Difference between Unearthed Cable & Earthed Cables


JANUARY 2, 2013 32 COMMENTS
Jignesh.Parmar

Introduction:
In HT electrical distribution, the system can be earthed or unearthed. The selection of earthed/unearthed cable will Blog Stats
depend on system. If distribution system is earthed then we have to use cable which is manufactured for earthed 15,295,254 hits
system. (Which the manufacturer specifies). If the system is unearthed then we need to use cable which is
manufactured for unearthed system. The unearthed system requires high insulation level compared to earthed
System. About Jignesh Parmar:
For earthed and unearthed XLPE cables, the IS 7098 part2 1985 does not give any difference in specification. The
Jignesh Parmar has completed M.Tech (Power
insulation level for cable for unearthed system has to be more.
System Control), B.E(Electrical). He is member

Earthed System: of Institution of Engineers (MIE) and CEng,India.


Membership No:M-1473586.He has more than
Earlier the generators and transformers were of small capacities and hence the fault current was less. The star 16 years experience in Transmission -
point was solidly grounded. This is called earthed system. Distribution-Electrical Energy theft detection-
In Three phases earthed system, phase to earth voltage is 1.732 times less than phase to phase voltage. Electrical Maintenance-Electrical Projects
Therefore voltage stress on cable to armor is 1.732 times less than voltage stress between conductors to (Planning-Designing-Technical Review-
conductor. coordination -Execution). He is Presently
Where in unearthed system, (if system neutral is not grounded) phase to ground voltage can be equal to phase to associate with one of the leading business group
phase voltage. In such case the insulation level of conductor to armor should be equal to insulation level of as a Deputy Manager at Ahmedabad,India. He
conductor to conductor. has published numbers of Technical Articles in
In an earthed cable, the three phase of cable are earthed to a ground. Each of the phases of system is grounded “Electrical Mirror”, “Electrical India”, “Lighting
to earth. Examples: 1.9/3.3 KV, 3.8/6.6 KV system India”,”Smart Energy”, “Industrial
Electrix”(Australian Power Publications)
Unearthed System: Magazines. He is Freelancer Programmer of
Advance Excel and design useful Excel base
Today generators of 500MVA capacities are used and therefore the fault level has increased. In case of an earth
Electrical Programs as per IS, NEC, IEC,IEEE
fault, heavy current flows into the fault and this lead to damage of generators and transformers. To reduce the fault
codes. He is Technical Blogger and Familiar with
current, the star point is connected to earth through a resistance. If an earth fault occurs on one phase, the voltage
English, Hindi, Gujarati, French languages. He
of the faulty phase with respect to earth appears across the resistance. Therefore, the voltage of the other two
wants to Share his experience & Knowledge and
healthy phases with respect to earth rises by 1.7 times. If the insulation of these phases is not designed for these
help technical enthusiasts to find suitable
increased voltages, they may develop earth fault. This is called unearthed system.
solutions and updating themselves on various
In an unearth system, the phases are not grounded to earth .As a result of which there are chances of getting
Engineering Topics.
shock by personnel who are operating it. Examples : 6.6/6.6 KV, 3.3/3.3 KV system.
Unearthed cable has more insulation strength as compared to earthed cable. When fault occur phase to ground
voltage is √3 time the normal phase to ground voltage. So if we used earthed cable in unearthed System, It may be
Follow Blog via Email
chances of insulation puncture. So unearthed cable are used. Such type of cable is used in 6.6 KV systems where
resistance type earthing is used. Enter your email address to follow this blog and
receive notifications of new posts by email.
Nomenclature:
Join 12,051 other followers
In simple logic the 11 KV earthed cable is suitable for use in 6.6 KV unearthed system. The process of
Enter your email address
manufacture of cable is same. The size of cable will depend on current rating and voltage level.
Voltage Grade (Uo/U) where Uo is Phase to Earth Voltage & U is Phase to Phase Voltage. Follow This Blog by Email
Earthed system has insulation grade of KV / 1.75 x KV.
For Earthed System (Uo/U): 1.9/3.3 kV, 3.8/6.6 kV, 6.35/11 kV, 12.7/22 kV and 19/33 kV.
Unearthed system has insulation grade of KV / KV.
Privacy & Cookies: This site uses cookies. By continuing to use this website, you agree to their use.
For Unearthed System (Uo/U): 3.3/3.3 kV and 11/11 kV. Close and accept
To find out more, including how to control cookies, see here: Cookie Policy BUY ELECTRICAL NOTES IN PDF
Follow
3 phase 3 wire system has normally Unearthed grade cables and 3 phase 4 wire systems can be used earthed
grade cables, insulation used is less, and cost is less.

