Self-diagnosis function

Error Numbers
- This document describes how to conduct a self-diagnosis on the product and lists possible failure types.
- In the LGMV error number field, a failure will be indicated by a code listed in the following table.
- If two or more failures occur at the same time, they are listed by order of their error numbers.
- If an error occurred and was then fixed, the error code will not be displayed.

Error Indication
- The error number on the LGMV screen is displayed along with the error number shown on the outdoor unit and
the unit number.
- Indoor unit errors are displayed on the screen of the unit. Outdoor unit and general operation errors are displayed
at the top right of the LGMV screen.
- When an error occurs, you can move your mouse over the error number and click it to view troubleshooting
methods.
- You will be provided with the meaning of the errors, and possible causes, as well as troubleshooting methods for
resolving those errors. Follow the troubleshooting guide to fix the errors.

Display Title Cause of Error


Air temperature sensor of indoor unit is open or
0 1 - Air temperature sensor of indoor unit
short
Inlet pipe temperature sensor of indoor Inlet pipe temperature sensor of indoor unit is open
0 2 -
unit or short
Communication error : wired remote con- Failing to receive wired remote controller signal in
0 3 -
troller indoor unit indoor unit PCB

0 4 - Drain pump Malfunction of drain pump

Communication error : outdoor unit Failing to receive outdoor unit signal in indoor unit
0 5 -
indoor unit PCB
Indoor unit related error

Outlet pipe temperature sensor of Outlet pipe temperature sensor of indoor unit is
0 6 -
indoor unit open or short
Hydro Kit Hot water storage tank
0 8 - Pipe temperature sensor is open or short
Temperature sensor
In case when the serial number marked on EEP-
0 9 - Indoor EEPROM Error
ROM of Indoor unit is 0 or FFFFFF
Disconnecting the fan motor connector / Failure of
1 0 - Poor fan motor operation
indoor fan motor lock
Communication error : System boiler
1 1 - Failing to receive Inv. PCB signal in indoor unit
Indoor unit £ Inv.PCB

1 2 - Hydro Kit Inv.PCB error Hydro Kit Inv.PCB error

Hydro Kit Solar heat piping tempera-


1 3 - Pipe temperature sensor is open or short
ture sensor error

1 4 - Hydro Kit Indoor unit Flow switch error Flow switch flow detection error

Hydro Kit Liquid pipe Strange overheat


1 5 - Temperature sensor defective or hot water inflow
Error
1
Display Title Cause of Error
Indoor unit related error

Hydro KitIndoor unit Inlet and Outlet


1 6 - Pipe temperature sensor is open or short
pipe Temperature sensor Error
Hydro Kit Indoor unit Inlet pipe
Temperature sensor Error
1 7 - Pipe temperature sensor is open or short
Outside air Introduction duct Inlet pipe
Temperature sensor Error
Hydro Kit Indoor unit Outlet pipe
1 8 - Pipe temperature sensor is open or short
Temperature sensor Error
Master Outdoor Unit Inverter Master Outdoor Unit Inverter Compressor Drive
1
Compressor IPM Fault IPM Fault
Slave1 Outdoor Unit Inverter Slave1 Outdoor Unit Inverter Compressor Drive
2
Compressor IPM Fault IPM Fault
2 1
Slave2 Outdoor Unit Inverter Slave2 Outdoor Unit Inverter Compressor Drive
3
Compressor IPM Fault IPM Fault
Slave3 Outdoor Unit Inverter Slave3 Outdoor Unit Inverter Compressor Drive
4
Compressor IPM Fault IPM Fault
Master Inverter Board Input Over Master Outdoor Unit Inverter Board Input Current
1
Current(RMS) of Master Outdoor Unit excess (RMS)
Slave1 Inverter Board Input Over Slave1 Outdoor Unit Inverter Board Input Current
2
Current(RMS) of Master Outdoor Unit excess (RMS)
2 2
Slave2 Inverter Board Input Over Slave2 Outdoor Unit Inverter Board Input Current
3
Current(RMS) of Master Outdoor Unit excess (RMS)
Slave3 Inverter Board Input Over
Outdoor unit related error

Slave3 Outdoor Unit Inverter Board Input Current


4
Current(RMS) of Master Outdoor Unit excess (RMS)
Master Outdoor Unit Inverter DC charging is not performed at Master Outdoor
1
Compressor DC link Low Voltage Unit after starting relay turn on.
Slave1 Outdoor Unit Inverter DC charging is not performed at Slave1 Outdoor
2
Compressor DC link Low Voltage Unit after starting relay turn on.
2 3
Slave2 Outdoor Unit Inverter DC charging is not performed at Slave2 Outdoor
3
Compressor DC link Low Voltage Unit after starting relay turn on.
Slave3 Outdoor Unit Inverter DC charging is not performed at Slave3 Outdoor
4 Compressor DC link Low Voltage Unit after starting relay turn on.
Master Outdoor Unit High Pressure System is turned off by Master Outdoor Unit high
1 Switch pressure switch.
Slave1 Outdoor Unit High Pressure System is turned off by Slave1 Outdoor Unit high
2 Switch pressure switch.
2 4
Slave2 Outdoor Unit High Pressure System is turned off by Slave2 Outdoor Unit high
3 Switch pressure switch.
Slave3 Outdoor Unit High Pressure System is turned off by Slave3 Outdoor Unit high
4 Switch pressure switch.
Master Outdoor Unit Input Voltage Master Outdoor Unit input voltage is over 487V
High/ Low Voltage or below 270V (ARUM***LTE5)
Master Outdoor Unit input voltage is over 289V
2 5 1 or below 173V (ARUM***BTE5)
Master Outdoor Unit input voltage is over 506V
or below 414V (ARUM***DTE5)

2
Display Title Cause of Error
Slave1 Outdoor Unit Input Voltage Slave1 Outdoor Unit input voltage is over 487V or
High/ Low Voltage below 270V (ARUM***LTE5)
Slave1 Outdoor Unit input voltage is over 289V or
2
below 173V (ARUM***BTE5)
Slave1 Outdoor Unit input voltage is over 506V or
below 414V (ARUM***DTE5)
Slave2 Outdoor Unit Input Voltage Slave2 Outdoor Unit input voltage is over 487V or
High/ Low Voltage below 270V (ARUM***LTE5)
Slave2 Outdoor Unit input voltage is over 289V or
2 5 3
below 173V (ARUM***BTE5)
Slave2 Outdoor Unit input voltage is over 506V or
below 414V (ARUM***DTE5)
Slave3 Outdoor Unit Input Voltage Slave3 Outdoor Unit input voltage is over 487V or
High/ Low Voltage below 270V (ARUM***LTE5)
4 Slave3 Outdoor Unit input voltage is over 289V or
below 173V (ARUM***BTE5)
Slave3 Outdoor Unit input voltage is over 506V or
below 414V (ARUM***DTE5)

1 Master Outdoor Unit Inverter The First Start Failure by Master Outdoor Unit
Compressor Start Failure Inverter Compressor Abnormality

2 Slave1 Outdoor Unit Inverter The First Start Failure by Slave1 Outdoor Unit
Compressor Start Failure Inverter Compressor Abnormality
2 6
Outdoor unit related error

3 Slave2 Outdoor Unit Inverter The First Start Failure by Slave2 Outdoor Unit
Compressor Start Failure Inverter Compressor Abnormality

4 Slave3 Outdoor Unit Inverter The First Start Failure by Slave3 Outdoor Unit
Compressor Start Failure Inverter Compressor Abnormality

1 Master Outdoor Unit Inverter Master Outdoor Unit Inverter Compressor Fault
Compressor Over Current OR Drive Fault

2 Slave1 Outdoor Unit Inverter Slave1 Outdoor Unit Inverter Compressor Fault
Compressor Over Current OR Drive Fault
2 9
Slave2 Outdoor Unit Inverter Slave2 Outdoor Unit Inverter Compressor Fault
3
Compressor Over Current OR Drive Fault
Slave3 Outdoor Unit Inverter Slave3 Outdoor Unit Inverter Compressor Fault
4
Compressor Over Current OR Drive Fault
Master Outdoor Unit Inverter Compressor1 Master Outdoor Unit Inverter Compressor1 High
1
High Discharge Temperature Discharge Temperature
Slave1 Outdoor Unit Inverter Compressor1 Slave1 Outdoor Unit Inverter Compressor1 High
2
High Discharge Temperature Discharge Temperature
3 2
Slave2 Outdoor Unit Inverter Compressor1 Slave2 Outdoor Unit Inverter Compressor1 High
3
High Discharge Temperature Discharge Temperature
Slave3 Outdoor Unit Inverter Compressor1 Slave3 Outdoor Unit Inverter Compressor1 High
4
High Discharge Temperature Discharge Temperature
Master Outdoor Unit Inverter Compressor2 Master Outdoor Unit Inverter Compressor2 High
1
High Discharge Temperature Discharge Temperature
Slave1 Outdoor Unit Inverter Compressor2 Slave1 Outdoor Unit Inverter Compressor2 High
2
High Discharge Temperature Discharge Temperature
3 3
Slave2 Outdoor Unit Inverter Compressor2 Slave2 Outdoor Unit Inverter Compressor2 High
3
High Discharge Temperature Discharge Temperature
Slave3 Outdoor Unit Inverter Compressor2 Slave3 Outdoor Unit Inverter Compressor2 High
4
High Discharge Temperature Discharge Temperature
3
Display Title Cause of Error
High Pressure of Master Outdoor Unit High Pressure of Master Outdoor Unit
1

High Pressure of Slave1 Outdoor Unit High Pressure of Slave1 Outdoor Unit
2
3 4
High Pressure of Slave2 Outdoor Unit High Pressure of Slave2 Outdoor Unit
3

High Pressure of Slave3 Outdoor Unit High Pressure of Slave3 Outdoor Unit
4

Low Pressure of Master Outdoor Unit Low Pressure of Master Outdoor Unit
1

Low Pressure of Slave1 Outdoor Unit Low Pressure of Slave1 Outdoor Unit
2
3 5
Low Pressure of Slave2 Outdoor Unit Low Pressure of Slave2 Outdoor Unit
3

Low Pressure of Slave3 Outdoor Unit Low Pressure of Slave3 Outdoor Unit
4

Master Outdoor Unit Inverter Master Outdoor Unit Inverter Compressor CT


1 Compressor CT Sensor Fault Sensor open or short
Outdoor unit related error

Slave1 Outdoor Unit Inverter Slave1 Outdoor Unit Inverter Compressor CT


2 Compressor CT Sensor Fault Sensor open or short
4 0
Slave2 Outdoor Unit Inverter Slave2 Outdoor Unit Inverter Compressor CT
3 Compressor CT Sensor Fault Sensor open or short
Slave3 Outdoor Unit Inverter Slave3 Outdoor Unit Inverter Compressor CT
4 Compressor CT Sensor Fault Sensor open or short
Master Outdoor Unit Inverter Master Outdoor Unit Inverter Compressor
1 Compressor1 Discharge Temperature Discharge Temperature Sensor open or short
Sensor Fault
Slave1 Outdoor Unit Inverter Slave1 Outdoor Unit Inverter Compressor
2 Compressor1 Discharge Temperature Discharge Temperature Sensor open or short
Sensor Fault
4 1
Slave2 Outdoor Unit Inverter Slave2 Outdoor Unit Inverter Compressor
3 Compressor1 Discharge Temperature Discharge Temperature Sensor open or short
Sensor Fault
Slave3 Outdoor Unit Inverter Slave3 Outdoor Unit Inverter Compressor
4 Compressor1 Discharge Temperature Discharge Temperature Sensor open or short
Sensor Fault

1 Master Outdoor Unit Low Pressure Master Outdoor Unit Low Pressure Sensor open or
Sensor Fault short

2 Slave1 Outdoor Unit Low Pressure Slave1 Outdoor Unit Low Pressure Sensor open or
Sensor Fault short
4 2
3 Slave2 Outdoor Unit Low Pressure Slave2 Outdoor Unit Low Pressure Sensor open or
Sensor Fault short

