Hospital De Andahuaylas

HVAC Load Analysis


for

Hospital De Andahuaylas

Prepared By:

Lunes, 17 de Mayo de 2004


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 2

General Project Data Input


General Project Information
Project file name: D:\Luigi-No Borrar\HVAC\PROYECTOS\2010\HOSPITALES\HOSP.
ANDAHUAYLAS\envio\07_14\Calculo Hvac Hosp.
Andahuaylas.CHV
Project title: Hospital De Andahuaylas
Project date: Lunes, 17 de Mayo de 2004
Weather reference city: LIMA, PERU
Client name: Hospital De Andahuaylas
Barometric pressure: 20.818 in.Hg.
Altitude: 9700 feet
Latitude: -13 Degrees
Mean daily temperature range: 0 Degrees
Starting & ending time for HVAC load calculations: 1am - 12am
Number of unique zones in this project: 30

Building Default Values


Calculations performed: Both heating and cooling loads
Lighting requirements: 2.34 Watts per square foot
Equipment requirements: 0.00 Watts per square foot
People sensible load multiplier: 250 Btuh per person
People latent load multiplier: 200 Btuh per person
Zone sensible safety factor: 10 %
Zone latent safety factor: 10 %
Zone heating safety factor: 10 %
People diversity factor: 100 %
Lighting profile number: 1
Equipment profile number: 1
People profile number: 1
Building default ceiling height: 9.00 feet
Building default wall height: 9.00 feet

Internal Operating Load Profiles (C = 100)


hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 C C C C C C C C C C C C C C C C C C C C C C C C
2 C C C C C C C C C C C C C C C C C C C C C C C C
3 C C C C C C C C C C C C C C C C C C C C C C C C
4 C C C C C C C C C C C C C C C C C C C C C C C C
5 C C C C C C C C C C C C C C C C C C C C C C C C
6 C C C C C C C C C C C C C C C C C C C C C C C C
7 C C C C C C C C C C C C C C C C C C C C C C C C
8 C C C C C C C C C C C C C C C C C C C C C C C C
9 C C C C C C C C C C C C C C C C C C C C C C C C
10 C C C C C C C C C C C C C C C C C C C C C C C C
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions
Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor
Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
October 69 65 50% 75 35.42 -13
November 73 69 50% 75 55.33 -9
December 71 67 50% 75 45.75 -11
Winter 39 72

Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 4 0.350 No Yes

Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 A 0.350 D

Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.350 1 33

Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 1.000 0.900 0.700 1 0.700
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 4

Building Summary Loads


Building peaks in November at 5pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 6,011 76,598 5.16 0 30,604 30,604 2.20
Wall 5,633 71,781 4.84 0 14,248 14,248 1.03
Glass 1,667 54,631 3.68 0 116,532 116,532 8.39
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 203,010 13.68 0 161,384 161,384 11.63
Lighting 38,136 0 0.00 0 143,138 143,138 10.31
Equipment 43,700 0 0.00 0 164,022 164,022 11.82
People 184 0 0.00 40,480 50,600 91,080 6.56
Partition 39,449 502,718 33.86 0 15,188 15,188 1.09
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 33,413 0 0.00 864,521 -51,146 813,374 58.59
Heat. Vent. 31,405 778,767 52.46 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 0 0 0.00
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 0 0 0.00
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 0 0.00 0 0 0 0.00
Return Duct 0 0 0.00 0 0 0 0.00
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 1,484,495 100.00 905,001 483,186 1,388,186 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 778,767 52.46 864,521 -51,146 813,374 58.59
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 705,728 47.54 40,480 534,332 574,812 41.41
Plenum Loads 0 0.00 0 0 0 0.00
Fan & Duct Loads 0 0.00 0 0 0 0.00
Building Totals 1,484,495 100.00 905,001 483,186 1,388,186 100.00

Check Figures
Total Building Supply Air (based on a 19° TD): 38,911 CFM
Total Building Vent. Air (85.87% of Supply): 33,413 CFM
Total Conditioned Air Space: 16,297 Sq.ft
Supply Air Per Unit Area: 2.3876 CFM/Sq.ft
Area Per Cooling Capacity: 140.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0071 Tons/Sq.ft
Heating Capacity Per Area: 91.09 Btuh/Sq.ft
Total Heating Required With Outside Air: 1,484,495 Btuh
Total Cooling Required With Outside Air: 115.68 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 5

Air Handler #1 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
4p SALA DE
288 15,162 14,815 1,320 None None
3 PARTOS 01
6 1,004 1,004 0 0 0
12am November
2,592 3.49 3.49 0 1,004 1,004

Zone Peak Totals: 288 15,162 14,815 1,320


Total Zones: 1 6 1,004 1,004 0 0 0
Unique Zones: 1 2,592 3.49 3.49 0 1,004 1,004
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 6

