You are on page 1of 19

CHAPTER 3 – Excavations and Foundations 3-1

Table of Contents
CHAPTER 3 - EXCAVATION AND FOUNDATION 3
SECTION 301 - GENERAL 3
301.1 Scope......................................................................3
301.2 Quality and Design.................................................3
301.3 Allowable Bearing Pressures..................................3
SECTION 302 - EXCAVATION AND FILLS 3
302.1 General...................................................................3
302.2 Cuts........................................................................3
302.2.1 General. 3
302.2.2 Slope. 3
302.2.4 Protection of Adjoining Property. 3
302.3 Fills.........................................................................3
302.3.1 General. 3
302.3.2 Preparation of Ground. 4
302.3.3 Fill Material. 4
302.3.4 Compaction. 5
302.3.5 Slope. 5
302.4 Setbacks..................................................................5
302.4.1 General. 5
302.4.2 Top of Cut Slope. 5
302.4.3 Toe of Fill Slope. 5
302.4.4 Modification of Slope Location. 5
302.5 Drainage and Terracing..........................................5
301.5.1 General. 5
302.5.2 Terrace. 5
302.5.3 Subsurface Drainage. 5
302.5.4 Disposal. 5
302.5.5 Interceptor Drains. 6
302.6 Erosion Control......................................................6
302.6.1 Slopes. 6
302.6.2 Other Devices. 6
SECTION 303 - FOUNDATION INVESTIGATION 6
303.1 General...................................................................6
303.2 Soil Classification..................................................6
303.3 Questionable Soil...................................................6
303.4 Liquefaction Study.................................................6
303.5 Expansive Soil........................................................7
303.6 Reports...................................................................7
303.7 Liquefaction Potential and Soil Strength Loss.......7
303.8 Adjacent Loads.......................................................7
303.9 Drainage.................................................................7
SECTION 304 - ALLOWABLE FOUNDATION AND LATERAL PRESSURES 9
SECTION 305 - FOOTINGS 9
305.1 General...................................................................9
305.2 Footing Design.......................................................9
305.2.1 Design Loads9
305.2.2 Vibratory Loads 9
305.3 Bearing Walls 9
305.4 Stepped Foundations............................................10

National Structural Code of the Philippines 6th Edition Volume 1


3-2 CHAPTER 3 – Excavations and Foundations

305.5 Footings On or Adjacent To Slopes......................10


305.5.1 Scope. 10
305.5.2 Building Clearance from Ascending Slopes. 10
305.5.3 Footing Setback from Descending Slope Surface. 10
305.5.4 Pools. 10
305.5.5 Foundation Elevation. 10
305.5.6 Alternate Setback and Clearance. 10
305.6 Foundation Plates or Sills.....................................10
305.7 Designs Employing Lateral Bearing....................10
305.7.1 General. 10
305.7.2 Design Criteria..................................................11
305.7.2.1 Nonconstrained. 11
305.7.2.3 Vertical Load. 11
305.7.3 Backfill. 11
305.7.2.2 Constrained. 11
305.7.4 Limitations. 12
305.8 Grillage Footings..................................................12
305.9 Bleacher Footings.................................................12
SECTION 306 - PILES - GENERAL REQUIREMENTS 12
306.1 General.................................................................12
306.2 Interconnection.....................................................12
306.3 Determination of Allowable Loads......................12
306.4 Static Load Test....................................................12
306.5 Dynamic Load Test..............................................13
306.6 Column Action.....................................................13
306.7 Group Action........................................................13
306.8 Piles in Subsiding Areas.......................................13
306.9 Jetting...................................................................13
306.10 Protection of Pile Materials................................13
306.11 Allowable Loads.................................................13
306.12 Use of Higher Allowable Pile Stresses...............13
SECTION 307 - PILES - SPECIFIC REQUIREMENTS 13
307.1 Round Wood Piles................................................13
307.1.1 Material. 13
307.1.2 Allowable Stresses. 13
307.2 Uncased Cast-In-Place Concrete Piles.................14
307.2.1 Material. 14
307.2.2 Allowable Stresses. 14
307.3 Metal-Cased Concrete Piles.................................14
307.3.1 Material. 14
307.3.2 Installation. 14
307.3.3 Allowable Stresses. 14
307.4 Precast Concrete Piles..........................................14
307.4.1 Materials. 14
307.4.2 Reinforcement Ties. 14
307.4.3 Allowable Stresses. 14
307.5 Precast Prestressed Concrete Piles (Pretensioned)15
307.5.1 Materials. 15
307.5.2 Reinforcement 15
307.5.2.1 Longitudinal Reinforcement. 15
307.5.2.2 Transverse Reinforcement. 15
307.5.3 Allowable Stresses. 15
307.5.4 Splicing. 15
307.6 Structural Steel Piles............................................15

Association of Structural Engineers of the Philippines


CHAPTER 3 – Excavations and Foundations 3-3

307.6.1 Material. 15
307.6.2 Allowable Stresses. 15
307.6.3 Minimum Dimensions. 15
307.7 Concrete-Filled Steel Pipe Piles...........................15
307.7.1 Material. 15
307.7.2 Allowable Stresses. 16
307.7.3 Minimum Dimensions. 16
SECTION 308 - FOUNDATION CONSTRUCTION-SEISMIC ZONE 4 16
308.1 General.................................................................16
308.2 Soil Capacity........................................................16
308.3 Superstructure to Foundation Connection............16
308.4 Foundation-Soil Interface.....................................16
308.5 Special Requirements for Piles and Caissons......16
308.5.1 General. 16
308.5.2 Steel Piles, Nonprestressed Concrete Piles and Prestressed Concrete Piles. 16
308.5.2.1 Steel Piles. 16
308.5.2.2 Nonprestressed Concrete Piles. 16
308.5.2.3 Prestressed Concrete Piles. 16
SECTION 309 - SPECIAL FOUNDATION, SLOPE STABILIZATION AND MATERIALS OF CONSTRUCTION
17
309.1 Special Foundation Systems................................17
309.2 Acceptance and Approval.....................................17
309.3 Specific Applications...........................................17

National Structural Code of the Philippines 6th Edition Volume 1


3-4 CHAPTER 3 – Excavations and Foundations

302.2 Cuts

302.2.1 General.
Unless otherwise recommended in the approved
geotechnical engineering or engineering geology report,
cuts shall conform to the provisions of this section. In the
absence of an approved geotechnical engineering report,
these provisions may be waived for minor cuts not intended
to support structures.

