CN-6000 Series

Features
• Multi-input
·CN-610 (except CN-640 )
: Thermocouple 12 types, RTD 5 types,
Analog (mV, V, mA) 6 types
·CN-640 : 0 to 50.00 kHz
• Improves visibility with negative LCD
: 12 segment, 3 colors (selectable red, green, yellow)
• Displays input type and unit on display part
• Various outputs
: 4EA, 2EA, 1EA alarm output,
0-20 mA transmission output
(adjustable insulation, output range),
0-10 VDC voltage output
(adjustable insulation, output range)
• Various functions
: High/Low peak monitoring, sensor disconnection
alarm output (burn-out), input correction, user input Please read “Caution for your safety” in operation manual
before using this unit.
range, display scale, transmission output scale,
analog output range setting
• Built-in power supply for sensor (24 VDC)

Ordering information

CN 6 10 0 C1
C1 Transmission output (0-20 mA) 1EA
C2 Transmission output (0-2 0mA) 2EA
V1 Transmission output (0-10 V) 1EA
Output
V2 Transmission output (0-10 V) 2EA
R1 Alarm output 1EA
R2 Alarm output 2EA
R4 Alarm output 4EA
Supply power 0 100-240 VAC 50 to 60 ㎐
1 24 VDC

Input 10 Universal input


40 Pulse input (※option)
Item
CN-6 Isolated Converter

Part descriptions
⑧ ① Display part (selectable red, green, yellow)
·Run mode: Displays current measured value.
·Parameter set mode: Displays parameters and SV.
② ②
② Unit display part (red)

③ Output scale Bar : For transmission output mode,
③ ④
displays output as % by scale bars.
④ Alarm output indicator: Turns ON when the alarm output is on.
⑥ ⑤ ( key: Used to enter parameter set mode, move to parameters,
⑤ ⑤ save SV and return to RUN mode.
⑥ 1, 4, 3 key: Used to change parameter SV.
⑦ ⑦ D.IN3 : Press the 4 and 3 keys for 3 sec. at the same time,
[ Transmission output model ] [ Alarm output model ] it operates the set function (alarm clear, display hold,
zero-point adjustment) at [DI-K].
⑧ Input type (only for CN-610 )
:Turns ON the selected temperature sensor type at [IN-P] pa-
rameter. (In case of thermocouple type, L, N, U, P types are not
displayed. In case of RTD type, RTD is displayed.)
(In case of thermocouple type, L, N, U, P types are not displayed.
In case of RTD type, RTD is displayed.)

C-2
Isolated Converter

Connections A. Recorder

■ CN-610 B. Indicator

● 8PIN
C. Converter

D. Controller

E. Thyristor
SOURCE unit
100-240VAC 50 to 60Hz,
24VDC F. Pressure
transmitter
※When using 2-wire transmitter,
short between no.4 and 5 terminals.
G. Temp.
transmitter

● 11PIN
H. Accessories

SOURCE
※When using 2-wire transmitter, 100-240VAC 50 to 60Hz,
short between no.6 and 4 terminals. 24VDC

■ CN-640 CN-6000

● 8PIN

Voltage

SOURCE
100-240VAC 50 to 60Hz,
24VDC

※ When inputting open collector to no. 3 and 5 terminals


for inputting contact, connect external resistance 10kΩ
(over 1/2W) to no.3 and 6 terminals.

● 11PIN

Voltage

SOURCE
100-240VAC 50 to 60Hz,
※ When inputting open collector to no. 5 and 4 terminals 24VDC
for inputting contact, connect external resistance
10kΩ(over 1/2W) to no.3 and 5 terminals.

C-3
CN-6000 Series
Specifications
Model CN-610 CN-640
AC voltage 100-240 VAC 50 to 60 Hz
Power supply
DC voltage 24 VDC
Allowable voltage range 90 to 110% of rated voltage
Power AC voltage Max. 8 VA
consumption DC voltage Max. 3 W
4digit : 12 Segment LCD Display (selectable red, green, yellow)
Display method
Graphic bar and Input/Unit display part (red)
Character size Display part : 6.4×11.0 mm (12 Segment), Input/Unit display part : 1.4×2.75 mm (unit)
RTD JPt100Ω, DPt100Ω, DPt50Ω, Cu50Ω, Cu100Ω
Thermocouple K, J, E, T, R, B, S, N, C, L, U, PLII
Input type • Voltage : -50.0-50.0 mV, -199.9-200.0 mV,
Analog -1.000-1.000 V, -1.00-10.00 V
• Current : 0.00-20.00 mA, 4.00-20.00 mA
Pulse input 0 to 50.00 kHz(input impedance 10 kΩ)
Transmission 0-20 mA(adjustable output range), load resistance max. 600 Ω (accuracy: ±0.3 F.S., resolutions: 8000)
output 0-10 VDC(adjustable output range), load resistance max. 10 kΩ (accuracy: ±0.3 F.S., resolutions: 8000)
Output
1-point : Relay contact capacity 250 VAC 5 A 1 a, 2-point : Relay contact capacity 250 VAC 3 A 1 c,
Alarm output
4-point : Relay contact capacity 250 VAC 5 A 1 a
±0.2%F.S. ±1digit (25±5 ℃), ±0.3%F.S. ±1digit (-10 to 20 ℃, 30 to 50 ℃)
Display accuracy ※CN-610 : For TC, the input below -100 ℃ is [±0.4%F.S.] ±1digit (TC-T, TC-U is max. ±2.0 ℃)
Setting method Set by front keys
Sampling cycle Analog input : 100 ms, Temperature sensor input : 250 ms
Same with pulse input cycle
Display cycle When pulse input cycle is over 10 sec., it is updated by
every 10 sec.
Dielectric voltage 2000 VAC 50/60 Hz for 1 min. (between input terminal and power terminal)
Vibration 0.75 mm amplitude at frequency of 5 to 55 Hz (for 1 min.) in each of X, Y, Z directions for 2 hours
Insulation resistance Min. 100 MΩ (at 500VDC megger)
Noise resistance Square shaped noise by noise simulator (pulse width 1 ㎲) ±2 kV
Memory retention Approx. 10 years (non-volatile semiconductor memory type)
Ambient 10 to 50 ℃, storage : 20 to 60 ℃
temperature
Environment
Ambient
35 to 85%RH, storage : 35 to 85%RH
humidity
Approval
Unit weight Approx. 160 g Approx. 200 g
※ Environment resistance is rated at no freezing or condensation.