Air Handler #1 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.92 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 12am in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 15,162 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 24,897 Btuh 1,004 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 40,058 Btuh
Heating Supply Air: 15,162 / (.696 X 1.08 X 20) = 1,004 CFM
Winter Vent Outside Air (100.0% of supply) = 1,004 CFM
Zone space sensible gain: 14,815 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 14,815 Btuh
Cooling Supply Air: 14,815 / (.696 X 1.1 X 19) = 1,004 CFM
Summer Vent Outside Air (100.0% of supply) = 1,004 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -1,536 Btuh 1,004 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -1,536 Btuh
Total sensible gain on air handling system: 13,279 Btuh
Zone space latent gain: 1,320 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 25,969 Btuh
Total latent gain on air handling system: 27,289 Btuh
Total system sensible and latent gain: 40,567 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 1,004 CFM
Total Air Handler Vent. Air (100.00% of Supply): 1,004 CFM
Total Conditioned Air Space: 288 Sq.ft
Supply Air Per Unit Area: 3.4852 CFM/Sq.ft
Area Per Cooling Capacity: 85.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0117 Tons/Sq.ft
Heating Capacity Per Area: 139.10 Btuh/Sq.ft
Total Heating Required With Outside Air: 40,058 Btuh
Total Cooling Required With Outside Air: 3.38 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 7

Air Handler #2 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
4p SALA DE
304 16,027 15,306 1,320 None None
4 PARTOS 02
6 1,038 1,038 0 0 0
12am November
2,739 3.41 3.41 0 1,038 1,038

Zone Peak Totals: 304 16,027 15,306 1,320


Total Zones: 1 6 1,038 1,038 0 0 0
Unique Zones: 1 2,739 3.41 3.41 0 1,038 1,038
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 8

Air Handler #2 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.92 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 12am in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 16,027 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 25,740 Btuh 1,038 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 41,767 Btuh
Heating Supply Air: 16,027 / (.696 X 1.08 X 21) = 1,038 CFM
Winter Vent Outside Air (100.0% of supply) = 1,038 CFM
Zone space sensible gain: 15,306 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 15,306 Btuh
Cooling Supply Air: 15,306 / (.696 X 1.1 X 19) = 1,038 CFM
Summer Vent Outside Air (100.0% of supply) = 1,038 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -1,590 Btuh 1,038 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -1,590 Btuh
Total sensible gain on air handling system: 13,717 Btuh
Zone space latent gain: 1,320 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 26,868 Btuh
Total latent gain on air handling system: 28,188 Btuh
Total system sensible and latent gain: 41,905 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 1,038 CFM
Total Air Handler Vent. Air (100.00% of Supply): 1,038 CFM
Total Conditioned Air Space: 304 Sq.ft
Supply Air Per Unit Area: 3.4127 CFM/Sq.ft
Area Per Cooling Capacity: 87.1 Sq.ft/Ton
Cooling Capacity Per Area: 0.0115 Tons/Sq.ft
Heating Capacity Per Area: 137.26 Btuh/Sq.ft
Total Heating Required With Outside Air: 41,767 Btuh
Total Cooling Required With Outside Air: 3.49 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 9

Air Handler #3 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
5p SALA DE
356 17,768 16,987 1,320 None None
5 OPERACIONES 1
6 1,158 1,158 0 0 0
6pm November
3,204 3.25 3.25 0 1,158 1,158

Zone Peak Totals: 356 17,768 16,987 1,320


Total Zones: 1 6 1,158 1,158 0 0 0
Unique Zones: 1 3,204 3.25 3.25 0 1,158 1,158
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 10

Air Handler #3 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.93 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 6pm in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 17,768 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 28,716 Btuh 1,158 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 46,484 Btuh
Heating Supply Air: 17,768 / (.696 X 1.08 X 20) = 1,158 CFM
Winter Vent Outside Air (100.0% of supply) = 1,158 CFM
Zone space sensible gain: 16,987 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 16,987 Btuh
Cooling Supply Air: 16,987 / (.696 X 1.1 X 19) = 1,158 CFM
Summer Vent Outside Air (100.0% of supply) = 1,158 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -1,772 Btuh 1,158 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -1,772 Btuh
Total sensible gain on air handling system: 15,215 Btuh
Zone space latent gain: 1,320 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 29,952 Btuh
Total latent gain on air handling system: 31,272 Btuh
Total system sensible and latent gain: 46,487 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 1,158 CFM
Total Air Handler Vent. Air (100.00% of Supply): 1,158 CFM
Total Conditioned Air Space: 356 Sq.ft
Supply Air Per Unit Area: 3.2514 CFM/Sq.ft
Area Per Cooling Capacity: 91.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0109 Tons/Sq.ft
Heating Capacity Per Area: 130.56 Btuh/Sq.ft
Total Heating Required With Outside Air: 46,484 Btuh
Total Cooling Required With Outside Air: 3.87 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 11

Air Handler #4 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
5p SALA DE
356 17,768 16,987 1,320 None None
6 OPERACIONES 2
6 1,158 1,158 0 0 0
6pm November
3,204 3.25 3.25 0 1,158 1,158