4 Slave3 Outdoor Unit Low Pressure Slave3 Outdoor Unit Low Pressure Sensor open or
Sensor Fault short

4
Display Title Cause of Error
Master Outdoor Unit High Pressure Master Outdoor Unit High Pressure Sensor open
1 Sensor Fault or short
Slave1 Outdoor Unit High Pressure Slave1 Outdoor Unit High Pressure Sensor open
2 Sensor Fault or short
4 3
Slave2 Outdoor Unit High Pressure Slave2 Outdoor Unit High Pressure Sensor open
3 Sensor Fault or short
Slave3 Outdoor Unit High Pressure Slave3 Outdoor Unit High Pressure Sensor open
4 Sensor Fault or short
Master Outdoor Unit Air Temperature Master Outdoor Unit Air Temperature Sensor open
1 Sensor Fault or short
Slave1 Outdoor Unit Air Temperature Slave1 Outdoor Unit Air Temperature Sensor open
2 Sensor Fault or short
4 4
Slave2 Outdoor Unit Air Temperature Slave2 Outdoor Unit Air Temperature Sensor open
3 Sensor Fault or short
Slave3 Outdoor Unit Air Temperature Slave3 Outdoor Unit Air Temperature Sensor open
4 Sensor Fault or short
Master Outdoor Unit Heat Exchanger Master Outdoor Unit Heat Exchanger Temperature
1 Temperature Sensor (Front side) Fault Sensor(Front side) open or short
Outdoor unit related error

Slave1 Outdoor Unit Heat Exchanger Slave1 Outdoor Unit Heat Exchanger Temperature
2 Temperature Sensor (Front side) Fault Sensor(Front side) open or short
4 5
Slave2 Outdoor Unit Heat Exchanger Slave2 Outdoor Unit Heat Exchanger Temperature
3 Temperature Sensor (Front side) Fault Sensor(Front side) open or short
Slave3 Outdoor Unit Heat Exchanger Slave3 Outdoor Unit Heat Exchanger Temperature
4 Temperature Sensor (Front side) Fault Sensor(Front side) open or short
Master Outdoor Unit Suction Master Outdoor Unit Suction Temperature Sensor
1 Temperature Sensor Fault open or short
Slave1 Outdoor Unit Suction Slave1 Outdoor Unit Suction Temperature Sensor
2 Temperature Sensor Fault open or short
4 6
Slave2 Outdoor Unit Suction Slave2 Outdoor Unit Suction Temperature Sensor
3 Temperature Sensor Fault open or short
Slave3 Outdoor Unit Suction Slave3 Outdoor Unit Suction Temperature Sensor
4 Temperature Sensor Fault open or short
Master Outdoor Unit Inverter Master Outdoor Unit Inverter Compressor2
1 Compressor2 Discharge Temperature Discharge Temperature Sensor open or short
Sensor Fault
Slave1 Outdoor Unit Inverter Slave1 Outdoor Unit Inverter Compressor2
2 Compressor2 Discharge Temperature Discharge Temperature Sensor open or short
Sensor Fault
4 7
Slave2 Outdoor Unit Inverter Slave2 Outdoor Unit Inverter Compressor2
3 Compressor2 Discharge Temperature Discharge Temperature Sensor open or short
Sensor Fault
Slave3 Outdoor Unit Inverter Slave3 Outdoor Unit Inverter Compressor2
4 Compressor2 Discharge Temperature Discharge Temperature Sensor open or short
Sensor Fault

5
Display Title Cause of Error
Master Outdoor Unit Faulty IPM Master Outdoor Unit IPM Temperature Sensor
1
Temperature Sensor short/open
Slave1 Outdoor Unit Faulty IPM Slave1 Outdoor Unit IPM Temperature Sensor
2
Temperature Sensor short/open
4 9
Slave2 Outdoor Unit Faulty IPM Slave2 Outdoor Unit IPM Temperature Sensor
3
Temperature Sensor short/open
Slave3 Outdoor Unit Faulty IPM Slave3 Outdoor Unit IPM Temperature Sensor
4
Temperature Sensor short/open
Omitting connection of R, S, T power Omitting connection of Master outdoor unit
1
of Master Outdoor Unit
Omitting connection of R, S, T power Omitting connection of Slave1 outdoor unit
2
of Slave1 Outdoor Unit
5 0
Omitting connection of R, S, T power Omitting connection of Slave2 outdoor unit
3
of Slave2 Outdoor Unit
Omitting connection of R, S, T power Omitting connection of Slave3 outdoor unit
4
of Slave3 Outdoor Unit
Excessive capacity of indoor units Excessive connection of indoor units compared to
5 1 1
capacity of Outdoor Unit
Outdoor unit related error

Master Outdoor Unit Communication Failing to receive inverter signal at main PCB of
1
error : inverter PCB → Main PCB Master Outdoor Unit
Slave1 Outdoor Unit Communication Failing to receive inverter signal at main PCB of
2
error : inverter PCB → Main PCB Slave1 Outdoor Unit
5 2
Slave2 Outdoor Unit Communication Failing to receive inverter signal at main PCB of
3 error : inverter PCB → Main PCB Slave2 Outdoor Unit
Slave3 Outdoor Unit Communication Failing to receive inverter signal at main PCB of
4 error : inverter PCB → Main PCB Slave3 Outdoor Unit
Communication error : indoor unit → Failing to receive indoor unit signal at main PCB of
5 3 1 Main PCB of Outdoor Unit Outdoor Unit.
Master Outdoor Unit Communication Failing to receive signal main PCB at inverter PCB
1 error : Main PCB → inverter PCB of Master Outdoor Unit
Slave1 Outdoor Unit Communication Failing to receive signal main PCB at inverter PCB
2 error : Main PCB → inverter PCB of Slave1 Outdoor Unit
5 7
Slave2 Outdoor Unit Communication Failing to receive signal main PCB at inverter PCB
3 error : Main PCB → inverter PCB of Slave2 Outdoor Unit
Slave3 Outdoor Unit Communication Failing to receive signal main PCB at inverter PCB
4 error : Main PCB → inverter PCB of Slave3 Outdoor Unit
Inverter PCB EEPROM Error of Master Access Error of Inverter PCB of Master Outdoor
1 Outdoor Unit Unit
Inverter PCB EEPROM Error of Slave1 Access Error of Inverter PCB of Slave1 Outdoor
2 Outdoor Unit Unit
6 0
Inverter PCB EEPROM Error of Slave2 Access Error of Inverter PCB of Slave2 Outdoor
3 Outdoor Unit Unit
Inverter PCB EEPROM Error of Slave3 Access Error of Inverter PCB of Slave3 Outdoor
4 Outdoor Unit Unit

6
Display Title Cause of Error
Master Outdoor Unit Inverter Heatsink System is turned off by Master Outdoor Unit
1
High Temperature Inverter Heatsink High Temperature

2 Slave1 Outdoor Unit Inverter Heatsink System is turned off by Slave1 Outdoor Unit
High Temperature Inverter Heatsink High Temperature
6 2
3 Slave2 Outdoor Unit Inverter Heatsink System is turned off by Slave2 Outdoor Unit
High Temperature Inverter Heatsink High Temperature

4 Slave3 Outdoor Unit Inverter Heatsink System is turned off by Slave3 Outdoor Unit
High Temperature Inverter Heatsink High Temperature
Master Outdoor Unit Inverter Heatsink Master Outdoor Unit Inverter Heatsink
1
Temperature Sensor Fault Temperature Sensor open or short
Slave1 Outdoor Unit Inverter Heatsink Slave1 Outdoor Unit Inverter Heatsink
2
Temperature Sensor Fault Temperature Sensor open or short
6 5
Slave2 Outdoor Unit Inverter Heatsink Slave2 Outdoor Unit Inverter Heatsink
3
Temperature Sensor Fault Temperature Sensor open or short
Slave3 Outdoor Unit Inverter Heatsink Slave3 Outdoor Unit Inverter Heatsink
4
Temperature Sensor Fault Temperature Sensor open or short
1 Master Outdoor Unit Fan Lock Restriction of Master Outdoor Unit
2 Slave1 Outdoor Unit Fan Lock Restriction of Slave1 Outdoor Unit
6 7
Outdoor unit related error

3 Slave2 Outdoor Unit Fan Lock Restriction of Slave2 Outdoor Unit


4 Slave3 Outdoor Unit Fan Lock Restriction of Slave3 Outdoor Unit

1 Converter CT Sensor Error of Master Converter CT Sensor open or short of Master


Outdoor Unit Outdoor Unit

2 Converter CT Sensor Error of Slave1 Converter CT Sensor open or short of Slave1


Outdoor Unit Outdoor Unit
7 1
3 Converter CT Sensor Error of Slave2 Converter CT Sensor open or short of Slave2
Outdoor Unit Outdoor Unit

4 Converter CT Sensor Error of Slave3 Converter CT Sensor open or short of Slave3


Outdoor Unit Outdoor Unit

1 Master Outdoor Unit Fan CT Sensor Master Outdoor Unit Fan CT Sensor open or short
Error

2 Slave1 Outdoor Unit Fan CT Sensor Slave1 Outdoor Unit Fan CT Sensor open or short
Error
7 5
3 Slave2 Outdoor Unit Fan CT Sensor Slave2 Outdoor Unit Fan CT Sensor open or short
Error
Slave3 Outdoor Unit Fan CT Sensor Slave3 Outdoor Unit Fan CT Sensor open or short
Error

1 Master Outdoor Unit Fan Over Current Master Outdoor Unit Fan Current is over 5A
Error
Slave1 Outdoor Unit Fan Over Current Slave1 Outdoor Unit Fan Current is over 5A
2
Error
7 7
Slave2 Outdoor Unit Fan Over Current Slave2 Outdoor Unit Fan Current is over 5A
3
Error
Slave3 Outdoor Unit Fan Over Current Slave3 Outdoor Unit Fan Current is over 5A
4
Error

7
Display Title Cause of Error
Master Outdoor Unit Fan Start Failure Master Outdoor Unit Fan First Position Sensing
1
Error Failure
Slave1 Outdoor Unit Fan Start Failure Slave1 Outdoor Unit Fan First Position Sensing
2
Error Failure
7 9
Slave2 Outdoor Unit Fan Start Failure Slave2 Outdoor Unit Fan First Position Sensing
3
Error Failure
Slave3 Outdoor Unit Fan Start Failure Slave3 Outdoor Unit Fan First Position Sensing
4
Error Failure
Master Outdoor Unit Main PCB EEP- Communication Fail Between Master Outdoor Unit
1
ROM Error Main MICOM and EEPROM or omitting EEPROM
Slave1 Outdoor Unit Main PCB EEP- Communication Fail Between Slave1 Outdoor Unit
2
ROM Error Main MICOM and EEPROM or omitting EEPROM
8 6
Slave2 Outdoor Unit Main PCB EEP- Communication Fail Between Slave2 Outdoor Unit
3
ROM Error Main MICOM and EEPROM or omitting EEPROM
Slave3 Outdoor Unit Main PCB EEP- Communication Fail Between Slave3 Outdoor Unit
4
ROM Error Main MICOM and EEPROM or omitting EEPROM
Outdoor unit related error

Master Outdoor Unit Fan PCB EEP- Communication Fail Between Master Outdoor Unit
1
ROM Error Fan MICOM and EEPROM or omitting EEPROM
Slave1 Outdoor Unit Fan PCB EEP- Communication Fail Between Slave1 Outdoor Unit
2
ROM Error Fan MICOM and EEPROM or omitting EEPROM
8 7
Slave2 Outdoor Unit Fan PCB EEP- Communication Fail Between Slave2 Outdoor Unit
3
ROM Error Fan MICOM and EEPROM or omitting EEPROM
Slave3 Outdoor Unit Fan PCB EEP- Communication Fail Between Slave3 Outdoor Unit
4
ROM Error Fan MICOM and EEPROM or omitting EEPROM
Master Outdoor Unit TVI Inlet The resistance value of the Master Outdoor Unit
1 Temperature Sensor Error sensor is abnormal.
Slave1 Outdoor Unit TVI Inlet The resistance value of the Slave1 Outdoor Unit
2 Temperature Sensor Error sensor is abnormal.
9 0
Slave2 Outdoor Unit TVI Inlet The resistance value of the Slave2 Outdoor Unit
3 Temperature Sensor Error sensor is abnormal.
Slave3 Outdoor Unit TVI Inlet The resistance value of the Slave3 Outdoor Unit
4 Temperature Sensor Error sensor is abnormal.
Master Outdoor Unit TVI Outlet The resistance value of the Master Outdoor Unit
1 Temperature Sensor Error sensor is abnormal.
Slave1 Outdoor Unit TVI Outlet The resistance value of the Slave1 Outdoor Unit
2 Temperature Sensor Error sensor is abnormal.
9 1
Slave2 Outdoor Unit TVI Outlet The resistance value of the Slave2 Outdoor Unit
3 Temperature Sensor Error sensor is abnormal.
Slave3 Outdoor Unit TVI Outlet The resistance value of the Slave3 Outdoor Unit
4 Temperature Sensor Error sensor is abnormal.

