Professional Documents
Culture Documents
EFS.10.05.01R.1 Design Basis For Instr PDF
EFS.10.05.01R.1 Design Basis For Instr PDF
CONTENTS
1.0 INTRODUCTION
1.1 GENERAL
The purpose of this document is to define the basis of design and the generic
guidelines to be applied for the design and selection of Instrumentation, systems
and equipment, in accordance with the latest international standards and industrial
practice. All parties involved in the design and engineering of offshore facilities for
QP, shall use this document to achieve the Standard required by QP.
1.2 DEFINITIONS
For the purposes of this document the following definitions of terms and
interpretations shall apply irrespective of any other meaning the words
may have in other projects.
QPis the party that initiates the project and ultimately pays for its design
and construction. QP will generally specify technical requirements. QP
may also include agent or consultant to act for QP.
CONTRACTOR is the party that carries out all aspects or part of the
design, engineering, procurement, construction and commissioning of the
plant. QP may sometimes undertake all or part of the duties of
CONTRACTOR.
1.2.2 Abbreviations
The codes, standards and specification listed in the standard EFS.00.08.02 shall
be used.
The selection of makes and types of instruments shall be made from the preferred
Instrument Vendors" as prepared by QP for each project.
The following factors shall be taken into consideration for selection of instruments:
Instrument maximum span should be selected suitable for the required precision
and accuracy. Unless otherwise specified, the calibrated instrument ranges shall
be selected such that the normal value will be between 50 and 75 percent of the
calibrated span, taking into account the specified minimum and maximum values
of the process conditions. In cases such as the flow meters, the ranges shall be
selected to cover start-up, circulation and upset conditions as well.
Selection of ranges for process stream analysers should also take into account
abnormal process, start-up and shutdown conditions.
Where the design pressure of the line is higher than the design range of the
instrument, over range protection shall be applied.
For automatic transmitter comparison, trip transmitters should have the same
range as those used for control. The setting of the trip action should be between
10% and 90% of the transmitter output.
The ranges of certain trip instruments, such as those for high level and gas
detection, shall be selected such that the trip point accuracy is not degraded.
For reasons of loop integrity, communication from DCS to the field mounted final
control elements shall be 4 to 20 mA.
Instrumentation such as for machine monitoring, fire and gas detection, tank
gauging, sub-systems for motor operated valves, etc. may have other signal
ranges, signal transmission voltage levels and wire systems according to
manufacturers' standards.
2.6.1 General
Safety certification for the selected type of protection for the installed
electrical apparatus shall be made available.
2.7.1 General
All instruments shall be fully rated to system design as per PEFDs and UEFDs.
Instruments, fire and gas tag numbers and equipment identification to abide QP
Engineering Standard ES.0.07.0031 entitled Offshore Plant Equipment Tag
Identifiers.
Material for sour service shall be certified in accordance with NACE MR 0175 as
well as in compliance with QP Engineering Standard ES-M-11 entitled Engineering
Standard for specification of sour service materials.
The use of aluminium and its alloys should be restricted, particularly in hazardous
areas due to the possibility of generation of incendive sparks.
• Type 316 stainless steel or Type 317 L stainless steel on all process
and utility services limited to a maximum temperature of 60 deg C
(140 deg F);
Particular attention shall be given to the salt content of the fluid streams,
the atmosphere and the related operating temperatures to assure that
chloride stress corrosion cracking, crevice corrosion pitting of corrosion
All materials that are not inherently corrosion resistant in the service
environment shall be externally painted.
2.16.6 Painting
Carbon steel and alloy steel surfaces shall be painted in accordance with
QP Engineering Specification ES-Q-12 entitled Specification for painting
and wrapping metal surfaces/new construction and maintenance.
Voltages lower than these shall be provided and derived from the above
complete with miniature circuit breakers for maintenance and isolation
purposes.
The Instrument Air header pressure is 7.0 Barg. However, all control valve
actuators shall be sized for a minimum instrument air supply pressure of 4.5
Barg.