Dimensions
(unit:mm)
DIN35 Rail
35.2
80

85

50 80 20 3.3

● 8PIN socket ● 11PIN socket


8 8

2-Ø4.5
76

76

2-Ø4.5 2-Ø4.5
40

Min. 51
40 40
50 50

C-4
Isolated Converter

Input type and range A. Recorder

٧٧Input type selection switch B. Indicator

● 8PIN ● 11PIN
· mA : Select it for 0(4)-20 mA input C. Converter
· 10 V :Select it for -1 V-10 V input
· TC, RTD, mV, ±1V : Select it for RTD, TC temperature sensor or D. Controller
±1 V, mV input
※The pulse input model (CN-640 ) does not have this input type
E. Thyristor
selection switch. unit

F. Pressure
transmitter
• This product is multi-input. Select the desired input type by the input
type selection switch and select the input type at [ IN-P] parameter. G. Temp.
• The selection of the input type selection switch and that of [IN-P] transmitter
parameter should be same to display correct value. Factory default
is 4-20 mA. H. Accessories

■ CN-610 (universal input)


Input type Parameter Input range (℃) Input range (℉)
TcK1 200 to 1350 328 to 2462
K(CA)
TcK2 199.9 to 999.9 328 to 1832
J(IC) TC-J 199.9 to 800.0 328 to 1472
E(CR) TC-E 199.9 to 800.0 328 to 1472
T(CC) TC-T 199.9 to 400.0 199.9 to 752.0
B(PR) TC- B 400 to 1800 752 to 3272
Thermocouple R(PR) TC-R 0 to 1750 32 to 3182
S(PR) TC-S 0 to 1750 32 to 3182
N(NN) TC-N 200 to 1300 328 to 2372
CN-6000
C(W5) TC-C 0 to 2300 32 to 4172
L(IC) TC-L 199.9 to 900.0 328 to 1652
U(CC) TC-U 199.9 to 400.0 199.9 to 752.0
Platinel II TC-P 0 to 1390 32 to 2534
Cu50Ω Cu50 199.9 to 200.0 199.9 to 392.0
Cu100Ω Cu10 199.9 to 200.0 199.9 to 392.0
RTD JPt100Ω JPt1 199.9 to 600.0 328 to 1112
DPt50Ω DPt5 199.9 to 600.0 328 to 1112
DPt100Ω DPt1 199.9 to 850.0 328 to 1530
0.00 - 20.00 mA aMA1
Current
4.00 - 20.00 mA aMA2
50.0 - 50.0 mV aMV1 1999 to 9999
Analog (display range depends
199.9 - 200.0 mV aMV2 on the decimal point position)
Voltage
1.000 - 1.000 V A-V1
1.00 - 10.00 V A-V2

■ CN-640 (pulse input)


Input type Measuring cycle Parameter Range
0 to 9.999 Hz Max. 10 sec. 10H
0 to 99.99 Hz Max. 10 sec. 100H 1999 to 9999
Pulse 0 to 999.9 Hz Max. 10 sec. 1KH (display range is variable
according to decimal point position.)
0 to 9.999 kHz Max. 1 sec. 10KH
0 to 50.00 kHz Max. 0.1 sec. 50KH
※ Pulse input: Non-contact 0 to 50 kHz, Contact 0 to 45 Hz (displays 0 for below 0.1Hz)
※ Input Low Level : 0-1 VDC / Input High Level : 5-24 VDC
※ Duty Ratio : 30 to 70%
※ The principle of displaying frequency is converting the time difference between input pulses to the frequency. 1 sec. is required to
measure 1 Hz, and 10 sec. is required to measure 0.1 Hz. Therefore, it is normal that the lower pulse, the slower response speed. In
case of 0 Hz, if there are no pulses for over 2 sec., it is programmed to display 0 Hz to prevent slow response speed.