8
Display Title Cause of Error
Communication Error Between Master Failing to receive Slave Unit signal at main PCB of
1 Outdoor Unit and Other Outdoor Unit Master Outdoor Unit
Communication Error Between Slave1 Failing to receive Slave Unit signal at main PCB of
2 Outdoor Unit and Other Outdoor Unit Slave1 Outdoor Unit
1 0 4
Communication Error Between Slave2 Failing to receive Slave Unit signal at main PCB of
3 Outdoor Unit and Other Outdoor Unit Slave2 Outdoor Unit
Communication Error Between Slave3 Failing to receive Slave Unit signal at main PCB of
4 Outdoor Unit and Other Outdoor Unit Slave3 Outdoor Unit
Master Outdoor Unit Fan PCB Failing to receive fan signal at main PCB of Master
1 Communication Error Outdoor unit
Slave1 Outdoor Unit Fan PCB Failing to receive fan signal at main PCB of Slave1
2 Communication Error Outdoor unit
1 0 5
Slave2 Outdoor Unit Fan PCB Failing to receive fan signal at main PCB of Slave2
3 Communication Error Outdoor unit
Slave3 Outdoor Unit Fan PCB Failing to receive fan signal at main PCB of Slave3
4 Communication Error Outdoor unit
Outdoor unit related error

Master Outdoor Unit FAN IPM Fault Instant Over Current at Master Outdoor Unit Fan
1 Error IPM
Slave1 Outdoor Unit FAN IPM Fault Instant Over Current at Slave1 Outdoor Unit Fan
2 Error IPM
1 0 6
Slave2 Outdoor Unit FAN IPM Fault Instant Over Current at Slave2 Outdoor Unit Fan
3 Error IPM
Slave3 Outdoor Unit FAN IPM Fault Instant Over Current at Slave3 Outdoor Unit Fan
4 Error IPM
Master Outdoor Unit Fan DC Link Low Master Outdoor Unit Fan DC Link Input Voltage is
1 Voltage Error under 380V
Slave1 Outdoor Unit Fan DC Link Low Slave1 Outdoor Unit Fan DC Link Input Voltage is
2 Voltage Error under 380V
1 0 7
Slave2 Outdoor Unit Fan DC Link Low Slave2 Outdoor Unit Fan DC Link Input Voltage is
3 Voltage Error under 380V
Slave3 Outdoor Unit Fan DC Link Low Slave3 Outdoor Unit Fan DC Link Input Voltage is
4 Voltage Error under 380V
Master Outdoor Unit Liquid pipe Liquid pipe temperature sensor of Master Outdoor
1 Temperature Sensor Error Unit is open or short
Slave1 Outdoor Unit Liquid pipe Liquid pipe temperature sensor of Slave1 Outdoor
2 Temperature Sensor Error Unit is open or short
1 1 3
Slave2 Outdoor Unit Liquid pipe Liquid pipe temperature sensor of Slave2 Outdoor
3 Temperature Sensor Error Unit is open or short
Slave3 Outdoor Unit Liquid pipe Liquid pipe temperature sensor of Slave3 Outdoor
4 Temperature Sensor Error Unit is open or short

9
Display Title Cause of Error
Master Outdoor Unit Subcooling Inlet Master Outdoor Unit Subcooling Inlet Temperature
1
Temperature Sensor Error Sensor Error
Slave1 Outdoor Unit Subcooling Inlet Slave1 Outdoor Unit Subcooling Inlet Temperature
2
Temperature Sensor Error Sensor Error
1 1 4
Slave2 Outdoor Unit Subcooling Inlet Slave2 Outdoor Unit Subcooling Inlet Temperature
3
Temperature Sensor Error Sensor Error
Slave3 Outdoor Unit Subcooling Inlet Slave3 Outdoor Unit Subcooling Inlet Temperature
4
Temperature Sensor Error Sensor Error
Master Outdoor Unit Subcooling Outlet Master Outdoor Unit Subcooling Outlet
1
Temperature Sensor Error Temperature Sensor Error
Slave1 Outdoor Unit Subcooling Outlet Slave1 Outdoor Unit Subcooling Outlet
2
Temperature Sensor Error Temperature Sensor Error
1 1 5
Slave2 Outdoor Unit Subcooling Outlet Slave2 Outdoor Unit Subcooling Outlet
3
Temperature Sensor Error Temperature Sensor Error
Slave3 Outdoor Unit Subcooling Outlet Slave3 Outdoor Unit Subcooling Outlet
4
Temperature Sensor Error Temperature Sensor Error
Master Outdoor Unit Oil Level Sensor Oil Level Sensor of Master Outdoor Unit is open or
1
Outdoor unit related error

Error short
Slave1 Outdoor Unit Oil Level Sensor Oil Level Sensor of Slave1 Outdoor Unit is open or
2 Error short
1 1 6
Slave2 Outdoor Unit Oil Level Sensor Oil Level Sensor of Slave2 Outdoor Unit is open or
3 Error short
Slave3 Outdoor Unit Oil Level Sensor Oil Level Sensor of Slave3 Outdoor Unit is open or
4 Error short
Master Outdoor unit Main Board - Master Outdoor unit Main Board - External Board
1 External Board communication Error communication Error
Slave1 Outdoor unit Main Board - Slave1 Outdoor unit Main Board - External Board
2 External Board communication Error communication Error
1 4 5
Slave2 Outdoor unit Main Board - Slave2 Outdoor unit Main Board - External Board
3 External Board communication Error communication Error
Slave3 Outdoor unit Main Board - Slave3 Outdoor unit Main Board - External Board
4 External Board communication Error communication Error
Master Outdoor Unit Discharge Master Outdoor Unit Compressor Discharge
1 Superheat not satisfied Superheat not satisfied during 5 Min.
Slave1 Outdoor Unit Discharge Slave1 Outdoor Unit Compressor Discharge
2 Superheat not satisfied Superheat not satisfied during 5 Min.
1 5 0
Slave2 Outdoor Unit Discharge Slave2 Outdoor Unit Compressor Discharge
3 Superheat not satisfied Superheat not satisfied during 5 Min.
Slave3 Outdoor Unit Discharge Slave3 Outdoor Unit Compressor Discharge
4 Superheat not satisfied Superheat not satisfied during 5 Min.
Failure of operation mode conversion Failure of operation mode conversion at Outdoor
1 5 1 1 at Outdoor Unit Unit

10
Display Title Cause of Error
Master Outdoor Unit Heat Exchanger Master Outdoor Unit Heat Exchanger Temperature
1
Temperature Sensor (upper part) Fault Sensor (upper part) Fault
Slave1 Outdoor Unit Heat Exchanger Slave1 Outdoor Unit Heat Exchanger Temperature
2
Temperature Sensor (upper part) Fault Sensor (upper part) Fault
1 5 3
Slave2 Outdoor Unit Heat Exchanger Slave2 Outdoor Unit Heat Exchanger Temperature
3
Temperature Sensor (upper part) Fault Sensor (upper part) Fault
Slave3 Outdoor Unit Heat Exchanger Slave3 Outdoor Unit Heat Exchanger Temperature
4
Temperature Sensor (upper part) Fault Sensor (upper part) Fault
Master Outdoor Unit Heat Exchanger Master Outdoor Unit Heat Exchanger Temperature
1
Temperature Sensor (lower part) Fault Sensor(lower part) open or short
Slave1 Outdoor Unit Heat Exchanger Slave1 Outdoor Unit Heat Exchanger Temperature
2
Temperature Sensor (lower part) Fault Sensor(lower part) open or short
1 5 4
Slave2 Outdoor Unit Heat Exchanger Slave2 Outdoor Unit Heat Exchanger Temperature
3
Temperature Sensor (lower part) Fault Sensor(lower part) open or short
Slave3 Outdoor Unit Heat Exchanger Slave3 Outdoor Unit Heat Exchanger Temperature
4
Temperature Sensor (lower part) Fault Sensor(lower part) open or short
Master Outdoor unit External Board Master Outdoor Unit Main Board Main-Sub Micom
1
Outdoor unit related error

Main-Sub Micom communication Error communication failed


Slave1 Outdoor unit External Board Slave1 Outdoor Unit Main Board Main-Sub Micom
2
Main-Sub Micom communication Error communication failed
1 8 2
Slave2 Outdoor unit External Board Slave2 Outdoor Unit Main Board Main-Sub Micom
3
Main-Sub Micom communication Error communication failed
Slave3 Outdoor unit External Board Slave3 Outdoor Unit Main Board Main-Sub Micom
4
Main-Sub Micom communication Error communication failed
Hydro - Kit P,HEX bursting error Inlet water temperature is below 5 degree or water
1 8 7 1
temperature error during defrosting operation.
Master Outdoor Unit Fan Heatsink High System is turned off by Master Outdoor Unit Fan
1 Temperature Heatsink High Temperature
Slave1 Outdoor Unit Fan Heatsink High System is turned off by Slave1 Outdoor Unit Fan
2 Temperature Heatsink High Temperature
1 9 3
Slave2 Outdoor Unit Fan Heatsink High System is turned off by Slave2 Outdoor Unit Fan
3 Temperature Heatsink High Temperature
Slave3 Outdoor Unit Fan Heatsink High System is turned off by Slave3 Outdoor Unit Fan
4 Temperature Heatsink High Temperature
Master Outdoor Unit Fan Heatsink Master Outdoor Unit Fan Heatsink Temperature
1 Temperature Sensor Fault Sensor open or short
Slave1 Outdoor Unit Fan Heatsink Slave1 Outdoor Unit Fan Heatsink Temperature
2 Temperature Sensor Fault Sensor open or short
1 9 4
Slave2 Outdoor Unit Fan Heatsink Slave2 Outdoor Unit Fan Heatsink Temperature
3 Temperature Sensor Fault Sensor open or short
Slave3 Outdoor Unit Fan Heatsink Slave3 Outdoor Unit Fan Heatsink Temperature
4 Temperature Sensor Fault Sensor open or short

11
Display Title Cause of Error
Searching pipe Error Failure of automatic addressing of valves
0 C + #HR
HR Unit related error

HR unit1 Liqiud sensor error Liquid pipe sensor of HR unit open or short
1 C + #HR

HR unit1 Sub Cooling Pipe sensor error Sub Cooling Pipe In sensor of HR unit open or
2 0 2 C + #HR short
HR unit1 Sub Cooling Pipe Out sensor Sub Cooling Pipe Out sensor of HR unit. open or
3 C + #HR error short
Communication error Failing to receive HR unit signal at outdoor unit
4 C + #HR

C: HR unit #: HR unit Number

12
Error Code check
Error No. Error Type Error Point Main Reasons

1 Indoor unit air sensor error


01(FAU) FAU Outlet air sensor error
2 Indoor unit pipe inlet sensor error
6 Indoor unit pipe outlet sensor error 1. Indoor unit PCB wrong
connection
17(FAU) FAU Inlet air sensor error Indoor unit sensor
2. Indoor unit PCB failure
08(Syster Boiler) Low Temperature Tank sensor error is open/short
3. Sensor problem
13(Syster Boiler) Solar heat pipe sensor error
(main reason)
16(Syster Boiler) Indoor unit water pipe sensor error
17(Syster Boiler) Indoor unit pipe inlet sensor error
18(Syster Boiler) Indoor unit pipe outlet sensor error

I Error diagnosis and countermeasure flow chart

Is sensor properly No
Connect properly to PCB
connected to PCB?