Where instruments require shades which are not available as standard equipment
or require specially made supports and brackets such as for in-line flow meters,
displacer level instruments, tank gauges, etc., these shall be shown on detailed
construction drawings.
Local panels shall be avoided wherever possible and in any case require the
approval of the Principal.
Contractor shall specify materials and an appropriate paint system suitable for the
intended location and atmosphere. Where the local panel or cubicle requires
openings for ventilation, these openings shall be provided with screens to prevent
the entry of animals or insects.
There shall be no direct process connections between process fluids and enclosed
instrument panels. Wherever necessary transmitters shall be applied.
Whenever possible, instruments shall be mounted at eye level, but in any case not
lower than 750 mm from the base.
Local panels shall be located well away from steam outlets and constant drizzles
of water.
If a single meter is insufficient to meet the turndown then parallel meters shall be
applied. Selection of parallel meters shall be controlled automatically by the DCS.
To ensure proper flow meter selection, correct process data such as flow rate,
temperature, pressure and density shall be provided for minimum, normal and
maximum operating conditions (including start-up and emergency conditions).
Required accuracy of the measurement and the maximum allowable pressure loss
under all process conditions shall also be available before the proper flow meter
can be selected.
The ratio of the orifice diameter to line diameter (d/D) for orifice plates
shall be between 0.50 and 0.70 with 0.60 the preferred d/D ratio
approach.
Orifice bores shall be calculated by the formulae from the latest edition of
“Flow Measurement Engineering Handbook” by Miller.
Junior or Simplex type orifice assemblies are preferred, however, the use
of conventional orifice flanges are acceptable provided it is in accordance
with Piping Material Specification.
The minimum ANSI rating for an orifice flange shall be 300 LB.
Orifice plates shall also have the equipment identification number and
type of material permanently embossed and readily visible on the metal.
The identification shall comply with ISA RP3.2, Recommended Practice
for Flange Mounted Sharp Edged Orifice Plates for Flow measurement.
The outlet side of the orifice plate tab handle shall be permanently
marked with; instrument tag number, orifice diameter (MM), line size,
pressure rating and plate material.
Square edge orifice plates, with flange tapings, shall be used wherever
possible.
Depending on line size and site preference, the orifice bore should be
rounded off to the nearest 0.1 or 1 mm.
Installation requirements
Restriction orifice plates are devices for creating a certain pressure drop
or for limiting a flow rate. They are not intended for flow measurement but
are similar to flow metering orifice plates, in construction and sizing
method. They are normally placed between normal piping flanges.
Meter runs for pipe sizes DN 50 and larger shall only be applied for
custody transfer requirement or where a high accuracy is required.
The use of transmitters with integral orifice, for flow metering in line sizes
smaller than DN 15, requires the approval of the Principal. For these
types of measurement, small Coriolis mass flow meters should also be
considered.
3. Vortex flow meters should not be used in wet gas or wet steam
applications.
4. Vortex flow meters should not be considered for very viscous, waxy
or erosive services.
5. Vortex flow meters shall be provided with process flanges. The use
of water type vortex flow meters requires the approval of the
Principal.
NOTE: The ratio of vortex meter range and vortex meter maximum
capacity shall normally be less than 1:3 and this criteria may be used as
a screening value in sizing reviews. Exceeding this ratio could lead to
elevated minimum flow threshold levels, making the meters unsuitable for
proper control.
5. If the meter size is smaller than the line size, concentric pipe
reducers shall be used.
6. Care shall be taken that the process gaskets are properly aligned
and do not interfere with the flow profile.
a) PTFE
b) PVA
Liquid penetration is less than for PTFE, but PVA does not
retain its original shape once this has changed under pressure
and temperature. This problem can be overcome by reinforcing
the liner with a steel wiring mat. Reinforced PVA is suitable for
vacuum service.
c) Ceramic
d) Rubber
2. Ultrasonic flow meters shall be considered for use on large lines and
for large turndowns, if the cost of a vortex flow meter is higher.
