Professional Documents
Culture Documents
AAMA 501-05
(Errata 4/5/05)
Methods of Tests
for Exterior Walls
M A N U F A C T U R E R S A S S O C I A T I O N
AAMA 501-05
(Errata 4/5/05)
Errata...................................................................................10
© 2005
American Architectural Manufacturers Association
1827 Walden Office Square, Suite 550, Schaumburg, IL 60173
PHONE 847/303-5664 FAX 847/303-5774
EMAIL webmaster@aamanet.org WEBSITE www.aamanet.org
All AAMA documents may be ordered at our web site in the “Publications Store”.
AAMA 501-05
Originally Published: 1983
Preceding Document: AAMA 501-94
Revised & Published: 2/05
Errata: 4/5/05
Reissued: 4/05
1.0 FOREWORD architectural drawings which represent the materials,
height and width of the mock-up, or provide a separate
mock-up elevation and plan view of the test specimen.
This “Methods of Test” publication AAMA 501-05 is a
The test loads for the mock-up based on design wind
revision of the previous publication 501-94 “Methods of
pressures shall be noted on the drawings or provided in
Test for Exterior Walls”. It is AAMA’s intent to
the specification.
reference in this publication current laboratory and field
testing methods for exterior wall systems comprised of
The following guide specification is provided to assist the
curtain walls, storefronts, and sloped glazing.
architect/specifier in preparing the specification for mock-
up testing.
The AAMA 501-94 publication was the successor
publication of AAMA 501-83. The AAMA 501-83
NOTE: Commentary text (in italics) following each item
publication was the successor publication of the 1968
presents supplementary information and data to aid the
standard known as NAAMM Standards FC-1 and TM-1-
specification writer.
68T originally published by the National Association of
Architectural Metal Manufacturers. All previous versions
of the AAMA 501 publication contained 501.1, 501.2, GUIDE SPECIFICATION FOR
and 501.3. AAMA has decided to publish 501.1 and LABORATORY TESTING
501.2 as stand alone documents. AAMA 501.3 has been
withdrawn and is replaced by AAMA 503-03. 2.1 The tests shall be listed in the order to be performed.
Unless otherwise specified, the following test order shall
The test methods, specifications, and field checks be used by the test agency. Tests listed as “optional”
referenced in this publication are used to evaluate the must be specifically included in the project specifications
structural adequacy of wall systems and their ability to to be included in the test protocol.
resist water penetration and air leakage. Optional tests are
provided, as needed for thermal cycling, interstory lateral 2.2 Preload the test specimen (ASTM E 330) at 50% of
displacement, dynamic seismic racking, acoustical and the specified positive design wind pressure.
thermal performance. Fenestration products covered by
AAMA/NWWDA 101/I.S.2-97 or AAMA/WDMA 2.3 The test for air leakage (ASTM E 283) shall be
101/I.S.2/NAFS-02 are not included in the scope of this conducted at an air pressure difference of _______ Pa
document unless these products are installed as a (psf). The maximum allowable rate of air leakage must
component of the exterior wall test specimen. The not exceed _________ L/s•m2 (cfm/ft2) for fixed wall area
methods for laboratory testing for air leakage, static water or ________ L/s•m2 (cfm/ft2) for operable fenestration
resistance, and structural performance are methods products contained within the test specimen.
prescribed by ASTM. The laboratory test for water
penetration under dynamic air pressure, seismic The Specification must establish air pressure difference
performance, thermal cycling, acoustical and thermal and allowable rate of air leakage. AAMA recommends a
performance are methods prescribed by AAMA. Only minimum air pressure difference for walls of 75 Pa (1.57
those portions of ASTM standards relating to scope and psf) and a maximum allowable rate of air leakage of 0.3
purpose, requirements for test specimens, and test reports L/s•m2 (0.06 cfm/ft2), which is adequate for many
are reproduced herein. The complete ASTM standards buildings. A maximum pressure difference of 300 Pa
may be obtained from ASTM (www.astm.org). (6.24 psf) and a maximum allowable rate of air leakage of
Individual copies of complete AAMA documents 0.3 L/s•m2 (0.06 cfm/ft2) is recommended for buildings in
referenced in this publication may be obtained from which greater control of air quality and/or humidity is
AAMA (www.aamanet.org). required.
2.0 GUIDE SPECIFICATION 2.4 The test for static water penetration (ASTM E 331)
shall be conducted at an air pressure difference of
When contract documents require a mock-up test in __________Pa (psf). There shall be no water leakage
accordance with this publication, they must specifically defined as defined by AAMA 501.1, paragraph 5.5.
indicate those tests which are required and the minimum
performance levels. The mock-up test shall comply with The Specification must establish a minimum air pressure
the procedures and documentation outlined in ASTM E difference at which no water leakage will occur. AAMA
2099 “Standard Practice for the Specification and recommends an air pressure difference equal to 20% of
Evaluation of Pre-Construction Laboratory Mock-ups of the positive design wind pressure with a minimum of 300
Exterior Wall Systems”. The overall size and Pa (6.24 psf) and a maximum of 720 Pa (15 psf).
configuration of the test specimen must also be stated.
The project specifications shall refer to an elevation view
of the mock-up by either designation of an area on the
Deflection shall not exceed 1/175 of the clear span at a 2.14 (Optional) The thermal performance of the test
uniform load equal to the specified design wind pressure. specimen (U-factor, SHGC, VT, and CRF) shall be
determined in accordance with AAMA 507.
If leakage occurs, corrections in wall design and/or 2. Water penetration tests shall be conducted at a static
installation procedures shall be made to eliminate the test pressure of ______ Pa (psf).
leakage problem. The test shall be repeated on a different
unit which has been modified or corrected. 3. The following shall also be field tested:
The AAMA 501.2 water leakage field check does not A. (Insert additional appropriate field tests and
simulate the effects of wind driven rain but does provide a procedures.)
simple, economical method of finding leaking joints.
When used on initially installed units, it permits
identification and correction of leakage problems before
an entire wall is installed. This field check is not
appropriate for testing of operable windows and doors.
DATE: 4/5/05
CODE: 501-05
TITLE: Methods of Test for Exterior Walls
AAMA 501-05, published in January of 2005 was found to have a measurement error in Section 2.3, and two
additional minor editorial errors. These errors have been corrected in AAMA 501-05 (Errata 4/5/05) Reissued 4/05.