Yes

Is the resistance value No


Change the sensor
of sensor normal?*

Yes

Change the PCB

** In case the value is more than 100kΩ (open) or less than 100Ω (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature(±5% margin)   Normal
Air temp sensor: 10°C = 20.7kΩ : 25°C= 10kΩ : 50°C= 3.4kΩ
Pipe temp sensor: 10°C = 10kΩ : 25°C= 5kΩ : 50°C= 1.8kΩ

13
Error
Error Type Error Point Main Reasons
No.

1. Remote controller fault


The remote controller
03 No communication between cabled did not receive the sig- 2. Indoor unit PCB fault
remote controller & indoor unit nal from indoor unit 3. Connector fault, Wrong connection
during specific time 4. Communication cable problem

I Error diagnosis and countermeasure flow chart

Does the error happens No Replace cabled remote


again if the remote
controller
controller is replaced?*

Yes

Does the error occurred No


when the cable of remote Check connection &
controller is replaced? communication cable **

Yes

Replace indoor unit PCB ***

* If there is no remote controller to replace : Use another unit’s remote controller doing well
** Check cable : Contact failure of connected portion or extension of cable are main cause
Check any surrounded noise ( check the distance with main power cable)
  make safe distance from the devices generate electromagnetic wave
*** After replacing indoor unit PCB, do Auto Addressing & input unit’s address if connected to central controller.
(All the indoor units connected should be turned on before Auto Addressing

14
Error
Error Type Error Point Main Reasons
No.

Float switch is open due to 1. Drain pump/float switch fault


rising of condensate water 2. Improper drain pipe location, clog-
04 Drain pump error level because of drain ging of drain pipe
pump fault or drain pipe
3. Indoor unit PCB fault
clogging

I Error diagnosis and countermeasure flow chart

Is the drain pan filled Is Float switch short


No No
half with condensate On measuring its Replace float switch
water? (half level of resistance?
float switch)*
Yes
Yes

Replace Indoor PCB or


reconnect the connector

In indoor unit PCB


Is drain pump working? No Does the terminal voltage No
(Sound/drain noise/ Replace indoor unit PCB
for drain pump has
contact etc.) 220V output?**
Yes Yes

Replace Drain Pump

No
Drain pump blocked by Check the drain head height
foreign particles? and slope***

Yes

Remove it & clean the pump

15
Error
Error Type Error Point Main Reasons
No.

1. Auto addressing is not done


2. Communication cable is not connected
3. Short circuit of communication cable
No signal communication
Indoor & Outdoor unit 4. Indoor unit communication circuit fault
between indoor & outdoor
05 communication error 5. Outdoor unit communication circuit fault
units.
6. Not enough distance between power and com-
munication cable?
7. T phase line disconnection or N phase connected.

I Error diagnosis and countermeasure flow chart


Replace the PCB of indoor unit
No Is total number of indoor No displayed error
Does all the IDUs show
units connected displayed
same error code CH05? Re-connect after check the
after auto addressing?
communication cable of indoor
Yes unit displayed error**
END
Replace outdoor PCB after
No Check the main power No checking
Is outdoor PCB LED
supply at the ODU
blinking?
terminal block? Replace TRANS after checking

Yes
Yes
Check the insulation of compressor
No compressor and replace if required
Is main circuit breaker off?
Check the capacity of main circuit
Yes breaker and replace if required

Improper connection of power supply cable Check T phase line connetion

Main power supply problem If all ok,


Turn on main circuit breaker
Check if the
communication cable is
properly connected No
Re connect communication cable
to indoor / outdoor
terminal block?*
Outdoor PCB fault
Replace after checking
Yes
Indoor PCB fault
Replace after checking

* (Note1) communication from IDU is normal if voltage * If the DC voltage between communication terminal A, B
fluctuation(-9V ~ +9V) exists when checking DC voltage of indoor unit is fluctuate within (-9V~+9V) then
of communication terminal between IDU and ODU communication from outdoor unit is normal

16
Error
Error Type Error Point Main Reasons
No.

1. Error developed in communication between the


09 Indoor unit EEPROM Error occur in EEPROM micro- processor and the EEPROM on the sur-
error of the Indoor PCB face of the PCB.
2. ERROR due to the EEPROM damage

I Error diagnosis and countermeasure flow chart

- Replace the indoor unit PCB, and then make sure to perform Auto addressing and input the address of central control

17
Error
Error Type Error Point Main Reasons
No.

Indoor unit BLDC fan motor Indoor BLDC fan motor 1. Motor connector connection fault
10 failure feedback signal is absent 2. Indoor PCB fault
(for 50 sec.) 3. Motor fault

I Error diagnosis and countermeasure flow chart

Is connector No
connection proper? Connect properly

Yes

Is fan motor No
Replace indoor unit fan motor
normal?*

Yes

Replace indoor unit PCB **

WARNING
• The connection of motor connector to PCB should be done under no power supplying to PCB.

18
Error
Error Type Error Point Main Reasons
No.

21*
1.Over current detection at Inverter compres-
sor(U,V,W)
Master 2.Compressor damaged (insulation dam-
211 IPM self protection circuit aged/Motor damaged)
Slave1 Inverter PCB Assy. IGBT activation 3.IPM overheating
212 Fault occur (Overcurrent/IPM overheat- (Heat sink disassembled)
Slave2 ing/Vcc low voltage) 4.Inverter compressor terminal disconnected
213 or loose
5.Inverter PCB assembly damaged
Slave3
214 6.ODU input current low

I Error diagnosis and countermeasure flow chart


Are there any power wire No 1. Check R/S/T/N Wiring Condition
connections normal? → Rewire them if abnormality found

Yes
1. Check resistance between each terminal of compressor
Compressor JQC068MA* JQC048MA*
Are the resistance Temp. 25℃ 75℃ 25℃ 75℃
Between each phase and No U-V 0.216 ± 7% Ω 0.258 ± 7% Ω 0.302 ± 7% Ω 0.360 ± 7% Ω
insulation resistance of Inverter V-W 0.216 ± 7% Ω 0.258 ± 7% Ω 0.302 ± 7% Ω 0.360 ± 7% Ω
compressor normal? W-U 0.216 ± 7% Ω 0.258 ± 7% Ω 0.302 ± 7% Ω 0.360 ± 7% Ω

2. Check insulation resistance between compressor


terminal and pipe (over 50M )
→ Replace compressor if abnormality found
Yes
1.Check Inverter PCB assembly U,V,W connector
Is compressor connection condition
No 2. Check wire disconnection and wiring
Wire connection
condition normal? 3. Check compressor terminal connection condition
(bad contact)
→ Reassemble if abnormality found
Yes

1.Check Inverter PCB assembly P,N connector


Is DC_Link Wire connection No connection condition
condition normal? 2.Check wire disconnection and wiring
→ Reassemble if abnormality found

Yes

No 1.Check Inverter PCB assembly Comp IPM heat sink


Is Comp IPM heat sink’s
joining condition
joining condition normal?
→ Reassemble if abnormality found

Yes

No Check Inverter PCB assembly IPM normality.


Is Inverter PCB assembly
→ Replace Inverter PCB assembly
normal?
if abnormality found.

Yes

Recheck power and installation condition

19
Error
Error Type Error Point Main Reasons
No.

22* 1. Overload operation (Pipe


Master clogging/Covering/EEV defect/Ref.
221 overcharge)
Slave1 Inverter PCB Assembly
2. Compressor damage(Insulation
222 AC Input Current Over Error input 3 phase power damage/Motor damage)
current is over limited
Slave2 3. Input voltage low
value(24A)
223 4. Power Line Misconnection
Slave3 5. Inverter PCB Assembly damage
224 (Input current sensing part)

I Error Diagnosis and Countermeasure Flow Chart

1. Check Pipe clogging/distortion


2. Check Covering (Indoor/Outdoor Unit)
Is installation No 3. Check EEV connector assemble condition/normal
condition normal?
operation
4. Check refrigerant pressure
→ Reassemble or manage if abnormality found
Yes
1. Check resistance between each terminal of compressor
Are the resistance (U-V:0.255 ±7%, V-W:0.255 ±7%, W-U:0.255 ±7%(75℃)
Between each phase and No
Compressor JQC068MA* JQC048MA*
insulation resistance of Inverter
Temp. 25℃ 75℃ 25℃ 75℃
compressor normal? U-V 0.216 ± 7% Ω 0.258 ± 7% Ω 0.302 ± 7% Ω 0.360 ± 7% Ω
V-W 0.216 ± 7% Ω 0.258 ± 7% Ω 0.302 ± 7% Ω 0.360 ± 7% Ω
W-U 0.216 ± 7% Ω 0.258 ± 7% Ω 0.302 ± 7% Ω 0.360 ± 7% Ω

2. Check insulation resistance between compressor


terminal and pipe (over 50M )
→ Replace compressor if abnormality found
Yes
1. Check Inverter PCB assembly U,V,W connector
connection condition
Is compressor
No 2. Check wire disconnection and wiring
Wire connection
3. Check compressor terminal connection condition
condition normal?
(bad contact)
→ Reassemble if abnormality found
Yes

Is Inverter PCB assembly No Check bridge diode in IGBTM of Inverter PCB


bridge diode joining condition normal? → joining again if abnormality found

Yes
Check
R~S/S~T/T~R phase voltage is 380V 10%
No
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V 10%
→ Check connection condition and wiring if power is
abnormal
Yes

Is Inverter PCB assembly No Check Inverter PCB assembly IPM normality


normal? → Replace Inverter PCB assembly

Yes

Recheck power and installation condition

20
Error
Error Type Error Point Main Reasons
No.

23*
Master
231 1. DC Link terminal misconnection/terminal
contact fault
Slave1
232 Inverter Compressor DC DC Voltage isn't charged 2. Condenser damage
Link Low Voltage after starting relay on 3. Comp PCB assembly damage
Slave2
233 (DC Link voltage sensing part)
Slave3 4. Input voltage low
234

I Error Diagnosis and Countermeasure Flow Chart

Are there any power wire No 1. Check R/S/T/N wiring conditions


connections normal? → Rewire them if abnormality found.

Yes

Check
R~S/S~T/T~R phase voltage is 380 V(-10 %)~415 V(+10 %)
No R~N/S~N/T~N phase voltage is 220 V(-10 %)~240 V(+10 %)
Is input voltage normal?
→ Check connection condition and wiring if power is
abnormal

Yes

1. Check joining condition of bridge diode and heatsink


No
Is bridge diode normal? 2. Check bridge diode
→ joining again or replacing bridge diode
if abnormality found

Yes

1.Check Inverter PCB assembly P,N connector


Is DC_Link Wire connection No connection condition
condition normal? 2. Check wire disconnection and wiring
→ Reassemble if abnormality found

Yes

Check joining condition of Inverter PCB assembly and


Is Inverter PCB assembly No
bridge diode
bridge diode joining condition normal?
→ joining again if abnormality found

Yes

No Check Inverter PCB assembly IPM normality.


Is Inverter PCB assembly
→ Replace Inverter PCB assembly if abnormality found.
normal?

Yes

Recheck power and installation condition

21
Error
Error Type Error Point Main Reasons
No.

1. Defective high pressure switch


24* 2. Defective fan of indoor unit or outdoor unit
Master 3. Check valve of compressor clogged
241 4. Pipe distortion due to the pipe damage
Slave1 5. Refrigerant overcharge
242 Excessive rise of discharge Compressor off due to the
6. Defective EEV at the indoor or outdoor unit.
pressure in outdoor com- high pressure switch in
Slave2 pressor 7. Covering or clogging(Outdoor covering dur-
outdoor unit ing the cooling mode /Indoor unit filter clog-
243
ging during the heating mode)
Slave3
8. SVC valve clogging
244
9. Defective outdoor PCB
10. Defective active path valve

I Error diagnosis and countermeasure flow chart

Is high pressure switch No


connector connected Connect securely
to PCB?*
Note 1)

Yes

Is high pressure switch No Is high pressure switch No


connector short Replace high pressure switch
terminal short?***
during off time?**
Note 2) Note 2)
Yes
Yes
Replace connecting cable

No
Is SVC valve open? Open SVC valve

Yes

Is this error appeared No Re-check momentary


again after reset? problem or not

Yes

Is high pressure No Replace PCB


more than 2500kPa CH24 : inverter compressor PCB
at manifold gauge? CH109~154 : sub unit PCB

Yes

Is high pressure of No
LGMV similar as Replace high pressure sensor
at manifold gauge?
Yes

Check pipe is blocked or


not and take measure

22
Error
Error Type Error Point Main Reasons
No.

25*
Master
251
Slave1 1. Input voltage abnormal (T-N, R-S, S-T, T-R)
Input voltage is over limited
252 Input Voltage high/low 2. Outdoor unit Inverter PCB assembly dam-
value of the product (304 V
age (input voltage sensing part)
Slave2 or less, 536 V or more)
3. N phase line disconnection
253
Slave3
254

I Error Diagnosis and Countermeasure Flow Chart

Are there any power wire No 1. Check R/S/T/N wiring conditions


connections normal? → Rewire them if abnormality found.