302.2.2 Slope.
The slope of cut surfaces shall be no steeper than is safe for
the intended use and shall be no steeper than 1 unit vertical
in 2 units horizontal (50% slope) unless a geotechnical
engineering or an engineering geology report, or both,
stating that the site has been investigated and giving an
opinion that a cut at a steeper slope will be stable and not
create a hazard to public or private property, is submitted
and approved. Such cuts shall be protected against erosion
or degradation by sufficient cover, drainage, engineering
CHAPTER 3 - EXCAVATION AND and/or biotechnical means.

FOUNDATION 302.2.3 Existing footings or foundations which may be


affected by any excavation shall be underpinned adequately
or otherwise protected against settlement and shall be
SECTION 301 - GENERAL protected against lateral movement.

301.1 Scope 302.2.4 Protection of Adjoining Property.


This chapter sets forth requirements for excavations, fills, The requirement for protection of adjacent property and the
footings and foundations for any building or structure. depth to which protection is required shall be defined by
prevailing law. Where not defined by law, the following
301.2 Quality and Design shall apply:
The quality and design of materials used structurally in 1. Any person making or causing an excavation to be
excavations, fills, footings and foundations shall conform to made to a depth of 3.5 meters or less below the grade
the requirements specified in Chapters 4, 5, 6 and 7. shall protect the excavation so that the soil of adjoining
property will not cave in or settle, but shall not be
liable for the expense of underpinning or extending the
301.3 Allowable Bearing Pressures foundation of structures on adjoining properties where
Allowable stresses and design formulas provided in this his excavation is not in excess of 3.5 meters in depth.
chapter shall be used with the allowable stress design load
combinations specified in Section 203.4. 2. Before commencing the excavation, the person making
or causing the excavation to be made shall notify in
writing the owners of adjoining building not less than
SECTION 302 - EXCAVATION AND 10 days before such excavation is to be made and that
the adjoining building should be protected.
FILLS
3. The owners of the adjoining property shall be given
access to the excavation for the purpose of protecting
302.1 General such adjoining buildings.
Excavation or fills for buildings or structures shall be
4. Any person making or causing an excavation to be
constructed or protected that they do not endanger life or
made exceeding 3.5 meters in depth below the grade
property. Reference is made to Section 109 of this code for
shall protect the excavation so that the adjoining soil
requirements governing excavation, grading and earthwork
will not cave in or settle and shall extend the
construction, including fills and embankments.
foundation of any adjoining buildings below the depth

Association of Structural Engineers of the Philippines


CHAPTER 3 – Excavations and Foundations 3-5

of 3.5 meters below grade at his own expense. The


owner of adjoining buildings shall extend the
foundation of these buildings to a depth of 3.5 meters
below grade at his own expense, as provided in the
preceding paragraph

302.3 Fills

302.3.1 General.
Unless otherwise recommended in the approved
geotechnical engineering report, fills shall conform to the
provisions of this section. In the absence of an approved
geotechnical engineering report, these provisions may be
waived for minor fills not intended to support structures.

National Structural Code of the Philippines 6th Edition Volume 1


3-6 CHAPTER 3 – Excavations and Foundations

Fills to be used to support the foundations of any building


or structure shall be placed in accordance with accepted The area beyond the toe of fill shall be sloped for sheet
engineering practice. A geotechnical investigation report overflow or a paved drain shall be provided. When fill is to
and a report of satisfactory placement of fill, both be placed over a cut, the bench under the toe of fill shall be
acceptable to the building official, shall be submitted when at least 3 meters wide but the cut shall be made before
required by the building official. placing the fill and acceptance by the geotechnical engineer
as a suitable foundation for fill.
No fill or other surcharge loads shall be placed adjacent to
any building or structure unless such building or structure is 302.3.3 Fill Material.
capable of withstanding the additional vertical and Detrimental amounts of organic material shall not be
horizontal loads caused by the fill or surcharge. permitted in fills. Except as permitted by the geotechnical
engineer, no rock or similar irreducible material with a
Fill slopes shall not be constructed on natural slopes steeper maximum dimension greater than 300 mm shall be buried
than 1 unit vertical in 2 units horizontal (50% slope) or placed in fills.
Exception:
302.3.2 Preparation of Ground.
The ground surface shall be prepared to receive fill by The placement of larger rock may be permitted when the
removing vegetation, organic materials, non-complying fill, geotechnical engineer properly devises a method of
topsoil and other unsuitable materials, and by scarifying to placement, and continuously inspects its placement and
provide a bond with the new fill. approves the fill stability. The following conditions shall
also apply:
Where the natural slopes are steeper than 1 unit vertical in 5 1. Prior to issuance of the grading permit, potential rock
units horizontal (20% slope) and the height is greater than disposal areas shall be delineated on the grading plan.
1.5 meters, the ground surface shall be prepared by
benching into sound bedrock or other competent material as 2. Rock sizes greater than 300 mm in maximum
determined by the geotechnical engineer. The bench under dimension shall be 3 meters or more below grade,
the toe of a fill on a slope steeper than 1 unit vertical in 5 measured vertically.
units horizontal (20% slope) shall be at least 3 meters wide.

Top of
Slope PA*
H/5 but
0.60 mm
min. and
Toe of 3 m max.
PA*
Slope

Cut or Fill Natural or Finish Grade


H/2 but 0.6 mm Slope
min. and 6 m
H
max.

Natural or Finish
Grade
* Permit Area Boundary

Figure 302-1 Setback Dimensions for Cut and Fill Slopes


Association of Structural Engineers of the Philippines
CHAPTER 3 – Excavations and Foundations 3-7

3. Mechanical stabilization or chemical treatment of the


fill slope surface to minimize erosion.
3. Rocks shall be placed so as to assure filling of all voids 4. Rockfall protection
with well-graded soil. 5. Provisions for the control of surface waters.

