Professional Documents
Culture Documents
3
System
Background
• Pakscan was originally introduced in 1986 specifically for
actuator control. Currently is undergoing its fourth
evolutionary phase.
• Used by hundreds of systems controlling thousands of
actuators world wide.
• Secure, mature communications.
• Proven interoperability with all major host system
suppliers.
• Fully pre-engineered system.
System
•
Features
Long loop distance - 20 km Loop length.
• No repeaters – up to 240 FCUs can be connected.
• Total redundancy throughout – loop, master station
modules (hot standby) and host communications
• Fast command response < 0.5 second per FCU.
• Acyclic data capabilities - FCU can be parameterised via
the loop.
• Efficient loop communications protocol - “One time” write
commands, i.e. multiple commands to the same device
are only sent once. This reduces bus traffic and
increases system response.
Fault
• Tolerance
Loop Fault Tolerance – Loopback Feature:
–Unique Loopback feature isolates faults in the event of
a cable failure, i.e. open-circuit, short-circuit or
earthing fault
Normal operation
20 mA
Loop
20 mA
Loop
Host
• Interfacing
Modbus TCP/RTU (Ethernet / Serial comms)
– Four in-built, field proven database formats:-
• Generic Modbus.
• Yokogawa Format.
• Honeywell EPLCG.
• Honeywell SI.
• Up to 10 hosts can be connected concurrently via
Ethernet
Host
Interfacing
– Four host comms ports available - 2 dedicated serial
ports and 2 dedicated Ethernet ports.
– Additional Ethernet service port (for commissioning).
– Serial comms baud rates 2.4 kB to 115 kB.
– Ethernet comms baud rates 10 / 100 MB
– Switch selectable RS232 / RS485 interface.
– Auto-sensing on Ethernet ports, i.e. no need for cross-
over cable or intermediate switch/hub
HMI Display
• P3 has a graphical colour
display with icons
representing the menus and
settings.
• Navigation is via a
simple set of push
buttons.
Web access
• Built in Web browser provides access to all
master station data:
Mounting