Introduction:
In HT electrical distribution, the system can be earthed or unearthed. The selection of earthed/unearthed cable will Blog Stats
depend on system. If distribution system is earthed then we have to use cable which is manufactured for earthed 15,295,254 hits
system. (Which the manufacturer specifies). If the system is unearthed then we need to use cable which is
manufactured for unearthed system. The unearthed system requires high insulation level compared to earthed
System. About Jignesh Parmar:
For earthed and unearthed XLPE cables, the IS 7098 part2 1985 does not give any difference in specification. The
Jignesh Parmar has completed M.Tech (Power
insulation level for cable for unearthed system has to be more.
System Control), B.E(Electrical). He is member
Thumb Rule:
As a thumb rule we can say that 6.6KV unearthed cable is equal to 11k earthed cable i.e. 6.6/6.6kv Unearthed
cable can be used for 6.6/11kv earthed system. because each core of cable have the insulation level to
withstand 6.6kv so between core to core insulation level will be 6.6kv+6.6kv = 11kv BUY ELECTRICAL SOFTWARES
For transmission of HT, earthed cable will be more economical due to low cost where as unearthed cables are not
economical but insulation will be good.
Generally 6.6 kV and 11kV systems are earthed through a neutral grounding resistor and the shield and armor are
also earthed, especially in industrial power distribution applications. Such a case is similar to an unearthed
application but with earthed shield (some times called solid bonding). In such cases, unearthed cables may be
used so that the core insulation will have enough strength but current rating is de-rated to the value of earthed
cables. But it is always better to mention the type of system earthing in the cable specification when ordering the
BUY ELECTRICAL NOTE IN PDF
cables so that the cable manufacturer will take care of insulation strength and de rating.
Rate this:
14 Votes
Share this:
Facebook Email LinkedIn More
BUY ELECTRICAL SOFTWARES.
Like
Be the first to like this.
Related
EHV/HV Cable Sheath Earthing Types of Neutral Earthing in Power Proud to be an IndiBlogger
With 42 comments Distribution electricalnotes.wordpress.c...
85
With 38 comments
/100
Type of Electrical Power Distribution systems
With 4 comments
Recent Posts
32 Responses to Difference between Unearthed Cable & Earthed Cables Electrical Thumb Rules-VENTILATION &
CEILING FAN
vamsi says:
Electrical Thumb Rules-Light Sources
January 3, 2013 at 5:49 am
Quick Reference-Fire Fighting (Part-2)
Plz mention where unearthed cables are used in detail.(with applications)
Quick Reference-Fire Fighting (Part-1)
Reply Electrical Thumb Rule- High Rise Building (As
per NBC)
sureshkumar says:
January 19, 2013 at 5:22 pm
Archives
Thank you.It is very useful to me
November 2019 (1)
Reply October 2019 (2)
Please describe me that can I used 11 kv xlpe HT cable in place of 23 KV HT cable ? January 2019 (3)
Thanks a lot for providing these much valuable information. But I am unable to download your Electrical Tools. Pl. October 2017 (1)
brief me how to download the same. September 2017 (1)
Thanks in advance
August 2017 (1)
Satyam
July 2017 (2)
Reply
June 2017 (1)
So, I am really confused, do we need unearthed cable for a MV system with LRG clearing the fault within 1 min or December 2014 (2)
Can you give any comments if semiconducting screens are required/ provided to make earthed 3.3kV grade May 2014 (2)
cables suitable for 3.3kV/ 3.3kV unearthed system, which is normally not provided with 3.3 kV system? April 2014 (2)
When using wye-broken delta earthing transformers, should we rate cables as like unearthed systems or earthed April 2012 (2)
systems?
March 2012 (3)
Reply February 2012 (2)
EEP
Sandeep Kalsi says:
December 14, 2015 at 11:02 am
Dear Sir,
I have 33 KV/ 11KV 2.5 MVA Delta /Star solidly grounded Step Down Transformer. The 33 KV Input is through
over head Conductor and output is 11 KV cable to VCB. Now We are going to install one more 11KV/415 volts
Delta Star Transformer at a distance of 390 Meter distance through overhead 11 KV 3 core cable. Please sugest
which cable we have to select Earthed or Unearthed. Also exp;lain why we selected for the same.
Reply
Reply
Abstract of CPWD-Part 1
Dear sir can please mention which specific standard shall be followed for 33KV Unearthed cable. As you know Abstract of IE Rules
that IS 7098 part-II and IEC 60502 (up to 30 KV)don’t cover it
Abstract of IS Code.
Reply IS 1255
IS 15652/11171/1445/1678
Thanx sir. Above explanation was very useful. IS 694 / 1554 / 11892
Reply
IE Rules for DP Structure
Electrical Notes
Anu says:
ElectRICAL. Q&A
June 14, 2016 at 6:45 am
Electrical Q&A Part-1
sir,if the cable tray is not earthed any problem for the mv cable running on the cable tray
Electrical Q&A Part-2
Reply
Electrical Q&A Part-3
EXCEL TOOL
In unearthed system,Neutral is earthed through a resistance to reduce the fault current,obviously,it can be called
as restricted neutral system rather than unearthed system.
Reply mediafire.com/file/0qu8mt…
mediafire.com/file/bkzwat…
This site uses Akismet to reduce spam. Learn how your comment data is processed.