302.3.4 Compaction. 302.4.4 Modification of Slope Location.


All fills shall be compacted to a minimum of 90 percent of The building official may approve alternate setbacks. The
maximum density as determined by ASTM Standard D-698, building official may require an investigation and
or D-1557. In-place density shall be determined in recommendation by a qualified geotechnical engineer to
accordance with ASTM D-1556, D-2167, D-2922, D-3017 demonstrate that the intent of this section has been satisfied.
or equivalent. For clean granular materials, the use of the
foregoing procedures is inappropriate. Relative density
criteria shall be used based on ASTM D5030 -04 302.5 Drainage and Terracing

302.3.5 Slope. 301.5.1 General.


The slope of fill surfaces shall be no steeper than is safe for Unless otherwise indicated on the approved grading plan,
the intended use. Fill slopes shall be no steeper than 1 unit drainage facilities and terracing shall conform to the
vertical in 2 units horizontal (50% slope) unless provisions of this section for cut or fill slopes steeper than 1
substantiating data justifying steeper slopes are submitted unit vertical in 3 units horizontal (33.3% slope).
and approved.
302.5.2 Terrace.
302.4 Setbacks Terraces at least 2 meters in width shall be established at
not more than 10 meters vertical intervals on all cut or fill
302.4.1 General. slopes to control surface drainage and debris except that
where only one terrace is required, it shall be at midheight.
Cut and fill slopes shall be set back from site boundaries in For cut or fill slopes greater than 20 meters and up to 40
accordance with this section unless an alternate setback is meters in vertical height, one terrace at approximately
approved by the building official (see Section 302.4.4). midheight shall be 4 meters in width. Terrace widths and
Setback dimensions shall be horizontal distances measured spacing for cut and fill slopes greater than 40 meters in
perpendicular to the site boundary. Setback dimensions height shall be designed by the civil engineer and approved
shall be as shown in Figure 302-1. by the building official. Suitable access shall be provided to
permit proper cleaning and maintenance.
302.4.2 Top of Cut Slope.
Swales or ditches on terraces shall have a minimum
The top of cut slopes shall not be made nearer to a site
boundary line than one fifth of the vertical height of cut gradient of 5 percent and must be paved with reinforced
concrete not less than 75 mm in thickness or an approved
with a minimum of 0.6 meter and a maximum of 3 meters.
equal paving material. They shall have a minimum depth at
The setback may need to be increased for any required
the deepest point of 0.3 meter and a minimum paved width
interceptor drains.
of 1.5 meters.

302.4.3 Toe of Fill Slope. A single run of swale or ditch shall not collect runoff from a
The toe of fill slope shall be made not nearer to the site tributary area exceeding 1,000 m2 (projected area) without
boundary line than one half the height of the slope with a discharging into a down drain.
minimum of 0.6 meter and a maximum of 6 meters. Where
a fill slope is to be located near the site boundary and the 302.5.3 Subsurface Drainage.
adjacent off-site property is developed, special precautions
shall be incorporated in the work as the building official Cut and fill slopes shall be provided with surface drainage
deems necessary to protect the adjoining property from as necessary for stability.
damage as a result of such grading. These precautions may
include but are not limited to: 302.5.4 Disposal.
1. Additional setbacks. All drainage facilities shall be designed to carry waters to
the nearest practicable drainage way approved by the
2. Provision for retaining or slough walls.

National Structural Code of the Philippines 6th Edition Volume 1


3-8 CHAPTER 3 – Excavations and Foundations

building official or other appropriate jurisdiction as a safe SECTION 303 - FOUNDATION


place to deposit such waters. Erosion of ground in the area
of discharge shall be prevented by installation of non- INVESTIGATION
erosive down drains or other devices or splash blocks.
303.1 General
Building pads shall have a drainage gradient of 2 percent
toward approved drainage facilities, unless waived by the Foundation investigation shall be conducted and a
building official. professional report shall be submitted at each building site
when required by the building official or when the
Exception: engineer-of-record requires such information.
The gradient from the building pad may be 1 percent if all
of the following conditions exist throughout the permit Foundation and soils investigation shall be conducted in
area: cases of questionable soils, expansive soils, groundwater
table to determine whether the existing ground water table
1. No proposed fills are greater than 3 meters in is above or within 1.5 meters below the elevation of the
maximum depth. lowest floor level or where such floor is located below the
finished ground level adjacent to the foundation, pile
2. No proposed finish cut or fill slope faces have a
foundations, or in rock strata where the rock is suspected to
vertical height in excess of 3 meters.
be of doubtful characteristics or indicate variations in the
3. No existing slope faces steeper than 1 unit vertical in structure of the rock or where solution cavities or voids are
10 units horizontal (10% slope) have a vertical height expected to be present in the rock..
in excess of 3 meters.
The building official may require that the interpretation and
evaluation of the results of the foundation investigation be
302.5.5 Interceptor Drains. made by a registered civil engineer, experienced and
Paved or lined interceptor drains shall be installed along the knowledgeable in the field of geotechnical engineering.
top of all cut slopes where the tributary drainage area above
slopes toward the cut and has a drainage path greater than
12 meters measured horizontally. Interceptor drains shall be 303.2 Soil Classification
paved with a minimum of 75 mm of concrete or gunite and For the purposes of this chapter, the definition and
reinforced. They shall have a minimum depth of 300 mm classification of soil materials for use in Table 304-1 shall
and a minimum paved width of 750 mm measured be according to ASTM D-2487.
horizontally across the drain. The slope of drain shall be
approved by the building official. Soil classification shall be based on observation and any
necessary tests of the materials disclosed by borings or
excavations made in appropriate locations. Additional
302.6 Erosion Control studies may be necessary to evaluate soil strength, the effect
of moisture variation on soil-bearing capacity,
302.6.1 Slopes. compressibility, liquefaction and expansiveness.
The faces of cut and fill slopes shall be prepared and
maintained to control against erosion. This control may 303.3 Questionable Soil
consist of effective planting adapted to the locality. The Where the classification, strength or compressibility of the
protection for the slopes shall be installed as soon as soil are in doubt, or where a load bearing value superior to
practicable and prior to calling for final approval. Where that specified in this code is claimed, the building official
cut slopes are not subject to erosion due to the erosion- shall require that the necessary soil investigation be made.
resistant character of the materials, such protection may be
omitted.
303.4 Liquefaction Study
302.6.2 Other Devices. The building official may require a geotechnical evaluation
in accordance with Section 303.6 when, during the course
Where necessary, check dams, cribbing, riprap or other of the foundation investigation, where all of the following
devices or methods shall be employed to control erosion conditions are discovered which could trigger liquefaction
and provide safety. or spreading:
1. Shallow ground water, 15 meters or less
2. Unconsolidated saturated sandy alluvium.