C-5
CN-6000 Series
Functions

■ Alarm [ AL-1, AL-2, AL-3, AL-4]


This product has 1 alarm or 2 or 4 alarms to operate individually when the value is too high or low. Alarm function is set by the
combination of alarm operation and alarm option.
To clear alarm, use digital input function (setting as AlRE for DI-K) or turn the power OFF and ON.
※For the model without alarm output (CN-6 -C1/C2/V1/V2), these parameters are not displayed.
AT!A
Alarm option

Alarm operation
٧٧Alarm operation
Mode Name Alarm operation Description

AT)_ ㅡ ㅡ No alarm operation

OFF H ON
AT! High limit alarm High limt alarm PV ≥ alarm temperature, alarm is ON
PV
value: 800℃

ON H OFF
AT@ ※1 Low limit alarm Low limt alarm PV ≤ alarm temperature, alarm is ON
PV
value:200℃
It will be ON when it detects sensor disconnection.
SBa_ Sensor break alarm ㅡ
Sensor break alarm does not have alarm option.
※ 1. Only for CN-610 . ※H : Alarm output hysteresis
٧٧Alarm option
Mode Name Descriptions

AT .A Standard alarm If it is an alarm condition, alarm output is ON. Unless an alarm condition, alarm output is OFF.
If it is an alarm condition, alarm output is ON. Before clearing the alarm, an ON condition is
AT .B Alarm latch
latched. (Holding the alarm output)
First alarm condition is ignored. From the second alarm condition, standard alarm operates.
AT .C Standby sequence When power is ON and it is an alarm condition, it is ignored. From the second alarm condition,
standard alarm operates.
If it is an alarm condition, it operates both alarm latch and standby sequence.
Alarm latch and
AT .D When power is ON and it is an alarm condition, it is ignored. From the second alarm condition,
standby sequence
alarm latch operates.

■ Alarm output hysteresis ■ High/Low peak monitoring


[Program mode : A-HY] [Monitoring mode: hPEK, lPEK]
Set the interval of ON/OFF alarm output. This function is to save high/low peak to check the invisible
The set hysteresis is applied to AL1 to AL4 and it is as abnormal condition of system at [ hPEK] or [ lPEK] in
below. monitoring mode.
※Ex) A-HY 4, high limit alarm value: 800, When the high/low peak is out of the temperature range,
it displays HHHH or LLLL.
low limit alarm value: 200
To initialize high/low peak, press the 4, 3 keys at the
same time for 3 sec. at [ hPEK] or [ lPEK] .
High limit
alarm value A-HY:4 In this case, peak value is the present input value.
800
■ Error
Display Descriptions Troubleshooting
Flashes when measured
800 796 LLLL sensor input is lower than the
When input is
ON OFF temperature range. moved within the
Flashes when measured sen- temperature range,
HHHH sor input is higher than the it is cleared.
temperature range
Low limit A-HY:4
alarm value
※1
Flashes when the sensor is Check temperature
BURN break or not connected. sensor connection.
200
Flashes when there is error to Check set conditions
ERR SV. and re-set it.
Flashes when [ IN-P] setting
200 204
ERR2 and input type selection switch Check input type.
ON OFF
setting are not same.
※ 1. Only for CN-610 .

C-6
Isolated Converter

■ Parameter initialization Display scale function is able to change display value for
max./min. measured input by setting high limit scale A. Recorder
To initialize all parameter as factory default, press the [H-SC] and low limit scale [L-SC] in program mode.
( and 1 keys at the same time in RUN mode and it ※Ex) Set high/low scale value (input range is 0 to 10V) B. Indicator
enters initialization parameter.
• L-SC= )00
RUN mode • H-SC= %00, 1)00, 1%00, `)00 C. Converter
Press the ( + 1 keys Display value
at the same time.
INIT 1%00 D. Controller
1)00
%00 E. Thyristor
3 unit
NO 4 YES 0
Input value
10V
F. Pressure
( transmitter
`)00
Completes initialization.
※ Parameter initialization is available only when lock G. Temp.
transmitter
[ LOCK] is set as OFF. • L-SC=1)00, H-SC= `)00
Display value H. Accessories
■ Temperature unit [Program mode : UNIT]
1%00
Temperature unit (℃/℉) is selectable. When changing
1)00
temperature unit, user input range, display scale, output
scale, alarm SV are initialized. You should set the
parameters again for your purpose. Input value
0 10V
※ When selecting analog input, this parameter [ UNIT] is
not displayed. `)00

■ Front display unit [Program mode : dUNT]


• When selecting analog input, select the unit (mV, V, mA, • L-SC=-%00, H-SC= %00
A, ℃, ℉, %)of display value.(CN-610 ) Display value
• When selecting pulse input, select the unit (kHz, Hz, %) 1%00
of display value. (CN-640 )
1)00
• When not displaying unit, set OFFand it turns OFF all %00
indicators. CN-6000
Input value
0 10V
■ User input range -%00
[Program mode : L-RG, H-RG]
When selecting analog input, you can set the input range
for your purpose. Set low limit input value [ L-RG] and ※ When changing input type, high/low scale is changed as
high limit input value [ H-RG] to limit the input range. factory default.