Yes

Check
R~S/S~T / T~R phase voltage is 380 V(-10 %) ~ 415 V(+ 10 %)
No R~N/S~N/T~N phase voltage is 220 V(-10 %) ~ 240 V(+ 10%)
Is input voltage normal?
→ Check connection condition and wiring if power is
abnormal

Yes

Is Inverter PCB assembly No


Check bridge diode in IGBTM of Inverter PCB
bridge diode joining condition normal?

Yes

No Replace Inverter PCB assembly.


Inverter PCB LED display error

Yes

Recheck power and installation condition

23
Error
Error Type Error Point Main Reasons
No.

26*
Master
1. Overload operation
261
(Pipe clogging/Covering/EEV defect/Ref.
Slave1 overcharge)
262 Inverter compressor starting Starting failure because of
2. Compressor damage
failure Error compressor abnormality
Slave2 (Insulation damage/Motor damage)
263 3. Compressor wiring fault
Slave3 4. ODU Comp PCB damage (CT)
264

I Error Diagnosis and Countermeasure Flow Chart

1. Check Pipe clogging/distortion


2. Check Covering (Indoor/Outdoor Unit)
Is installation No 3. Check EEV connector assemble condition/normal
condition normal? operation
4. Check refrigerant pressure
→ Reassemble or manage if abnormality found
Yes

Are there any power wire No 1. Check R/S/T/N wiring conditions


connections normal? → Rewire them if abnormality found.

Yes

1. Check resistance between each terminal of compressor


Are the resistance
No Compressor JQC068MA* JQC048MA*
Between each phase and
Temp. 25℃ 75℃ 25℃ 75℃
insulation resistance of Inverter U-V 0.216 ± 7% Ω 0.258 ± 7% Ω 0.302 ± 7% Ω 0.360 ± 7% Ω
compressor normal? V-W 0.216 ± 7% Ω 0.258 ± 7% Ω 0.302 ± 7% Ω 0.360 ± 7% Ω
W-U 0.216 ± 7% Ω 0.258 ± 7% Ω 0.302 ± 7% Ω 0.360 ± 7% Ω

2. Check insulation resistance between compressor


terminal and pipe (over 50M )
→ Replace compressor if abnormality found
Yes
1. Check Comp PCB assembly U,V,W connector
connection condition
Is compressor 2. Check wire disconnection and wiring
No
Wire connection 3. Check compressor terminal connection condition
condition normal? (bad contact)
→ Reassemble if abnormality found
Yes

No Check Inverter PCB assembly IPM normality


Is Inverter PCB assembly normal? → Replace Inverter PCB assembly

Yes

Recheck power and installation condition

24
Error
Error Type Error Point Main Reasons
No.

28*
Master
281
Slave1
282 1. Input voltage abnormal (R,S,T,N)
Inverter DC link high Inv PCB DC link voltage
2. ODU Comp PCB damage
Slave2 voltage error supplied over 780V
283 (DC Link voltage sensing part)
Slave3
284

I Error Diagnosis and Countermeasure Flow Chart

1. Check R/S/T/N wiring conditions


Are there any power wire No 2. Check Noise filter wiring conditions
connections normal?
→ Rewire them if abnormality found.

Yes
Check
R~S/S~T/T~R phase voltage is 380V 10%
No R~N/S~N/T~N phase voltage is 220V 10%
Is input voltage normal?
→ Check connection condition and wiring if power is
abnormal

Yes

No
Is Inverter PCB assembly Replace Inverter PCB assembly
normal?

Yes

Recheck power and installation condition

25
Error
Error Type Error Point Main Reasons
No.

29*
Master
1. Overload operation
291
(Pipe clogging/Covering/EEV defect/Ref.
Slave1 overcharge)
292 Inverter compressor over Inverter compressor input
2. Compressor damage(Insulation
current current is over 30A
Slave2 damage/Motor damage)
293 3. Input voltage low
Slave3 4. ODU Inverter PCB assembly damage
294

I Error Diagnosis and Countermeasure Flow Chart

1. Check Pipe clogging/distortion


2. Check Covering (Indoor/Outdoor Unit)
Is installation No 3. Check EEV connector assemble condition/normal
condition normal? operation
4. Check refrigerant pressure
→ Reassemble or manage if abnormality found
Yes

1.Check resistance between each terminal of compressor


Are the resistance
Between each phase and No Compressor JQC068MA* JQC048MA*
Temp. 25℃ 75℃ 25℃ 75℃
insulation resistance of Inverter U-V 0.216 ± 7% Ω 0.258 ± 7% Ω 0.302 ± 7% Ω 0.360 ± 7% Ω
compressor normal? V-W 0.216 ± 7% Ω 0.258 ± 7% Ω 0.302 ± 7% Ω 0.360 ± 7% Ω
W-U 0.216 ± 7% Ω 0.258 ± 7% Ω 0.302 ± 7% Ω 0.360 ± 7% Ω

2.Check insulation resistance between compressor terminal


and pipe (over 50M )
→ Replace compressor if abnormality found
Yes

1. Check Inverter PCB assembly U,V,W connector


Is compressor No connection condition
Wire connection 2. Check wire disconnection and wiring
condition normal? 3. Check compressor terminal connection condition
(bad contact)
→ Reassemble if abnormality found
Yes

Check
No R~S/S~T/T~R phase voltage is 380V ±10%
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V ±10%
→ Check connection condition and wiring if power is
abnormal
Yes

No Check Inverter PCB assembly IPM normality


Is Inverter PCB assembly normal? → Replace Inverter PCB assembly

Yes

Recheck power and installation condition

26
Error No. Error Type Error Point Main Reasons

32* 1. Temperature sensor defect of inverter com-


Compressor is off because
Master 321 Over-increase discharge pressor 1 discharge pipe
of over-increase discharge
Slave1 322 temperature of inverter com- 2. Refrigerant shortage / leak
temperature of inverter
Slave2 323 pressor 1 at main outdoor unit 3. EEV defect
compressor 1
Slave3 324 4. Liquid injection valve defect

33* 1. Temperature sensor defect of inverter com-


Compressor is off because
Master 331 Over-increase discharge pressor 2 discharge pipe
of over-increase discharge
Slave1 332 temperature of inverter com- 2. Refrigerant shortage / leak
temperature of inverter
Slave2 333 pressor 2 at main outdoor unit 3. EEV defect
compressor 2
Slave3 334 4. Liquid injection valve defect

I Error diagnosis and countermeasure flow chart

Is the amount of No No Change the amount of


Is there pipe crack
refrigerant normal? refrigerant
or trace of leakage?
[refer refrigerant part] (Charge additive amount)
Yes Yes

Weld / reconnect the cracked


portion and recharge refrigerant

Is the resistance of discharge No Replace discharge


temperature sensor normal?* temperature sensor

Yes
* Resistance value of discharge temperature sensor
10°C = 362kΩ, 25°C= 200kΩ, 50°C= 82kΩ, 100°C= 18.5kΩ
Is EEV in
outdoor unit normal No
at heating operation? Replace outdoor unit EEV
[refer electric
component part]
Yes

No Check another components


Is there pipe
and operation conditions
(strainer etc.) clogging?
/ Take measures
Yes

Replace strainer

27
Error
Error Type Error Point Main Reasons
No.
1. Defect of high pressure sensor
34* 2. Defect of indoor or outdoor unit fan
Error happens 3. Deformation because of damage of refrigerant pipe
Master because of 10 times 4. Over-charged refrigerant
341 successive compres- 5. Defective indoor / outdoor unit EEV
Over-increase of dis-
Slave1 sor off due to over- 6. When blocked
charge pressure of
342 increase of high pres- - Outdoor unit is blocked during cooling
compressor
Slave2 sure by high pressure - Indoor unit filter is blocked during heating
343 sensor 7. SVC valve is clogged
Slave3 8. PCB defect of outdoor unit
344 9. Indoor unit’s pipe temperature defect
10. Indoor unit pipe temperature sensor defect

I Error diagnosis and countermeasure flow chart


No
Is service valve opened ? Open service valve

Yes

Are communication No Check and repair communication


cable / pipe connection
cable / pipe connection
normal?

Yes

Is refrigerant No
amount normal? Adjust refrigerant amount
[refer refrigerant part]
Yes

Is fan normal?
(Indoor fan during heating No
Replace related parts
Outdoor fan during cooling)

Yes

Is filter blocked
(Heating:indoor, No Clean indoor filter (heating)
Cooling:outdoor /outdoor heat exchanger (cooling)?
heat exchanger)?
Yes

Is value of high pressure No


sensor same as Manifold Replace sensor of high pressure
value(Is it high actually)?

Yes

Check indoor unit LEV


Check indoor unit PCB
Check in/outdoor installation
condition
28
Error
Error Type Error Point Main Reasons
No.
1. Defective low pressure sensor
35* 2. Defective outdoor/indoor unit fan
Error happens 3. Refrigerant shortage/leakage
Master because of 3 times 4. Deformation because of damage of refrigerant pipe
351 successive compres- 5. Defective indoor / outdoor unit EEV
Excessive drop of
Slave1 discharge pressure sor off due to exces- 6. Covering / clogging
352 of compressor sive drop of low pres- (outdoor unit covering during the cooling mode/
Slave2 sure by the low pres-
indoor unit filter clogging during heating mode)
353 sure sensor
7. SVC valve clogging
Slave3 8. Defective outdoor unit PCB
354
9. Defective indoor unit pipe sensor

I Error diagnosis and countermeasure flow chart


Is service valve
Open service valve
opened?

Yes

No
Are communication cable/ check communication/
piping normal? piping correction.

Yes

No Is there pipe crack or trace No Adjust the amount of


Is amount of refrigerant
normal? of refrigerant leakage? refrigerant (Additive charge)

Yes Yes

Weld / reconnect the cracked


portion and recharge refrigerant

Is fan normal? No
(in heating outdoor fan, Check and replace related parts
in cooling indoor fan)
Yes

No
Is strainer Ok?* Replace the strainer

Yes

Are the values of manifold No


and low pressure sensor same? Replace the pressure sensor
( Is the low pressure value
actually low?)

Yes
* If the temperature difference between inlet and outlet of strainer
Check indoor / outdoor unit LEV is so large that frost or ice formation can be seen or confirmed
Check Indoor unit PCB
Check indoor / outdoor unit then clogging of strainer should be checked
installation conditions (Notice: it is not full ice forming of strainer, in case that there is
not at inlet portion but at outlet portion)
29
Error
Error Type Error Point Main Reasons
No.

40*
Master
401
1. Input voltage abnormal (T-N)
Slave1 Micom input voltage isn't
402 Inverter compressor CT 2. DC power part damage (DC 5V)
within 2.5V ±0.3V at initial
sensor error 3. Outdoor unit’s inverter PCB damage
Slave2 state of power supply
(CT sensing part)
403
Slave3
404

I Error Diagnosis and Countermeasure Flow Chart

1. Check R/S/T/N wiring conditions


Are there any power wire No 2. Check Noise filter wiring conditions
connections normal?
→ Rewire them if abnormality found.

Yes

Check
R~S/S~T/T~R phase voltage is 380V±10%
No
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V±10%
→ Check connection condition and wiring if power is
abnormal
Yes
No Replace Inverter PCB assembly
Is Inverter PCB assembly normal?

