EARTH MAT DESIGN CALCULATION

ANNEXURE - A

40mm diameter and 3 meter long of Mild Steel Rod Electrode.

S.No. Equipment/ Location Qty/equip. Equip. Qty. Total


6 Grid Corner 1 6 8
7 220kV LA 1 16 16
8 220kV Line Side Shield Wire 1 5 5
9 33kV LA 1 18 18
10 33kV Line Side Shield Wire 1 8 8
11 LM 2 4 8
12 Control Room Building Equip. Earthing 6 1 4
13 220kV GIS Building Equip. Earthing 6 1 6
14 33kV GIS Building Equip. Earthing 4 1 2
12 Control Room Building DSLP 6 1 6
13 220kV GIS Building DSLP 6 1 6
14 33kV GIS Building DSLP 4 1 4
15 Grid Periphery @ Every 50 Mtr. 10 1 10

Total 101

40mm diameter and 3 meter long of Pipe Earth Electrode (Treated Pit)

S.No. Equipment/ Location Qty/equip. Equip. Qty. Total


1 230/33kV Trafo Bank HV Neutral 2 1 2
2 230/33kV Trafo Bank LV Neutral 2 2 4
3 250kVA Aux. Transformer 2 2 4
4 DG Set 2 1 2
Total 10