Professional Documents
Culture Documents
8510223P01A Instructions VTZ PDF
8510223P01A Instructions VTZ PDF
0.5% slope
4 m/s or more
max. 4 m
A B
U-trap
8 to 12 m/s
max. 4 m
0.5% slope Evaporator
4m/s or more
Fig 5
Fig. 1
Fig. 3
Fig. 2
IN
OUT
Fig 5
Application Envelopes
For the application envelopes of the different va- rant refer to the Danfoss Commercial Compres-
riable speed compressors and applicable refrige- sors dedicated application guidelines.
d
• Installation
Make always sure that there is no possibility of done in relation with the present drawings.
exhaust hot air by-pass from the drive. This will Generally speaking shielded cables have to be
lead to overheating thermal trip of the inverter. used all over the frequency converter and va-
riable speed compressor, except network line to
d
The wiring of a variable speed system is to be frequency converter.
done in a very professional way.
The main precautions on assembly has to be d Fig 6
175ZA786.10
3 Phase
91 (L1)
Power 92 (L2)
Input 93 (L3)
95 PE
Fig 7
Mains and earthing connections
• Motor connections
Fig 8
Motor cable must be screened/armoured. Use on this plate and install the screened part of the connected on both end of the cable: frequency
the accessory decoupling plate. Make sure the motor cable as shown on the above drawings. converter and compressor.
earth wire is connected to the earth terminal Earth wire and screen cable part must be earth
• Control cables
Control cables must be screened/armoured. Use the screen to the decoupling plate for control
the clamp from the accessory bag to connect cables.
Fig 9
Note: CD compressor Drive frequency converters are delivered with a factory preset “open loop control” for compressor speed magement.
®
Frequency converter Compressor Drive
Digital
output
Analog Analog
RS 485
output input
12 13 16 17 18 19 20 27 29 32 33 37 39 42 45 50 53 54 55 60 61 68 69 4 5 1 2 3
0/4-20 mA
0/4-20 mA
0/4-20 mA
+10 V
0 ± 10 V
COM
COM
or 4-20
Incorporate security
devices on 27 input
Bus
mA
Start
to external
Open Loop input 0-10V fault relay
between 13 55
Fig 10
To switch from open loop to process loop cable Reference / Ramps Parameter 3.15Reference ressource 1no
signal connections have to be done has shown Parameter 3.01 bar function
below. Parameter 3.02 -1 bar Control: Analog signal 4-20 mA for -1 / 12 bar
Parameter 3.03 +12 bar is connectected on input 54
The only parameters modifications are: Parameter 3.10 suction pressure adjus- Control Input 54: switch it on I position
Load / motor tement required as a percentage of the sensor (switch located back to the local control panel)
Parameter 1.00Configuration mode: Process pressure range (28% for 3.4 bar -10°C R404A)
TM
Frequency converter CD302 Compressor Drive
Digital
output
Analogue Analogue
RS 485
output input
12 13 16 17 18 19 20 27 29 32 33 37 39 42 45 50 53 54 55 60 61 68 69 4 5 1 2 3
0/4-20 mA
0/4-20 mA
0/4-20 mA
+10 V
0 ± 10 V
0 ± 10 V
COM
COM
Incorporate security
devices on 27 input
Bus
Start
to external
fault relay
Fig 11
Process Control via an AKS32
TM
Frequency converter CD302 Compressor Drive
Digital
output
Analog Analog
RS 485
output input
12 13 16 17 18 19 20 27 29 32 33 37 39 42 45 50 53 54 55 60 61 68 69 4 5 1 2 3
0/4-20 mA
0/4-20 mA
0/4-20 mA
+10 V
0 ± 10 V
COM
COM
or 4-20
Incorporate security
devices on 27 input
Bus
mA
Start
to external
fault relay
Fig 12
Process Control via an AKS33
8510223 P01-A