Association of Structural Engineers of the Philippines


CHAPTER 3 – Excavations and Foundations 3-9

3. Seismic Zone 4 6. Seismicity consideration such as near source factor,


soil classification based on Chapter 2 of this code.
Exception:
7. Laboratory strength and compressibility parameters.
The building official may waive this evaluation upon
receipt of written opinion of a qualified geotechnical
The soil classification and design-bearing capacity shall be
engineer that liquefaction is not probable.
shown on the plans, unless the foundation conforms to
Table 305-1.
303.5 Expansive Soil
When expansive soils are present, the building official may
When the expansive characteristic of a soil is suspected
require that special provisions be made in the foundation
and needs to be determined, the procedures shall be in
design and construction to safeguard against damage due to
accordance with ASTM D-4546 or D-4829 and the soil
this expansiveness. The building official may require a
shall be classified according to Table 303-1. Foundations
special investigation and report to provide these design and
for structures resting on soils with an expansion index
construction criteria.
greater than 20 shall require special design consideration. If
the soil expansion index varies with depth, the variation is
to be included in the engineering analysis of the expansive 303.7 Liquefaction Potential and Soil Strength Loss
soil effect upon the structure. When required by Section 303.4, the potential for soil
liquefaction and soil strength loss during earthquakes shall
Table 303-1 Classification of Expansive Soil be evaluated during the geotechnical investigation. The
geotechnical evaluation shall assess potential consequences
Expansion Index Potential Expansion
of any liquefaction and soil strength loss, including
0 - 20 Very Low estimation of differential settlement, lateral movement or
reduction in foundation soil-bearing capacity, and discuss
21 - 50 Low mitigating measures. Such measures shall be given
51 - 90 Medium consideration in the design of the building and may include,
but are not limited to, ground stabilization, selection of
91 - 130 High appropriate foundation type and depths, selection of
Above 130 Very High appropriate structural systems to accommodate anticipated
displacements, or any combination of these measures.

303.6 Reports The potential for liquefaction and soil strength loss shall be
evaluated for a site peak ground acceleration that, as a
The building official may require submission of a written
minimum, conforms to the probability of exceedance
professional report and record of the investigation, which
specified in Section 208.6.2. Peak ground acceleration may
shall include, but need not be limited to, the following
be determined based on a site-specific study taking into
information:
account soil amplification effects.
1. A plot showing the location of all test borings and/or
excavations. In the absence of such a study, peak ground acceleration
may be assumed equal to the seismic zone factor in Table
2. Descriptions and classifications of the materials
208-3.
encountered.
3. Elevation of the water table, if encountered.
303.8 Adjacent Loads
4. Recommendations for foundation type and design Where footings are placed at varying elevations, the effect
criteria, including bearing capacity, pile or pier load of adjacent induced lateral and vertical loads shall be
capacity, including special foundation solutions, included in the foundation design.
provisions to mitigate the effects of differential
settlements and expansive soils, provisions to mitigate
the effects of liquefaction and soil strength loss, and the 303.9 Drainage
effects of adjacent loads Provisions shall be made for the control and drainage of
5. Expected total and differential settlements. surface water around buildings. (See also Section 305.5.5.)
and ensure that scour will not threaten such structures.

National Structural Code of the Philippines 6th Edition Volume 1


3-10 CHAPTER 3 – Excavations and Foundations

Lateral
Bearing Lateral Sliding1
Allowable
Below
Foundation
Class of Materials2 Natural
Pressure3
Grade4 Resistance6
(kPa) Coefficient5
(kPa/m of (kPa)
depth)

1. Massive Crystalline Bedrock 200 200 0.70 -

2. Sedimentary and Foliated Rock 100 60 0.35 -

3. Sandy Gravel and /or Gravel(GW & GP) 100 30 0.35 -


4. Well-graded Sand, Poorly-graded Sand, Silty Sand,
Clayey Sand, Silty Gravel and Clayey Gravel (SW, SP, 75 25 0.25 -
SM, SC, GM and GC)
5. Clay, Sandy Clay, Silty Clay and Clayey Silt (CL, ML, 7
MH, and CH) 50 15 - 7

Table 304-1 Allowable Foundation and Lateral Pressure


1
Lateral bearing and lateral sliding resistance may be combined.
2
For soil classification OL, OH and PT (i.e., organic clays and peat), a foundation investigation shall be required.
3
All values of allowable foundation pressure are for footings having a minimum width of 300 mm and a minimum depth of 300 mm into natural grade.
Except as in Footnote 7 below, increase of 20 percent is allowed for each additional 300 mm of width and/or depth to a maximum value of three
times the designated value.
4
The amount of the designated value may be increased for each additional 300 mm of depth to a maximum of 15 times the designated value. Isolated
poles for uses such as flagpoles or signs and poles used to support structures which are not adversely affected by a 12 mm motion at ground surface
due to short term lateral bearing values equal to two times the tabulated values.
5
Coefficient to be multiplied by the dead load.
6
Lateral sliding resistance value to be multiplied by the contact area. In no case shall the lateral sliding resistance exceed one half the dead load.
7
No increase for width is allowed.

SECTION 304 - ALLOWABLE


FOUNDATION AND LATERAL
PRESSURES

The allowable foundation and lateral pressures shall not


exceed the values set forth in Table 304-1 unless data to
substantiate the use of higher values are submitted. Table
304-1 may be used for design of foundations on rock , non-
liquefiable sites or non-expansive soil for structures that do
not exceed three stories in height or for structures that have
continuous footings having a load of less than 30 kN/m and
isolated footings with loads of less than 250 kN.

Allowable bearing pressures provided in Table 304-1 shall


be used with the allowable stress design load combinations
specified in Section 203.4.