Zone Peak Totals: 356 17,768 16,987 1,320


Total Zones: 1 6 1,158 1,158 0 0 0
Unique Zones: 1 3,204 3.25 3.25 0 1,158 1,158
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 12

Air Handler #4 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.93 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 6pm in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 17,768 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 28,716 Btuh 1,158 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 46,484 Btuh
Heating Supply Air: 17,768 / (.696 X 1.08 X 20) = 1,158 CFM
Winter Vent Outside Air (100.0% of supply) = 1,158 CFM
Zone space sensible gain: 16,987 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 16,987 Btuh
Cooling Supply Air: 16,987 / (.696 X 1.1 X 19) = 1,158 CFM
Summer Vent Outside Air (100.0% of supply) = 1,158 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -1,772 Btuh 1,158 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -1,772 Btuh
Total sensible gain on air handling system: 15,215 Btuh
Zone space latent gain: 1,320 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 29,952 Btuh
Total latent gain on air handling system: 31,272 Btuh
Total system sensible and latent gain: 46,487 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 1,158 CFM
Total Air Handler Vent. Air (100.00% of Supply): 1,158 CFM
Total Conditioned Air Space: 356 Sq.ft
Supply Air Per Unit Area: 3.2514 CFM/Sq.ft
Area Per Cooling Capacity: 91.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0109 Tons/Sq.ft
Heating Capacity Per Area: 130.56 Btuh/Sq.ft
Total Heating Required With Outside Air: 46,484 Btuh
Total Cooling Required With Outside Air: 3.87 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 13

Air Handler #5 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
5p SALA DE
356 17,768 16,987 1,320 None None
7 OPERACIONES 3
6 1,158 1,158 0 0 0
6pm November
3,204 3.25 3.25 0 1,158 1,158

Zone Peak Totals: 356 17,768 16,987 1,320


Total Zones: 1 6 1,158 1,158 0 0 0
Unique Zones: 1 3,204 3.25 3.25 0 1,158 1,158
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 14

Air Handler #5 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.93 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 6pm in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 17,768 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 28,716 Btuh 1,158 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 46,484 Btuh
Heating Supply Air: 17,768 / (.696 X 1.08 X 20) = 1,158 CFM
Winter Vent Outside Air (100.0% of supply) = 1,158 CFM
Zone space sensible gain: 16,987 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 16,987 Btuh
Cooling Supply Air: 16,987 / (.696 X 1.1 X 19) = 1,158 CFM
Summer Vent Outside Air (100.0% of supply) = 1,158 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -1,772 Btuh 1,158 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -1,772 Btuh
Total sensible gain on air handling system: 15,215 Btuh
Zone space latent gain: 1,320 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 29,952 Btuh
Total latent gain on air handling system: 31,272 Btuh
Total system sensible and latent gain: 46,487 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 1,158 CFM
Total Air Handler Vent. Air (100.00% of Supply): 1,158 CFM
Total Conditioned Air Space: 356 Sq.ft
Supply Air Per Unit Area: 3.2514 CFM/Sq.ft
Area Per Cooling Capacity: 91.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0109 Tons/Sq.ft
Heating Capacity Per Area: 130.56 Btuh/Sq.ft
Total Heating Required With Outside Air: 46,484 Btuh
Total Cooling Required With Outside Air: 3.87 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 15

Air Handler #6 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
5p SALA DE
335 17,011 16,671 1,320 None None
8 OPERACIONES 4
6 1,135 1,135 0 0 0
6pm November
3,018 3.38 3.39 0 1,135 1,135

Zone Peak Totals: 335 17,011 16,671 1,320


Total Zones: 1 6 1,135 1,135 0 0 0
Unique Zones: 1 3,018 3.38 3.39 0 1,135 1,135
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 16

Air Handler #6 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.93 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 6pm in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 17,011 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 28,145 Btuh 1,135 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 45,156 Btuh
Heating Supply Air: 17,011 / (.696 X 1.08 X 20) = 1,135 CFM
Winter Vent Outside Air (100.0% of supply) = 1,135 CFM
Zone space sensible gain: 16,671 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 16,671 Btuh
Cooling Supply Air: 16,671 / (.696 X 1.1 X 19) = 1,135 CFM
Summer Vent Outside Air (100.0% of supply) = 1,135 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -1,738 Btuh 1,135 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -1,738 Btuh
Total sensible gain on air handling system: 14,933 Btuh
Zone space latent gain: 1,320 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 29,373 Btuh
Total latent gain on air handling system: 30,693 Btuh
Total system sensible and latent gain: 45,626 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 1,135 CFM
Total Air Handler Vent. Air (100.00% of Supply): 1,135 CFM
Total Conditioned Air Space: 335 Sq.ft
Supply Air Per Unit Area: 3.3854 CFM/Sq.ft
Area Per Cooling Capacity: 88.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0113 Tons/Sq.ft
Heating Capacity Per Area: 134.66 Btuh/Sq.ft
Total Heating Required With Outside Air: 45,156 Btuh
Total Cooling Required With Outside Air: 3.80 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 17