1. Ultrasonic flow meters can be installed at any point in the pipe run.
However, locations having high noise, such as cavitating or noisy
control valves, should be avoided. The meter shall not be installed
directly downstream of sources of aeration, such as cavitating
pumps, throttling valves or an aerating mixing tank.
2. The pressure drop across the meter under normal and abnormal
conditions is an important factor in the selection of Coriolis mass
flow meters. Care shall be taken to ensure that cavitation does not
occur under any process condition, as this will seriously damage the
meter.
3. Certain types of Coriolis mass flow meters are also suitable for gas
applications. Typically, a minimum gas density of 4.5 kg/m3 is
required. For all gas applications, the supplier shall be consulted to
confirm suitability.
4. Avoid the use of Coriolis mass flow meters in two-phase fluids. The
presence of a small amount of gas will create erratic
measurements.
The use of "variable area" flow meters, often called "rotameters", shall be
restricted to simple applications such as measurement of purge, bubble-type level
measurements, cooling or sealing fluids, or in sample conditioning systems for
analysers.
Turbine meters shall have flanged connections and the body material shall be
carbon steel with stainless steel internals, unless the application requires other
materials as specified by the Principal.
Turbine meters for custody transfer shall have two pick-up coils for use with an
electronic pulse integrity input circuit in the read-out system. All turbine meters
shall have signal amplifiers mounted close to the meter. Turbine meter systems
for liquid custody transfer shall be designed and installed in accordance with the
API Manual of Petroleum Measurement Standards.
Flow straighteners shall be used with turbine meters if specified by the vendor to
meet the required flow meter performance.
Positive displacement meters (PD meters) shall have flanged connections. The
body material shall be carbon steel unless the application requires other materials
as specified by the Principal.
PD meters shall not be selected for use with non-lubricating liquids such as LPG.
Flow limiting devices shall be considered to prevent over-ranging of PD meters.
Certain types of PD meters have their maximum capacity limited not only by flow
but also by the maximum allowable pressure drop across the meter. Consideration
should be given to limiting the maximum pressure drop, especially when the meter
is used with liquids having a high viscosity when starting from cold.
PD meters shall have a direct-coupled pulse generator and shall be provided with
signal amplifiers mounted close to the meter. If used for toxic products, the meters
shall have magnetic couplings to counters.
The meters shall be protected against damage due to hydraulic shock, e.g.
caused by the quick opening and closing of valves.
3.9 ACCESSORIES
3.9.1 Strainers
The strainer enclosure shall be of the quick-opening type with valve vent
and drain connections. The strainer shall have replaceable stainless steel
inserts.
The mesh size for the screen shall be as recommended by the meter
supplier.
For liquid applications, turbine meters and PD meters should have gas
eliminating facilities upstream of the meters. For heavy products, this
may be achieved by a vent valve on the strainer, venting being done
manually from time to time. Automatic gas eliminators shall be provided
where the separation of entrained air or other gases can be expected
more frequently. They should be of the tangential type.
In addition to the automatic vent valve, the gas eliminator shall have
facilities for manual draining and venting. The float operation of the
automatic vent valve shall be capable of opening this valve at the
maximum allowable operating pressure of the gas eliminator, as proved
by testing or by a design calculation.
If none of the flow meter described above will satisfy the requirements of a specific
application, other types of instruments may be supplied if approved in writing by
QP.
External level instrument cages shall be fitted with plugged vent valve, plugged
fill valve and test connection.
6. For liquid / liquid interface service, special attention shall be paid to the
diameter of the displacer or float to achieve a satisfactory sensitivity,
especially when the difference in densities is small.
7. For special applications, such as highly viscous, waxy process fluids, fouling
services, and emulsive interface levels where the above measuring
techniques cannot provide accurate measurements or where intensive
maintenance is needed to ensure accurate level measurement, other
measurement principles shall be considered. These techniques include
ultrasonic, capacitance, admittance, radar, microwave, radioactive, laser or
bubble. Such applications require the agreement of the Principal.
For the measurement of liquid level in vessels in which the vapour space
is truly at the ambient atmospheric pressure, the low-pressure connection
of the instrument can be left open to atmosphere.