• Set conditions :
Low limit input value [ L-RG] +20% F.S. < High limit
input value [ H-RG] ■ Input correction [Program mode: IN-B]

■ Decimal point [Program mode: dP] This function is to correct the error occurring from a
thermocouple, a RTD or analog input out of allowable
It is able to change decimal point position for high/low limit
error range of this unit.
scale value. It changes decimal point position of display
value. This is also available to correct error when a sensor
cannot contact the subject position by calculating the error
■ Display scale [Program mode: L-SC, H-SC] temperature.
For analog input, this function is to set ( 1999 to 9999)for Variable temperature sensors have accuracy level.
particular high/low limit value in order to display high/low Because high accuracy type is expansive, standard
limit value of measurement input. If measurement inputs thermocouples are generally used.
are ‘a’ and ‘b’ and particular values are ‘A’ and ‘B’, it will In this case, temperature sensor may occur error. By
display a=A, b=B as below graphs. executing this function, you can get more accurate
Display Display temperature.
Display value B value
value B When executing input correction function, you should
B measure the error from a sensor accurately. If the
A measured error is not correct, error may be greater.
A
a b Ex)When measured temperature is 4 ℃ and actual
a b a b A
Input Input temperature is 0 ℃. Set IN-B as -4, and display
Input value value
value value is 0 ℃.
Display Display Display
value value value A
a b
B a b
A
A
a b B B
Input Input Input
value value value

C-7
CN-6000 Series
■ Transmission output range ■ Input special function [Program mode: InSF]
[Program mode: lOR , hOR ] When selecting analog input, this function is to display the
Transmission output scale calculated actual value by square, root (√), or two unit
[Program mode: lOU , hOU ] function (TUF) as display value.
This function is to set output scale and range for display
Parameter Functions Graph Applications
value for transmission output.
Display
When the input value set at lOU1/ lOU2 is displayed, Y = AX + B Standard
Outputs
the output value set at lOR1/ lOR2 is transmitted. characteristics.
LIN as input Input for
Input
When the input value set at hOU1/hOU2 is displayed, value
linearity.
the output value set at hOR1/ hOR2 is transmitted.
Outputs Display
Output Output
the
Y = A( X ) + B Used for
(X ≥ 0)
rooted measuring flows
ROOT Y=0(X < 0)
by pressure
(√) input Input signal.
value
Display Display Outputs Display Used for
Y = A(X)2 + B
the (X > 0) outputting
※Relation among input range, user input range, display SQAR squared Input differential
input Y = -A(X)2 + B pressure by flow
scale, transmission scale, and output range
value (X < 0) signal.
The below figure is the example for 4 to 20 mA input and
0-20 mA transmission output. TUF Refer to ‘Two unit function’
※Display value and mA output value for SQAR:
Input range
Input value - L-RG 2×(
Display value={( ) H-SC-L-SC)} + L-SC
(output value) H-RG - L-RG
User
input range ※Display value and mA output value for ROOT:
(6 mA to 16 mA)
Input value - L-RG
Display value={( )×( H-SC-L-SC)} + L-SC
Display scale H-RG - L-RG
(0 to 1000) (output value)

٧٧Two Unit Function [ TUF]


Output scale
When connecting a pressure sensor, compound
pressure which is below atmospheric pressure (0) is for
vacuum as mmHg and which is atmospheric pressure
Output range or over it is for positive pressure as kg/cm2.
4 mA 20 mA Atmospheric pressure is 0kg/cm2 . When this unit
transmission transmission
does not display 0kg/cm2 , you can correct zero-point
When display value is 100, it outputs 4 mA. adjustment function.
When display value is 900, it outputs 20 mA.
When using two unit function, L-SC is fixed as -760.
L-SC parameter is displayed but you cannot set this.
■ Bar display channel You can set H-SC within 0 to 9999 range.
[Program mode: BAR, User level: HIGH]
This function is to select OUT1 or OUT2 for Bar display of ■ Atmospheric pressure (0) setting
transmission output scale. for Two Unit Function
※ Only for the model which has two transmission outputs [Program mode: )PSI, InSF: TUF]
(CN-6 -C2/V2), this parameter is displayed. This function is to set analog input value for atmospheric
pressure (0) at analog input range.
■ Input and transmission output extension Ex) When pressure range is 760.0 mmHg to 3.000 kg/
[Program mode : ExIO] cm2 , and pressure transmitter outputs 4-20 mA and
it outputs 8.00 mA for atmospheric pressure (0), set
This function is to extend analog input and 4 to 20 mA, input special function as TUF, H-SC: 3000, dP:
0-10 VDC transmission output to 5% or 10% range. )000, )PSI: 0800. This unit displays for 4 mA input
The below table is the case of 4 to 20 mA transmission as -760, for 8 mA input as )000 and 20 mA input
output range setting. as #000.

Mode Operation
Display
Outputs 4 to 20 mA within analog input
0P range.
Outputs 3.2 to 20.8 mA for 5% out of the
5P analog input range.
Outputs 2.4 to 21.6 mA for 10% out of the Input
10P analog input range. 8 mA

※ This parameter is not displayed for not transmission


output (4-20 mA, 0-10 V) model, or for selecting
temperature sensor input.
※ Below 0 mA, 0 VDC cannot extend.
※ ±1 VDC, 10 VDC input are available to extend only 5%. ※This function is only for CN-610 .

