Error Numbers
- This document describes how to conduct a self-diagnosis on the product and lists possible failure types.
- In the LGMV error number field, a failure will be indicated by a code listed in the following table.
- If two or more failures occur at the same time, they are listed by order of their error numbers.
- If an error occurred and was then fixed, the error code will not be displayed.
Error Indication
- The error number on the LGMV screen is displayed along with the error number shown on the outdoor unit and
the unit number.
- Indoor unit errors are displayed on the screen of the unit. Outdoor unit and general operation errors are displayed
at the top right of the LGMV screen.
- When an error occurs, you can move your mouse over the error number and click it to view troubleshooting
methods.
- You will be provided with the meaning of the errors, and possible causes, as well as troubleshooting methods for
resolving those errors. Follow the troubleshooting guide to fix the errors.
Communication error : outdoor unit Failing to receive outdoor unit signal in indoor unit
0 5 -
indoor unit PCB
Indoor unit related error
Outlet pipe temperature sensor of Outlet pipe temperature sensor of indoor unit is
0 6 -
indoor unit open or short
Hydro Kit Hot water storage tank
0 8 - Pipe temperature sensor is open or short
Temperature sensor
In case when the serial number marked on EEP-
0 9 - Indoor EEPROM Error
ROM of Indoor unit is 0 or FFFFFF
Disconnecting the fan motor connector / Failure of
1 0 - Poor fan motor operation
indoor fan motor lock
Communication error : System boiler
1 1 - Failing to receive Inv. PCB signal in indoor unit
Indoor unit £ Inv.PCB
1 4 - Hydro Kit Indoor unit Flow switch error Flow switch flow detection error
2
Display Title Cause of Error
Slave1 Outdoor Unit Input Voltage Slave1 Outdoor Unit input voltage is over 487V or
High/ Low Voltage below 270V (ARUM***LTE5)
Slave1 Outdoor Unit input voltage is over 289V or
2
below 173V (ARUM***BTE5)
Slave1 Outdoor Unit input voltage is over 506V or
below 414V (ARUM***DTE5)
Slave2 Outdoor Unit Input Voltage Slave2 Outdoor Unit input voltage is over 487V or
High/ Low Voltage below 270V (ARUM***LTE5)
Slave2 Outdoor Unit input voltage is over 289V or
2 5 3
below 173V (ARUM***BTE5)
Slave2 Outdoor Unit input voltage is over 506V or
below 414V (ARUM***DTE5)
Slave3 Outdoor Unit Input Voltage Slave3 Outdoor Unit input voltage is over 487V or
High/ Low Voltage below 270V (ARUM***LTE5)
4 Slave3 Outdoor Unit input voltage is over 289V or
below 173V (ARUM***BTE5)
Slave3 Outdoor Unit input voltage is over 506V or
below 414V (ARUM***DTE5)
1 Master Outdoor Unit Inverter The First Start Failure by Master Outdoor Unit
Compressor Start Failure Inverter Compressor Abnormality
2 Slave1 Outdoor Unit Inverter The First Start Failure by Slave1 Outdoor Unit
Compressor Start Failure Inverter Compressor Abnormality
2 6
Outdoor unit related error
3 Slave2 Outdoor Unit Inverter The First Start Failure by Slave2 Outdoor Unit
Compressor Start Failure Inverter Compressor Abnormality
4 Slave3 Outdoor Unit Inverter The First Start Failure by Slave3 Outdoor Unit
Compressor Start Failure Inverter Compressor Abnormality
1 Master Outdoor Unit Inverter Master Outdoor Unit Inverter Compressor Fault
Compressor Over Current OR Drive Fault
2 Slave1 Outdoor Unit Inverter Slave1 Outdoor Unit Inverter Compressor Fault
Compressor Over Current OR Drive Fault
2 9
Slave2 Outdoor Unit Inverter Slave2 Outdoor Unit Inverter Compressor Fault
3
Compressor Over Current OR Drive Fault
Slave3 Outdoor Unit Inverter Slave3 Outdoor Unit Inverter Compressor Fault
4
Compressor Over Current OR Drive Fault
Master Outdoor Unit Inverter Compressor1 Master Outdoor Unit Inverter Compressor1 High
1
High Discharge Temperature Discharge Temperature
Slave1 Outdoor Unit Inverter Compressor1 Slave1 Outdoor Unit Inverter Compressor1 High
2
High Discharge Temperature Discharge Temperature
3 2
Slave2 Outdoor Unit Inverter Compressor1 Slave2 Outdoor Unit Inverter Compressor1 High
3
High Discharge Temperature Discharge Temperature
Slave3 Outdoor Unit Inverter Compressor1 Slave3 Outdoor Unit Inverter Compressor1 High
4
High Discharge Temperature Discharge Temperature
Master Outdoor Unit Inverter Compressor2 Master Outdoor Unit Inverter Compressor2 High
1
High Discharge Temperature Discharge Temperature
Slave1 Outdoor Unit Inverter Compressor2 Slave1 Outdoor Unit Inverter Compressor2 High
2
High Discharge Temperature Discharge Temperature
3 3
Slave2 Outdoor Unit Inverter Compressor2 Slave2 Outdoor Unit Inverter Compressor2 High
3
High Discharge Temperature Discharge Temperature
Slave3 Outdoor Unit Inverter Compressor2 Slave3 Outdoor Unit Inverter Compressor2 High
4
High Discharge Temperature Discharge Temperature
3
Display Title Cause of Error
High Pressure of Master Outdoor Unit High Pressure of Master Outdoor Unit
1
High Pressure of Slave1 Outdoor Unit High Pressure of Slave1 Outdoor Unit
2
3 4
High Pressure of Slave2 Outdoor Unit High Pressure of Slave2 Outdoor Unit
3
High Pressure of Slave3 Outdoor Unit High Pressure of Slave3 Outdoor Unit
