Bulk Storage Facility CQS-EPR-TS-GEN-SPC-001
Specification for Safety Equipment Rev 3.0
1.0 INTRODUCTION
Eko Petrochem and Refining Company Limited wishes to construct and commission
20 new PMS storage tanks on a green field maximizing its capacity utilization.
In view of this, Crystaquantum Solutions has been awarded the contract to carry out
the Detailed Engineering Design and the requisite design to meet industry and
regulatory requirements.
The facility is intended to hold storage of one white product, Premium Motor Spirit
(PMS). The tank farm has a combined storage capacity of 453,640 cubic metres of
PMS.
1.1 Scope
The purpose of this document is to specify the basic safety and fire protection systems
and arrangements to be provided on Eko Petrochem and Refining Company Limited
BULK STORAGE FACILITYRMINAL. It covers the specification of equipment for fire
fighting, personnel safety and plant security.
3 of 12
Bulk Storage Facility CQS-EPR-TS-GEN-SPC-001
Specification for Safety Equipment Rev 3.0
4 of 12
Bulk Storage Facility CQS-EPR-TS-GEN-SPC-001
Specification for Safety Equipment Rev 3.0
Safeguarding of personnel.
Safeguarding of facilities.
Safeguarding of the environment.
To accomplish these safeguarding activities two steps will be followed:
Providing a safe plant layout by separation of the entire facility into hazardous
zones.
Provision of adequate access and escape routes.
Use of local and international codes and standard as it applies to the design,
installation and operation of oil and gas facility.
5 of 12
Bulk Storage Facility CQS-EPR-TS-GEN-SPC-001
Specification for Safety Equipment Rev 3.0
6 of 12
Bulk Storage Facility CQS-EPR-TS-GEN-SPC-001
Specification for Safety Equipment Rev 3.0
One hour nine minute (1hr 9mins) of maximum flow rate from fire water
storage tanks is expected via the fire water pump to fight fire.
Tank capacity of 1767m3 each is required for the fire water storage tanks and
shall be in accordance with the requirements of NFPA 22 and IP standard part
19.
7 of 12
Bulk Storage Facility CQS-EPR-TS-GEN-SPC-001
Specification for Safety Equipment Rev 3.0
The fire water main shall be permanently pressurized by means of a jockey pump. It
shall be pressurized at 6 barg at the highest point of the fire water network.
5.8 Hydrants
Hydrants shall be readily accessible from roads and be located in such a way that
possible damage by road traffic will be minimized and it shall be at a space of 80
meter to each other round the facility.
8 of 12
Bulk Storage Facility CQS-EPR-TS-GEN-SPC-001
Specification for Safety Equipment Rev 3.0
6.0 EXTINGUISHERS
6.1 Fixed Fire Extinguishing Systems
Fixed systems designed to extinguish fires shall be provided typically:
Sprinkler systems for storage tanks, and loading and unloading gantry.
The design and installation of fixed water spray systems shall conform to
NFPA 15.
6.2 Portable and Mobile Fire Fighting Equipment
One Hose cabinet containing firefighting equipment for use with hydrants shall be
located adjacent to hydrants or group of hydrants. The equipment contained shall be
sufficient to allow two hydrants hose streams to be operated and shall be typically:
Admin/Utility building
Customer service
Tank Farm Area
Product Pump house
Fire water pump house
Switch gear room
Workshop/storage
Canteen
Fire Truck Terminal
All portable fire extinguishers shall be of cartridge or stored pressure type, designed
for controlled discharge capability.
9 of 12
Bulk Storage Facility CQS-EPR-TS-GEN-SPC-001
Specification for Safety Equipment Rev 3.0
The water supply to foam systems is fresh from water tanks and of suitable quality to
prevent adverse effects on foam formation or foam stability. There will be supply from
foam tank to each storage tank, loading and unloading gantry.
Annually, all foam systems shall be thoroughly inspected and checked for proper
operation. The inspection shall include performance evaluation of the foam
concentrate or premix solution quality or both. Test results that deviate more than 10
percent from those recorded in acceptance testing shall be discussed immediately
with the manufacturer.
A foam system will extinguish a flammable liquid fire if operated within the proper
ranges of solution pressure and concentration and at sufficient discharge density per
square feet (square meters) of protected surface. The acceptance test of a foam
system should ascertain the following;