C-8
Isolated Converter

■ Span correction ■ Digital input [Program mode: DI-K]


A. Recorder
[Program mode: SPAN, User level: HIGH]
By front digital input keys (D.IN3: 4 + 3 for 3 sec.), one of
It corrects the error of display value for 100% input. three functions executes as the below table.
B. Indicator
• Set range : 0.900 to 1.100 Function Operaiton
Output
※ When alarm is ON in RUN mode, it
C. Converter
clears alarm forcibly. (It applies only for
alarm latch, alarm latch and standby
sequence options.)
D. Controller
※ Alarm clear operates only when the
Alarm
AlRE clear
value is out of the alarm value range.
E. Thyristor
After clearing alarm, alarm operates its
unit
Input option normally.
0.00 kgf/cm2 10.00 kgf/cm2 ※ For the model without alarm output F. Pressure
(CN-6 -C1/C2/V1/V2), this transmitter
parameter is not displayed.
■ Digital filter G. Temp.
Temporarily indicated value is stopped in
[Program mode: AvF/ MAvF, User level: HIGH] Display transmitter
HOLD HOLD
order to confirm indicated value in unstable
Digital filter is able to stably display and output the noise input.
H. Accessories
from input line and irregular signals. Set preset display value as 0.
Normal average filter AvF displays the averaged Zero- This function is related with input
point correction [ IN-B]. When executing zero
N times of input values periodically. Moving average ZERO adjust- adjustment function in display value as
filter MAvFdisplays the moving averaged N times of input
ment 4, input correction value IN-B is set -4
values in real time.
automatically.
• Filter set range : 01 to 16
※When setting as 01, digital filter function does not run.
■ Display color [Program mode: CLOR]
100ms This function is to change display color for occurring error,
operating alarm automatically. User can check the status
of this unit directly.
S1 S2 S3 S4 S5 S6 S7 S8 S9 ※ Color of monitoring mode, program mode is red.
٧٧EVENT: When occurring alarm and
Sn: Sampling value displaying HHHH, LLLL, BURN, ERR
Dn: Display value
Parameter Display color CN-6000

SV RUN EVENT
RED Red Red
D1 D2 D3 D4 D5 D6 D7 D8
GRN Green Green
D1=S1, D2=S2, D3=S3 YELO Yellow Yellow
: Initial operation before averaging 4 R--G Red Green
S1+S2+S3+S4 S2+S3+S4+S5 G--R Green Red
D4= D5=
4 4
S3+S4+S5+S6 S4+S5+S6+S7 ■ Alarm output for disconnecting input sensor
D6= D7=
4 4 [Program mode: BURN]
S5+S6+S7+S8 When disconnecting input sensor, you can set the status
D8= of transmission output.
4
It flashes BURN and it outputs the set value of HHHH or
LLLL.
For transmission output, it outputs the set max./min. value
of I/O expansion function.

Transmission
Parameter SV Alarm output
output (4-20 mA)
High limit Low limit
ON 20 mA
alarm ON alarm OFF
BURN
High limit Low limit
OFF 4 mA
alarm OFF alarm ON

■ Lock [Program mode: LOCK]


It limits to check parameter set value and to change it.

OFF LOC1 LOC2


Program mode
Monitoring mode

: Enable to check/set
: Enable to check, disable to set,
: Disable to check
※ In LOC2, only LOCK parameter displays in program
mode.

C-9
CN-6000 Series
Monitoring mode
※ 1. S :Press any key among the 1, 3, 4.
RUN mode ※ 2. 1 : Moves digits / 4, 3: Changes SV.
※ 3. Press the key after checking/changing SV in each parameter.
The value flashes twice and is saved. It moves to next parameter.
Press MODE key. ※ After entering setting group, press the key for 3 sec. or there is no additional key
operation in 30 sec., it returns to RUN mode.
※ This parameter might not be displayed depending on other parameter settings.

※1 ※2 ※Displays only for the transmission output model.


1CH output value
S
OUT1 ----
MODE MODE ※3

Displays output value by each channel.


2CH output value
S
OUT2 ----
MODE

※Displayed only for alarm output model.


Alarm 1 value
S
AL1 10)0
MODE

Alarm 2 value
S Set each alarm value; [ AL-1 to AL-4] in program mode.
AL2 00)0
MODE · Set range: Temperature sensor input → within temperature range
Analog input → L-SC to H-SC
※ When alarm operation[ AL-1 to AL-4] in program mode is
Alarm 3 value no alarm [ AT)_] or sensor disconnection alarm [ SBa_], these
S parameters are not displayed.
AL3 10)0
MODE ※ For 1EA (CN-6 -R1) or 2EA (CN-6 -R2) alarm models,
AL3, AL4 are not displayed.