4
Low Pressure of Master Outdoor Unit Low Pressure of Master Outdoor Unit
1
Low Pressure of Slave1 Outdoor Unit Low Pressure of Slave1 Outdoor Unit
2
3 5
Low Pressure of Slave2 Outdoor Unit Low Pressure of Slave2 Outdoor Unit
3
Low Pressure of Slave3 Outdoor Unit Low Pressure of Slave3 Outdoor Unit
4
1 Master Outdoor Unit Low Pressure Master Outdoor Unit Low Pressure Sensor open or
Sensor Fault short
2 Slave1 Outdoor Unit Low Pressure Slave1 Outdoor Unit Low Pressure Sensor open or
Sensor Fault short
4 2
3 Slave2 Outdoor Unit Low Pressure Slave2 Outdoor Unit Low Pressure Sensor open or
Sensor Fault short
4 Slave3 Outdoor Unit Low Pressure Slave3 Outdoor Unit Low Pressure Sensor open or
Sensor Fault short
4
Display Title Cause of Error
Master Outdoor Unit High Pressure Master Outdoor Unit High Pressure Sensor open
1 Sensor Fault or short
Slave1 Outdoor Unit High Pressure Slave1 Outdoor Unit High Pressure Sensor open
2 Sensor Fault or short
4 3
Slave2 Outdoor Unit High Pressure Slave2 Outdoor Unit High Pressure Sensor open
3 Sensor Fault or short
Slave3 Outdoor Unit High Pressure Slave3 Outdoor Unit High Pressure Sensor open
4 Sensor Fault or short
Master Outdoor Unit Air Temperature Master Outdoor Unit Air Temperature Sensor open
1 Sensor Fault or short
Slave1 Outdoor Unit Air Temperature Slave1 Outdoor Unit Air Temperature Sensor open
2 Sensor Fault or short
4 4
Slave2 Outdoor Unit Air Temperature Slave2 Outdoor Unit Air Temperature Sensor open
3 Sensor Fault or short
Slave3 Outdoor Unit Air Temperature Slave3 Outdoor Unit Air Temperature Sensor open
4 Sensor Fault or short
Master Outdoor Unit Heat Exchanger Master Outdoor Unit Heat Exchanger Temperature
1 Temperature Sensor (Front side) Fault Sensor(Front side) open or short
Outdoor unit related error
Slave1 Outdoor Unit Heat Exchanger Slave1 Outdoor Unit Heat Exchanger Temperature
2 Temperature Sensor (Front side) Fault Sensor(Front side) open or short
4 5
Slave2 Outdoor Unit Heat Exchanger Slave2 Outdoor Unit Heat Exchanger Temperature
3 Temperature Sensor (Front side) Fault Sensor(Front side) open or short
Slave3 Outdoor Unit Heat Exchanger Slave3 Outdoor Unit Heat Exchanger Temperature
4 Temperature Sensor (Front side) Fault Sensor(Front side) open or short
Master Outdoor Unit Suction Master Outdoor Unit Suction Temperature Sensor
1 Temperature Sensor Fault open or short
Slave1 Outdoor Unit Suction Slave1 Outdoor Unit Suction Temperature Sensor
2 Temperature Sensor Fault open or short
4 6
Slave2 Outdoor Unit Suction Slave2 Outdoor Unit Suction Temperature Sensor
3 Temperature Sensor Fault open or short
Slave3 Outdoor Unit Suction Slave3 Outdoor Unit Suction Temperature Sensor
4 Temperature Sensor Fault open or short
Master Outdoor Unit Inverter Master Outdoor Unit Inverter Compressor2
1 Compressor2 Discharge Temperature Discharge Temperature Sensor open or short
Sensor Fault
Slave1 Outdoor Unit Inverter Slave1 Outdoor Unit Inverter Compressor2
2 Compressor2 Discharge Temperature Discharge Temperature Sensor open or short
Sensor Fault
4 7
Slave2 Outdoor Unit Inverter Slave2 Outdoor Unit Inverter Compressor2
3 Compressor2 Discharge Temperature Discharge Temperature Sensor open or short
Sensor Fault
Slave3 Outdoor Unit Inverter Slave3 Outdoor Unit Inverter Compressor2
4 Compressor2 Discharge Temperature Discharge Temperature Sensor open or short
Sensor Fault
5
Display Title Cause of Error
Master Outdoor Unit Faulty IPM Master Outdoor Unit IPM Temperature Sensor
1
Temperature Sensor short/open
Slave1 Outdoor Unit Faulty IPM Slave1 Outdoor Unit IPM Temperature Sensor
2
Temperature Sensor short/open
4 9
Slave2 Outdoor Unit Faulty IPM Slave2 Outdoor Unit IPM Temperature Sensor
3
Temperature Sensor short/open
Slave3 Outdoor Unit Faulty IPM Slave3 Outdoor Unit IPM Temperature Sensor
4
Temperature Sensor short/open
Omitting connection of R, S, T power Omitting connection of Master outdoor unit
1
of Master Outdoor Unit
Omitting connection of R, S, T power Omitting connection of Slave1 outdoor unit
2
of Slave1 Outdoor Unit
5 0
Omitting connection of R, S, T power Omitting connection of Slave2 outdoor unit
3
of Slave2 Outdoor Unit
Omitting connection of R, S, T power Omitting connection of Slave3 outdoor unit
4
of Slave3 Outdoor Unit
Excessive capacity of indoor units Excessive connection of indoor units compared to
5 1 1
capacity of Outdoor Unit
Outdoor unit related error
Master Outdoor Unit Communication Failing to receive inverter signal at main PCB of
1
error : inverter PCB → Main PCB Master Outdoor Unit
Slave1 Outdoor Unit Communication Failing to receive inverter signal at main PCB of
2
error : inverter PCB → Main PCB Slave1 Outdoor Unit
5 2
Slave2 Outdoor Unit Communication Failing to receive inverter signal at main PCB of
3 error : inverter PCB → Main PCB Slave2 Outdoor Unit
Slave3 Outdoor Unit Communication Failing to receive inverter signal at main PCB of
4 error : inverter PCB → Main PCB Slave3 Outdoor Unit
Communication error : indoor unit → Failing to receive indoor unit signal at main PCB of
5 3 1 Main PCB of Outdoor Unit Outdoor Unit.
