408 6 Current return circuit and earthing
for voltage impulses,
‘nominal voltage KV 15 25
overvoltage category mi) wim) w
withstand surge voltage kV | 75 | 95 | 145 | 170
impulse earthing resistance | 19 | 24 | 36 | 43
operation of a three-phase star point conductor without special protection measures only over
a distance of less than 1,5km along the AC railway system [6.55],
If components of crossing road lie within the overhead contact line and pantograph
zone, then EN 50 122-1 and the DB Directive 954.0107 specify additional earthing provisions
to ensure personal safety. Figure 6.45 illustrates recommended treatments:
= galvanized steel strip on both bridge walls, if these are located in the overhead contact
line zone
= galvanized steel strip ot angle section-profile above the overhead line at the start and
end of the bridge if the bridge ceiling is within the pantograph zone
— protective fence or projecting device to avoid touching components possibly live on the
bridge sides.
The metallic parts are connected at two points to the return circuit. It is recommended that
the reinforcement of new bridges is also interconnected electrically and then connected to the
return circuit for lightning protection, The bridge foundations can also be employed as earth
electrodes in this case.
6.6.4.9 Lightning protection
Railway systems require high reliability and availability. Consequently, it is necessary to de-
termine the measures to be applied to protect them against damage from lightning strokes,
according to the risk management regime in IEC . Lightning strokes into the over-
head contact line system cause a flash-over of the neighbouring insulators and the current is,
conducted via the poles and the earthing installations into the carth. It is possible for insula-
tors to be damaged, however, a fracture is unlikely. The earth connections should be kept a
short as possible, to keep the impulse resistance and inductance in the arrester path to a mini-
mum. Suitable overvoltage protection circuits, in addition to the external lightning protection,
are adopted to protect sensitive equipment assets,
Evaluations of the frequency of lightning current in accordance with IEC 62.305-2 revealed
that 95% of all lightning currents are lower than 40kA and 99% lower than 60kA. Back
flashovers should not be expected if the following condition is fulfilled:
Rass