Yes

Recheck power and installation condition

30
Error No. Error Type Error Point Main Reasons
41*
1. Defective connection of the compressor1 discharge
(Inverter1)
Compressor1 dis- Sensor measurement pipe temperature sensor
Master 411
charge pipe tempera- value is abnormal 2. Defective discharge pipe compressor sensor of the
Slave1 412
ture sensor error (Open/Short) compressor1 (open/short)
Slave2 413
3. Defective outdoor PCB
Slave3 414
47*
1. Defective connection of the compressor1 discharge
(Inverter2)
Compressor2 dis- Sensor measurement pipe temperature sensor
Master 471
charge pipe tempera- value is abnormal 2. Defective discharge pipe compressor sensor of the
Slave1 472
ture sensor error (Open/Short) compressor1 (open/short)
Slave2 473
3. Defective outdoor PCB
Slave3 474

I Error diagnosis and countermeasure flow chart

Sensor connection to PCB No


Insert sensor connector to PCB properly
is normal?

Yes

Is the resistance of No
Replace sensor
sensor normal?*

Yes

Is sensor resistance No
value same as temperature Replace corresponding outdoor PCB
value of LGMV?
Yes

Replace corresponding sensor

* Error is generated if the resistance is more than 5 MΩ(open) and less than 2 kΩ (short)

Note: Standard values of resistance of sensors at different temperatures (5% variation)


10°C = 362kΩ : 25°C= 200kΩ : 50°C= 82kΩ : 100°C= 18.5kΩ

31
Error
Error Type Error Point Main Reasons
No.

42*
Master 421 Abnormal value of 1. Bad connection of low pressure sensor connector
Slave1 422 Sensor error of low sensor 2. Defect of low pressure sensor connector (Open/Short)
Slave2 423 pressure (Open/Short) 3. Defect of outdoor PCB
Slave3 424
43*
Master 431 Abnormal value of 1. Bad connection of high pressure sensor connector
Sensor error of high
Slave1 432 sensor 2. Defect of high pressure sensor connector (Open/Short)
pressure
Slave2 433 (Open/Short) 3. Defect of outdoor PCB
Slave3 434

I Error diagnosis and countermeasure flow chart

Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly?

Yes

After replacement of No
Replace corresponding
outdoor unit main PCB
pressure sensor
is the system normal?

Yes

END

32
Error No. Error Type Error Point Main Reasons

44* 1. Bad connection of air temperature connector


Master 441 Sensor error of
Abnormal value of
Slave1 442 outdoor air temper- 2. Defect of air temperature connector(Open/Short)
Slave2 443 sensor (Open/Short)
Slave3 444 ature 3. Defect of outdoor PCB

45* Piping temperature


Master 451 sensor error of heat Abnormal value of 1. Bad connection of air temperature connector
Slave1 452 exchanger in sensor 2. Defect of air temperature connector(Open/Short)
Slave2 453 master & slave out-
Slave3 454 door unit heat (Open/Short) 3. Defect of outdoor PCB
exchanger (A,B)
46*
Master 461 Compressor suc- 1. Bad connection of air temperature connector
Abnormal value of
Slave1 462 tion temperature 2. Defect of air temperature connector(Open/Short)
Slave2 463 sensor (Open/Short)
sensor error 3. Defect of outdoor PCB
Slave3 464

49* Outdoor Unit


Master 491 Outdoor Unit IGBTM 1. Bad connection of air temperature connector
Slave1 492 IGBTM Temperature Sensor 2. Defect of air temperature connector(Open/Short)
Slave2 493 Temperature Open or Short 3. Defect of outdoor PCB
Slave3 494 Sensor Fault

I Error diagnosis and countermeasure flow chart

Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly??

Yes

No
Is sensor value correct?* Replace sensor

Yes
* If value is 100kΩ ↑(open) or 100Ω ↓(short), error occurs

Replace corresponding NB: Resistance value of temperature sensor change according to


outdoor unit PCB temperature
It is normal if value shown as below (±5% error)
Sensor of air temperature: 10°C = 20.7kΩ : 25°C= 10kΩ : 50°C= 3.4kΩ
Sensor of piping temperature: 10°C = 10kΩ : 25°C= 5Ωk : 50°C= 1.8kΩ

Error No. Error Type Error Point Main Reasons

153* Outdoor Unit


Master 1531 Outdoor Unit Upper 1. Temperature Sensor Connecting Fault
Upper Heat
Slave1 1532 Heat Exchanger 2. Temperature Sensor(Open/Short)
Exchanger
Slave2 1533 Temperature Sensor 3. Main PCB Fault
Temperature
open or short
Slave3 1534 Sensor Fault
154* Outdoor Unit Low Outdoor Unit Low
Master 1541 1. Temperature Sensor Connecting Fault
Heat Exchanger Heat Exchanger
Slave1 1542 2. Temperature Sensor(Open/Short)
Temperature Sensor Temperature Sensor
Slave2 1543 Fault 3. Main PCB Fault
open or short
Slave3 1544

33
Error
Error Type Error Point Main Reasons
No.

50*
Master
501 1. Input Voltage abnormal (R,S,T,N)
Slave1 ODU 3phase power omis- Omitting one or more of 2. Check power Line connection condition
502 sion error R,S,T input power 3. Main PCB damage
Slave2 4. Inverter PCB input current sensor fault
503
Slave3
504

I Error Diagnosis and Countermeasure Flow Chart

Are there any power wire No 1. Check R/S/T/N wiring conditions


connections normal? → Rewire them if abnormality found.

Yes
Check
Is input voltage normal? R~S/S~T/T~R phase voltage is 380V±10%
No R~N/S~N/T~N phase voltage is 220V±10%
→ Check connection condition and wiring if power is
abnormal

Yes
1. Check R~N/S~N/T~N phase voltage is
220V±10%
Is Main PCB assembly No 2. Check Main PCB assemblywire
normal? disconnection and wiring
→ Reassemble if abnormality found
Yes

INV. PCB LED display error No Replace inverter PCB assembly.

Yes

Recheck power and installation condition

34
Error
Error Type Error Point Main Reasons
No.
1. 130% more than outdoor unit rated capacity
Over-Capacity 2. Wrong connection of communication
51* Sum of indoor unit capaci- cable/piping
(Sum of indoor unit capaci-
Master ty is more than outdoor ty exceed outdoor unit 3. Control error of slave outdoor unit Dip switch
511 capacity) capacity specification 4. Power supply defect of slave unit PCB
5. Defect of outdoor unit PCB

I Error diagnosis and countermeasure flow chart

Is capacity sum of Are quantity and capacity


No No Check communication cables
indoor units less than of indoor units installed between indoor and outdoor
130% of outdoor unit same as the data of LGMV? units
capacity at LGMV?
Yes
Yes
Adjust the capacity of indoor
Check following and outdoor unit
dip S/W setting is on
No
Slave1: No.6 Adjust corresponding DIP switch
Slave2: No.7
Slave3: No.6,7

Yes

Is power of Slave PCB No No Supply main


Is main power really supplied?
On? (Check LED blinking) power again
(Terminal Block T-N)

Yes Yes

Check and replace PCB,


Line Fuse, Transformer

Is communicationmission
No
cables between outdoor units Re-connect
connected correctly?*

Yes

Is error code released


No
in order(Slave2➠Slave1➠Main) Replace Main or Slave PCB
after power reset?

Yes

End

* In order to check communication cables between outdoor units,


check in order as below : PCB connectors ➠ terminal block ➠ communication cables

35
Error
Error Type Error Point Main Reasons
No.

52*
Communication error Main PCB of Master unit 1. Power cable or communication cable is not
Master 521 between of Master unit can’t connected
Slave1 522 (Comp1/Comp2 PCB receive signal from 2. Defect of outdoor Main PCB or
Slave2 523
  Main PCB) Comp1/Comp2 controller Comp1/Comp2 PCB
Slave3 524

I Error diagnosis and countermeasure flow chart

Is communication
LED (Yellow) of No Is noise filter or Inverter PCB’S
Noise filter or Fuse change
Inverter 1 / Inverter 2 line fuse normal?
PCB on?
Yes

No
Is communication cable
Re-connect communication cable Change Inverter PCB
connected correctly?

Yes

No
Is Main PCB normal? Replace Main PCB

Yes

Replace Comp1/Comp2 PCB

* The method of checking Main PCB and Inverter 1 / Inverter 2 PCB (If normal, communication LED blinks)

36
Error
Error Type Error Point Main Reasons
No.

1. Communication cables are not connected between


External PCB and indoor PCB
2. Communication cables are not connected between
Communication error In case Main PCB can’t Main PCB and External PCB
53*
receive signal from indoor 3. Communication cables are not connected between
Master (Indoor unit   Main PCB)
unit Main PCB and Communication PCB
531 4. Communication cables are short/open
5. Indoor PCB power off
6. Defect of outdoor Main/Communication/indoor PCB
7. Communication wire connection fault

I Error diagnosis and countermeasure flow chart

Is power supplied No
to indoor PCB? Supply power

Yes 1. Check communication cable between External and indoor PCB


→ Re-connect communication cable
2. Check communication cable between Cycle and External PCB
No → Re-connect communication cable
Is communication cable
3. Check communication cable between Cycle and Communication PCB
connected correctly?
→ Re-connect communication cable
4. Check communication cable soldering correctly
Yes → Replace communication cable

Are quantity of indoor No


1. Is indoor unit quantity correct after auto addressing
Units installed same as
→ Check Communication PCB
The data of LGMV?
2. Check communication PCB LED blinking
Yes → Replace communication PCB
3. Auto addressing after replace Communication PCB
Check communication cable
→ Check outdoor Main PCB
and installation

In case of CH53, almost happened with CH05, the indoor units not operated actually are normal so check with same
method of CH05. and additionally check as shown as below and above flow chart
• Although the quantity of indoor units installed is same as LGMV data there may be a few indoor units with which the
number of communication is not increased with LGMV
• Although the quantity of indoor units installed is not same as LGMV data, and if communication of the indoor unit dis-
played at LGMV is done well then the indoor unit suspected to have some problem (and is not appear at LGMV) may
have following problems
Πwrong connection of communication cable or power cable
 fault of power / PCB / communication cable
Ž duplication of indoor unit number
• If communication is not doing well wholly then the Auto Addressing is not done
• The case that CH53 appear at indoor unit also Auto Addressing is not done so indoor unit address may be duplicated

* After replacement of indoor unit PCB, Auto Addressing should be done, if central controller is installed then the
central control address also should be input.
In case that only communication PCB is replaced above process is not needed

37
Error
Error Type Error Point Main Reasons
No.

57* 1. Bad Connection Between Comp PCB and


Master 571 Failing to receive inverter Comp PCB
Communication error : Main
Slave1 572 signal at main PCB of 2. Communication Wire Noise Effect
PCB --> Inverter PCB
Slave2 573 Outdoor Unit 3. ODU Main PCB Damage
Slave3 574 4. ODU Main PCB Damage

I Error diagnosis and countermeasure flow chart


Are there any No
communication wire 1. Check communication wiring conditions
connections normal? 2. Check connector conditions
→ Rewire them if abnormality found.
Yes

Is Inverter PCB No
assembly 1. Replace Inverter PCB
normal?

Yes

Is there any error Yes 1. Replace Main PCB


when power reset?

No

Recheck power and


installation condition

38
Error No. Error Type Error Point Main Reasons

60*
1. EEPROM contact defect/wrong insertion
Master 601 Inverter PCB EEPROM Access error
2. Different EEPROM Version
Slave1 602 EEPROM error and Check SUM error
3. ODU Inverter PCB assembly damage
Slave2 603
Slave3 604

I Error Diagnosis and Countermeasure Flow Chart

1.Check EEPROM insert direction/connection condition


No
Is EEPROM insertion normal? 2.Check EEPROM Check SUM
→ Replace if abnormality found

Yes

No Replace Inverter PCB assembly


Is Inverter PCB assembly normal?