Master Outdoor Unit Communication Failing to receive signal main PCB at inverter PCB
1 error : Main PCB → inverter PCB of Master Outdoor Unit
Slave1 Outdoor Unit Communication Failing to receive signal main PCB at inverter PCB
2 error : Main PCB → inverter PCB of Slave1 Outdoor Unit
5 7
Slave2 Outdoor Unit Communication Failing to receive signal main PCB at inverter PCB
3 error : Main PCB → inverter PCB of Slave2 Outdoor Unit
Slave3 Outdoor Unit Communication Failing to receive signal main PCB at inverter PCB
4 error : Main PCB → inverter PCB of Slave3 Outdoor Unit
Inverter PCB EEPROM Error of Master Access Error of Inverter PCB of Master Outdoor
1 Outdoor Unit Unit
Inverter PCB EEPROM Error of Slave1 Access Error of Inverter PCB of Slave1 Outdoor
2 Outdoor Unit Unit
6 0
Inverter PCB EEPROM Error of Slave2 Access Error of Inverter PCB of Slave2 Outdoor
3 Outdoor Unit Unit
Inverter PCB EEPROM Error of Slave3 Access Error of Inverter PCB of Slave3 Outdoor
4 Outdoor Unit Unit
6
Display Title Cause of Error
Master Outdoor Unit Inverter Heatsink System is turned off by Master Outdoor Unit
1
High Temperature Inverter Heatsink High Temperature
2 Slave1 Outdoor Unit Inverter Heatsink System is turned off by Slave1 Outdoor Unit
High Temperature Inverter Heatsink High Temperature
6 2
3 Slave2 Outdoor Unit Inverter Heatsink System is turned off by Slave2 Outdoor Unit
High Temperature Inverter Heatsink High Temperature
4 Slave3 Outdoor Unit Inverter Heatsink System is turned off by Slave3 Outdoor Unit
High Temperature Inverter Heatsink High Temperature
Master Outdoor Unit Inverter Heatsink Master Outdoor Unit Inverter Heatsink
1
Temperature Sensor Fault Temperature Sensor open or short
Slave1 Outdoor Unit Inverter Heatsink Slave1 Outdoor Unit Inverter Heatsink
2
Temperature Sensor Fault Temperature Sensor open or short
6 5
Slave2 Outdoor Unit Inverter Heatsink Slave2 Outdoor Unit Inverter Heatsink
3
Temperature Sensor Fault Temperature Sensor open or short
Slave3 Outdoor Unit Inverter Heatsink Slave3 Outdoor Unit Inverter Heatsink
4
Temperature Sensor Fault Temperature Sensor open or short
1 Master Outdoor Unit Fan Lock Restriction of Master Outdoor Unit
2 Slave1 Outdoor Unit Fan Lock Restriction of Slave1 Outdoor Unit
6 7
Outdoor unit related error
1 Master Outdoor Unit Fan CT Sensor Master Outdoor Unit Fan CT Sensor open or short
Error
2 Slave1 Outdoor Unit Fan CT Sensor Slave1 Outdoor Unit Fan CT Sensor open or short
Error
7 5
3 Slave2 Outdoor Unit Fan CT Sensor Slave2 Outdoor Unit Fan CT Sensor open or short
Error
Slave3 Outdoor Unit Fan CT Sensor Slave3 Outdoor Unit Fan CT Sensor open or short
Error
1 Master Outdoor Unit Fan Over Current Master Outdoor Unit Fan Current is over 5A
Error
Slave1 Outdoor Unit Fan Over Current Slave1 Outdoor Unit Fan Current is over 5A
2
Error
7 7
Slave2 Outdoor Unit Fan Over Current Slave2 Outdoor Unit Fan Current is over 5A
3
Error
Slave3 Outdoor Unit Fan Over Current Slave3 Outdoor Unit Fan Current is over 5A
4
Error
7
Display Title Cause of Error
Master Outdoor Unit Fan Start Failure Master Outdoor Unit Fan First Position Sensing
1
Error Failure
Slave1 Outdoor Unit Fan Start Failure Slave1 Outdoor Unit Fan First Position Sensing
2
Error Failure
7 9
Slave2 Outdoor Unit Fan Start Failure Slave2 Outdoor Unit Fan First Position Sensing
3
Error Failure
Slave3 Outdoor Unit Fan Start Failure Slave3 Outdoor Unit Fan First Position Sensing