Alarm 4 value
S
AL4 00)0
MODE

High peak value


S
hPEK ----
MODE Displays high/low peak value.
※High/Low peak value is available only to check and initialize it.
(Refer to ‘High/Low peak monitoring’ for initialization.)
Low peak value
S ※ Initial high/low peak is saved after 2 sec. from supplying the power.
lPEK ----
MODE

C-10
Isolated Converter

Program mode A. Recorder

■ CN-610 (universal input)


※ 1. S :Press any key among the 1, 3, 4. B. Indicator
RUN mode ※ 2. 1 : Moves digits / 4, 3: Changes SV.
Press MODE key ※ 3. Press the key after checking/changing SV in each parameter. C. Converter
for 3 sec. The value flashes twice and is saved. It moves to next parameter.
※ After entering setting group, press the key for 3 sec. or there is no additional
key operation in 30 sec., it returns to RUN mode. D. Controller
※ This parameter might not be displayed depending on other parameter settings.
Input type ※1 ※2 E. Thyristor
S unit
IN-P aMA2 Select input type. (Refer to「Input type and range」.)
MODE MODE ※3 F. Pressure
transmitter
※Displayed only when selecting temperature sensor input type.
Temperature unit G. Temp.
S transmitter
UNIT ?C Select temperature unit. ?C ?F
MODE
H. Accessories

Display unit ※Displayed only when selecting analog input type.


S Select front display unit.
dUNT ?/O
MODE
?/O OFF MV V MA ?C ?F

Low limit input value


S
Set low limit of input range.
L-RG 0$00 · Set range : within analog input type range
MODE

High limit input value


S Set high limit of input range.
H-RG 2)00 · Set range : within analog input type range
MODE

Decimal point CN-6000


S Select decimal point position of display scale value.
dP )0
MODE )0 )00 )000 0
Low limit
scale value
S Set low limit scale value.
L-SC 00)0 · Set range : -1999 to 9999
MODE

High limit
scale value
S Set high limit scale value.
H-SC 10)0 · Set range : -1999 to 9999
MODE

Input correction
S Set input correction value.
IN-B 000 · Set range : -999 to 999
MODE

※Displays only for the transmission output model.


Transmission output 1
low-limit
S Set low limit value of transmission output 1.
lOR1 0$00 · Set range : Current output → 0-20 mA, Voltage output → 0-10 VDC
MODE

Transmission output 1
high-limit
S Set high limit value of transmission output 1.
hOR1 2)00 · Set range : Current output → 0-20 mA, Voltage output → 0-10 VDC
MODE

Transmission output 2
low-limit
S Set low limit value of transmission output 2.
lOR2 0$00 · Set range : Current output → 0-20 mA, Voltage output → 0-10 VDC
MODE

Transmission output 2
high-limit
S Set high limit value of transmission output 2.
hOR2 2)00 · Set range : Current output → 0-20 mA, Voltage output → 0-10 VDC
MODE

C-11
CN-6000 Series
※Displays only for the transmission output model.
Bar display CH
S Select the channel for Bar display.
BAR OUT1 ※Displayed only when selecting user level [ USER] as HIGH.
MODE
OUT1 OUT2
Transmission output 1
low-limit scale
S Set low limit scale value of transmission output 1.
lOU1 00)0 · Set range : Temperature sensor input → within temperature range,
MODE Analog input → L-SC to H-SC

Transmission output 1
high-limit scale
S Set high limit scale value of transmission output 1.
hOU1 10)0 · Set range : Temperature sensor input → within temperature range,
MODE Analog input → L-SC to H-SC

Transmission output 2
low-limit scale Set low limit scale value of transmission output 2.
S
lOU2 00)0 · Set range : Temperature sensor input → within temperature range,
MODE Analog input → L-SC to H-SC

Transmission output 2
high-limit scale Set high limit scale value of transmission output 2.
S
hOU2 10)0 · Set range : Temperature sensor input → within temperature range,
MODE Analog input → L-SC to H-SC

Input and transmission


※Displayed only for transmission output models with selecting analog input type.
output extension
S Select extension range of analog input and transmission output.
EX.IO SP ※Displayed only when selecting user level [ USER] as HIGH.
MODE
SP 10P 0P

※Displayed only for alarm output model.


AL1 mode
S
AL-1 AT!A
MODE Set AL1 to <Alarm operation> <Alarm option>
AL4 alarm S
AL2 mode operation AT!A AT!A
AL-1
S and option.
AL-2 AT@A MODE
MODE

MODE AL-2 AT@A AT!B


MODE

AL3 mode AL-3 SBa_ AT!C


S MODE

AL-3 AT!A AL-4


MODE MODE AT)_ AT!D
Next parameter
AL4 mode ※SV changing method of AL-2 to AL-4 is same as AL-1’s.
S
AL-4 AT@A ※ For 1EA (CN-610 -R1) or 2EA (CN-610 -R2) alarm models,
MODE AL-3, AL-4 are not displayed.
※ No alarm [ AT)_], sensor break alarm [ SBa_] do not have alarm
option.
※ Set alarm value [ AL1 to AL4] in monitoring mode.
AL output hysteresis
S Set alarm output hysteresis.
A-HY 001 · Set range : 001 to 999
MODE
※ When alarm operation[ AL-1 to AL-4] in program mode is no alarm [ AT)_] or
sensor disconnection alarm [ SBa_], this parameter is not displayed.

※Displayed only when selecting analog input type.