Air Handler #7 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
9 5p UCIN (12 CAM.) 2,086 77,684 55,779 3,300 None None
5pm November 15 3,837 3,837 0 0 0
18,776 1.84 1.84 0 3,837 3,837
Zone Peak Totals: 2,086 77,684 55,779 3,300
Total Zones: 1 15 3,837 3,837 0 0 0
Unique Zones: 1 18,776 1.84 1.84 0 3,837 3,837
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 18

Air Handler #7 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.94 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 77,684 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 95,148 Btuh 3,837 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 172,833 Btuh
Heating Supply Air: 77,684 / (.696 X 1.08 X 27) = 3,837 CFM
Winter Vent Outside Air (100.0% of supply) = 3,837 CFM
Zone space sensible gain: 55,779 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 55,779 Btuh
Cooling Supply Air: 55,779 / (.696 X 1.1 X 19) = 3,837 CFM
Summer Vent Outside Air (100.0% of supply) = 3,837 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -5,873 Btuh 3,837 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -5,873 Btuh
Total sensible gain on air handling system: 49,907 Btuh
Zone space latent gain: 3,300 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 99,266 Btuh
Total latent gain on air handling system: 102,566 Btuh
Total system sensible and latent gain: 152,473 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 3,837 CFM
Total Air Handler Vent. Air (100.00% of Supply): 3,837 CFM
Total Conditioned Air Space: 2,086 Sq.ft
Supply Air Per Unit Area: 1.8390 CFM/Sq.ft
Area Per Cooling Capacity: 164.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0061 Tons/Sq.ft
Heating Capacity Per Area: 82.84 Btuh/Sq.ft
Total Heating Required With Outside Air: 172,833 Btuh
Total Cooling Required With Outside Air: 12.71 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 19

Air Handler #8 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
10 5p_RECUPERACION 979 42,089 41,160 2,640 None None
5pm November 12 2,824 2,824 0 0 0
8,815 2.88 2.88 0 2,824 2,824
Zone Peak Totals: 979 42,089 41,160 2,640
Total Zones: 1 12 2,824 2,824 0 0 0
Unique Zones: 1 8,815 2.88 2.88 0 2,824 2,824
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 20

Air Handler #8 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.94 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 42,089 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 70,028 Btuh 2,824 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 112,117 Btuh
Heating Supply Air: 42,089 / (.696 X 1.08 X 20) = 2,824 CFM
Winter Vent Outside Air (100.0% of supply) = 2,824 CFM
Zone space sensible gain: 41,160 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 41,160 Btuh
Cooling Supply Air: 41,160 / (.696 X 1.1 X 19) = 2,824 CFM
Summer Vent Outside Air (100.0% of supply) = 2,824 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -4,323 Btuh 2,824 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -4,323 Btuh
Total sensible gain on air handling system: 36,837 Btuh
Zone space latent gain: 2,640 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 73,069 Btuh
Total latent gain on air handling system: 75,709 Btuh
Total system sensible and latent gain: 112,546 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 2,824 CFM
Total Air Handler Vent. Air (100.00% of Supply): 2,824 CFM
Total Conditioned Air Space: 979 Sq.ft
Supply Air Per Unit Area: 2.8835 CFM/Sq.ft
Area Per Cooling Capacity: 104.4 Sq.ft/Ton
Cooling Capacity Per Area: 0.0096 Tons/Sq.ft
Heating Capacity Per Area: 114.48 Btuh/Sq.ft
Total Heating Required With Outside Air: 112,117 Btuh
Total Cooling Required With Outside Air: 9.38 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 21

Air Handler #9 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
4p_SALA
PUERPERIO 617 29,322 21,908 1,540 None None
2 (4CAMAS) 7 1,499 1,499 0 0 0
9am October 5,550 2.43 2.43 0 1,499 1,499

Zone Peak Totals: 617 29,322 21,908 1,540


Total Zones: 1 7 1,499 1,499 0 0 0
Unique Zones: 1 5,550 2.43 2.43 0 1,499 1,499
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 22

Air Handler #9 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.93 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 10am in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in October at 9am is different
from the total system peak time, hence the air system CFM was computed using a zone sensible load of 21,908.
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 29,322 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 37,172 Btuh 1,499 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 66,494 Btuh
Heating Supply Air: 29,322 / (.696 X 1.08 X 26) = 1,499 CFM
Winter Vent Outside Air (100.0% of supply) = 1,499 CFM
Zone space sensible gain: 20,291 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 20,291 Btuh
Cooling Supply Air: 21,908 / (.696 X 1.1 X 19) = 1,499 CFM
Summer Vent Outside Air (100.0% of supply) = 1,499 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -2,294 Btuh 1,499 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -2,294 Btuh
Total sensible gain on air handling system: 17,997 Btuh
Zone space latent gain: 1,540 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 38,775 Btuh
Total latent gain on air handling system: 40,315 Btuh
Total system sensible and latent gain: 58,312 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 1,499 CFM
Total Air Handler Vent. Air (100.00% of Supply): 1,499 CFM
Total Conditioned Air Space: 617 Sq.ft
Supply Air Per Unit Area: 2.4303 CFM/Sq.ft
Area Per Cooling Capacity: 126.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0079 Tons/Sq.ft
Heating Capacity Per Area: 107.83 Btuh/Sq.ft
Total Heating Required With Outside Air: 66,494 Btuh
Total Cooling Required With Outside Air: 4.86 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 23