4
Error Failure
Master Outdoor Unit Main PCB EEP- Communication Fail Between Master Outdoor Unit
1
ROM Error Main MICOM and EEPROM or omitting EEPROM
Slave1 Outdoor Unit Main PCB EEP- Communication Fail Between Slave1 Outdoor Unit
2
ROM Error Main MICOM and EEPROM or omitting EEPROM
8 6
Slave2 Outdoor Unit Main PCB EEP- Communication Fail Between Slave2 Outdoor Unit
3
ROM Error Main MICOM and EEPROM or omitting EEPROM
Slave3 Outdoor Unit Main PCB EEP- Communication Fail Between Slave3 Outdoor Unit
4
ROM Error Main MICOM and EEPROM or omitting EEPROM
Outdoor unit related error
Master Outdoor Unit Fan PCB EEP- Communication Fail Between Master Outdoor Unit
1
ROM Error Fan MICOM and EEPROM or omitting EEPROM
Slave1 Outdoor Unit Fan PCB EEP- Communication Fail Between Slave1 Outdoor Unit
2
ROM Error Fan MICOM and EEPROM or omitting EEPROM
8 7
Slave2 Outdoor Unit Fan PCB EEP- Communication Fail Between Slave2 Outdoor Unit
3
ROM Error Fan MICOM and EEPROM or omitting EEPROM
Slave3 Outdoor Unit Fan PCB EEP- Communication Fail Between Slave3 Outdoor Unit
4
ROM Error Fan MICOM and EEPROM or omitting EEPROM
Master Outdoor Unit TVI Inlet The resistance value of the Master Outdoor Unit
1 Temperature Sensor Error sensor is abnormal.
Slave1 Outdoor Unit TVI Inlet The resistance value of the Slave1 Outdoor Unit
2 Temperature Sensor Error sensor is abnormal.
9 0
Slave2 Outdoor Unit TVI Inlet The resistance value of the Slave2 Outdoor Unit
3 Temperature Sensor Error sensor is abnormal.
Slave3 Outdoor Unit TVI Inlet The resistance value of the Slave3 Outdoor Unit
4 Temperature Sensor Error sensor is abnormal.
Master Outdoor Unit TVI Outlet The resistance value of the Master Outdoor Unit
1 Temperature Sensor Error sensor is abnormal.
Slave1 Outdoor Unit TVI Outlet The resistance value of the Slave1 Outdoor Unit
2 Temperature Sensor Error sensor is abnormal.
9 1
Slave2 Outdoor Unit TVI Outlet The resistance value of the Slave2 Outdoor Unit
3 Temperature Sensor Error sensor is abnormal.
Slave3 Outdoor Unit TVI Outlet The resistance value of the Slave3 Outdoor Unit
4 Temperature Sensor Error sensor is abnormal.
8
Display Title Cause of Error
Communication Error Between Master Failing to receive Slave Unit signal at main PCB of
1 Outdoor Unit and Other Outdoor Unit Master Outdoor Unit
Communication Error Between Slave1 Failing to receive Slave Unit signal at main PCB of
2 Outdoor Unit and Other Outdoor Unit Slave1 Outdoor Unit
1 0 4
Communication Error Between Slave2 Failing to receive Slave Unit signal at main PCB of
3 Outdoor Unit and Other Outdoor Unit Slave2 Outdoor Unit
Communication Error Between Slave3 Failing to receive Slave Unit signal at main PCB of
4 Outdoor Unit and Other Outdoor Unit Slave3 Outdoor Unit
Master Outdoor Unit Fan PCB Failing to receive fan signal at main PCB of Master
1 Communication Error Outdoor unit
Slave1 Outdoor Unit Fan PCB Failing to receive fan signal at main PCB of Slave1
2 Communication Error Outdoor unit
1 0 5
Slave2 Outdoor Unit Fan PCB Failing to receive fan signal at main PCB of Slave2
3 Communication Error Outdoor unit
Slave3 Outdoor Unit Fan PCB Failing to receive fan signal at main PCB of Slave3
4 Communication Error Outdoor unit
Outdoor unit related error
Master Outdoor Unit FAN IPM Fault Instant Over Current at Master Outdoor Unit Fan
1 Error IPM
Slave1 Outdoor Unit FAN IPM Fault Instant Over Current at Slave1 Outdoor Unit Fan
2 Error IPM
1 0 6
Slave2 Outdoor Unit FAN IPM Fault Instant Over Current at Slave2 Outdoor Unit Fan
3 Error IPM
Slave3 Outdoor Unit FAN IPM Fault Instant Over Current at Slave3 Outdoor Unit Fan
4 Error IPM
Master Outdoor Unit Fan DC Link Low Master Outdoor Unit Fan DC Link Input Voltage is
1 Voltage Error under 380V
Slave1 Outdoor Unit Fan DC Link Low Slave1 Outdoor Unit Fan DC Link Input Voltage is
2 Voltage Error under 380V
1 0 7
Slave2 Outdoor Unit Fan DC Link Low Slave2 Outdoor Unit Fan DC Link Input Voltage is
3 Voltage Error under 380V
Slave3 Outdoor Unit Fan DC Link Low Slave3 Outdoor Unit Fan DC Link Input Voltage is
4 Voltage Error under 380V
Master Outdoor Unit Liquid pipe Liquid pipe temperature sensor of Master Outdoor
1 Temperature Sensor Error Unit is open or short
Slave1 Outdoor Unit Liquid pipe Liquid pipe temperature sensor of Slave1 Outdoor
2 Temperature Sensor Error Unit is open or short
1 1 3
Slave2 Outdoor Unit Liquid pipe Liquid pipe temperature sensor of Slave2 Outdoor
3 Temperature Sensor Error Unit is open or short
Slave3 Outdoor Unit Liquid pipe Liquid pipe temperature sensor of Slave3 Outdoor
4 Temperature Sensor Error Unit is open or short
9
Display Title Cause of Error
Master Outdoor Unit Subcooling Inlet Master Outdoor Unit Subcooling Inlet Temperature
1
Temperature Sensor Error Sensor Error
Slave1 Outdoor Unit Subcooling Inlet Slave1 Outdoor Unit Subcooling Inlet Temperature
2
Temperature Sensor Error Sensor Error
1 1 4
Slave2 Outdoor Unit Subcooling Inlet Slave2 Outdoor Unit Subcooling Inlet Temperature
3
Temperature Sensor Error Sensor Error
Slave3 Outdoor Unit Subcooling Inlet Slave3 Outdoor Unit Subcooling Inlet Temperature