Yes

Recheck power and installation condition

39
Error No. Error Type Error Point Main Reasons

1. Inverter PCB IGBTM Connection Condition


62*
Abnormal
Master 621
Inverter PCB Heatsink Heatsink Temperature 2. Outdoor Unit Fan Motor Operation Abnormal
Slave1 622
Temperature High is Over 90°C 3. Outdoor Unit Inverter PCB Assembly Defect
Slave2 623
4. Overload Operation (Pipe Clogging/ Covering/EEV
Slave3 624
Defect/Ref. Overcharge)

I Error diagnosis and countermeasure flow chart

1. Check Pipe Clogging/ Distortion


2. Check Covering (Outdoor/Indoor Unit)
Is Installation No 3. Check EEV Connector Assemble Condition/Normal Operation
Condition Normal? 4. Check Refrigerant Pressure
5. Check Power Wire/ Connection Condition
Yes Reassemble or Manage if abnormality Found

No
Inverter PCB IGBTM Connection 1. Check Inverter PCBA Screw Connection Condition
Condition Normal? Reassemble or Manage if abnormality Found

Yes

No
1. Check Outdoor Unit Fan Motor Operation or Lock
Is ODU Fan Motor Normal?
Reassemble or Manage if abnormality Found

Yes

No
Is Inverter PCB assembly 1. Reset
Normal? Replace Inverter PCB Assembly

Yes
Recheck Power and
Installation Condition

40
Error No. Error Type Error Point Main Reasons

65*
Master
651
Slave1 Abnormal sensor resis- 1. Defective temperature sensor connection
Inverter PCB Power
652 tance value 2. Defective temperature sensor (Open / Short)
Module sensor error
Slave2 (Open/Short) 3. Defective outdoor unit PCB
653
Slave3
654

I Error diagnosis and countermeasure flow chart

Is temperature sensor No
connector connections Connect sensor connector to PCB
are normal?
Yes

Is the value of temperature No


Replace sensor
sensor resistance normal?*

Yes

Replace outdoor unit PCB

* Sensor resistance 100 kΩover (open) or 100 Ω below (short) will generate error
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ
Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ

41
Error No. Error Type Error Point Main Reasons

1. Fan motor defect / assembly condition


67* abnormal
Fan RPM is 10RPM or less 2. Wrong connection of fan motor connector
Master 671 for 5 sec. when ODU fan (U,V,W output)
Fan Lock Error
Slave1 672 starts or 40 RPM or less
3. Reversing rotation after RPM target apply
Slave2 673 after fan starting.
4. Fan PCB assembly defect
Slave3 674
5. Fan lock by Heavy Snowfall.

I Error Diagnosis and Countermeasure Flow Chart

Is ODU Fan Motor Assemble No Check ODU Fan Motor assemble condition and fan locking
condition normal? → Reassemble or replace if abnormality found

Yes

1. Check resistance between each phase(U,V,W) of ODU


No fan motor terminal (16.8Ω ±5% at 75°…)
Is ODU Fan Motor normal? 2. Check insulation resistance between ODU fan motor
terminal(U,V,W)
→ Replace fan motor if abnormality found
Yes

Check wiring between ODU fan motor and fan PCB


Is wire connection of No ( Check if and Motor output terminal color is matched)
ODU Fan Motor wire normal? → Reassemble if abnormality found

Yes

No Replace Fan PCB assembly


Is Fan PCB assembly normal?

Yes

Recheck power and installation condition

42
Error No. Error Type Error Point Main Reasons

71*
Micom input voltage
Master 711
isn’t within 2.5V±0.3V 1. Input Voltage is abnormal (R-N)
Slave1 712 PFC CT Sensor Error
at initial state of power 2. ODU Inverter PCB damage (CT sensing part)
Slave2 713
supply
Slave3 714

I Error diagnosis and countermeasure flow chart

No 1. Check R/S/T/N wiring conditions


Are there any power wire
2. Check noise filer wiring conditions
Connections normal?
Rewire them if abnormality found

Yes

No Check
R~S/S~T/T~R phase voltage 380V±10%
Is input voltage normal?
R~N/S~N/T~N phase voltage 200V±10%
Check connection condition and wiring if power is abnormal

Yes

No
Is Inverter PCB
Assembly normal? 1. Replace Inverter PCB

Yes

Recheck Power and


Installation Condition

43
Error No. Error Type Error Point Main Reasons

75*
Offset of Micom which 1. Input Voltage is abnormal (not 15V)
Master
which sense the fan 2. Fan PCB assembly defect
Slave1 Fan CT Sensor Error
motor phase current is 3. Power wire open and connecting fault
Slave2
not 2.5V ± 0.3V 4. Inverter PCB assembly defect
Slave3

I Error diagnosis and countermeasure flow chart

No 1. Check 15V input power wiring conditions


Is input voltage normal? Rewire them if abnormality found

Yes

No
Is Fan PCB normal? 1. Replace Fan PCB

Yes

No
Is there any error 1. Check Fan PCB IPM normal or not.
When power reset? Replace Fan PCB

Yes

Recheck Power and


Installation Condition

44
Error No. Error Type Error Point Main Reasons

77* 1. Overload operation


Master 771 2. Fan Motor defect
Slave1 772 Fan Over Current Error Output current is over 7A. 3. Fan PCB assembly defect
Slave2 773 4. Fan Motor connector insert defect
Slave3 774
5. Condenser icing or blocking

I Error Diagnosis and Countermeasure Flow Chart

Is installation No Check ODU fan motor assemble condition and locking


condition normal? → Reassemble or replace if abnormality found

Yes
1. Check resistance between each motor output terminal
Are the resistance No Chassis UXA UXB
Between each phase and insulation
resistance of motor output Resistance 15 ± 7 % Ω 13 ± 7 % Ω
terminal normal? 2. Check insulation resistance between ODU fan motor terminal(U,V,W) and pipe (over 100M )
→ Replace fan motor if abnormality found
Yes

No 1.Check if color of motor output terminal(U,V,W) connector matched with PCB’s


Is motor wire connection 2.Check wire disconnection and wiring
condition normal?
→ Reassemble or replace if abnormality found

No
Is Fan PCB assembly normal? 1. Check fan PCB assembly IPM normal
→ Replace Fan PCB assembly

Yes

Recheck power and


installation condition

45
Error No. Error Type Error Point Main Reasons

79* 1.Fan motor defect/ assemble condition abnor-


Master 791 mal
Fan Starting Failure
Slave1 792 Fan Motor initial starting failure 2.Fan motor connector misconnection(U,V,W
Error
Slave2 793 ouput)
Slave3 794 3.Fan PCB defect

I Error Diagnosis and Countermeasure Flow Chart

No
Is fan motor assemble Check ODU fan motor assemble condition and locking
condition normal? → Reassemble or replace if abnormality found

Yes
1.Check resistance between each motor output terminal
Are the resistance No Chassis UXA UXB
Between each phase and insulation
resistance of motor output Resistance 15 ± 7 % Ω 13 ± 7 % Ω
terminal normal?
2. Check insulation resistance between ODU fan motor terminal(U,V,W) and pipe (over 100M )
→Replace fan motor if abnormality found

No
Is fan motor connection
1. Check if color of motor output terminal(U,V,W) connector matched with PCB’s
condition normal?
2. Check wire disconnection and wiring
→ Reassemble or replace if abnormality found

No
Check fan PCB assembly IPM normal
Is fan PCB assembly normal?
→ Replace Fan PCB assembly

Yes

Recheck power and


installation condition

46
Error No. Error Type Error Point Main Reasons

86*
Master 861
1. No EEPROM
Slave1 862 Main PCB EEPROM EEPROM Access Error
Slave2 863 2. EEPROM wrong insertion
Slave3 864

I Error Diagnosis and Countermeasure Flow Chart

No
Is EEPROM assemble
Reset after checking EEPROM assemble condition
condition normal?

Yes

No
Correct check sum Replace Correct EEPROM

Yes

Recheck power and


installation condition

47
Error No. Error Type Error Point Main Reasons

87*
Master 871 Error occurs when checking the 1.EEPROM bad contact/wrong insertion
Fan PCB EEPROM
Slave1 872 EEPROM checksum as initializing 2.EEPROM Version is different
Error
Slave2 873 after power is supplied 3.ODU fan PCB assembly damage
Slave3 874

I Error Diagnosis and Countermeasure Flow Chart

No 1.Check EEPROM insertion direction/connection condition


Is EEPROM insertion normal? 2.Check EEPROM checksum
→ Replace EEPROM if abnormality found

Yes

No
Is Fan PCB assembly normal? Replace fan PCB assembly

Yes

Recheck power and


installation condition

48
Error No. Error Type Error Point Main Reasons

104*
Master
1041
Slave1 Communication Master displays ODU number 1.Loose connection of power cable/ communi-
1042 Error Between which is not communicated. cation cable¸(Open/Short)
Slave2 Outdoors Slave displays own error number 2.Defect of each outdoor unit PCB
1043
Slave3
1044

I Error Diagnosis and Countermeasure Flow Chart

Is communication No
cable installed Connect communication cable
normally?

Yes

Is Slave Unit Dip SW No


Dip SW setting
setting done?

Yes

Is Main PCB power No


Connect power cable
supplied?

Yes

Replace Main PCB

*Slave Outdoor unit setting

DIP Switch setting Remarks

Slave1 setting

Slave2 setting

Slave3 setting

49
Error No. Error Type Error Point Main Reasons

105*
Master
1051 1. Wrong connection between Comp and Fan
Slave1 Communication error
Fan controller didn't receive signal PCB
1052 (Fan PCB £ Inverter
Slave2 from Inverter PCB 2. Fan PCB power not supplied
PCB)
1053 3. ODU Comp/Fan PCB defect
Slave3
1054

I Error Diagnosis and Countermeasure Flow Chart

Is fan PCB communication No


1. Check communication cable between Inverter PCB and fan PCB
LED(yellow) blinking → Reconnect or replace wire if abnormality found
normally?

Yes

Is Inverter PCB No
communication LED(yellow) Check communication cable between Inverter PCB and fan PCB
blinking normally? → Reconnect or replace wire if abnormality found

Yes
No
No
Is fan PCB assembly normal? Fan PCB assembly

Yes Yes

Recheck power and


installation condition

Replace inverter PCB assembly

50
Error No. Error Type Error Point Main Reasons

106*
Master 1. Overload operation (Pipe clogging/Covering/EEV
1061
Slave1 defect/Ref. overcharge
ODU Fan PCB IPM protection circuit activation
1062 2. ODU fan motor assemble condition abnormal
Slave2 IPM Fault (over current)
(Coil disconnection/Short/Insulation damage)
1063
Slave3 3. Fan PCB assembly defect
1064

I Error Diagnosis and Countermeasure Flow Chart

No
Is fan motor assemble Check ODU fan motor assemble condition and locking
condition normal? → Reassemble or replace if abnormality found

Yes
No 1.Check fan motor U,V,W connector connection condition
Is fan motor wire connection → Reassemble wire if abnormality found
condition normal? 2.Check fan motor wire disconnection
→ Replace ODU fan motor if abnormality found
Yes

No 1.Check fan PCB connector condition


Is fan PCB assemble → Reassemble if abnormality found
condition normal? 2.Check assemble condition between fan PCB and Heatsink
→ Reassemble heatsink if abnormality found
Yes

No

Is fan PCB assembly normal? Replace fan PCB assembly

Yes

Recheck power and


installation condition

51
Error No. Error Type Error Point Main Reasons

107*
Master 1. Overload operation (Pipe clogging/Covering/EEV
1071
Slave1 Fan Control part defect/Ref. overcharge
Fan PCB not received the data
1072 communication 2. ODU fan motor assemble condition abnormal
Slave2 from Main PCB
defect (Coil disconnection/Short/Insulation damage)
1073
Slave3 3. Fan PCB assembly defect
1074

I Error Diagnosis and Countermeasure Flow Chart

No
Is fan motor assemble Check ODU fan motor assemble condition and locking
condition normal? → Reassemble or replace if abnormality found

Yes
No 1.Check fan motor U,V,W connector connection condition
Is fan motor wire connection → Reassemble wire if abnormality found
condition normal? 2.Check fan motor wire disconnection
→ Replace ODU fan motor if abnormality found
Yes

No 1.Check fan PCB connector condition


Is fan PCB assemble → Reassemble if abnormality found
condition normal? 2.Check assemble condition between fan PCB and Heatsink
→ Reassemble heatsink if abnormality found
Yes

No

Is fan PCB assembly normal? Replace fan PCB assembly

Yes

Recheck power and


installation condition

52
Error No. Error Type Error Point Main Reasons

1. Wrong wiring between Inverter PCB and


107*
Master Fan PCB
1071 Fan DC Link Low Fan PCB DC link voltage supplied 2. Fan PCB assembly defect
Slave2
1072 Voltage Error below 380V 3. Reactor terminal contact defect
Slave3 4. DC link terminal wiring/contact defect
1074
5. Bridge diode defect