• the reference leg will fill with the process liquid when it condenses
under operating pressure at the highest ambient temperature.
Two options are available for filling the wet reference leg:
If a dry reference leg is used, the range elevation is only required if the
minimum level to be measured is higher than the lower connection and/or
if the instrument centre is below the lower connection of the vessel.
If a wet reference leg is used, the range suppression shall take into
account the static heads of the liquid in the reference leg on the low-
pressure side and of the liquid between the minimum level and the
instrument centre on the high-pressure side.
Ranges for displacer instruments shall be 356 mm (14”), 813 mm (32”) or 1219
mm (60”).
For instruments with internal vessel mounting of the displacer tube, the hanger
extension length shall be as required by the application and specified by the
Principal.
For high temperature as well as low temperature and cryogenic services, torque
tube heat insulation extensions or torque tube extensions shall be applied. The
instrument supplier shall be consulted for details.
Measuring principle shall be micro power impulse radar with Time Domain
Reflectometry (TDR) with co-axial/twin rod probes guided wave radar transmitters.
Electronic transmitters shall be integral with twin rod probes for normal application
less than 200°C and remote for high temperature applications.
For liquids services, which tend to foul an admittance probe should be considered.
All level switch applications shall utilise differential –pressure type level
transmitter.
This type of level gauge is the one most commonly required by the piping
classes. They are restricted to ANSI 150, 300 and 600 pressure ratings
and the design temperature shall not exceed 265 ºC. Reflex type level
gauges without lighting shall be used wherever possible. Through vision
type level gauges in combination with lighting shall only be used for
4.7.1.2 Bull’s-eye-type level gauges are restricted to the ANSI 900 and 1500
pressure ratings and shall be used in steam services.
4.7.1.3 Magnetic-type level gauges are restricted to the ANSI 150, 300, 600 and
900 pressure ratings and shall be of the magnetic-coupled level indicator
type. Each level gauge shall have DN 20 flanged vent and drain
connection and shall be used in very toxic services.
The position of a level gauge shall allow reading from ground level,
platforms or ladders.
Flange pairs of level gauges shall be in line and vertically above each
other to ensure a truly vertical position.
If the required level range is too large for a single gauge, multiple level
gauges shall be used, with the connection nozzles staggered for a
visibility overlap of at least 25 mm.
General purpose Bourdon tube type pressure gauges should be specified. Where
general purpose pressure gauges are not suitable due to corrosion, plugging, etc.,
pressure gauges with a diaphragm seal shall be used.
Pressure gauge ranges shall be selected from the following series such that the
operating pressure is between 50 to 75% of scale and the design pressure (relief
valve set pressure) should not exceed the range:
The ranges for pressure instruments should be selected from the series as given
for pressure gauges (5.1), but where narrow-span instruments are required the
range shall cover the minimum and maximum values as specified in the
instrument engineering data sheets.
6.1 GENERAL
For remote temperature indication resistance elements (8.4) shall be used. For
temperatures above 200ºC, thermo couples shall be used.
Thermowells shall be flanged 1.5” with 6.5 mm bore and ½” NPT female
connection for the temperature element.
For the measurement of a fluid temperature below 0 °C, the length of the head
extension shall suit the insulation thickness, and the head shall extend at least 200
mm outside the insulation.
The use of optical pyrometers should be considered for monitoring furnace tubes
at very high temperatures.
6.3 THERMOCOUPLES
Resistance elements shall normally be of the platinum type Pt 100 (100 ohm at 0
°C), tolerance class A, using the 3-wire system.
Linearisation shall take place at the local transmitter. The transmitter output signal
shall be linear with the measured temperature.
All temperature transmitters shall have a galvanic separation between the sensor
element and the output amplifier.
On critical and variable speed rotating equipment, the speed measurement should
have a separate channel in the machine monitoring system.
For equipment such as forced-draught fans of boilers or furnaces, where the
speed instruments are not supplied as part of the equipment, their make and type
shall be as specified by the Principal.