4
Temperature Sensor Error Sensor Error
Master Outdoor Unit Subcooling Outlet Master Outdoor Unit Subcooling Outlet
1
Temperature Sensor Error Temperature Sensor Error
Slave1 Outdoor Unit Subcooling Outlet Slave1 Outdoor Unit Subcooling Outlet
2
Temperature Sensor Error Temperature Sensor Error
1 1 5
Slave2 Outdoor Unit Subcooling Outlet Slave2 Outdoor Unit Subcooling Outlet
3
Temperature Sensor Error Temperature Sensor Error
Slave3 Outdoor Unit Subcooling Outlet Slave3 Outdoor Unit Subcooling Outlet
4
Temperature Sensor Error Temperature Sensor Error
Master Outdoor Unit Oil Level Sensor Oil Level Sensor of Master Outdoor Unit is open or
1
Outdoor unit related error
Error short
Slave1 Outdoor Unit Oil Level Sensor Oil Level Sensor of Slave1 Outdoor Unit is open or
2 Error short
1 1 6
Slave2 Outdoor Unit Oil Level Sensor Oil Level Sensor of Slave2 Outdoor Unit is open or
3 Error short
Slave3 Outdoor Unit Oil Level Sensor Oil Level Sensor of Slave3 Outdoor Unit is open or
4 Error short
Master Outdoor unit Main Board - Master Outdoor unit Main Board - External Board
1 External Board communication Error communication Error
Slave1 Outdoor unit Main Board - Slave1 Outdoor unit Main Board - External Board
2 External Board communication Error communication Error
1 4 5
Slave2 Outdoor unit Main Board - Slave2 Outdoor unit Main Board - External Board
3 External Board communication Error communication Error
Slave3 Outdoor unit Main Board - Slave3 Outdoor unit Main Board - External Board
4 External Board communication Error communication Error
Master Outdoor Unit Discharge Master Outdoor Unit Compressor Discharge
1 Superheat not satisfied Superheat not satisfied during 5 Min.
Slave1 Outdoor Unit Discharge Slave1 Outdoor Unit Compressor Discharge
2 Superheat not satisfied Superheat not satisfied during 5 Min.
1 5 0
Slave2 Outdoor Unit Discharge Slave2 Outdoor Unit Compressor Discharge
3 Superheat not satisfied Superheat not satisfied during 5 Min.
Slave3 Outdoor Unit Discharge Slave3 Outdoor Unit Compressor Discharge
4 Superheat not satisfied Superheat not satisfied during 5 Min.
Failure of operation mode conversion Failure of operation mode conversion at Outdoor
1 5 1 1 at Outdoor Unit Unit
10
Display Title Cause of Error
Master Outdoor Unit Heat Exchanger Master Outdoor Unit Heat Exchanger Temperature
1
Temperature Sensor (upper part) Fault Sensor (upper part) Fault
Slave1 Outdoor Unit Heat Exchanger Slave1 Outdoor Unit Heat Exchanger Temperature
2
Temperature Sensor (upper part) Fault Sensor (upper part) Fault
1 5 3
Slave2 Outdoor Unit Heat Exchanger Slave2 Outdoor Unit Heat Exchanger Temperature
3
Temperature Sensor (upper part) Fault Sensor (upper part) Fault
Slave3 Outdoor Unit Heat Exchanger Slave3 Outdoor Unit Heat Exchanger Temperature
4
Temperature Sensor (upper part) Fault Sensor (upper part) Fault
Master Outdoor Unit Heat Exchanger Master Outdoor Unit Heat Exchanger Temperature
1
Temperature Sensor (lower part) Fault Sensor(lower part) open or short
Slave1 Outdoor Unit Heat Exchanger Slave1 Outdoor Unit Heat Exchanger Temperature
2
Temperature Sensor (lower part) Fault Sensor(lower part) open or short
1 5 4
Slave2 Outdoor Unit Heat Exchanger Slave2 Outdoor Unit Heat Exchanger Temperature
3
Temperature Sensor (lower part) Fault Sensor(lower part) open or short
Slave3 Outdoor Unit Heat Exchanger Slave3 Outdoor Unit Heat Exchanger Temperature
4
Temperature Sensor (lower part) Fault Sensor(lower part) open or short
Master Outdoor unit External Board Master Outdoor Unit Main Board Main-Sub Micom
1
Outdoor unit related error
11
Display Title Cause of Error
Searching pipe Error Failure of automatic addressing of valves
0 C + #HR
HR Unit related error
HR unit1 Liqiud sensor error Liquid pipe sensor of HR unit open or short
1 C + #HR
HR unit1 Sub Cooling Pipe sensor error Sub Cooling Pipe In sensor of HR unit open or
2 0 2 C + #HR short
HR unit1 Sub Cooling Pipe Out sensor Sub Cooling Pipe Out sensor of HR unit. open or
3 C + #HR error short
Communication error Failing to receive HR unit signal at outdoor unit
4 C + #HR
12
Error Code check
Error No. Error Type Error Point Main Reasons
Is sensor properly No
Connect properly to PCB
connected to PCB?
Yes
Yes
** In case the value is more than 100kΩ (open) or less than 100Ω (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature(±5% margin) Normal
Air temp sensor: 10°C = 20.7kΩ : 25°C= 10kΩ : 50°C= 3.4kΩ
Pipe temp sensor: 10°C = 10kΩ : 25°C= 5kΩ : 50°C= 1.8kΩ
13
Error
Error Type Error Point Main Reasons
No.
Yes
Yes
* If there is no remote controller to replace : Use another unit’s remote controller doing well
** Check cable : Contact failure of connected portion or extension of cable are main cause
Check any surrounded noise ( check the distance with main power cable)
make safe distance from the devices generate electromagnetic wave
*** After replacing indoor unit PCB, do Auto Addressing & input unit’s address if connected to central controller.
(All the indoor units connected should be turned on before Auto Addressing
14
Error
Error Type Error Point Main Reasons
No.
