You are on page 1of 9

3.

SUCTION AND DISCHARGE LINES

3.1 Suction Line


The gas velocity in the common
suction line between evaporators To pack
and the suction header must be 0.5 % slope
minimum 4 m/s in horizontal max. 4 m 4 m/S or more
lines and minimum 8 m/s in
vertical lines (recommendation
8 to 12 m/s). Gas velocities
greater than 12 m/s will create
high noise levels and high suction
line pressure drop which will max. 4 m
8 to 12 m/s
0.5 % slope
decrease system capacity. 4 m/S or more
The suction line diameter
should be calculated according
to the minimum refrigerant U- trap, as short as possible
flow (at minimum evaporating
temperature and maximum
condensing temperature). Figure 3.1 Suction line design
The common suction line
when horizontal shall be sloping
down toward the suction header
(0.5% slope, 5mm rise for every
1m of run). If the suction line
must rise over 6 meters, multiple
suction risers must be created
every 4 meters as shown
in fig.3.1.
This is necessary to increase
the velocity of returning gas and
therefore insure proper oil return.
To avoid large quantities of oil
accumulation, create U-trap(s)
as short as possible.
It is important to note that
standard size suction rotolock Figure 3.2 Double suction riser with U-traps
valves ordered through Danfoss
Maneurop are designed for
general-purpose applications. It
is important to select rotolock
valve sizes according to the gas
flow and not only according to
pipe size. Gas velocity in suction
lines of parallel systems may vary compressors running. It is general this means that double
considerably due to fluctuations important to ensure sufficient suction risers with U-traps are
in load and the number of oil return under any load. In imperative. See figure 3.2.

RECIPROCATING COMPRESSORS
Parallel Application 8
3.2 Suction Header fitted into the suction header equalization with an oil equalization
and the end tube cut at an angle line system, the header must be
The suction header must be
of 60° (see figures 3.4 & 3.5). symmetrical and the lines from
placed as close as possible to
This configuration will result in the suction header to each
the compressors.
higher gas velocity at pick up compressor must be short &
The lines between the suction tube inlet and proper oil return identical.These precautions are
header and the compressor when the oil level in the suction not as critical when an oil level
suction connection must be header rises.The compressor regulator is used.
flexible, i.e. equipped with suction lines must always enter
The following recommendations
vibration absorbers. the suction header on the topside.
are necessary for secure
A recommended suction header
The suction lines from installation:
design is shown in figure 3.3.
the header towards each • The suction line "A" and
individual compressor must be To insure ideal pressure the suction header "B" must

Suction

Figure 3.3 Suction header configuration with header below the compressor suction connections.

60 °

2-3 mm 60 ° 60 °

Figure 3.4 Detail of suction line inside Figure 3.5 Construction of suction header above the compressor suction
the suction header connections

9 Parallel Application RECIPROCATING COMPRESSORS


be horizontal to avoid Therefore the following the discharge lines enter
unbalanced oil distribution. construction details are of the discharge header from
importance: the top. (See figure 3.7).
• The gas velocity in the suction
• Whenever possible, mount
header must be a maximum • To avoid operational noise
the discharge header below
of 4 m/s. the check valve dimension
the compressor discharge
must always be selected
• The suction line and the suction connections (see figure 3.6).
according to the compressor
header must be insulated to The compressor discharge lines
capacity and not the pipe size.
limit the suction gas superheat. are below the compressors
Contact your check valve
and enter the discharge header
Note: An alternative to supplier for correct selection.
from above.This design
the construction of a suction
eliminates the risk of liquid • The discharge header cross
header is to purchase a pre-made
flood back. Check valves section must be the sum of each
multiple compressor suction
(or non return valves), such discharge tube cross section.
accumulators.
as Danfoss’ NRV, located In an effort to avoid oil traps
between the compressor never oversize the discharge
3.3 Discharge Header
discharge connection and header.
A properly constructed the discharge header must
discharge header will not allow be installed to prevent liquid
liquid flood back or migration of condensation
the oil back to the compressor.
In non-running compressors.
Furthermore it must restrict hot
discharge gas from returning to • If it is impossible to mount
switch off compressors where it the discharge header below
will condense and cause liquid the discharge connections
hammering at compressor a special construction is
start up. required.The key is to ensure

▼ ▼ ▼

NRV Vibration absorber


Figure 3.6 Discharge header below compressor discharge connections.