9.1 GENERAL
For monitoring the vibration and shaft position of rotating equipment, the probes
and oscillator/demodulators are usually supplied with the equipment. The make
and type of these items shall therefore be agreed upon at an early stage of the
project, to ensure compatibility with this permanent monitoring system and the
portable test equipment used by the Principal.
This section is based on the usual situation where each measured value (axial
shaft position or radial vibration) will have independent probes and
oscillator/demodulators, hereafter called "channels".
9.2 MONITORS
Where axial shaft position is monitored, this will normally be used for alarm
annunciation and for machine protection.
These monitors shall be of the dual-channel input type with a selector switch
enabling a shutdown initiation by either channel alone or by both channels
together when reaching the set point(s), i.e. a 'dual voting' monitor.
NOTE: During normal operation, the selector switch shall be in the dual-voting
position where both channels are required for initiating a shutdown. If one channel
becomes inoperative, the remaining healthy channel shall be selected for the
shutdown.
The monitors shall not have a shutdown override switch (shutdown by-pass).
NOTE: This deviates from the specifications in API 670. Where a shutdown
override is required, this shall be incorporated in the (downstream) IPS.
Where radial vibration is monitored (mainly for alarm purposes), the monitors may
be of the single-channel or dual-channel type.
Doc. File No: EFS.10.05.01R1 Page 34 of 49 Custodian : ENF/4
DESIGN BASIS FOR INSTRUMENTATION
The key-phaser channel, if present, does not need a permanent monitor. This
signal shall be available on a test socket for orbit analysis, etc.
Each monitor shall be provided with potential-free contacts for external alarms and
a 4 to 20 mA auxiliary output or a serial communication link for remote monitoring.
If indicated in the PEFS, the display on the local panel (near the rotating
equipment) should comprise:
a) pre-alarms (alert) and trip alarms (danger) as specified above for the main
panel;
Valves shall be in accordance with Instrument Data Sheet, Valve Data Sheet and
shall also comply with the requirements of Piping and Valves Material
specification.
Only during shutdown, blowdown or upset condition may the noise level generated
exceed 85 dBA at 1 meter from the valve. Under no circumstances shall the noise
level exceed 120 dBA irrespective of duration.
Ancillaries such as solenoid operated valves, manual reset latch, filters regulators,
speed controllers and the like shall be installed inside a GRP junction box readily
accessible from a single location 1400 mm. Above ground.
All shutdown and blowdown valves shall be reset manually at the field prior to re-
activation to service.
Pneumatic actuators shall be of failsafe, spring return, piston type. All shutdown
and blowdown valves shall be certified fire-safe to API 6FA or API 607.
Shutdown or blowdown valve closing speed shall be better than 1 second per inch
of line size diameter.
All accessories including filter regulators, etc. shall be of 316 L stainless steel
constructions or aluminium with epoxy powder coating.
Each blowdown valve shall have downstream manual block valves with bleed
valves.
Isolation valves, for equipment, which require regular access and where the total
energy required to open or close the valve is large, shall be fitted with locally
operated motor operators.
Motor Operated Valves shall be supplied with motor, gearbox and handwheel and
shall be complete with integral control unit, motor starter, control gear and selector
switch for local-off-remote and spring-return rotary knob switch for open/close and
emergency stop pushbutton.
Valve position switch for the indication of valve position either in the fully open or
fully closed position shall be provided. Illuminated position indication shall be
provided locally.
All MOV shall be provided with remote control capability to be opened & closed
from the DSC via direct digital looped to a maximum of five units per closed loop.
Doc. File No: EFS.10.05.01R1 Page 36 of 49 Custodian : ENF/4
DESIGN BASIS FOR INSTRUMENTATION
Electric motor actuators shall be suitable for use with a normal 415 volts, 3 phase,
50 HZ power supply and the hazardous area classification.
Each wellhead choke valve should have trim capacity to fit the maximum flowing
condition. Mechanical limit stop to prevent the well being overproduced shall NOT
be utilised.
Wells containing sand and for noise control; multi-stage, multi-path, velocity
control trim with solid tungsten carbide stack, plug and seat ring shall be utilised.