No
Drain pump blocked by Check the drain head height
foreign particles? and slope***
Yes
15
Error
Error Type Error Point Main Reasons
No.
Yes
Yes
Check the insulation of compressor
No compressor and replace if required
Is main circuit breaker off?
Check the capacity of main circuit
Yes breaker and replace if required
* (Note1) communication from IDU is normal if voltage * If the DC voltage between communication terminal A, B
fluctuation(-9V ~ +9V) exists when checking DC voltage of indoor unit is fluctuate within (-9V~+9V) then
of communication terminal between IDU and ODU communication from outdoor unit is normal
16
Error
Error Type Error Point Main Reasons
No.
- Replace the indoor unit PCB, and then make sure to perform Auto addressing and input the address of central control
17
Error
Error Type Error Point Main Reasons
No.
Indoor unit BLDC fan motor Indoor BLDC fan motor 1. Motor connector connection fault
10 failure feedback signal is absent 2. Indoor PCB fault
(for 50 sec.) 3. Motor fault
Is connector No
connection proper? Connect properly
Yes
Is fan motor No
Replace indoor unit fan motor
normal?*
Yes
WARNING
• The connection of motor connector to PCB should be done under no power supplying to PCB.
18
Error
Error Type Error Point Main Reasons
No.
21*
1.Over current detection at Inverter compres-
sor(U,V,W)
Master 2.Compressor damaged (insulation dam-
211 IPM self protection circuit aged/Motor damaged)
Slave1 Inverter PCB Assy. IGBT activation 3.IPM overheating
212 Fault occur (Overcurrent/IPM overheat- (Heat sink disassembled)
Slave2 ing/Vcc low voltage) 4.Inverter compressor terminal disconnected
213 or loose
5.Inverter PCB assembly damaged
Slave3
214 6.ODU input current low
Yes
1. Check resistance between each terminal of compressor
Compressor JQC068MA* JQC048MA*
Are the resistance Temp. 25℃ 75℃ 25℃ 75℃
Between each phase and No U-V 0.216 ± 7% Ω 0.258 ± 7% Ω 0.302 ± 7% Ω 0.360 ± 7% Ω
insulation resistance of Inverter V-W 0.216 ± 7% Ω 0.258 ± 7% Ω 0.302 ± 7% Ω 0.360 ± 7% Ω
compressor normal? W-U 0.216 ± 7% Ω 0.258 ± 7% Ω 0.302 ± 7% Ω 0.360 ± 7% Ω
Yes
Yes
Yes
19
Error
Error Type Error Point Main Reasons
No.
Yes
Check
R~S/S~T/T~R phase voltage is 380V 10%
No
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V 10%
→ Check connection condition and wiring if power is
abnormal
Yes
Yes
20
Error
Error Type Error Point Main Reasons
No.
23*
Master
231 1. DC Link terminal misconnection/terminal
contact fault
Slave1
232 Inverter Compressor DC DC Voltage isn't charged 2. Condenser damage
Link Low Voltage after starting relay on 3. Comp PCB assembly damage
Slave2
233 (DC Link voltage sensing part)
Slave3 4. Input voltage low
234
Yes
Check
R~S/S~T/T~R phase voltage is 380 V(-10 %)~415 V(+10 %)
No R~N/S~N/T~N phase voltage is 220 V(-10 %)~240 V(+10 %)
Is input voltage normal?
→ Check connection condition and wiring if power is
abnormal
Yes
Yes
Yes
Yes
Yes
21
Error
Error Type Error Point Main Reasons
No.
Yes
No
Is SVC valve open? Open SVC valve
Yes
Yes
Yes
Is high pressure of No
LGMV similar as Replace high pressure sensor
at manifold gauge?
Yes
22
Error
Error Type Error Point Main Reasons
No.
25*
Master
251
Slave1 1. Input voltage abnormal (T-N, R-S, S-T, T-R)
Input voltage is over limited
252 Input Voltage high/low 2. Outdoor unit Inverter PCB assembly dam-
value of the product (304 V
age (input voltage sensing part)
Slave2 or less, 536 V or more)
3. N phase line disconnection
253
Slave3
254
Yes
Check
R~S/S~T / T~R phase voltage is 380 V(-10 %) ~ 415 V(+ 10 %)
No R~N/S~N/T~N phase voltage is 220 V(-10 %) ~ 240 V(+ 10%)
Is input voltage normal?
→ Check connection condition and wiring if power is
abnormal
Yes
Yes
Yes
23
Error
Error Type Error Point Main Reasons
No.
26*
Master
1. Overload operation
261
(Pipe clogging/Covering/EEV defect/Ref.
Slave1 overcharge)
262 Inverter compressor starting Starting failure because of
2. Compressor damage
failure Error compressor abnormality
Slave2 (Insulation damage/Motor damage)
263 3. Compressor wiring fault
Slave3 4. ODU Comp PCB damage (CT)
264
Yes
Yes
24
Error
Error Type Error Point Main Reasons
No.
28*
Master
281
Slave1
282 1. Input voltage abnormal (R,S,T,N)
Inverter DC link high Inv PCB DC link voltage
2. ODU Comp PCB damage
Slave2 voltage error supplied over 780V
283 (DC Link voltage sensing part)
Slave3
284
Yes
Check
R~S/S~T/T~R phase voltage is 380V 10%
No R~N/S~N/T~N phase voltage is 220V 10%
Is input voltage normal?
→ Check connection condition and wiring if power is
abnormal
Yes
No
Is Inverter PCB assembly Replace Inverter PCB assembly
normal?
Yes
25
Error
Error Type Error Point Main Reasons
No.
29*
Master
1. Overload operation
291
(Pipe clogging/Covering/EEV defect/Ref.