Thumb Rule:
As a thumb rule we can say that 6.6KV unearthed cable is equal to 11k earthed cable i.e. 6.6/6.6kv Unearthed
cable can be used for 6.6/11kv earthed system. because each core of cable have the insulation level to
withstand 6.6kv so between core to core insulation level will be 6.6kv+6.6kv = 11kv BUY ELECTRICAL SOFTWARES
For transmission of HT, earthed cable will be more economical due to low cost where as unearthed cables are not
economical but insulation will be good.
Generally 6.6 kV and 11kV systems are earthed through a neutral grounding resistor and the shield and armor are
also earthed, especially in industrial power distribution applications. Such a case is similar to an unearthed
application but with earthed shield (some times called solid bonding). In such cases, unearthed cables may be
used so that the core insulation will have enough strength but current rating is de-rated to the value of earthed
cables. But it is always better to mention the type of system earthing in the cable specification when ordering the
BUY ELECTRICAL NOTE IN PDF
cables so that the cable manufacturer will take care of insulation strength and de rating.

Rate this:
14 Votes

Share this:
 Facebook  Email  LinkedIn  More
BUY ELECTRICAL SOFTWARES.

Like
Be the first to like this.

Related

EHV/HV Cable Sheath Earthing Types of Neutral Earthing in Power Proud to be an IndiBlogger
With 42 comments Distribution electricalnotes.wordpress.c...

85
With 38 comments

/100
Type of Electrical Power Distribution systems
With 4 comments

FILED UNDER UNCATEGORIZED


SEARCH

About Jignesh.Parmar Copyright © 2018


Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical). He is member of The content in electricalnotes.wordpress.com is
Institution of Engineers (MIE) and CEng,India. Membership No:M-1473586.He has more than 16 for personal, non-commercial use only. you can
years experience in Transmission -Distribution-Electrical Energy theft detection-Electrical not reproduce,republish or communicate any of
Maintenance-Electrical Projects (Planning-Designing-Technical Review-coordination -Execution). the content , including files downloadable from
He is Presently associate with one of the leading business group as a Deputy Manager at
this website, without the permission of the
Ahmedabad,India. He has published numbers of Technical Articles in “Electrical Mirror”, “Electrical India”, “Lighting copyright owner.The use of this content on any
India”,”Smart Energy”, “Industrial Electrix”(Australian Power Publications) Magazines. He is Freelancer other websites breaches copyright Act. If You
Programmer of Advance Excel and design useful Excel base Electrical Programs as per IS, NEC, IEC,IEEE find this content in any other site,it makes the
codes. He is Technical Blogger and Familiar with English, Hindi, Gujarati, French languages. He wants to Share page you are viewing an infringement of the
his experience & Knowledge and help technical enthusiasts to find suitable solutions and updating themselves on copyright.
various Engineering Topics.

Recent Posts
32 Responses to Difference between Unearthed Cable & Earthed Cables Electrical Thumb Rules-VENTILATION &
CEILING FAN
vamsi says:
Electrical Thumb Rules-Light Sources
January 3, 2013 at 5:49 am
Quick Reference-Fire Fighting (Part-2)
Plz mention where unearthed cables are used in detail.(with applications)
Quick Reference-Fire Fighting (Part-1)
Reply Electrical Thumb Rule- High Rise Building (As
per NBC)

Jignesh.Parmar says: Calculate Motor Pump Size


January 3, 2013 at 5:27 pm
Calculate Size of Cable for Motor (As NEC)
Yes Sir, How to Design efficient Street lighting-(Part-6)

Reply How to Design efficient Street lighting-(Part-5)

How to Design efficient Street lighting-(Part-4)

How to Design efficient Street lighting-(Part-3)


Khin Shwe says:
How to Design efficient Street lighting-(Part-2)
January 8, 2013 at 11:21 am
How to Design efficient Street lighting-(Part-1)
Thank a lat for your Electrical Notes.
Calculate Size of Pole Foundation & Wind
Reply Pressure on Pole

Calculate Size of Circuit Breaker/ Fuse for

abinesh says: Transformer (As per NEC)

January 10, 2013 at 7:05 am Selection of Various Types of UPS (Part-2)

hi sir Selection of Various Types of UPS (Part-1)


above note is very useful one Electrical Thumb Rules-Illumination-(Part-19).

Reply Electrical Thumb Rules-Illumination-(Part-18).