Association of Structural Engineers of the Philippines


CHAPTER 3 – Excavations and Foundations 3-11

SECTION 305 - FOOTINGS Slab-on-grade and mat-type footings for structures located
on expansive soils may be designed in accordance with the
geotechnical recommendation as permitted by the building
305.1 General official.
Footings shall be so designed that the allowable bearing Table 305-1 – Foundations for Stud Bearing Walls – Minimum Requirements
1,2,3
capacity of the soil is not exceeded, and that differential
settlement is minimized to within limits tolerable to the Thickness of Depth
Number of Width Thickness Below
structure. Floors Foundation Wall
of of Undisturbed
Supported (mm)
Footings and foundations shall be constructed of masonry, by the Footing Footing Ground
Foundations Concrete Unit Surface
concrete or treated wood permanently under the water table (mm) (mm)
Masonry
in conformance with Chapter 4, 5, 6 and 7. Footings of (mm)
concrete and masonry shall be of solid material.
1 150 150 300 150 300
Foundations supporting wood shall extend at least 150 mm
above the adjacent finish grade. Footings shall have a 2 200 200 375 175 450
minimum depth as indicated in Table 305-1, unless another
depth is recommended by a foundation investigation. 3 250 250 450 200 600
1
Where unusual conditions are found, footings and foundations shall be
The provisions of this section do not apply to building and as required in Section 305.1.
foundation systems in those areas subject to scour and 2
The ground under the floor may be excavated to the elevation of the top
water pressure by wind and wave action. Buildings and of the footing.
3
Foundation may support a roof in addition to the stipulated number of
foundations subject to such loads shall be designed in floors. Foundations supporting roofs only shall be as required for
accordance with approved national standards and supported supporting one floor.
by calculation of scour depth.
305.2.1 Design Loads
305.2 Footing Design Footings shall be designed for the most unfavorable load
Except for special provisions of Section 307 covering the effects due to combinations of loads. The dead load is
design of piles, all portions of footings shall be designed in permitted to include the weight of foundations, footings and
accordance with the structural provisions of this code and overlying fill. Reduced live loads as permitted in the
shall be designed to minimize differential settlement when Chapter on Loadings are permitted to be used in the design
necessary and the effects of expansive soils when present. of footings.

305.2.2 Vibratory Loads


Where machinery operations or other vibratory loads or
vibrations are transmitted to the foundations, consideration
shall be given in the report to address the foundation design
to prevent detrimental disturbances to the soil.

305.3 Bearing Walls


Bearing walls shall be supported on masonry or concrete
foundations or piles or other permitted foundation system
that shall be of sufficient size to support all loads.

Where a design is not provided, the minimum foundation


requirements for stud bearing walls shall be as set forth in
Table 305-1, unless expansive soils of a severity to cause
differential movement are known to exist.

Exceptions:
National Structural Code of the Philippines 6th Edition Volume 1
3-12 CHAPTER 3 – Excavations and Foundations

1. A one-storey wood or metal-frame structure not used 305.5.4 Pools.


for human occupancy and not over 40 m 2 in floor area The setback between pools regulated by this code and
may be constructed with walls supported on a wood slopes shall be equal to one half the building footing
foundation plate when permitted by the building setback distance required by this section. That portion of
official. the pool wall within a horizontal distance of 2 meters from
2. The support of structures by posts embedded in earth the top of the slope shall be capable of supporting the water
shall be designed as specified in Section 305.7. Wood in the pool without soil support.
posts or poles embedded in earth shall be pressure
treated with an approved preservative. Steel posts or 305.5.5 Foundation Elevation.
poles shall be protected as specified in Section 306.10.
On graded sites, the top of any exterior foundation shall
extend above the elevation of the street gutter at point of
305.4 Stepped Foundations discharge or the inlet of an approved drainage device a
Foundations for all buildings where the surface of the minimum of 300 mm plus 2 percent. The building official
ground slopes more than 1 unit vertical in 10 units may permit alternate elevations, provided it can be
horizontal (10% slope) shall be level or shall be stepped so demonstrated that required drainage to the point of
that both top and bottom of such foundation are level. discharge and away from the structure is provided at all
locations on the site.

305.5 Footings On or Adjacent To Slopes


305.5.6 Alternate Setback and Clearance.
The building official may approve alternate setbacks and
305.5.1 Scope.
clearances. The building official may require an
The placement of buildings and structures on or adjacent to investigation and recommendation of a qualified engineer
slopes steeper than 1 unit vertical in 3 units horizontal to demonstrate that the intent of this section has been
(33.3% slope) shall be in accordance with this section. satisfied. Such an investigation shall include consideration
of material, height of slope, slope gradient, load intensity
305.5.2 Building Clearance from Ascending Slopes. and erosion characteristics of slope material.
In general, buildings below slopes shall be set a sufficient
distance from the slope to provide protection from slope 305.6 Foundation Plates or Sills
drainage, erosion and shallow failures. Except as provided Wood plates or sills shall be bolted to the foundation or
for in Section 305.5.6 and Figure 305-1, the following foundation wall. Steel bolts with a minimum nominal
criteria will be assumed to provide this protection. Where diameter of 12 mm shall be used in Seismic Zone 2. Steel
the existing slope is steeper than 1 unit vertical in 1 unit bolts with a minimum nominal diameter of 16 mm shall be
horizontal (100% slope), the toe of the slope shall be used in Seismic Zone 4. Bolts shall be embedded at least
assumed to be at the intersection of a horizontal plane 180 mm into the concrete or masonry and shall be spaced
drawn from the top of the foundation and a plane drawn not more than 2 meters apart. There shall be a minimum of
tangent to the slope at an angle of 45 degrees to the two bolts per piece with one bolt located not more than 300
horizontal. Where a retaining wall is constructed at the toe mm or less than seven bolt diameters from each end of the
of the slope, the height of the slope shall be measured from piece. A properly sized nut and washer shall be tightened
the top of the wall to the top of the slope. on each bolt to the plate. Foundation plates and sills shall be
the kind of wood specified in Chapter 6.
305.5.3 Footing Setback from Descending Slope Surface.
Footings on or adjacent to slope surfaces shall be founded 305.7 Designs Employing Lateral Bearing
in firm material with an embedment and setback from the
slope surface sufficient to provide vertical and lateral
305.7.1 General.
support for the footing without detrimental settlement.
Except as provided for in Section 305.5.6 and Figure 305-1, Construction employing posts or poles as columns
the following setback is deemed adequate to meet the embedded in earth or embedded in concrete footings in the
criteria. Where the slope is steeper than 1 unit vertical in 1 earth may be used and designed to resist both axial and
unit horizontal (100% slope), the required setback shall be lateral loads. The depth to resist lateral loads shall be
measured from an imaginary plane 45 degrees to the determined by means of the design criteria established
horizontal, projected upward from the toe of the slope. herein or other methods approved by the building official.

Association of Structural Engineers of the Philippines


CHAPTER 3 – Excavations and Foundations 3-13

305.7.2 Design Criteria

305.7.2.1 Nonconstrained.
The following formula may be used in determining the
depth of embedment required to resist lateral loads where 305.7.2.3 Vertical Load.
no constraint is provided at the ground surface, such as The resistance to vertical loads is determined by the
rigid floor or rigid ground surface pavement. allowable soil-bearing pressure set forth in Table 304-1.