RECIPROCATING COMPRESSORS
Parallel Application 10

▼ ▼ ▼

NRV Vibration absorber


Figure 3.7 Discharge header above compressor discharge connections.

4. COMPRESSOR CONTROL
SEQUENCE

By starting only one compressor reduce the risk of refrigerant • There shall be no more
at a time the peak load on the migration in compressors stopped than 12 starts per hour per
power supply will be reduced. over long periods of time. compressor.A higher number
reduces the service life of
Parallel installations also offer One example of a compressor
the compressor. It is necessary
many possibilities for efficient control sequence:
to use an anti-short cycle timer
capacity control.
• First start: Start compressors in the control circuit to limit
For example, three compressors in order 1, 2, 3 and also stop in the number of starts.
of different capacity mounted in order 1, 2, 3
• If a risk of long minimum load
parallel offer 7 different rated
• Second start: Start operation exists, it is recommend
capacities.The control system
compressors in order 2, 3, 1 to install a timer which will force
should be designed to match
and also stop in order 2, 3, 1 run the entire system at 100%
the cooling demand of the system
capacity for 5 minutes every
by staging compressors on and • Third start: Start compressors
5 hours.This will insure proper
off, thus reducing the amount in order 3, 1, 2 and also stop in
oil return.
of wasted energy in a system. order 3, 1, 2
A secondary function of Repeat sequence to balance each
the control system is to ensure compressors number of running
the compressors have an equal hours. Recommendations for
number of running hours and proper control:

11 Parallel Application RECIPROCATING COMPRESSORS


5. SYSTEM COMPONENTS

Typical system requirements and possibility to install filter drier organization for further
recommendations for parallel cartridges (type 48-DN), or burn information.
installations are listed below: out cartridges (type 48-DA),
while allowing easy after sales 5.4 Thermostatic
5.1 Suction line service. Expansion Valve
accumulator
When the parallel installation
For parallel installations, it is 5.3 Crankcase heater is serving a single evaporator
recommended to always use system the dimensioning of
Compressors must be installed
a suction line accumulator. Be sure the thermostatic expansion valve
with continuously energized
to select the proper size suction (TEV) becomes critical and must
self-regulating crankcase heaters
line accumulator according to be made in relation to both
(PTC elements).These heaters
manufacturer recommendations. minimum and maximum capacity.
are to be installed with heat
In systems with an oil level This will ensure correct superheat
conductive paste.The use of
regulator it is best to use either control in all situations.
an additional belt crankcase heater
one suction line accumulator
may be necessary in some cases.
per compressor or a multi-line 5.5 Condensing pressure
That belt crankcase heaters
accumulator having a connection control
must be switched on only when
for each compressor.
the compressor is not running. A condensing pressure control
should be installed to maintain
5.2 Suction filter The compressors should be
the minimum condensing pressure
installed in a room of moderate
It is strongly recommended according to the application
temperature to avoid refrigerant
to install a large suction filter range published for each
condensation in non-running
just before the suction header compressor / refrigerant
compressors.
or suction accumulator.This will combination.This condensing
filter all foreign particles out References of crankcase heaters pressure control will also allow
of the installation to protect are given in the selection and for an ideal liquid distribution in
the compressors. Danfoss DCR Application Guidelines" the system (expansion valve
filters with interchangeable strainer for MT/MTZ or LTZ operation).
type 48-F are recommended. compressors. Contact
These filter shells provide the your local Danfoss Maneurop