Electrical Thumb Rules-Illumination-(Part-17).

sureshkumar says:
January 19, 2013 at 5:22 pm
Archives
Thank you.It is very useful to me
November 2019 (1)
Reply October 2019 (2)

September 2019 (2)

Dineshbhalaji. D says: August 2019 (2)


April 22, 2013 at 12:33 pm
July 2019 (2)
Lot of useful information u have provided..Thanx to u sir.. June 2019 (1)

Reply May 2019 (2)

April 2019 (3)

santosh says: March 2019 (2)


June 8, 2013 at 9:08 am
February 2019 (2)

Please describe me that can I used 11 kv xlpe HT cable in place of 23 KV HT cable ? January 2019 (3)

Reply December 2018 (2)

November 2018 (2)

nusret says: October 2018 (1)


June 23, 2013 at 9:05 pm
September 2018 (2)

thank you for your explanation August 2018 (3)

Reply July 2018 (1)

June 2018 (1)

Ajay says: May 2018 (1)


June 25, 2013 at 5:18 am April 2018 (1)

Really useful one. March 2018 (1)

Reply February 2018 (2)

January 2018 (1)

December 2017 (1)


Satyam M Patel says:
August 11, 2013 at 5:28 am November 2017 (1)

Thanks a lot for providing these much valuable information. But I am unable to download your Electrical Tools. Pl. October 2017 (1)
brief me how to download the same. September 2017 (1)
Thanks in advance
August 2017 (1)
Satyam
July 2017 (2)
Reply
June 2017 (1)

May 2017 (1)


mervyn alexander says:
April 2017 (1)
August 18, 2013 at 11:44 am
March 2017 (1)
if your lose “a” phase HV earth on your 11 kv transformer what will happen.
February 2017 (1)
Reply
January 2017 (1)

December 2016 (1)


Gajendra Yadav says: November 2016 (1)
January 16, 2014 at 9:46 am
October 2016 (1)
is 11kV(UE) equal to 22kV(E)?
September 2016 (1)
Reply
August 2016 (1)

July 2016 (1)


Baidyanath says: June 2016 (1)
January 31, 2014 at 12:55 pm
May 2016 (1)
We have power transformer 132 kv /11kv , primary star connected and solid earthed & secondary 11 kv delta
April 2016 (2)
connected & two out put ckt .The impedence voltage of the transformer 20%.My question is 11kv earth panel is
suitable for this application or going for 11 kv unearth panel for motor & transformer feeders. March 2016 (2)

February 2016 (2)


Reply
January 2016 (2)

December 2015 (1)


A.DHANDAPANI says:
March 25, 2014 at 4:44 pm November 2015 (1)

October 2015 (2)


THANKS FOR YOUR INPUTS
September 2015 (1)
Reply
August 2015 (1)

July 2015 (1)


Dony Rojerson says:
November 21, 2014 at 12:58 am
June 2015 (1)

May 2015 (1)


The explanation of ungrounded and grounded cable is very useful.
April 2015 (1)
But considering the IEC 60502-2, the cables need not to be ungrounded cable if the fault is cleared in the MV
system within one hour explained as category A,B and C. March 2015 (2)

February 2015 (2)


Generally, most of the MV system (3.3, 6.6 and 11 kV) are earthed through LRG. In IEEE 141, it is mentioned that
the ungrounded system whose fault cannot be cleared within 1 hour need 173% insulation. January 2015 (2)

So, I am really confused, do we need unearthed cable for a MV system with LRG clearing the fault within 1 min or December 2014 (2)

1 hour. November 2014 (2)

Reply October 2014 (2)

September 2014 (2)

Vijay says: August 2014 (3)


January 3, 2015 at 3:52 pm
July 2014 (2)

Sir, June 2014 (2)

Can you give any comments if semiconducting screens are required/ provided to make earthed 3.3kV grade May 2014 (2)
cables suitable for 3.3kV/ 3.3kV unearthed system, which is normally not provided with 3.3 kV system? April 2014 (2)

Reply March 2014 (3)

February 2014 (4)

dasari santosh says: January 2014 (2)


January 28, 2015 at 6:10 am
December 2013 (1)

Dear sir, November 2013 (1)


In a distribution transformer(11/440 DYn11) primary is not grounded.So,which kind of cable is preferred out of
October 2013 (2)
E/UE. September 2013 (3)
Kindly send your response pls…….
August 2013 (3)
Reply
July 2013 (3)

June 2013 (3)


virendra says: May 2013 (3)
April 1, 2015 at 10:52 am
April 2013 (2)
Which cable is better for 33kv underground work ?
March 2013 (3)
Reply
February 2013 (2)

January 2013 (3)


R.V.Krishnamachari says:
April 28, 2015 at 9:04 am
December 2012 (2)