Tungsten carbide trip design shall be certified to take impact load of 420 joules.
Wellhead choke valves shall be directly flanged onto the X-mas trees.
Wellhead choke valves shall be speed limited such that they cannot be opened a
maximum production in less than 1 hour.
Fixed beam chokes are required in addition to adjustable chokes only if high high
flow alarms are not provided.
Actuation medium shall be instrument air. Hydraulic fluid may replace instrument
air, as actuation medium if minimum pressure needed is higher than 100 psig.
All actuators shall be low volume double acting piston to provide the necessary
stiffness for control. Valves sizes DN 50 and below may use spring diaphragm
actuators.
Control valve shall NOT be used for any shutdown or blowdown application.
On venting applications where the valve is closed most of the time, control valves
shall be class V or class VI leakage per ANSI 16.104, and in very critical
applications where leakage is not allowed, control valves shall have MSS SP 61
leakage classification
Doc. File No: EFS.10.05.01R1 Page 37 of 49 Custodian : ENF/4
DESIGN BASIS FOR INSTRUMENTATION
High speed valves shall be fitted with stop plates at the top of the plug. Valves
shall be designed to stop at the bonnet for safety reasons. Limit stops in the
actuator assembly shall be avoided.
Anti-surge control valve shall be suited for its service and shall be high
performance, quick response having a linear flow characteristics and be sized to
have a rated Cv of 1.8 to 2.2 times the calculated Cv at normal flow to prevent
surge.
Control valves that requires faster speed of response shall be properly calculated
and when necessary aided with boosters and quick exhaust valves.
Multi-path, multi-stage trim design that reduces velocity and energy shall
be considered for unusual application such as highly erosive stream for
noise and cavitation control.
11.4.2 Noise
This noise shall be based on a bare pipe without any considerations for
thermal and acoustic insulation. Noise calculation shall be provided with
plus zero tolerance. Noise calculation shall be based on the latest edition
of IEC 60534-8-3 standard.
Control valves shall be furnished with stem travel indicators with scales.
For liquid service, the trim outlet velocity shall not exceed 100 feet per
second. For gas and vapour service, the trim outlet velocity head shall
not exceed 79 psig.
The Supplier shall calculate and record on the data sheet the minimum,
normal and maximum required Cv.
Actuators shall be adequately sized to stroke the valve based on the line
rating at the differential pressure to which the valve will be exposed.
Valve actuators shall be air operated, low volume, double acting piston.
For valve sizes DN 50 and below actuator can be of the spring return
diaphragm type.
PRESSURE CLASSIFICATION
The minimum pressure ratings for carbon steel or alloy valves shall be in
accordance with ANSI B16.5, Pipe flanges and Flange Fittings given in
the Piping Material Specifications.
The minimum ANSI flange rating classes for valves shall be 300 lbs.
BODY
The minimum valve body size for hydrocarbon services shall be DN 25.
The minimum body size for air or water services shall be DN 20. Body
sizes smaller than DN 20 may use pressure regulator. Subject to QP
written approval.
BODY TESTS
Test pressure for valve bodies shall be in accordance with the rating
defined in ANSI B16.5.
FACE-TO-FACE DIMENSIONS
TRIM
Standard trim (plug, seat rings, valve plug stems, stem lock pins, packing
springs, spacers, and packing followers) shall be fabricated as a
minimum from 316 L stainless steel, unless stated otherwise by wetted
material criterion.
• Flushing liquids;
• Fluids containing solids;
• Pressure drops above 300 psig;
• Services above 600 deg F(316oC) unless a higher grade material is
required;
• Cavitating Liquid;
• Anti-surge valve;
• Vent valve
GUIDE BUSHINGS
PACKING GLANDS
BODY CONNECTIONS
HANDWHEEL
Handwheel shall be sized so that the rim pull does not exceed 60 pounds
force.
LUBRICATORS
All control valves with non – PTFE stem packing shall have lubricators
and steel isolating valves.