Slave1 overcharge)
292 Inverter compressor over Inverter compressor input
2. Compressor damage(Insulation
current current is over 30A
Slave2 damage/Motor damage)
293 3. Input voltage low
Slave3 4. ODU Inverter PCB assembly damage
294
Check
No R~S/S~T/T~R phase voltage is 380V ±10%
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V ±10%
→ Check connection condition and wiring if power is
abnormal
Yes
Yes
26
Error No. Error Type Error Point Main Reasons
Yes
* Resistance value of discharge temperature sensor
10°C = 362kΩ, 25°C= 200kΩ, 50°C= 82kΩ, 100°C= 18.5kΩ
Is EEV in
outdoor unit normal No
at heating operation? Replace outdoor unit EEV
[refer electric
component part]
Yes
Replace strainer
27
Error
Error Type Error Point Main Reasons
No.
1. Defect of high pressure sensor
34* 2. Defect of indoor or outdoor unit fan
Error happens 3. Deformation because of damage of refrigerant pipe
Master because of 10 times 4. Over-charged refrigerant
341 successive compres- 5. Defective indoor / outdoor unit EEV
Over-increase of dis-
Slave1 sor off due to over- 6. When blocked
charge pressure of
342 increase of high pres- - Outdoor unit is blocked during cooling
compressor
Slave2 sure by high pressure - Indoor unit filter is blocked during heating
343 sensor 7. SVC valve is clogged
Slave3 8. PCB defect of outdoor unit
344 9. Indoor unit’s pipe temperature defect
10. Indoor unit pipe temperature sensor defect
Yes
Yes
Is refrigerant No
amount normal? Adjust refrigerant amount
[refer refrigerant part]
Yes
Is fan normal?
(Indoor fan during heating No
Replace related parts
Outdoor fan during cooling)
Yes
Is filter blocked
(Heating:indoor, No Clean indoor filter (heating)
Cooling:outdoor /outdoor heat exchanger (cooling)?
heat exchanger)?
Yes
Yes
Yes
No
Are communication cable/ check communication/
piping normal? piping correction.
Yes
Yes Yes
Is fan normal? No
(in heating outdoor fan, Check and replace related parts
in cooling indoor fan)
Yes
No
Is strainer Ok?* Replace the strainer
Yes
Yes
* If the temperature difference between inlet and outlet of strainer
Check indoor / outdoor unit LEV is so large that frost or ice formation can be seen or confirmed
Check Indoor unit PCB
Check indoor / outdoor unit then clogging of strainer should be checked
installation conditions (Notice: it is not full ice forming of strainer, in case that there is
not at inlet portion but at outlet portion)
29
Error
Error Type Error Point Main Reasons
No.
40*
Master
401
1. Input voltage abnormal (T-N)
Slave1 Micom input voltage isn't
402 Inverter compressor CT 2. DC power part damage (DC 5V)
within 2.5V ±0.3V at initial
sensor error 3. Outdoor unit’s inverter PCB damage
Slave2 state of power supply
(CT sensing part)
403
Slave3
404
Yes
Check
R~S/S~T/T~R phase voltage is 380V±10%
No
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V±10%
→ Check connection condition and wiring if power is
abnormal
Yes
No Replace Inverter PCB assembly
Is Inverter PCB assembly normal?
Yes
30
Error No. Error Type Error Point Main Reasons
41*
1. Defective connection of the compressor1 discharge
(Inverter1)
Compressor1 dis- Sensor measurement pipe temperature sensor
Master 411
charge pipe tempera- value is abnormal 2. Defective discharge pipe compressor sensor of the
Slave1 412
ture sensor error (Open/Short) compressor1 (open/short)
Slave2 413
3. Defective outdoor PCB
Slave3 414
47*
1. Defective connection of the compressor1 discharge
(Inverter2)
Compressor2 dis- Sensor measurement pipe temperature sensor
Master 471
charge pipe tempera- value is abnormal 2. Defective discharge pipe compressor sensor of the
Slave1 472
ture sensor error (Open/Short) compressor1 (open/short)
Slave2 473
3. Defective outdoor PCB
Slave3 474
Yes
Is the resistance of No
Replace sensor
sensor normal?*
Yes
Is sensor resistance No
value same as temperature Replace corresponding outdoor PCB
value of LGMV?
Yes
* Error is generated if the resistance is more than 5 MΩ(open) and less than 2 kΩ (short)
31
Error
Error Type Error Point Main Reasons
No.
42*
Master 421 Abnormal value of 1. Bad connection of low pressure sensor connector
Slave1 422 Sensor error of low sensor 2. Defect of low pressure sensor connector (Open/Short)
Slave2 423 pressure (Open/Short) 3. Defect of outdoor PCB
Slave3 424
43*
Master 431 Abnormal value of 1. Bad connection of high pressure sensor connector
Sensor error of high
Slave1 432 sensor 2. Defect of high pressure sensor connector (Open/Short)
pressure
Slave2 433 (Open/Short) 3. Defect of outdoor PCB
Slave3 434
Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly?
Yes
After replacement of No
Replace corresponding
outdoor unit main PCB
pressure sensor
is the system normal?
Yes
END
32
Error No. Error Type Error Point Main Reasons
Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly??
Yes
No
Is sensor value correct?* Replace sensor
Yes
* If value is 100kΩ ↑(open) or 100Ω ↓(short), error occurs
33
Error
Error Type Error Point Main Reasons
No.
50*
Master
501 1. Input Voltage abnormal (R,S,T,N)
Slave1 ODU 3phase power omis- Omitting one or more of 2. Check power Line connection condition
502 sion error R,S,T input power 3. Main PCB damage
Slave2 4. Inverter PCB input current sensor fault
503
Slave3
504
Yes
Check
Is input voltage normal? R~S/S~T/T~R phase voltage is 380V±10%
No R~N/S~N/T~N phase voltage is 220V±10%
→ Check connection condition and wiring if power is
abnormal
Yes
1. Check R~N/S~N/T~N phase voltage is
220V±10%
Is Main PCB assembly No 2. Check Main PCB assemblywire
normal? disconnection and wiring
→ Reassemble if abnormality found
Yes
Yes
34
Error
Error Type Error Point Main Reasons
No.