RECIPROCATING COMPRESSORS
Parallel Application 12
6. INSTALLATION & SERVICE

Installation and service Suction and discharge lines must capacity.The application envelope
procedures for a parallel system have adequate 3 dimensional of a parallel installation is
are similar to basic system flexibility. For parallel systems the same as for the individual
installations.The selection of the simplest means of acquiring compressors.
additional system components this is by the use of vibration
for parallel installations follows absorbers. 6.4 Pressure switch settings
the basic system common rules.
The connecting suction and The pump down pressure switch
Therefore refer to the "Selection
discharge header pipes must be (for example Danfoss type KP1)
and Application Guidelines" of
as short as possible.Therefore it must have a set point slightly
the compressor for detailed
is a benefit to mount compressors higher than the lowest
installation and service
as close together as possible.All compressor safety pressure
procedures.
compressors must be mounted switch set point.The high-
on the same level. pressure safety switch shall
6.1 Compressor mounting
stop all compressors.
Individual compressors must 6.2 Rotation direction
always be mounted using 6.5 Failure analysis
Compressors should run with
the provided mounting
the same rotation direction. When one compressor in
grommets. If this is not done
This can be achieved by having a parallel system fails the chance
the system will transmit
the same phase sequence on of foreign particles entering other
vibration and in turn reduce
each compressor motor compressors is greatly increased.
compressor life.A common base
terminal (L1-T1, L2-T2, L3-T3). Therefore a failure analysis must
frame, rigid enough to support
be done quickly to insure further
the weight of the compressors,
6.3 Total capacity and proper running conditions for
must be used for installation.
application envelope the overall installation (i.e.: oil
The common frame may be
analysis).
mounted on grommets to reduce The total cooling capacity of
transmission of vibration to a parallel installation is slightly
the floor. It is recommended to less that the sum of the cooling
install all control and safety capacities of the individual
devices on an independent compressors.This is due to
frame.These devices should the extra pressure drop in suction
be connected to the common and discharge headers. In general
frame using flexible tubing. this loss is about 1% of the total

13 Parallel Application RECIPROCATING COMPRESSORS


7. MANEUROP COMPRESSOR
CHARACTERISTICS

All Maneurop reciprocating compressors (until 1988) had a


compressors MT, MTZ, LT & 1"1/4 rotolock connection for
LTZ are available in VE version, this purpose (see figure 7.3).
specially designed for parallel
For compressor replacement in
installation.
a parallel system with
These compressors are provided compressors fitted with this
with an oil equalization connection rotolock connection, an adapter
and a threaded oil sight glass is available through Danfoss
(see figure 7.1). Maneurop (ref. 7754010).
The standard compressors are The position of the 3/8’’ flare oil
not suitable for parallel mounting. equalization fitting has recently
been modified so that equalization
7.1 Oil level regulator and only occurs when the oil level in
oil sight glass the compressor reaches the
An oil level regulator can be maximum.
mounted on the compressor oil Further, to prevent oil drainage
sight glass connection from the non-running compressors
during part load operation, maxi
7.2 Oil equalization the flare connector protrudes
connection into the compressor shell
A 3/8" oil equalization line can (see figure 7.2).
be connected to the 3/8’’ flare mini
FSA adapter (023 U 8014) is
connection (see figure 7.2).
available to convert the flare
Recommended torque is 30 connection to a brazed
Nm. Note that older Maneurop connection design.
Figure 7.1 Correct oil level
in sight glass

15.9 ± 0.1
Compressor
shell
Ø 5/8 - 18UNF
Ø 13.5
Ø 7.9

Oil 45 °
sump

Figure 7.2 Oil equalization connection, 3/8" flare connection Figure 7.3 Former rotolock
with adaptor accessory.

RECIPROCATING COMPRESSORS
Parallel Application 14
The Danfoss Maneurop
facilities

Anse
France

Lawrenceville
Georgia - USA
GA 045 - 10/00 - GB

Trévoux
France

Danfoss Maneurop
Commercial Compressors

BP 331 F- 01603 Trévoux France


Tél. 04 74 00 28 29 - (33) 4 74 00 28 29
Fax 04 74 00 52 44 - (33) 4 74 00 52 44
Every effort has been made to provide accurate descriptions and data.
However, due to the continuing process of product improvement and evolvement, all information in this brochure is subject to change without notification.
Maneurop® is a registered trademark of Danfoss.

You might also like