Air Handler #10 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
4p-SALA
1,261 55,254 38,394 2,860 None None
1 DILATACION
13 2,621 2,621 0 0 0
9am October
11,346 2.08 2.08 0 2,621 2,621

Zone Peak Totals: 1,261 55,254 38,394 2,860


Total Zones: 1 13 2,621 2,621 0 0 0
Unique Zones: 1 11,346 2.08 2.08 0 2,621 2,621
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 24

Air Handler #10 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.93 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 10am in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in October at 9am is different
from the total system peak time, hence the air system CFM was computed using a zone sensible load of 38,394.
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 55,254 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 64,994 Btuh 2,621 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 120,249 Btuh
Heating Supply Air: 55,254 / (.696 X 1.08 X 28) = 2,621 CFM
Winter Vent Outside Air (100.0% of supply) = 2,621 CFM
Zone space sensible gain: 35,744 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 35,744 Btuh
Cooling Supply Air: 38,394 / (.696 X 1.1 X 19) = 2,621 CFM
Summer Vent Outside Air (100.0% of supply) = 2,621 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -4,012 Btuh 2,621 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -4,012 Btuh
Total sensible gain on air handling system: 31,732 Btuh
Zone space latent gain: 2,860 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 67,808 Btuh
Total latent gain on air handling system: 70,668 Btuh
Total system sensible and latent gain: 102,400 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 2,621 CFM
Total Air Handler Vent. Air (100.00% of Supply): 2,621 CFM
Total Conditioned Air Space: 1,261 Sq.ft
Supply Air Per Unit Area: 2.0789 CFM/Sq.ft
Area Per Cooling Capacity: 147.7 Sq.ft/Ton
Cooling Capacity Per Area: 0.0068 Tons/Sq.ft
Heating Capacity Per Area: 95.39 Btuh/Sq.ft
Total Heating Required With Outside Air: 120,249 Btuh
Total Cooling Required With Outside Air: 8.53 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 25

Air Handler #11 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
11 4p_AISLADO 109 6,847 5,326 440 None None
3pm October 2 336 362 0 0 0
981 3.08 3.32 0 336 362

4p_UCI NEONATAL
939 43,083 30,779 2,640 None None
12 (7 CAMAS)
12 2,115 2,089 0 0 0
3pm October
8,447 2.25 2.23 0 2,115 2,089

Zone Peak Totals: 1,048 49,930 36,106 3,080


Total Zones: 2 14 2,451 2,451 0 0 0
Unique Zones: 2 9,428 2.34 2.34 0 2,451 2,451
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 26

Air Handler #11 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.92 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 3pm in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in October at 3pm is different
from the total system peak time, hence the air system CFM was computed using a zone sensible load of 36,106.
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 49,930 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 60,779 Btuh 2,451 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 110,709 Btuh
Heating Supply Air: 49,930 / (.696 X 1.08 X 27) = 2,451 CFM
Winter Vent Outside Air (100.0% of supply) = 2,451 CFM
Zone space sensible gain: 34,087 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 34,087 Btuh
Cooling Supply Air: 36,106 / (.696 X 1.1 X 19) = 2,451 CFM
Summer Vent Outside Air (100.0% of supply) = 2,451 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -3,751 Btuh 2,451 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -3,751 Btuh
Total sensible gain on air handling system: 30,336 Btuh
Zone space latent gain: 3,080 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 63,408 Btuh
Total latent gain on air handling system: 66,488 Btuh
Total system sensible and latent gain: 96,824 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 2,451 CFM
Total Air Handler Vent. Air (100.00% of Supply): 2,451 CFM
Total Conditioned Air Space: 1,048 Sq.ft
Supply Air Per Unit Area: 2.3394 CFM/Sq.ft
Area Per Cooling Capacity: 129.8 Sq.ft/Ton
Cooling Capacity Per Area: 0.0077 Tons/Sq.ft
Heating Capacity Per Area: 105.68 Btuh/Sq.ft
Total Heating Required With Outside Air: 110,709 Btuh
Total Cooling Required With Outside Air: 8.07 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 27

Air Handler #13 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
4p_PREPARACION
545 24,007 27,696 1,320 None 6/Hr
13 Y EMPAQUE
6 1,915 1,915 0 0 491
5pm December
4,908 3.51 3.51 0 0 491