Input special function
S
InSF LIN Select input special function.
MODE
LIN ROOT SQAR TUF

C-12
Isolated Converter

Atmospheric pressure
S A. Recorder
Set analog input value for atmospheric pressure (0) at Two Unit Function.
)PSI 0*00 · Set range : L-RG to H-RG
MODE
※Displayed when setting input special function [ InSF] as TUF.
B. Indicator

Span correction
S Correct the error of display value for 100% input. C. Converter
SPAN !000 · Set range :0.900 to 1.100
MODE
※Displayed only when selecting user level [ USER] as HIGH.
D. Controller
Normal average
digital filter
S Set the number of normal average digital filters. E. Thyristor
AvF 01 · Set range : 01 to 16
unit
MODE
※Displayed only when selecting user level [ USER] as HIGH. F. Pressure
transmitter
Moving average
digital filter
S Set the number of moving average digital filters. G. Temp.
MAvF 04 · Set range : 01 to 16 transmitter
MODE
※Displayed only when selecting user level [ USER] as HIGH.
H. Accessories
Digital input key Select digital input function by front keys.
S
DI-K HOLD ※ Press 3, 4 keys for 3 sec. at the same time and
MODE
it executes the selected function.
※ For the model without alarm output (CN-610 -C1/C2/V1/V2),
AlRE is not displayed.

HOLD ZERO AlRE


Display color
S Select display part color for RUN mode and error.
COLR GRN
MODE
※Refer to 「Display color」.

GRN YELO R--G G--R RED

Sensor break ※Displayed only when selecting temperature sensor input type.
alarm output CN-6000
S
Select output status when sensor disconnection.
BURN ON
MODE
ON OFF

User level
S Select user level.
USER STND
MODE STND HIGH

Lock
S Select lock function.
LOCK OFF
MODE
OFF LOC1 LOC2

C-13
CN-6000 Series
■ CN-640 (pulse input)
※ 1. S :Press any key among the 1, 3, 4.
RUN mode ※ 2. 1 : Moves digits / 4, 3: Changes SV.
※ 3. Press the key after checking/changing SV in each parameter.
Press MODE key The value flashes twice and is saved. It moves to next parameter.
for 3 sec. ※ After entering setting group, press the key for 3 sec. or there is no additional
key operation in 30 sec., it returns to RUN mode.
※1
※ This parameter might not be displayed depending on other parameter settings.
Input type ※2
S
IN-P 50KH Select input type. (Refer to 「Input type and range」.)
MODE MODE ※3

Display unit
S Select front display unit.
dUNT KHZ
MODE
KHZ HZ ?/O OFF

Low limit input value


S
Set low limit of input range.
L-RG 0)00 · Set range : within input type range
MODE

High limit input value


S Set high limit of input range.
H-RG 5)00 · Set range : within input type range
MODE

Decimal point
S Select decimal point position of display scale value.
dP )00
MODE
)0 )00 )000 0
Low limit scale value
S Set low limit scale value.
L-SC 0)00 · Set range : -1999 to 9999
MODE

High limit scale value


S Set high limit scale value.
H-SC 5)00 · Set range : -1999 to 9999
MODE

Input correction
S Set input correction value.
IN-B 000 · Set range : -999 to 999
MODE

Transmission output 1 ※Displays only for the transmission output model.


low-limit
S Set low limit scale value of transmission output 1.
lOR1 0)00 · Set range : Current output → 0-20 mA, Voltage output → 0-10 VDC
MODE

Transmission output 1
high-limit
S Set high limit scale value of transmission output 1.
hOR1 1)00 · Set range : Current output → 0-20 mA, Voltage output → 0-10 VDC
MODE

Transmission output 2
low-limit
S Set low limit scale value of transmission output 2.
lOR2 0)00 · Set range : Current output → 0-20 mA, Voltage output → 0-10 VDC
MODE

Transmission output 2
high-limit
S Set high limit scale value of transmission output 2.
hOR2 1)00 · Set range : Current output → 0-20 mA, Voltage output → 0-10 VDC
MODE

Bar display CH
S Select the channel for Bar display.
BAR OUT1 ※Displayed only when selecting user level [ USER] as HIGH.
MODE
OUT1 OUT2

C-14
Isolated Converter

Transmission output 1 ※Displays only for the transmission output model. A. Recorder
low-limit scale
S Set low limit scale value of transmission output 1.
lOU1 0)00 · Set range : L-SC to H-SC
MODE B. Indicator

Transmission output 1
high-limit scale
S Set high limit scale value of transmission output 1. C. Converter
hOU1 5)00 · Set range : L-SC to H-SC
MODE
D. Controller
Transmission output 2
low-limit scale
S Set low limit scale value of transmission output 2.
lOU2 0)00 · Set range : L-SC to H-SC
E. Thyristor
unit
MODE

Transmission output 2 F. Pressure


high-limit scale transmitter
S Set high limit scale value of transmission output 2.
hOU2 5)00 · Set range : L-SC to H-SC G. Temp.
MODE
transmitter
Input and transmission
output extension Select extension range of analog input
S
EX.IO SP and transmission output. SP 10P 0P H. Accessories
※Displayed only when selecting user level [ USER] as HIGH.
MODE

※Displayed only for alarm output model.