305.7.3 Backfill.
(305-1)

305.7.2.2 Constrained.
where:
The following formula may be used to determine the depth
of embedment required to resist lateral loads where
constraint is provided at the ground surface, such as a rigid
floor or pavement.
b = diameter of round post or footing or diagonal
Ph
dimension of square post or footing, meters . d 2  4.25 (305-2)
S3 b
d = depth of embedment in earth in meters but not
over 3.5 meters for purpose of computing lateral The backfill in the annular space around column not
pressure. embedded in poured footings shall be by one of the
following methods:
H = distance in meters from ground surface to point of
application of “P.” 1. Backfill shall be of concrete with an ultimate strength
of 15 MPa at 28 days. The hole shall not be less than
P = applied lateral force in kilonewtons .
100 mm larger than the diameter of the column at its
S1 = allowable lateral soil-bearing pressure as set forth in bottom or 100 mm larger than the diagonal dimension
Table 304-1 based on a depth of one third the depth of a square or rectangular column.
of embedment (kPa).
2. Backfill shall be of clean sand. The sand shall be
S3 = allowable lateral soil-bearing pressure as set forth in thoroughly compacted by tamping in layers not more
Table 304-1 based on a depth equal to the depth of than 200 mm in depth.
embedment (kPa).

Face of Footing

Top of Slope

Face of
Toe of Slope
Structure
H/2 but
need not
exceed
4.5.m H
max.
H/3 but need not
exceed 12 m max.

th
National
Figure 305-1Structural
SetbackCode of the Philippines
Dimensions 6 Edition
For Building Volume
Clearance from1Slopes
3-14 CHAPTER 3 – Excavations and Foundations

4. Field inspection and reporting procedures (to include


procedures for verification of the installed bearing
capacity where required).
5. Pile load test requirements.
The use of piles not specifically mentioned in this chapter
shall be permitted, subject to the approval of the building
305.7.4.1 The frictional resistance for retaining walls and
official upon submission of acceptable test data,
slabs on silts and clays shall be limited to one half of the
calculations or other information relating to the properties
normal force imposed on the soil by the weight of the
and load-carrying capacities of such piles.
footing or slab.

306.2 Interconnection
305.7.4 Limitations.
Individual pile caps and caissons of every structure
The design procedure outlined in this section shall be
subjected to seismic forces shall be interconnected by ties.
subject to the following limitations:
Such ties shall be capable of resisting, in tension or
compression, a minimum horizontal force equal to 10
305.7.4.1 Posts embedded in earth shall not be used to
percent of the largest column vertical load.
provide lateral support for structural or nonstructural
materials such as plaster, masonry or concrete unless
Exception:
bracing is provided that develops the limited deflection
Other approved methods may be used where it can be
required.
demonstrated that equivalent restraint can be provided.

305.8 Grillage Footings


306.3 Determination of Allowable Loads
When grillage footings of structural steel shapes are used
The allowable axial and lateral loads on piles shall be
on soils, they shall be completely embedded in concrete.
determined by an approved formula, by a foundation
Concrete cover shall be at least 150 mm on the bottom and
investigation or by load tests. Static axial compressive pile
at least 100 mm at all other points.
load test shall be in accordance with ASTM Standard D-
1143, and lateral load testing of piles shall conform with
305.9 Bleacher Footings ASTM Standard D-3966. Dynamic pile tests shall be in
Footings for open-air seating facilities shall comply with accordance with ASTM Standard D-4945. Static axial
Chapter 3. tensile load testing to determine the uplift capacity of pile-
soil systems shall be in accordance with ASTM Standard D-
Exceptions: 3689.
Temporary open-air portable bleachers may be supported
upon wood sills or steel plates placed directly upon the 306.4 Static Load Test
ground surface, provided soil pressure does not exceed 50
kPa. Static axial compressive pile load test shall be in
accordance with ASTM Standard D-1143. The building
official may require that the test be conducted under the
SECTION 306 - PILES - GENERAL supervision of a registered civil engineer experienced and
knowledgeable in the practice of static pile load testing
REQUIREMENTS
When the allowable axial compressive load of a single pile
306.1 General is determined by a static load test, one of the following
methods shall be used:
Pile foundations shall be designed and installed on the basis
of a foundation investigation as defined in Section 303
Method 1. It shall not exceed 50 percent of the yield point
where required by the building official.
under test load. The yield point shall be defined as that
point at which an increase in load produces a
The investigation and report provisions of Section 303 shall
disproportionate increase in settlement.
be expanded to include, but not be limited to, the following:
1. Recommended pile types and installed capacities. Method 2. It shall not exceed one half of the load, which
causes a net settlement, after deducting rebound, of 0.03
2. Driving criteria. mm/kN of test load, which has been applied for a period of
3. Installation procedures. at least 24 hours.

Association of Structural Engineers of the Philippines


CHAPTER 3 – Excavations and Foundations 3-15

shall be driven down until the required resistance is


Method 3. It shall not exceed one half of that load under obtained.
which, during a 40-hour period of continuous load
application, no additional settlement takes place.
306.10 Protection of Pile Materials
Where the boring records of site conditions indicate
possible deleterious action on pile materials because of soil
306.5 Dynamic Load Test constituents, changing water levels or other factors, such
High-strain dynamic load test may be used to determine the materials shall be adequately protected by methods or
bearing capacity of piles, in accordance with ASTM processes approved by the geotechnical engineer.
Standard D-4945. The building official may require that
the test be conducted by a registered civil engineer The effectiveness of such methods or processes for the
experienced and knowledgeable in the practice of dynamic particular purpose shall have been thoroughly established
load testing. by satisfactory service records or other evidence, which
demonstrates the effectiveness of such protective measures.
306.6 Column Action
All piles standing unbraced in air, water or material not 306.11 Allowable Loads
capable of lateral support shall conform with the applicable The allowable loads based on soil conditions shall be
column formula as specified in this code. Such piles driven established in accordance with Section 306.
into firm ground may be considered fixed and laterally
supported at 1.5 meters below the ground surface and in Exception:
soft material at 3 meters from the ground surface unless Any uncased cast-in-place pile may be assumed to develop
otherwise prescribed by the building official after a a frictional resistance equal to one sixth of the bearing
foundation investigation by an approved agency. value of the soil material at minimum depth as set forth in
Table 305-1 but not to exceed 25 kPa unless a greater value
is allowed by the building official after a foundation
306.7 Group Action
investigation as specified in Section 303 is submitted.
Consideration shall be given to the reduction of allowable Frictional resistance and bearing resistance shall not be
pile load when piles are placed in groups. assumed to act simultaneously unless recommended after a
foundation investigation as specified in Section 303.
Where soil conditions make such load reductions advisable
or necessary, the allowable axial load determined for a
single pile shall be reduced by any rational method or 306.12 Use of Higher Allowable Pile Stresses
formula submitted to the building official. Allowable compressive stresses, greater than those
specified in Section 307 shall be permitted when
substantiating data justifying such higher stresses are
306.8 Piles in Subsiding Areas
submitted to and approved by the building official. Such
Where piles are driven through subsiding fills or other substantiating data shall be included in the foundation
subsiding strata and derive support from underlying firmer investigation report in accordance with Section 306.1.
materials, consideration shall be given to the downward
frictional forces, which may be imposed on the piles by the
subsiding upper strata. SECTION 307 - PILES - SPECIFIC
Where the influence of subsiding fills is considered as
REQUIREMENTS
imposing loads on the pile, the allowable stresses specified
in this chapter may be increased if satisfactory 307.1 Round Wood Piles
substantiating data are submitted.
307.1.1 Material.
306.9 Jetting Except where untreated piles are permitted, wood piles
Installation of piles by water jetting shall not be used except shall be pressure treated. Untreated piles may be used only
where and as specifically permitted by the building official. when it has been established that the cutoff will be below
When used, jetting shall be carried out in such a manner lowest groundwater level assumed to exist during the life of
that the carrying capacity of existing piles and structures the structure.
shall not be impaired. After withdrawal of the jet, piles