Zone Peak Totals: 545 24,007 27,696 1,320


Total Zones: 1 6 1,915 1,915 0 0 491
Unique Zones: 1 4,908 3.51 3.51 0 0 491
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 28

Air Handler #13 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.95 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in December at 5pm is
different from the total system peak time, hence the air system CFM was computed using a zone sensible load of 27,696.
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 24,007 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 24,007 Btuh
Heating Supply Air: 24,007 / (.696 X 1.08 X 17) = 1,915 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 27,452 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 27,452 Btuh
Cooling Supply Air: 27,696 / (.696 X 1.1 X 19) = 1,915 CFM
Summer Vent Outside Air (25.6% of supply) = 491 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -751 Btuh 491 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -751 Btuh
Total sensible gain on air handling system: 26,701 Btuh
Zone space latent gain: 1,320 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 12,698 Btuh
Total latent gain on air handling system: 14,018 Btuh
Total system sensible and latent gain: 40,719 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 1,915 CFM
Total Air Handler Vent. Air (25.63% of Supply): 491 CFM
Total Conditioned Air Space: 545 Sq.ft
Supply Air Per Unit Area: 3.5121 CFM/Sq.ft
Area Per Cooling Capacity: 160.7 Sq.ft/Ton
Cooling Capacity Per Area: 0.0062 Tons/Sq.ft
Heating Capacity Per Area: 44.02 Btuh/Sq.ft
Total Heating Required With Outside Air: 24,007 Btuh
Total Cooling Required With Outside Air: 3.39 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 29

Air Handler #14 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
4p_RECEPCION DE
EMPAQUES Y 479 23,421 24,565 1,320 None None
14 CLASIFICACION 6 1,694 1,694 0 0 0
5pm December 4,312 3.54 3.53 0 1,694 1,694

Zone Peak Totals: 479 23,421 24,565 1,320


Total Zones: 1 6 1,694 1,694 0 0 0
Unique Zones: 1 4,312 3.54 3.53 0 1,694 1,694
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 30

Air Handler #14 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.95 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in December at 5pm is
different from the total system peak time, hence the air system CFM was computed using a zone sensible load of 24,565.
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 23,421 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 42,007 Btuh 1,694 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 65,428 Btuh
Heating Supply Air: 23,421 / (.696 X 1.08 X 18) = 1,694 CFM
Winter Vent Outside Air (100.0% of supply) = 1,694 CFM
Zone space sensible gain: 24,379 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 24,379 Btuh
Cooling Supply Air: 24,565 / (.696 X 1.1 X 19) = 1,694 CFM
Summer Vent Outside Air (100.0% of supply) = 1,694 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -2,593 Btuh 1,694 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -2,593 Btuh
Total sensible gain on air handling system: 21,786 Btuh
Zone space latent gain: 1,320 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 43,821 Btuh
Total latent gain on air handling system: 45,141 Btuh
Total system sensible and latent gain: 66,928 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 1,694 CFM
Total Air Handler Vent. Air (100.00% of Supply): 1,694 CFM
Total Conditioned Air Space: 479 Sq.ft
Supply Air Per Unit Area: 3.5350 CFM/Sq.ft
Area Per Cooling Capacity: 85.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0116 Tons/Sq.ft
Heating Capacity Per Area: 136.56 Btuh/Sq.ft
Total Heating Required With Outside Air: 65,428 Btuh
Total Cooling Required With Outside Air: 5.58 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 31

Air Handler #15 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
15 5p_UCI (6 CAMAS) 1,360 54,479 33,548 1,980 None 100%
8am November 9 2,341 2,264 0 0 0
12,242 1.72 1.66 0 2,341 2,264

16 5p_AISLADO 181 8,850 6,763 440 None 100%


10am October 2 380 457 0 0 0
1,633 2.10 2.52 0 380 457
Zone Peak Totals: 1,542 63,328 40,311 2,420
Total Zones: 2 11 2,721 2,721 0 0 0
Unique Zones: 2 13,875 1.77 1.77 0 2,721 2,721
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 32

Air Handler #15 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.94 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 8am in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 63,328 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 67,474 Btuh 2,721 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 130,803 Btuh
Heating Supply Air: 63,328 / (.696 X 1.08 X 31) = 2,721 CFM
Winter Vent Outside Air (100.0% of supply) = 2,721 CFM
Zone space sensible gain: 39,599 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 39,599 Btuh
Cooling Supply Air: 39,599 / (.696 X 1.1 X 19) = 2,721 CFM
Summer Vent Outside Air (100.0% of supply) = 2,721 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -4,165 Btuh 2,721 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -4,165 Btuh
Total sensible gain on air handling system: 35,434 Btuh
Zone space latent gain: 2,420 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 70,402 Btuh
Total latent gain on air handling system: 72,822 Btuh
Total system sensible and latent gain: 108,256 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 2,721 CFM
Total Air Handler Vent. Air (100.00% of Supply): 2,721 CFM
Total Conditioned Air Space: 1,542 Sq.ft
Supply Air Per Unit Area: 1.7650 CFM/Sq.ft
Area Per Cooling Capacity: 170.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0059 Tons/Sq.ft
Heating Capacity Per Area: 84.85 Btuh/Sq.ft
Total Heating Required With Outside Air: 130,803 Btuh
Total Cooling Required With Outside Air: 9.02 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 33