AL1 mode
S
<Alarm operation>
AL-1 AT!A S
<Alarm option>
MODE Set AL1 to AT!A AT!A
AL-1
AL4 alarm MODE
AL2 mode MODE
operation
S AL-2 AT!B
AL-2 AT@A and option. AT@A
MODE
MODE
AL-3 SBa_ AT!C
MODE
AL3 mode
S
AL-3 AT!A AL-4
MODE AT)_ AT!D
MODE
Next parameter CN-6000
AL4 mode ※SV changing method of AL-2 to AL-4 is same as AL-1’s.
S
AL-4 AT@A ※ For 1EA (CN-640 -R1) or 2EA (CN-640 -R2) alarm models,
MODE
AL-3, AL-4 are not displayed.
※ No alarm [ AT)_], sensor break alarm [ SBa_] do not have alarm
option.
AL output hysteresis ※ Set alarm value [ AL1 to AL4] in monitoring mode.
S Set alarm output hysteresis.
A-HY 001 · Set range : 001 to 999
MODE ※ When alarm operation [ AL-1 to AL-4] in program mode is no alarm [ AT)_]
or sensor disconnection alarm [ SBa_], this parameter is not displayed.
Span correction
S Correct the error of display value for 100% input.
SPAN !000 ·Set range : 0.900 to 1.100
MODE ※Displayed only when selecting user level [ USER] as HIGH.
Moving average
digital filter
S Set the number of moving average digital filters.
MAvF 04 ·Set range : 01 to 16
MODE ※Displayed only when selecting user level [ USER] as HIGH.

Digital input key


S Select digital input function by front keys.
DI-K HOLD ※Press the 3, 4 keys for 3 sec. at the same time and it executes the selected function.
MODE ※ For the model without alarm output (CN-640 -C1/C2/V1/V2), AlRE is not displayed.

HOLD ZERO AlRE


Display color
S Select display part color for RUN mode and error.
COLR GRN ※Refer to「Display color」.
MODE
GRN YELO R--G G--R RED
User level
S
USER STND Select user level. STND HIGH
MODE

Lock
S
LOCK OFF Select lock function. OFF LOC1 LOC2
MODE

C-15
CN-6000 Series
Factory default

■ CN-610 (universal input)


٧٧Monitoring mode
Parameter Default Parameter Default Parameter Default Parameter Default
OUT1 ---- AL1 10)0 AL3 10)0 hPEK ----
OUT2 ---- AL2 00)0 AL4 00)0 lPEK ----

٧٧Program mode
Parameter Default Parameter Default Parameter Default Parameter Default
IN-P aMA2 lOR1 0$00※1 0)00※2 ExIO 5P SPAN !000
UNIT ?C hOR1 2)00 ※1 1)00 ※2 AL-1 AT!A AvF 01
dUNT ?/O lOR2 0$00※1 0)00※2 AL-2 AT@A MAvF 04
L-RG 0$00 hOR2 2)00※1 1)00※2 AL-3 AT!A DI-K HOLD
H-RG 2)00 BAR OUT1 AL-4 AT@A COLR GRN
dP )0 lOU1 00)0 A-HY 001 BURN ON
L-SC 00)0 hOU1 10)0 InSF LIN USER STND
H-SC 10)0 lOU2 00)0 )PSI 0*00 LOCK OFF
IN-B 000 hOU2 10)0
※ 1. Displayed only for current transmission output, alarm output model (CN-610 -C1/C2/R1/R2/R4).
※ 2. Displayed only for voltage transmission output model (CN-610 -V1/V2).

■ CN-640 (pulse input)


٧٧Monitoring mode
Parameter Default Parameter Default Parameter Default Parameter Default
OUT1 ---- AL1 00)0 AL3 10)0 hPEK ----
OUT2 ---- AL2 00)0 AL4 10)0 lPEK ----

٧٧Program mode
Parameter Default Parameter Default Parameter Default Parameter Default
IN-P 50KH lOR1 0)00 hOU2 5)00 MAvF 04
dUNT KHZ hOR1 1)00 ExIO 5P DI-K HOLD
L-RG 0)00 lOR2 0)00 AL-1 AT!A COLR GRN
H-RG 5)00 hOR2 1)00 AL-2 AT!A USER STND
dP )00 BAR OUT1 AL-3 AT!A LOCK OFF
L-SC 0)00 lOU1 0)00 AL-4 AT!A
H-SC 5)00 hOU1 5)00 A-HY 001
IN-B 000 lOU2 0)00 SPAN !000

Proper usage

■ Caution for using


• For connecting the power, use a crimp terminal (M3.5, min. • When supplying input, if HHHH or LLLLis displayed,
7.2 mm). measured input may have problem. Turn off the power and
• The connection of this unit should be separated from check the line.
the power line and high voltage line in order to prevent • Installation environment
inductive noise. ① It shall be used indoors.
• Install a power switch or a circuit breaker to supply or cut ② Pollution degree 2
off the power. ③ Altitude max. 2,000m
• Switch or circuit breaker should be installed nearby users ④ Installation category Ⅱ
for convenient control. • It may cause malfunction if above instructions are not
• Do not use this unit near the high frequency instruments followed.
(high frequency welding machine & sewing machine, large
capacity SCR controller).

C-16