• Supply pressure;
• Controller input signal;
• Positioner output signal;
• Valve positioner for all services shall be calibrated for a input of 4-20
mA DC signal;
• Valve positioner and booster cases shall be of corrosion resistant
material.
Limit switches shall be snap acting and have the minimum form of two
single-pole, single-throw (SPST) contacts rated 24 VDC, 1.0 amp.
Globe valves shall be singled seated. Single seated valves may be either
top or cage guided.
Normally closed valves that control pressures and levels (such as for
flares and dumps) shall have single port trim for positive shutoff. Ö”ring
seals in the seat ring or plug are NOT acceptable for positive shutoff.
Butterfly valves may be supplied if the pressure drop is five psig or less.
The shaft of a butterfly valve shall be sealed at both ends and supported
with external bearings.
Butterfly valves that have been modified by having holes cut in the wafers
or discs are NOT acceptable.
All relief valves shall comply with the referenced codes and standards
including API 520/521.
Only during shutdown, blowdown or upset condition may the noise level
generated exceed 85 dBA at 1 meter from the valve. Under no
circumstances shall the noise level exceed 120 dBA irrespective of
duration.
11.5 REGULATORS
The application is at a remote location where air is not available for control valve
operation.
The pneumatic pilot valves function as pilot devices only. The pilot valves shall
NOT control process flow.
Solenoid valve shall function as pilot device only and shall NOT control process
flow.
Solenoid valve coil shall be rated for continuous duty in encapsulated high
temperature coils 180°C (350°F), Class H insulation and 316L stainless steel
bodies and trim.
Solenoid valve for intrinsically safe application shall be rated 12-28 VDC with
maximum power consumption of 3-6 watts and be used with approved galvanic
isolator.
Solenoid valves for shutdown and blowdown application shall be provided with
local manual reset mechanism and rated EEx”d”.
Solenoid valve shall be direct acting type. Pilot operated or activated are NOT
acceptable.
11.8 PROXIMITY
Probes that are maintainable or retrievable on-line and has higher signal to noise
ratio are preferred.
Industry standard twisted pair is preferred, special cabling from probe to analyser
is NOT acceptable without written approval from QP.
The measuring cell/sensor shall be either two or four electrode with integrated
RTD temperature sensor of Pt 100. The sensor type shall preferably be inductive
conductivity sensor with completely encapsulated sensor electronics.
Clamp-on type sand monitor shall be installed at each production manifold, a non-
intrusive type and on-line maintainable either of ultrasonic or nucleonic monitoring.
Corrosion and erosion coupons shall be located at all points as indicated in the P
& ID’s where significant corrosion or erosion is anticipated.
13.1 GENERAL
This section applies to instruments on which the measured variables are displayed
in the control room by a Distributed Control System (DCS). Use of dedicated
(analogue) instruments, such as indicators, recorders and controllers, shall be
kept to a minimum and requires the approval of the Principal.
Monitoring and control functions shall be implemented in the control system (DCS)
with open architecture. All DCS modules necessary for control (process
manipulation), communication, man-machine interface and interface with other
sub-systems shall be implemented to achieve the system availability and mean
time between failure (MTBF) specified by the Principal. The extent of required
redundancy shall be determined in consultation with the Principal. This includes all
components in a control loop such as process variable inputs (may be multiple
Doc. File No: EFS.10.05.01R1 Page 47 of 49 Custodian : ENF/4
DESIGN BASIS FOR INSTRUMENTATION
The contractor shall engineer, design, and install the required marshalling
cabinets.
All field cables, except for the Fire & gas, shall be marshalled in marshalling
cabinets.
All incoming field cables shall be connected to separation terminals, from there
marshalling wiring to interface unit eg. trip amps/isolators and then marshalling
wiring to system cables terminal blocks. Connection between marshalling cabinets
and ESD and DCS cabinets will be by system cables.
14.0 CUSTODIANSHIP
Note :
The revision history log shall be updated with each revision of the document. It shall
contain a written audit trail of the reason why the changes/amendments have
occurred, what the changes/amendments were, and the date at which the
changes/amendments were made