I Error Diagnosis and Countermeasure Flow Chart

No
Is wiring between fan motor 1. Check DC_Link Wire connection
and PCB normal? 2. DC_Link
→ Replace wire if abnormality found
Yes

No
Measure DC_Link voltage
Is DC_Link voltage normal?
→ Check Inverter PCB if voltage is below 380V

Yes

No
Is Fan PCB assembly normal? Replace fan PCB assembly

Yes

Recheck power and


installation condition

53
Error No. Error Type Error Point Main Reasons

113*
Master
1131
Slave1 Outdoor unit liquid Abnormal sensor resis- 1. Defective temperature sensor connection
1132 pipe (condenser) tem- tance value 2. Defective temperature sensor (Open / Short)
Slave2 perature sensor error (Open/Short) 3. Defective outdoor unit PCB
1133
Slave3
1134
114*
Master
1141
Outdoor Unit
Slave1 Abnormal sensor resis- 1. Defective temperature sensor connection
Subcooling Inlet
1142 tance value 2. Defective temperature sensor (Open/Short)
Temperature Sensor
Slave2 (Open/Short) 3. Defective outdoor PCB
Error
1143
Slave3
1144
115*
Master
1151
Outdoor Unit
Slave1 Abnormal sensor resis- 1. Defective temperature sensor connection
Subcooling Outlet
1152 tance value 2. Defective temperature sensor (Open/Short)
Temperature Sensor
Slave2 (Open/Short) 3. Defective outdoor PCB
Error
1153
Slave3
1154

 Error diagnosis and countermeasure flow chart

Is temperature sensor No
connector connections Check and correct connection
are normal?
Yes

Is the value of temperature No


Replace sensor
sensor resistance normal?*

Yes

Replace outdoor unit PCB

* Sensor resistance 100 kΩover (open) or 100 Ω below (short) will generate error
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ
Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ

54
Error No. Error Type Error Point Main Reasons

145*
Master
1451 Communication Error 1. Power cable or communication
Slave1 between Cycle controller of Master unit of cable is not connected
1452 Master unit can’t receive signal
Slave2 (Main PCB  External 2. Defect of outdoor Cycle/External
from External controller
1453 PCB) PCB
Slave3
1454

 Error diagnosis and countermeasure flow chart


Is communication LED No
(Yellow) of Re-connect Power cable
External PCB on?
Yes

No
Is communication cable Re-connect communication cable
connected correctly?

Yes

No
Is Main PCB normal Replace Main PCB

Yes

Replace External PCB

* The Method of checking Main PCB and External PCB (If normal, communication LED blinks)

55
Error No. Error Type Error Point Main Reasons

Check liquid bypass


1. Individual power of indoor unit is
open during operation
Discharge 2. Indoor unit EEV fault(ref. leak
superrheat is much)
CH150 Discharge superheat low
under 3℃ 3. Indoor unit EEV connector discon-
(liquid back) nected.
4. SC EEV fault(ref. leak much)
5. Liquid pipe – gas pipe direct con-
nection

 Error diagnosis and countermeasure flow chart


Is there indoor unit No No Check liquid pipe
Is SC EEV or SC
which leaks ref. – gas pipe direct connection
circuit leaks?
much1)?

Yes

Change SC EEV or SC EEV


assembly
Yes

Is EEV head(Coil) No Assemble again or change


assembly normally? EEV head(coiL)

Yes

Is EEV connector No
Connect EEV connector
connected normally?

Yes

Change EEV assembly

1) Ref. leakage much


: Both Pipe in, pipe out temp. is under 10℃
during unit is off(EEV 40pls)
Also, big refrigerant flow noise occured

56
Error
Error Type Error Point Main Reasons
No.

1. Wrong operation of 4way valve because of sludge


etc. inflow
151* Function error of outdoor Function error of 4way 2. No pressure difference because of compressor
Master 4way (reversing valve) (reversing valve) in Main or fault
1511 Slave outdoor units
3. Wrong installation of In/outdoor common pipe
4. Defect of 4way valve

 Error diagnosis and countermeasure flow chart

Is 4-Way valve connecter No


connection are properly Reconnect it
connected?
Yes

Is 4 Way valve coil No


Change 4 Way valve coil
resistance normal?*

Yes

Is 4 way valve coil connected No


Re-insert 4 way valve coil
to 4 way valve normally?**

Yes

In case of more than


2 units, does master outdoor No
Refer to CH 51 & make measure
unit recognize
ø as more
than 2 units? ***

Yes

After reset, can we


check supply voltage at PCB No
Replace outdoor unit PCB
when starting heating
mode operation****

Yes

No Check and replace compressor,


Is compressor working
Magnet switch, corresponding PCB
normally?
[refer electric component part]
Yes

After opposite
mode operation to present No If the same error is occurred in
mode, is the same error near future replace 4way valve
occurred again?
Yes

Replace 4 way valve*****

57
Error No. Error Type Error Point Main Reasons

182*
Master 1821 Communication Error Failure Receiving Signal
1. Failure Receiving Signal Between
Slave1 1822 Between Main and Sub Between Main and Sub
Main and Sub Micom
Slave2 1823 Micom of External PCB Micom
Slave3 1824

 Error diagnosis and countermeasure flow chart

Communication Between
Main-Sub Micom
LED (Yellow) Blinking
No

’ the
Press
Rest Button *

No

No
Replay
Replace External PCB
On-boarding *

58
Error No. Error Type Error Point Main Reasons

193*
Master
1931 1. Fan PCBA IPM Connection Condition Abnormal
Slave1 2. Outdoor Unit Fan Motor Operation Abnormal
Fan PCB Heatsink Heatsink Temperature
1932 3. Outdoor Unit Fan PCB Assembly Defect
Temperature High is Over 90°C
Slave2 4. Overload Operation (Pipe Clogging/ Covering/EEV
1933 Defect/Ref. Overcharge)
Slave3
1934

 Error diagnosis and countermeasure flow chart

1. Check Pipe Clogging/ Distortion


2. Check Covering (Outdoor/Indoor Unit)
Is Installation No 3. Check EEV Connector Assemble Condition/Normal Operation
Condition Normal? 4. Check Refrigerant Pressure
5. Check Power Wire/ Connection Condition
Yes Reassemble or Manage if abnormality Found

No
Fan PCB IPM Connection 1. Check Fan PCBA Screw Connection Condition
Condition Normal? Reassemble or Manage if abnormality Found

Yes

No
1. Check Outdoor Unit Fan Motor Operation or Lock
Is ODU Fan Motor Normal?
Reassemble or Manage if abnormality Found

Yes

No
Is Fan PCB assembly 1. Reset
Normal? Replace Fan PCB Assembly

Yes

Recheck Power and


Installation Condition

59
Error No. Error Type Error Point Main Reasons

194*
Master
1941
Slave1 Outdoor unit Fan PCB Outdoor unit Fan PCB 1. Defective temperature sensor connection
1942 heatsink temperature heatsink temperature 2. Defective temperature sensor (Open / Short)
Slave2 sensor error sensor error 3. Defective outdoor unit PCB
1943
Slave3
1944

 Error diagnosis and countermeasure flow chart

Is temperature sensor No
connector connections Check and correct connection
are normal?
Yes

Is the value of temperature No


Replace sensor
sensor resistance normal?*

Yes

Replace outdoor unit PCB

60
Error
Error type Error point Main reasons
No.

1. HR unit’s power cable or communication cable connec-


After the auto operation,
tion defect
if the number of the
2001 2. After auto-addressing, wrong address setting of the
indoor units detected is
Master Pipe detection error indoor unit (Defective indoor power / transmission error
different from the number
21  001 communicating indoor
and PCB defect)
unit 3. Wrong setting of the HR unit’s rotary switch or dip switch
4. HR unit PCB defect

HR: Heat Recovery

 Error diagnosis and countermeasure flow chart


1) Check the periodic blinking of the HR unit’s green LED (transmission LED )
2) When green LED (communication LED) of HR unit blinks regularly,
2.1) Check input power of HR unit.(220V±10%)
2.2) After reset of power of outdoor, wait for more than 30 minutes, temperature of pipes will be cool down then,
do auto-addressing
2.2) While power of HR unit is on, check total indoors display ‘CH05’ or not.(Refer to CH05)
3) When green LED (communication LED) of HR unit blinks regularly, Check setting of rotary switch and dip
switch, After reset of power of outdoor and HR unit, wait for more than 30 minutes, temperature of pipes will be
cool dow then, do auto-addressing *
4) If indoor unit quantity is different between installed quantity and quantity which check thru piping searching,
check pipe installation condition
Outdoor unit  HR unit  Indoor unit
5) If indoor unit has not been connected to #1 valve of HR unit, set pipes of HR unit manually**
6) If it is not applied as above, set pipes of HR unit as manual
[NB] How to check display method of outdoor main PCB 7-segment ?:
'88'  Indoor qty which check thru 'Auto-Addressing'  '88'  Indoor qty which check thru ‘piping checking'

61
Error No. Error type Error point Main reasons

• Defective temperature sensor connection


HR unit liquid pipe tem- Abnormal value of sensor • Defective temperature sensor
201C#HR
perature sensor error measurement (Open / Short) (Open/Short)
• Defective outdoor unit PCB

Error No. Error type Error point Main reasons

HR unit • Defective temperature sensor connection


Sub-cooling inlet pipe Abnormal value of sensor • Defective temperature sensor
202C#HR
temperature sensor measurement(Open / Short ) (Open/Short)
error • Defective outdoor unit PCB

Error No. Error type Error point Main reasons

HR unit • Defective temperature sensor connection


Sub-cooling discharge Abnormal value of sensor • Defective temperature sensor
203C#HR
pipe temperature sensor measurement(Open / Short) (Open/Short)
error • Defective outdoor unit PCB

 Error diagnosis and countermeasure flow chart


1) Check connection condition of temperature sensor and lead cable
2) Is value of temperature sensor normal? If not replace sensor
- Piping temperature sensor : 10°C = 10kΩ : 25°C= 5kΩ : 50°C= 1.8kΩ
3) If connection of sensor and value is correct, replace outdoor unit PCB

 HR unit error display No.


HR Unit HR #1 HR #2 HR #3 HR #4 HR #5 HR #6 HR #7 HR #8 HR #9 HR #10 HR #11 HR #12 HR #13 HR #14 HR #15 HR#16
Error display C01 C02 C03 C04 C05 C06 C07 C08 C09 C10 C11 C12 C13 C14 C15 C16

 Example of HR unit error display.


#16 HR unit Sub-cooling inlet pipe temperature sensor error 200  C16 (Repeat)
C: HR unit
#: HR unit Nuber

62
Error No. Error type Error point Main reasons

1. Defective connection in HR unit power


Transmission error supply and communication connection
204C#HR Transmission error between
between the HR unit 2. Wrong setting of the HR unit rotary
the HR unit and outdoor unit switch and dip switch
and outdoor unit
3. Defective HR unit PCB

 Error diagnosis and countermeasure flow chart


1) Check connection between power cables and communication cables, check communication green LED blink of
HR unit PCB
2) If communication green LED blink of HR unit PCB is normal, check setting of rotary switch of HR unit and dip
switch(Refer to CH200),
Reset power of outdoor and HR unit
(If communication error of HR unit occurs, it can’t be released until reset of outdoor power)
3) If communication green LED blink of HR unit PCB is abnormal(not blinking,just on), check communication condi-
tion of total indoor units(Refer to CH05)
If communication green LED blink of HR unit PCB is abnormal(not blinking, just on) even if communication con-
dition is normal, replace HR unit PCB
[NB] If Indoor units/communication cables of HR unit and cables of power 220V has been changed each other,
communication parts and indoor will be burnt

63
Error No. Error Type Error Point Main Reasons

1. RS-485 communication wiring defect


2. Communication defect between
242* Network error of central con-
Network Error remote controller and indoor unit
Master troller
2421 3. RS-485 dip switch setting error
4. Indoor unit addressing ssetting error
on central controller

 Error diagnosis and countermeasure flow chart

Are there any No


communication wire of
RS-485 connections 1. Reconnect RS-485 communication wire
normal?
Yes

Are there any overlap of Yes


IDU address? Reset the overlap of IDU address for single address

No

Is Simple central No
controller setting 1. Set the slave mode with Simple central controller after reset.
normal?

Yes

Recheck power and


installation condition

64