Conf. Expos. 2 (2003)
content of the fault current during single-phase to grounding faults in 574–578.
compensated network, in: Proc. IEEE Buch. Power Tech. Conf., June 28–July 2, [17] K.M. Winter, The RCC ground fault neutralizer — a novel scheme for fast
2009, pp. 2497–2501. earth-fault protection, in: International Conference and Exhibition on
[7] Xiangning Lin, Jingguang Huang, Shuohao Ke, Faulty feeder detection and Electricity Distribution, Turin, Italy, 2005, pp. 1–4.
fault self-extinguishing by adaptive Petersen coil control, IEEE Trans. Power [18] J. Tian, Q. Chen, L. Cheng, Y. Zhang, Arc-suppression coil based on transformer
Deliv. 26 (April (2)) (2011) 1290–1291. with controlled load, IET Elect Power Appl. 5 (September (8)) (2011) 644–653.
[8] A. Kalyuzhny, Analysis of temporary overvoltages during open-phase faults in [19] W. Peng, C. Baichao, T. Cuihua, B. Sun, M. Zhou, J. Yuan, A novel neutral
distribution networks with resonant grounding, IEEE Trans. Power Deliv. 30 electromagnetic hybrid flexible grounding method in distribution networks,
(February (1)) (2015) 420–427. IEEE Trans. Power Deliv. 32 (June (3)) (2017) 1350–1358.
[9] Q. Wang, M. Cheng, Z. Chen, Steady-state analysis of electric springs with a [20] W. Wang, X. Zeng, L. Yan, X. Xu, J.M. Guerrero, Principle and control design of
novel ␦ control, IEEE Trans. Power Electron. 30 (December (12)) (2015) active ground-fault arc suppression device for full compensation of ground
7159–7169. current, IEEE Trans. Ind. Electron. 64 (6) (2017) 4561–4570.
[10] B. Gustavsen, J.A. Walseth, A case of abnormal overvoltages in a Petersen [21] R. Burgess, A. Ahfock, Minimising the risk of cross-country faults in systems
grounded 132-kV system caused by broken conductor, IEEE Trans. Power using arc suppression coils, IET Gener. Transm. Distrib. 5 (July (7)) (2011)
Deliv. 18 (January (1)) (2003) 195–200. 703–711.
[11] F.M. Gatta, A. Geri, S. Lauria, M. Maccioni, Analytical prediction of abnormal [22] B. Xu, J. Zhang, X. Cai, Grounding phase determination in non-effective
temporary overvoltages due to grounding faults in MV networks, Elect. Power grounding systems in case of unsymmetrical voltage, Trans. China
Syst. Res. 77 (August (10)) (2007) 1305–1313. Electrotechn. Soc. 26 (December (12)) (2011) 175–182.
[12] L. Kai, L. Mengshu, L. Zhengfeng, D. Zhenghua, T. Shaoju, Analytical [23] B. Liu, C. Wang, X. Li, Analysis and application of zero-sequence voltage of
closed-form expressions of DC current ripple for three-level neutral point single-phase ground fault asymmetrical system, Proc. CSEE 34 (October (28))
clamped inverters with space-vector pulse-width modulation, IET Power (2014) 4959–4967.
Electron. 9 (April (5)) (2016) 930–937.