Project
LACOSTE FANCOIL
Date
FC-01 3
Unit Report 4
Certified Drawing 5
Performance Summary 7
Guide Specifications 9
FC-01
FC-01
Unit Report
Warranty Information
First Year - Parts Only (Standard)
Ordering Information
Certified Drawing
JOBNAME
JOBNUMBER
NOTES:
1. Caution: Disconnect power before servicing.
2. See nameplate for correct voltage, use 75°C min. copper conductors only. DATE
Unit terminals are not designed to accept any other wiring. 02/10/2012
3. Blower motor(s) thermally protected.
4. Provide disconnect means and over current protection as required. DRAWINGNUMBER REVISION SHEET
5. All contractor wiring must conform to electrical codes, national and local.
42B-204-1 1 OF 1
Performance Summary
Cooling Data
Coil Type: Cold Fluid Cooling
Coil Rows: 4 Rows
Fluid Type: Fresh Water
Total Capacity: 66,682 BTU/hr
Sensible Capacity: 48,424 BTU/hr
Entering Air Dry Bulb Temperature: 80.0 F
Entering Air Wet Bulb Temperature: 67.0 F
Leaving Air Dry Bulb Temperature: 58.0 F
Leaving Air Wet Bulb Temperature: 56.4 F
Fluid Flow Rate: 14.0 gpm
Fluid Pressure Drop: 6.27 ft wg
Fluid Entering Temperature: 44.0 F
Fluid Leaving Temperature: 53.4 F
Electrical Data
Motor Voltage: 208-1-60 V-Ph-Hz
Motor FLA: 6.6
Acoustical Data:
Factory-Installed Options
Unit Arrangement: Rear Return / Front Supply
Filters: 2 in. MERV 8 Pleated Filter
Motor HP: 3/4 HP
AAV / Drains: Manual Air Vents only
Coil Hand: Left Hand
Thermostats: Field Supplied/Installed Thermostat
Unit Controls: No Controls no EH (motor wired only to external J-box.)
Insulation: Std. 1 in. Fiberglass
Packaging: Units shipped on treated wood pallet
2.6
2.4
2.2 1200RPM
Static Pressure (in. wg.)
1.00BHP
2.0
1.8 0.75BHP
90%
1.6 1000RPM SC
1.4 0.50BHP
1.2 80%
800RPM 0.33BHP
1.0 RP
70%
0.8
0.6 600RPM
0.4
0.2
0.0
0.0 0.4 0.8 1.2 1.6 2.0 2.4 2.8
Airflow(CFM-thousands)
RPM=808 BHP=0.66 MaximumRPM=1323 MaximumHP=1.50
Note:Pleasecontactapplicationengineeringforselectionsoutsidetheshadedregion.
SC-SystemCurve RP-RatedPoint MP-MinimumPoint
Guide Specifications
Size Range:
600 to 4000 Nominal Cfm
Part 1 — General
1.01 SYSTEM DESCRIPTION
Horizontal and vertical, 2-pipe or 4-pipe, belt-driven, galvanized casing model fan coil unit for ducted installation above
the ceiling or within floor-mounted cabinet, with full access to internal components.
1.02 QUALITY ASSURANCE
A. Unit shall be constructed in accordance with ETL and ETL, Canada standards. Units comply with the minimum
requirements of the US and Canadian national product safety standard, UL 1995/CSA C22.2 No. 236. Factory-
installed motors and electric heaters shall be UL approved. Insulation and adhesive shall meet NFPA-90A
requirements for flame spread and smoke generation.
B. Coils shall be tested in accordance with AHRI standard 410, latest edition. Each coil shall be factory tested for
leakage at 300-psig air pressure with coil submerged in water.
1.03 DELIVERY, STORAGE AND HANDLING
Unit shall be handled and stored in accordance with the manufacturer’s instructions.
Part 2 — Products
2.01 EQUIPMENT
A. General:
Factory-assembled, horizontal and vertical, draw-thru type fan coil unit for ducted installation above the ceiling or
floor mounting. Unit shall be complete with water coils, fan(s), motor, belt drive, drain pan, and filter.
B. Casing:
Construction shall be heavy-gage galvanized steel, lined with one-in. thick fiberglass Tuf-Skin™ II
thermal/acoustical insulation. Knockouts shall be provided for hanging the horizontal unit, that will accept 3/8-in.
threaded rod at the top and bottom of all unit corners. Supply and return duct connections shall be 1 in. long.
Removable side panels shall be provided for access to the fan/motor assembly. Access panels shall be easily
removable with hex key tool on vertical unit, and without tools on horizontal unit. A double-sloped drain pan shall
be constructed of stainless steel, extending under the full length and width of the coil(s) with a 3/4-in. male nominal
pipe thread stainless steel drain connection and 1/2-in. male NPT stainless secondary drain connection (cap when
not required). The outside surface of the drain pan shall be insulated with 1/8-in. closed cell insulation. Drain pan is
removable from cabinet from same end as coil connections for ease of cleaning.
C. Fans:
Belt-driven, double-width fan wheels shall have forward- curved blades and be statically and dynamically balanced.
Fan drive shall consist of variable-pitch motor pulley, fixed-diameter blower sheave with keyed shaft, and V-belt.
Fan drive shall be designed for 120% of rated fan horsepower. Fans and scrolls shall be of galvanized steel.
Bearings are ball bearings, permanently lubricated and sealed for life. Bearings are isolated from the blower
housing by rubber mounts set into heavy gage metal support system. The blower housing shall be isolated from
the cabinet and motor.
D. Coils:
Standard unit shall be equipped with a 4-row coil for installation in a 2-pipe system and additional rows of coil shall
be provided as an option for installation in a 4-pipe system. Coils shall have 1/2-in. copper tubes, aluminum fins
bonded to the tubes by mechanical expansion and have a working pressure of 250 psig at 200 F. Each coil shall
have a manual air vent and sweat connections for copper tubes.
E. Operating Characteristics:
A single-circuit coil unit installed in a 2-pipe system shall be capable of providing heating or cooling as determined
by the operating mode of the central water supply system. A double-circuit coil unit installed in a 4-pipe system
Fan Coil Builder 4.10b Page 9 of 10
Guide Specification for FC-01
Project: LACOSTE FANCOIL 01/08/2020
Prepared By: 08:45a.m.