AUX-ARVIIControl System

3 Indoor unit error code explanation


Error Recovery
Error code definition Problem possible reasons
code or not

Indoor PCB is broken


Indoor ambient temperature sensor
A1 Yes The fuse of indoor PCB is broken
failure
temperature sensor broken , or exceed test limit
Indoor PCB is broken
Temperature sensor about middle
A2 Yes The fuse of indoor PCB is broken
position of evaporator failure
temperature sensor broken , or exceed test limit
Indoor PCB is broken
Indoor coil pipe inlet temperature
A3 Yes The fuse of indoor PCB is broken
sensor failure
temperature sensor broken , or exceed test limit
Indoor PCB is broken
Indoor coil pipe outlet temperature
A4 Yes The fuse of indoor PCB is broken
sensor failure
temperature sensor is broken , or exceed test limit
Water pump no power
Water pump switch short-circuit or unconnected
A5 Indoor water pump failure Yes Water pump is broken
Drain pipe block or up lean
Indoor PCB is broken
Fan motor failure
Fan motor block
A6 Failure of indoor PG fan No
The connection between PCB and fan motor failure.
Indoor fan block
Failure of reversible synchronous Step motor failure
A7 No
motor The connection between PCB and step motor failure.
Indoor unit PCB is broken
A8 Indoor unit ERRPROM module failure No
Error module is broken.
The communication wire between indoor unit and outdoor
The communication between indoor unit is broken.
A9 No Indoor unit power close
unit and outdoor unit failed
Indoor PCB is broken
The communication wire between indoor unit and outdoor
unit is broken.
The communication between indoor Indoor unit power close
AA No
unit and wire controller failed
Indoor PCB is broken
Wire controller is broken
Two or more indoor unit central
AC Yes The central control address setting incorrect
control system address repeated
AE Operation mode conflict Yes The operation mode setting incorrect
Two or more indoor unit refrigerant
AH Yes System address setting incorrect
system address repeated
AJ Indoor unit total capacity exceeded Yes Stop some indoor units
EXV is blocked
AF The EXV leakage Yes Indoor unit temperature sensor issue.
Evaporator inlet sensor failure.
A0 The EXV to open failure No

476
AUX-ARVIII Appendix

4.Outdoor unit error code explanation


Recovery
Code Error code definition or not
Possible reason
Temperature sensor failure or test temperature exceed limit.
Ambient temperature
C1 Yes Sensor connection is incorrect.
sensor “Tao”failure
Outdoor unit PCB failure.
Temperature sensor failure or test temperature exceed limit.
Defrosting temperature
C2 Yes Sensor connection is incorrect.
sensor “Tdef1” failure
Outdoor unit PCB failure.
Discharge temperature of Temperature sensor failure or test temperature exceed limit.
C3 inverter compressor "Tda" Yes Sensor connection is incorrect.
failure Outdoor unit PCB failure.
Discharge temperature of Temperature sensor failure or test temperature exceed limit.
C4 fixed frequency Yes Sensor connection is incorrect.
compressor"Tdb" failure Outdoor unit PCB failure.
Temperature sensor failure or test temperature exceed limit.
Suction pipe temperature
C6 Yes Sensor connection is incorrect.
of compressor "Ts" failure
Outdoor unit PCB failure.
Subcooling of inlet liquid Temperature sensor failure or test temperature exceed limit.
CH pipe temperature sensor Yes Sensor connection is incorrect.
“Tci” failure Outdoor unit PCB failure.
High pressure sensor failure
High pressure sensor "Pd"
F1 Yes Low pressure sensor connection is incorrect.
failure
Outdoor unit PCB failure
Exhaust pipe or condenser pipe block
High pressure sensor "Pd" Condenser dirty
F3 Yes
protection. Outdoor unit fan stop or low speed
Refrigerant overcharge
Low pressure sensor is broken.
Low pressure sensor "Ps"
F4 Yes The connection between sensor and outdoor PCB incorrect
failure.
Outdoor unit PCB failure
Indoor unit fan stop or low speed
Evaporator dirty
Low pressure sensor "Ps" Indoor EXV full open in cooling mode (Outdoor EXV full open in
F6 No
protection. heating mode)
Lack refrigerant
The pipe between evaporator and suction port block
Compression ratio too high
F8 No Once confirm the unrecoverable
protection
Compression ratio too low
F9 No Once confirm the unrecoverable
protection
DC inverter compressor
low discharge temperature
FB No Once confirm the unrecoverable
"Tdi" limit frequency
protection
System pressure exceed high pressure switch limit.
High pressure switch failure
DC inverter compressor
H1 high pressure switch No High pressure sensor failure
"HPSi" failure
Instantaneous power-off
Stop valve closed