National Structural Code of the Philippines 6th Edition Volume 1


3-16 CHAPTER 3 – Excavations and Foundations

307.1.2 Allowable Stresses.


The allowable unit stresses for round woodpiles shall not Piles shall be driven in such order and with such spacing as
exceed those set forth in Chapter 6. to ensure against distortion of or injury to piles already in
place. No pile shall be driven within four and one-half
The allowable values listed in, for compression parallel to average pile diameters of a pile filled with concrete less
the grain at extreme fiber in bending are based on load than 24 hours old unless approved by the geotechnical
sharing as occurs in a pile cluster. For piles which support engineer.
their own specific load, a safety factor of 1.25 shall be
applied to compression parallel to the grain values and 1.30
to extreme fiber in bending values. 307.3.3 Allowable Stresses.
Allowable stresses shall not exceed the values specified in
307.2 Uncased Cast-In-Place Concrete Piles Section 307.2.2, except that the allowable concrete stress
may be increased to a maximum value of 0.40f’c for that
portion of the pile meeting the following conditions:
307.2.1 Material.
Concrete piles cast in place against earth in drilled or bored 1. The thickness of the metal casing is not less than 1.7
holes shall be made in such a manner as to ensure the mm (No. 14 carbon sheet steel gage).
exclusion of any foreign matter and to secure a full-sized 2. The casing is seamless or is provided with seams of
shaft. equal strength and is of a configuration that will
provide confinement to the cast-in-place concrete.
The length of such pile shall be limited to not more than 30
times the average diameter. Concrete shall have a specified 3. The specified compressive strength f’c shall not exceed
compressive strength f’c of not less than 17.5 MPa. 35 MPa and the ratio of steel minimum specified yield
strength Fy to concrete specified compressive strength
Exception: f’c shall not be less than 6.
The length of pile may exceed 30 times the diameter 4. The pile diameter is not greater than 400 mm.
provided the design and installation of the pile foundation
is in accordance with an approved foundation investigation
report. 307.4 Precast Concrete Piles

307.2.2 Allowable Stresses. 307.4.1 Materials.


The allowable compressive stress in the concrete shall not Precast concrete piles shall have a specified compressive
exceed 0.33f’c. The allowable compressive stress of strength f’c of not less than 20 MPa, and shall develop a
reinforcement shall not exceed 34 percent of the yield compressive strength of not less than 20 MPa before
strength of the steel or 175 MPa. driving.

307.3 Metal-Cased Concrete Piles 307.4.2 Reinforcement Ties.


The longitudinal reinforcement in driven precast concrete
piles shall be laterally tied with steel ties or wire spirals.
307.3.1 Material.
Ties and spirals shall not be spaced more than 75 mm apart,
Concrete used in metal-cased concrete piles shall have a center to center, for a distance of 600 mm from the ends and
specified compressive strength f’c of not less than 17.5 not more than 200 mm elsewhere. The gage of ties and
MPa. spirals shall be as follows:
1. For piles having a diameter of 400 mm or less, wire
307.3.2 Installation. shall not be smaller than 5.5 mm (No. 5 B.W.gage).
Every metal casing for a concrete pile shall have a sealed
2. For piles, having a diameter of more than 400 mm and
tip with a diameter of not less than 200 mm.
less than 500 mm, wire shall not be smaller than 6 mm
(No.4 B.W.gage).
Concrete piles cast in place in metal shells shall have shells
driven for their full length in contact with the surrounding 3. For piles having a diameter of 500 mm and larger, wire
soil and left permanently in place. The shells shall be shall not be smaller than 6.5 mm
sufficiently strong to resist collapse and sufficiently
(No.3 B.W. gage).
watertight to exclude water and foreign material during the
placing of concrete.
Association of Structural Engineers of the Philippines
CHAPTER 3 – Excavations and Foundations 3-17

307.4.3 Allowable Stresses. f c  0.33 f ' c 0.27 f pc


Precast concrete piling shall be designed to resist stresses (307-1)
induced by handling and driving as well as by loads. The
allowable stresses shall not exceed the values specified in where:
Section 307.2.2. fpc = effective prestress stress on the gross section.

Effective prestress shall be based on an assumed loss of 200


MPa in the prestressing steel. The allowable stress in the
307.5 Precast Prestressed Concrete Piles (Pretensioned) prestressing steel shall not exceed the values specified in
Section 418.5.
307.5.1 Materials.
Precast prestressed concrete piles shall have a specified 307.5.4 Splicing.
compressive strength f’c of not less than 35 MPa and shall Where required, splicing for concrete piles shall be by use
develop a compressive strength of not less than 27 MPa of embedded and properly anchored thick steel plates at the
before driving. ends being joined which shall then be fully welded, or by
use of adequate sized dowel rods and steel receiving
sleeves. The dowels and the faces shall then be joined by
307.5.2 Reinforcement
structural epoxy. Metal splice cans are not allowed.