Air Handler #17 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
17 2p_LAB. CITOPAT. 174 11,409 10,185 660 None 100%
7am December 3 620 584 0 0 0
1,563 3.57 3.36 0 620 584

2P_LAB. PATOL.
163 10,926 9,763 660 None 100%
18 MOLEC.
3 594 560 0 0 0
7am December
1,468 3.64 3.43 0 594 560

2p_LABORAT.
264 14,062 11,798 880 None 100%
19 HISTOPAT.
4 764 676 0 0 0
4pm October
2,377 2.89 2.56 0 764 676

20 2p_MICROSC. 141 6,993 8,873 660 None 100%


3pm October 3 380 509 0 0 0
1,267 2.70 3.61 0 380 509

2p_TRABAJO
154 9,017 9,042 660 None 100%
21 MICROSC
3 490 518 0 0 0
3pm October
1,382 3.19 3.38 0 490 518

Zone Peak Totals: 895 52,405 49,662 3,520


Total Zones: 5 16 2,847 2,847 0 0 0
Unique Zones: 5 8,058 3.18 3.18 0 2,847 2,847
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 34

Air Handler #17 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.92 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 3pm in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in October at 3pm is different
from the total system peak time, hence the air system CFM was computed using a zone sensible load of 41,922.
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 52,405 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 70,599 Btuh 2,847 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 123,004 Btuh
Heating Supply Air: 52,405 / (.696 X 1.08 X 24) = 2,847 CFM
Winter Vent Outside Air (100.0% of supply) = 2,847 CFM
Zone space sensible gain: 41,458 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 41,458 Btuh
Cooling Supply Air: 41,922 / (.696 X 1.1 X 19) = 2,847 CFM
Summer Vent Outside Air (100.0% of supply) = 2,847 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -4,359 Btuh 2,847 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -4,359 Btuh
Total sensible gain on air handling system: 37,099 Btuh
Zone space latent gain: 3,520 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 73,673 Btuh
Total latent gain on air handling system: 77,193 Btuh
Total system sensible and latent gain: 114,292 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 2,847 CFM
Total Air Handler Vent. Air (100.00% of Supply): 2,847 CFM
Total Conditioned Air Space: 895 Sq.ft
Supply Air Per Unit Area: 3.1804 CFM/Sq.ft
Area Per Cooling Capacity: 94.0 Sq.ft/Ton
Cooling Capacity Per Area: 0.0106 Tons/Sq.ft
Heating Capacity Per Area: 137.39 Btuh/Sq.ft
Total Heating Required With Outside Air: 123,004 Btuh
Total Cooling Required With Outside Air: 9.52 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 35

Air Handler #20 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
2p_LABORATORIO
339 15,705 11,685 880 None None
22 HEMATOLOGÍA
4 810 796 0 0 0
3pm October
3,055 2.39 2.34 0 810 796

2p_LABORATORIO
311 11,883 9,389 880 None None
23 INMUNOLOGÍA
4 613 639 0 0 0
3pm October
2,795 1.97 2.06 0 613 639

24 2p_LAB. URIANÁL. 240 9,530 9,161 660 None None


3pm October 3 491 624 0 0 0
2,161 2.05 2.60 0 491 624

2p_LABORATORIO
503 21,826 14,386 1,100 None None
25 BIOQUÍMICA
5 1,125 980 0 0 0
3pm October
4,527 2.24 1.95 0 1,125 980

Zone Peak Totals: 1,393 58,943 44,620 3,520


Total Zones: 4 16 3,039 3,039 0 0 0
Unique Zones: 4 12,538 2.18 2.18 0 3,039 3,039
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 36

Air Handler #20 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.93 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 3pm in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in October at 3pm is different
from the total system peak time, hence the air system CFM was computed using a zone sensible load of 44,620.
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 58,943 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 75,360 Btuh 3,039 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 134,303 Btuh
Heating Supply Air: 58,943 / (.696 X 1.08 X 26) = 3,039 CFM
Winter Vent Outside Air (100.0% of supply) = 3,039 CFM
Zone space sensible gain: 42,188 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 42,188 Btuh
Cooling Supply Air: 44,620 / (.696 X 1.1 X 19) = 3,039 CFM
Summer Vent Outside Air (100.0% of supply) = 3,039 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -4,652 Btuh 3,039 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -4,652 Btuh
Total sensible gain on air handling system: 37,536 Btuh
Zone space latent gain: 3,520 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 78,631 Btuh
Total latent gain on air handling system: 82,151 Btuh
Total system sensible and latent gain: 119,687 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 3,039 CFM
Total Air Handler Vent. Air (100.00% of Supply): 3,039 CFM
Total Conditioned Air Space: 1,393 Sq.ft
Supply Air Per Unit Area: 2.1815 CFM/Sq.ft
Area Per Cooling Capacity: 139.7 Sq.ft/Ton
Cooling Capacity Per Area: 0.0072 Tons/Sq.ft
Heating Capacity Per Area: 96.41 Btuh/Sq.ft
Total Heating Required With Outside Air: 134,303 Btuh
Total Cooling Required With Outside Air: 9.97 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 37