477
AUX-ARVIII Appendix

Outdoor unit fan stop


Outdoor unit air outlet block
In heating mode indoor unit fan stop
In heating mode indoor unit EXV block
System pressure exceed high pressure switch limit.
High pressure switch failure
High pressure sensor failure
Instantaneous power-off
Fix speed compressor high
H2 pressure switch "HPS1" No Stop valve closed
failure
Outdoor unit fan stop
Outdoor unit air outlet block
In heating mode indoor unit fan stop
In heating mode indoor unit EXV block
System pressure lower than low pressure switch limit.
Low pressure switch failure
Low pressure sensor failure
Instantaneous power-off
Low pressure switch "LPS"
H4 Yes Stop valve closed
failure
In cooling mode indoor unit EXV close or block
In heating mode outdoor unit EXV close or block
In heating mode outdoor unit fan stop
In heating mode outdoor unit air outlet block
H5 Lack refrigerant No System leakage
The stop valve closed
Outdoor unit air outlet block
Fix speed compressor 1
H8 Yes System supply power voltage exceed limit (Rated voltage 15%)
over current protection
Compressor failure
Current transformer failure
The stop valve closed
Outdoor unit air outlet block
Fix speed compressor 2
H9 Yes System supply power voltage exceed limit (Rated voltage 15%)
over current protection
Compressor failure
Current transformer failure
Supply power phase-reversal
HJ Main power failure No Supply power phase lack
Outdoor unit PCB failure
System less refrigerant
DC inverter Compressor failure
Compressor air return filter block
EXV open degree is small
DC inverter discharge
E3 temperature "Tda"too high No EXV block
shutdown protection
Gas pipe stop valve closed
Liquid pipe stop valve closed
System exhaust sensor failure
Outdoor unit PCB failure

478
AUX-ARVIII Appendix

System less refrigerant


Fix speed compressor failure
Fix speed compressor air return filter block
Fixed speed compressor EXV open degree is small
No.1 discharge
E4 No EXV block
temperature "Tdb" too high
shutdown protection Gas pipe stop valve closed
Liquid pipe stop valve closed
System exhaust temperature sensor failure
Outdoor unit PCB failure
System less refrigerant
Fix speed compressor failure
Fix speed compressor air return filter block
Fixed speed compressor EXV open degree is small
No.2 discharge
E5 No EXV block
temperature "Tdc" too high
shutdown protection Gas pipe stop valve closed
Liquid pipe stop valve closed
System exhaust temperature sensor failure
Outdoor unit PCB failure
Low discharge temperature
protection of fixed
EC No Once confirm the unrecoverable
frequency compressor
No.1,”Tdb”
Low discharge temperature
protection of fixed
EJ No Once confirm the unrecoverable
frequency compressor
No.2,"Tdc"
The communication wire between outdoor units is disconnect, short
The communication circuit or connect incorrect.
J1 between outdoor units Yes Outdoor unit PCB failure
failure
Outdoor unit main power failed
The communication wire between indoor unit and outdoor unit
The communication disconnect, short circuit or connect incorrect.
J2 between outdoor unit and Yes Indoor unit main power failed
indoor unit failure
Indoor unit PCB failure
The connection between driving module and main PCB failure
The communication The communication part of outdoor unit control PCB failure
J3 between PCB and INV Yes
module failure Frequency driving board failure
Compressor failure
The communication
between main PCB and DC DC fan motor drive module failure
J4 Yes
fan motor drive module
failure DC fan failure
Outdoor unit parameter Outdoor unit dial switch incorrect
J5 Yes
setting incorrect Mail PCB failure
Outdoor unit main control
J7 PCB ERROM module No Mail PCB failure
failure
Indoor unit total capacity
JJ Yes /
exceeding
Oil return failure or
JE Yes /
defrosting failure
“MCU” automatic reset
JF Yes /
failure

479
AUX-ARVIII Appendix

Supply voltage below level let the current excessive


31 Module protection (F0) Yes Supply voltage exceed limit
Outdoor fan stop or low speed
Supply voltage below level let the current excessive
Module hardware
32 Yes Supply voltage exceed limit
protection
Outdoor fan stop or low speed
Supply voltage below level let the current excessive
33 Module software protection Yes Supply voltage exceed limit
Outdoor fan stop or low speed
The connect of driving module and DC inverter compressor incorrect
34 Compressor unconnected Yes Driving module failure
Compressor failure
Compressor overload
Compressor phase current Compressor coil disconnect
35 Yes
overload protection Inverter driving board failure
Compressor failure
Supply voltage below level
DC bus voltage
36 over-voltage or Yes Supply voltage exceed limit
under-voltage failure
Driving module failure
Temperature sensor of
37 drive module heat fins No Inverter driving board failure
failure
Driving module failure
Drive module high
38 temperature limit frequency Yes Compressor failure
failure
Outdoor unit fan stop or low speed
Driving module failure
Drive module high
39 temperature shutdown Yes Compressor failure
protection
Temperature sensor failure
DC fan motor drive module
3A No Once confirm the unrecoverable
protection
DC fan motor drive module
3C overcurrent protection or No Once confirm the unrecoverable
overcurrent sensor failure
DC fan motor drive module
3H start failure or Running out No Once confirm the unrecoverable
of step
DC fan motor drive module
3J over-voltage or No Once confirm the unrecoverable
under-voltage protection
DC inverter compressor
3E No Once confirm the unrecoverable
running out of step
DC inverter compressor
41 No Once confirm the unrecoverable
drive module IPM alarm
DC fan motor overspeed
42 No Once confirm the unrecoverable
protection
DC fan motor drive module
43 No Once confirm the unrecoverable
Eeprom data corruption
Communication wire between indoor units failure
47 Indoor unit loss failure Yes Indoor PCB failure
Power supply of indoor units failure

480