307.5.2.1 Longitudinal Reinforcement.


307.6 Structural Steel Piles
The longitudinal reinforcement shall be high-tensile seven-
wire strand conforming to ASTM Standards. Longitudinal
reinforcement shall be laterally tied with steel ties or wire 307.6.1 Material.
spirals. Structural steel piles, steel pipe piles and fully welded steel
piles fabricated from plates shall conform to one of the
material specifications listed in Section 501.3.
307.5.2.2 Transverse Reinforcement.
Ties or spiral reinforcement shall not be spaced more than
75 mm apart, center to center, for a distance of 600 mm 307.6.2 Allowable Stresses.
from the ends and not more than 200 mm elsewhere. The allowable axial stresses shall not exceed 0.35 of the
minimum specified yield strength Fy or 85 MPa, whichever
At each end of the pile, the first five ties or spirals shall be is less.
spaced 25 mm center to center.
For piles having a diameter of 600 mm or less, wire shall Exception:
not be smaller than 5.5 mm (No. 5 B.W.gage). When justified in accordance with Section 306.12, the
allowable axial stress may be increased above 85 MPa and
For piles having a diameter greater than 600 mm but less 0.35Fy, but shall not exceed 0.5Fy.
than 900 mm, wire shall not be smaller than 6 mm
(No. 4 B.W.gage).
307.6.3 Minimum Dimensions.
For piles having a diameter greater than 900 mm, wire shall Sections of driven H-piles shall comply with the following:
not be smaller than 6 mm (No.3 B.W.gauge). 1. The flange projection shall not exceed 14 times the
minimum thickness of metal in either the flange or the
307.5.3 Allowable Stresses. web, and the flange widths shall not be less than 80
Precast prestressed piling shall be designed to resist stresses percent of the depth of the section.
induced by handling and driving as well as by loads. The 2. The nominal depth in the direction of the web shall not
effective prestress in the pile shall not be less than 2.5 MPa be less than 200 mm.
for piles up to 10 meters in length, 4 MPa for piles up to 15
meters in length, and 5 MPa for piles greater than 15 meters 3. Flanges and webs shall have a minimum nominal
in length. thickness of 10 mm.

The compressive stress in the concrete due to externally Sections of driven pipe piles shall have an outside diameter
applied load shall not exceed: of not less than 250 mm and a minimum thickness of not
less than 6 mm.

National Structural Code of the Philippines 6th Edition Volume 1


3-18 CHAPTER 3 – Excavations and Foundations

307.7 Concrete-Filled Steel Pipe Piles

307.7.1 Material.
The steel pipe of concrete-filled steel pipe piles shall
conform to one of the material specifications listed in
Section 501.3. The concrete in concrete-filled steel pipe
piles shall have a specified compressive strength f’c of not
less than 17.5 MPa.

308.4 Foundation-Soil Interface.


For regular structures, the force Ft as provided in Section
307.7.2 Allowable Stresses.
208.5.5 may be omitted when determining the overturning
The allowable axial stresses shall not exceed 0.35 of the moment to be resisted at the foundation-soil interface.
minimum specified yield strength Fy of the steel plus 0.33
of the specified compressive strength f’c of concrete,
provided Fy shall not be assumed greater than 250 MPa for 308.5 Special Requirements for Piles and Caissons.
computational purposes.
308.5.1 General.
Exception:
Piles, caissons and caps shall be designed according to the
When justified in accordance with Section 306.12, the
provisions of Chapter 2, including the effects of lateral
allowable stresses may be increased to 0.50 Fy.
displacements. Special detailing requirements as described
in Section 308.5.2 shall apply for a length of piles equal to
307.7.3 Minimum Dimensions. 120 percent of the flexural length. Flexural length shall be
Driven piles of uniform section shall have a nominal considered as a length of pile from the first point of zero
outside diameter of not less than 200 mm. lateral deflection to the underside of the pile cap or grade
beam.

SECTION 308 - FOUNDATION 308.5.2 Steel Piles, Nonprestressed Concrete Piles and
CONSTRUCTION-SEISMIC Prestressed Concrete Piles.
ZONE 4
308.5.2.1 Steel Piles.
308.1 General Piles shall conform to width-thickness ratios of stiffened,
unstiffened and tubular compression elements as specified
In Seismic Zones 4, the further requirements of this section
in Chapter 5.
shall apply to the design and construction of foundations,
foundation components and the connection of
superstructure elements thereto. See Section 421.9 for 308.5.2.2 Nonprestressed Concrete Piles.
additional requirements for structural concrete foundations Piles shall have transverse reinforcement meeting the
resisting seismic forces. requirements of Section 421.5

308.2 Soil Capacity Exception:


Transverse reinforcement need not exceed the amount
The foundation shall be capable of transmitting the design
determined by Equation 421-2 for spiral and circular hoop
base shear and overturning forces prescribed in Chapter 2
reinforcement, or by Equation 421-4 for rectangular hoop
from the structure into the supporting soil. The short term
reinforcement.
dynamic nature of the loads may be taken into account in
establishing the soil properties.
308.5.2.3 Prestressed Concrete Piles.
308.3 Superstructure to Foundation Connection. Piles shall have a minimum volumetric ratio of spiral
reinforcement no less than 0.021 for 350 mm square and
The connection of superstructure elements to the foundation
smaller piles and 0.012 for 600 mm square and larger piles
shall be adequate to transmit to the foundation the forces for
unless a smaller value can be justified by rational analysis.
which the elements were required to be designed.
Interpolation may be used between the specified ratios for
intermediate sizes.

Association of Structural Engineers of the Philippines


CHAPTER 3 – Excavations and Foundations 3-19

SECTION 309 - SPECIAL


FOUNDATION, SLOPE
STABILIZATION AND
MATERIALS OF
CONSTRUCTION

309.1 Special Foundation Systems


Special foundation systems or materials other than specified
in the foregoing Sections may be introduced provided that
such systems can be supported by calculations and theory to
be providing safe foundation systems and when approved
by the engineer-of-record. Materials for incorporation into
the foundation should have proven track record of
successful usage in similar applications.

309.2 Acceptance and Approval.


Structure support on improved ground using such special
systems or proprietary systems may be approved subject to
submittal of calculations and other proof of acceptance and
successful usage.

309.3 Specific Applications


Specialty foundation systems may be applied or used
specifically to address any or combinations of the
following: bearing capacity improvement, liquefaction
mitigation, slope stability enhancement, control and/or
acceleration of consolidation settlements or immediate
settlements, increase in soil shear capacity, increased
pullout or overturning capacity, special anchors in soil and
rock and other beneficial effects. Controlled low strength
materials (CLSM) to reduce fill loads may be allowed for
use where applicable.

National Structural Code of the Philippines 6th Edition Volume 1

You might also like