Air Handler #21 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
2p_LABORATORIO
MICROBIOLOGÍA Y 513 24,760 17,160 1,100 None 100%
26 MEDIO DE 5 1,096 1,071 0 0 0
7am November 4,615 2.14 2.09 0 1,096 1,071

27 2p_ESCL. 51 2,835 715 0 None 100%


12am November 0 125 150 0 0 0
458 2.46 2.95 0 125 150
Zone Peak Totals: 564 27,594 17,875 1,100
Total Zones: 2 5 1,221 1,221 0 0 0
Unique Zones: 2 5,073 2.17 2.17 0 1,221 1,221
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 38

Air Handler #21 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.94 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 7am in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 27,594 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 30,278 Btuh 1,221 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 57,872 Btuh
Heating Supply Air: 27,594 / (.696 X 1.08 X 30) = 1,221 CFM
Winter Vent Outside Air (100.0% of supply) = 1,221 CFM
Zone space sensible gain: 17,782 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 17,782 Btuh
Cooling Supply Air: 17,782 / (.696 X 1.1 X 19) = 1,221 CFM
Summer Vent Outside Air (100.0% of supply) = 1,221 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -1,870 Btuh 1,221 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -1,870 Btuh
Total sensible gain on air handling system: 15,912 Btuh
Zone space latent gain: 1,100 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 31,603 Btuh
Total latent gain on air handling system: 32,703 Btuh
Total system sensible and latent gain: 48,615 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 1,221 CFM
Total Air Handler Vent. Air (100.00% of Supply): 1,221 CFM
Total Conditioned Air Space: 564 Sq.ft
Supply Air Per Unit Area: 2.1670 CFM/Sq.ft
Area Per Cooling Capacity: 139.1 Sq.ft/Ton
Cooling Capacity Per Area: 0.0072 Tons/Sq.ft
Heating Capacity Per Area: 102.67 Btuh/Sq.ft
Total Heating Required With Outside Air: 57,872 Btuh
Total Cooling Required With Outside Air: 4.05 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 39

Air Handler #22 Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1p_OBSERV.
1,175 40,273 33,237 2,200 None 3.5/Hr
28 HOMBRES
10 2,247 2,271 0 0 617
5pm December
10,576 1.91 1.93 0 0 617

29 1p_OBSERV. NIÑOS 861 27,158 22,983 1,760 None 3.5/Hr


5pm December 8 1,515 1,570 0 0 452
7,753 1.76 1.82 0 0 426

1p_OBSERV.
857 32,815 25,635 1,980 None 3.5/Hr
30 MUJERES
9 1,831 1,752 0 0 450
5pm December
7,710 2.14 2.04 0 0 476

Zone Peak Totals: 2,893 100,245 81,855 5,940


Total Zones: 3 27 5,593 5,593 0 0 1,519
Unique Zones: 3 26,038 1.93 1.93 0 0 1,519
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Hospital De Andahuaylas
Hell Page 40

Air Handler #22 Total Load Summary


Air Handler Description: Constant Volume - Proportion
Sensible Heat Ratio: 0.93 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in November.
Outdoor Conditions: 73° DB, 69° WB, 148.85 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in December at 5pm is
different from the total system peak time, hence the air system CFM was computed using a zone sensible load of 81,855.
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 100,245 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 100,245 Btuh
Heating Supply Air: 100,245 / (.696 X 1.08 X 24) = 5,593 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 81,235 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 81,235 Btuh
Cooling Supply Air: 81,855 / (.696 X 1.1 X 19) = 5,593 CFM
Summer Vent Outside Air (27.2% of supply) = 1,519 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -2,325 Btuh 1,519 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: -2,325 Btuh
Total sensible gain on air handling system: 78,910 Btuh
Zone space latent gain: 5,940 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 39,300 Btuh
Total latent gain on air handling system: 45,240 Btuh
Total system sensible and latent gain: 124,150 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 5,593 CFM
Total Air Handler Vent. Air (27.16% of Supply): 1,519 CFM
Total Conditioned Air Space: 2,893 Sq.ft
Supply Air Per Unit Area: 1.9331 CFM/Sq.ft
Area Per Cooling Capacity: 279.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0036 Tons/Sq.ft
Heating Capacity Per Area: 34.65 Btuh/Sq.ft
Total Heating Required With Outside Air: 100,245 Btuh
Total Cooling Required With Outside Air: 10.35 Tons