Tan Delta Test On 6KV HT Motor
Tan Delta Test On 6KV HT Motor
08/22/2011 9:12 AM
Dear friends,
We tested Tan Delta test on a 6 KV HT Motor. We got the following readings at different
voltages,
Motor Details:
KW: 275KW
KV: 6KV
The tested party said that these readings indicate partial discharge. We don't have any
spare motor for this. Kindly suggest these readings really indicate serious Partial
discharge???
If we run the motor it will fail? Or it will take long time to fail??
| |
#2 "Re: Tan Delta Test on 6KV HT Motor" by TonyS on 08/22/2011 9:21 AM (score
1)
#5 "Re: Tan Delta Test on 6KV HT Motor" by rsbarve on 08/23/2011 1:01 AM (score
1)
Anonymous
Poster #1 #1
http://en.wikipedia.org/wiki/Tan_delta_test
Register to Reply
TonyS
#2
Guru
If you don't have a spare what choice do you have? You run it and get
a spare sorted quickly. If you can leave it shut down then you've all
the time in the world, until you need it in a hurry!
Posts: 3650
Register to Reply Score 1 for Good Answer
Good Answers: 143
olehwi
#3
Power-User
How soon will the motor break down - will depend on the insulation
used in the motor and on the number, amplitude and frequency of
over-voltages and surges appearing at the terminals of the motor.
Register to Reply
leveles
#4
Guru
Join Date: Jan 2008 The scarcity of the explanations allow two possibility. One is Olehwi's:
the motor run long enough highly stressed, and low level of corona
Posts: 1756 discharge is eating the insulation at the end of its life. The other is,
that the motor was in storage long enough to absorb moisture in the
Good Answers: 59
insulation. That can be cooked out by running the motor without load
for a couple of days, giving a chance the moisture to bake out.
BUT, I have a problem with the basic question itself. Any motor is a
very lossy capacitor from the silicon iron lamination alone. What is the
loss factor in a newly assembled motor? Without knowing that,
deterioration - if any - can only be guesstimated.
One more note. Corona and other insulation failure modes are voltage
threshold dependent. You will see them at higher than normal
voltages. Attempting to measure them at low voltages, as reported, is
meaningless.
Register to Reply
rsbarve
#5
Participant
2) Take heart! Does not appear too bad as various factors are
involved in diagnosis. One of them is the insulation system used.
Older systems have higher tan delta on which IEC allowed approx.4.5
% at rated voltage. Olehvi & levles are right and you should have
report of condition on new motor for better understanding.Otherwise,
check the system used and results of same make from same
manufacturer.
5) Cleaner and dry 0verhang can improve tan delta if the windings are
found contaminated with conducting dust.
regards
Register to Reply Score 1 for Good Answer
No more "Almost" Good Answers.
MMKumar
#6
Active Contributor
In reply to #5
Posts: 13 kindly give details how do u analysis the tan delta results.
Register to Reply
ARUN DOGRA
#7
Participant
In reply to #6
Posts: 3 AS YOU KNOW THE TAN DELTA TEST ALSO CALLED LOSS ANGLE OR
DISSIPATION FACTOR TESTING , IS A DIAGNOSTIC METHOD OF
TESTING MOTOR WINDINGS INSULATION QUALITY. IF THE
INSULATION IS GOOD, FREE FROM DEFECTS LIKE WATER TREE,
ELECTRICAL TREE, MOISTURE AND AIR POCKETS ETC THE WINDING
APPROACHES THE PROPERTY OF A PERFECT CAPACITOR. IF THERE
ARE IMPURITIES IN THE INSULATION, THE RESISTANCE OF
INSULATION DECREASES, RESULTING THE INCREASE IN RESISTIVE
CURRENT THROUGH THE INSULATION. THE CURRENT AND VOLTAGE
WILL NO LONGER BE 90 DEGREE OUT OF PHASE AND THE
DIFFERENCE IN OUT OF PHASE (FROM PEFECT POSITION OF 90
DEGREE) IS THE INDICATIVE LEVEL OF INSULATION
CONTAMINATION/DETEORIATION. THIS IS CALLED TAN DELTA.
ANALYSIS OF READINGS THE READINGS SHALL BE ANALYSED IN
REFERENCE TO THE MANUFACTURER RESULTS/DESIGN RESULTS.
THE INCREASING TREND W.R.T INCREASING TEST VOLTAGE AND BY
AGAING GIVES THE INDICATION OF FUTURE FAILURE. NORMALY THE
VALUE SHOULD BE BELOW .03 RADIAN (3%) HOWEVER THE
INTERPRETATION SHALL BE CONCLUDED ON CHECKING PD,PI,
DELTA C , DC LEAKAGE CURRENT & SURGE TEST ALSO. REGARDS
AKD
mohanlal (Electrical)
(OP)
9 Jan 06 06:18
The generator / motor winding power factor or tan delta test was carried out for the 3.3 KV equipments. The
generator ratings are 8.0 MW & motor ratings are from 175 KW to 1600 KW.
The test referred to as Tip-up test is performed at a number of levels of voltage from 25% to 100% of line to
ground voltage to obtain the PF vs voltage chs. PF Tip up value is defined as the difference between the PF
measured at the line to ground voltage and the PF measurred at teh lowest voltage in the test range (usually
25% of the line to ground voltage.)
The double system includes online DTA expert condition evaluation software,which evaluates and rates the
dielectric condition of the insulation tested
from the test results by comparison against the limits of PF of reliable winding insulation of units of identical
make, type, and ratings with the unit tetsed as well as against previous test records of the unit where
available.
In such test one of the generator is having % PF of average 6% for phase to ground and 3 % for phase to
phase. If the insulation is epoxy-mica, then the % pf is high and indicates possible deterioration.
Recommended to test it again within next three months to monitor the trending. Now the equipment is on
line.
Could anybody conclude from the test values and what is required to be done next?
I request Ragunath also to join in this question forum.
Thanks,
Subramanian
By all means repeat in three months - but ask the company or persons who are doing the tests for you to
justify why you need them.
i require information/explanation on how to do this test & why is required. What are expected values from
tests. Does this give one a foot print of the insulation of bushing/winding, etc?