November 2012 (3)


XLPE Insulated, Armored, PVC Jacketted size, voltage, material of conductor
October 2012 (1)
Reply
September 2012 (3)

August 2012 (7)

magesh gopi says: July 2012 (2)


June 9, 2015 at 2:07 pm May 2012 (7)

When using wye-broken delta earthing transformers, should we rate cables as like unearthed systems or earthed April 2012 (2)
systems?
March 2012 (3)
Reply February 2012 (2)

January 2012 (1)

sumit prajapati says: December 2011 (3)


July 24, 2015 at 5:40 pm
November 2011 (2)
Nice and useful… October 2011 (4)

Reply September 2011 (2)

August 2011 (1)

Shivaji Gaikwad says: June 2011 (5)


August 24, 2015 at 12:56 pm
May 2011 (3)
Thanks for above IMP information bcs I was selected a UE cable for 11kv distribution transformer which have delta April 2011 (12)
primary thank’s allot. …
March 2011 (17)
Reply

EEP
Sandeep Kalsi says:
December 14, 2015 at 11:02 am

Dear Sir,
I have 33 KV/ 11KV 2.5 MVA Delta /Star solidly grounded Step Down Transformer. The 33 KV Input is through
over head Conductor and output is 11 KV cable to VCB. Now We are going to install one more 11KV/415 volts
Delta Star Transformer at a distance of 390 Meter distance through overhead 11 KV 3 core cable. Please sugest
which cable we have to select Earthed or Unearthed. Also exp;lain why we selected for the same.

Reply

jose spencer says:


February 1, 2016 at 9:38 am

This is only applicable for IS, in IEC no specific un-earthed cable.

Reply

rubel dhar says: Pages


February 18, 2016 at 5:53 am
Abstract

Abstract of CPWD-Part 1
Dear sir can please mention which specific standard shall be followed for 33KV Unearthed cable. As you know Abstract of IE Rules
that IS 7098 part-II and IEC 60502 (up to 30 KV)don’t cover it
Abstract of IS Code.
Reply IS 1255

IS 15652/11171/1445/1678

Sohail Umallawala says: IS 3043 / 5039


March 31, 2016 at 6:07 am
IS 5613

Thanx sir. Above explanation was very useful. IS 694 / 1554 / 11892

Reply
IE Rules for DP Structure

Electrical Notes
Anu says:
ElectRICAL. Q&A
June 14, 2016 at 6:45 am
Electrical Q&A Part-1
sir,if the cable tray is not earthed any problem for the mv cable running on the cable tray
Electrical Q&A Part-2
Reply
Electrical Q&A Part-3

Electrical Q&A Part-4


S Anandavel says:
July 6, 2016 at 7:32 am
Electrical.Tool

EXCEL TOOL
In unearthed system,Neutral is earthed through a resistance to reduce the fault current,obviously,it can be called
as restricted neutral system rather than unearthed system.

Reply Top Clicks


electricalnotes.files.wor…

Manjit says: electricalnotes.files.wor…


April 29, 2017 at 1:47 pm mediafire.com/file/5040ut…

Can we use 22 KV earth HT Cable in place of 11 KV unearth cable instamojo.com/jiguparmar/…

Reply mediafire.com/file/0qu8mt…

mediafire.com/file/bkzwat…

Sankaralingam says: electricalnotes.files.wor…

June 10, 2017 at 7:24 am mediafire.com/file/vc7vfk…

In which system[Earthed/Unearthed] ELR to be used?

Reply Recent Comments


Dr Mukesh Kumar on Electrical Thumb
Rules-VENTILA…
Subharanjan khan says:
Muhammad Mohsin Ansa… on Electrical
August 25, 2018 at 2:10 pm
Thumb Rules-VENTILA…
Thanx a lot for information. Muhammad Mohsin Ansa… on Electrical
Thumb Rules-Light…
Reply
Muhammad Mohsin Ansa… on Quick
Reference-Fire Fighting…
Dinesh says: Nikhil Garde on Quick Reference-Fire
October 17, 2018 at 5:17 am Fighting…
J.Sridharan on Electrical Thumb Rule- High
can anyone pls. advice the cable voltage grade for 22kV resistance earthed system with IEC standard reference.
Ri…
Reply Muhammad Mohsin Ansa… on Electrical
Thumb Rule- High Ri…
AKHIL S M on Current Transformer
Leave a Reply Subhabrata Sarkar on Calculate Motor
Pump Size

Enter your comment here... Muhammad Mohsin Ansa… on Calculate


Motor Pump Size

This site uses Akismet to reduce spam. Learn how your comment data is processed.

You might also like