1. 130% more than outdoor unit rated capacity
Over-Capacity 2. Wrong connection of communication
51* Sum of indoor unit capaci- cable/piping
(Sum of indoor unit capaci-
Master ty is more than outdoor ty exceed outdoor unit 3. Control error of slave outdoor unit Dip switch
511 capacity) capacity specification 4. Power supply defect of slave unit PCB
5. Defect of outdoor unit PCB
Yes
Yes Yes
Is communicationmission
No
cables between outdoor units Re-connect
connected correctly?*
Yes
Yes
End
35
Error
Error Type Error Point Main Reasons
No.
52*
Communication error Main PCB of Master unit 1. Power cable or communication cable is not
Master 521 between of Master unit can’t connected
Slave1 522 (Comp1/Comp2 PCB receive signal from 2. Defect of outdoor Main PCB or
Slave2 523
Main PCB) Comp1/Comp2 controller Comp1/Comp2 PCB
Slave3 524
Is communication
LED (Yellow) of No Is noise filter or Inverter PCB’S
Noise filter or Fuse change
Inverter 1 / Inverter 2 line fuse normal?
PCB on?
Yes
No
Is communication cable
Re-connect communication cable Change Inverter PCB
connected correctly?
Yes
No
Is Main PCB normal? Replace Main PCB
Yes
* The method of checking Main PCB and Inverter 1 / Inverter 2 PCB (If normal, communication LED blinks)
36
Error
Error Type Error Point Main Reasons
No.
Is power supplied No
to indoor PCB? Supply power
In case of CH53, almost happened with CH05, the indoor units not operated actually are normal so check with same
method of CH05. and additionally check as shown as below and above flow chart
• Although the quantity of indoor units installed is same as LGMV data there may be a few indoor units with which the
number of communication is not increased with LGMV
• Although the quantity of indoor units installed is not same as LGMV data, and if communication of the indoor unit dis-
played at LGMV is done well then the indoor unit suspected to have some problem (and is not appear at LGMV) may
have following problems
wrong connection of communication cable or power cable
fault of power / PCB / communication cable
duplication of indoor unit number
• If communication is not doing well wholly then the Auto Addressing is not done
• The case that CH53 appear at indoor unit also Auto Addressing is not done so indoor unit address may be duplicated
* After replacement of indoor unit PCB, Auto Addressing should be done, if central controller is installed then the
central control address also should be input.
In case that only communication PCB is replaced above process is not needed
37
Error
Error Type Error Point Main Reasons
No.
Is Inverter PCB No
assembly 1. Replace Inverter PCB
normal?
Yes
No
38
Error No. Error Type Error Point Main Reasons
60*
1. EEPROM contact defect/wrong insertion
Master 601 Inverter PCB EEPROM Access error
2. Different EEPROM Version
Slave1 602 EEPROM error and Check SUM error
3. ODU Inverter PCB assembly damage
Slave2 603
Slave3 604
Yes
Yes
39
Error No. Error Type Error Point Main Reasons
No
Inverter PCB IGBTM Connection 1. Check Inverter PCBA Screw Connection Condition
Condition Normal? Reassemble or Manage if abnormality Found
Yes
No
1. Check Outdoor Unit Fan Motor Operation or Lock
Is ODU Fan Motor Normal?
Reassemble or Manage if abnormality Found
Yes
No
Is Inverter PCB assembly 1. Reset
Normal? Replace Inverter PCB Assembly
Yes
Recheck Power and
Installation Condition
40
Error No. Error Type Error Point Main Reasons
65*
Master
651
Slave1 Abnormal sensor resis- 1. Defective temperature sensor connection
Inverter PCB Power
652 tance value 2. Defective temperature sensor (Open / Short)
Module sensor error
Slave2 (Open/Short) 3. Defective outdoor unit PCB
653
Slave3
654
Is temperature sensor No
connector connections Connect sensor connector to PCB
are normal?
Yes
Yes
* Sensor resistance 100 kΩover (open) or 100 Ω below (short) will generate error
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ
Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ
41
Error No. Error Type Error Point Main Reasons
Is ODU Fan Motor Assemble No Check ODU Fan Motor assemble condition and fan locking
condition normal? → Reassemble or replace if abnormality found
Yes
Yes
Yes
42
Error No. Error Type Error Point Main Reasons
71*
Micom input voltage
Master 711
isn’t within 2.5V±0.3V 1. Input Voltage is abnormal (R-N)
Slave1 712 PFC CT Sensor Error
at initial state of power 2. ODU Inverter PCB damage (CT sensing part)
Slave2 713
supply
Slave3 714
Yes
No Check
R~S/S~T/T~R phase voltage 380V±10%
Is input voltage normal?
R~N/S~N/T~N phase voltage 200V±10%
Check connection condition and wiring if power is abnormal
Yes
No
Is Inverter PCB
Assembly normal? 1. Replace Inverter PCB
Yes
43
Error No. Error Type Error Point Main Reasons
75*
Offset of Micom which 1. Input Voltage is abnormal (not 15V)
Master
which sense the fan 2. Fan PCB assembly defect
Slave1 Fan CT Sensor Error
motor phase current is 3. Power wire open and connecting fault
Slave2
not 2.5V ± 0.3V 4. Inverter PCB assembly defect
Slave3
Yes
No
Is Fan PCB normal? 1. Replace Fan PCB
Yes
No
Is there any error 1. Check Fan PCB IPM normal or not.
When power reset? Replace Fan PCB
Yes
44
Error No. Error Type Error Point Main Reasons
Yes
1. Check resistance between each motor output terminal
Are the resistance No Chassis UXA UXB
Between each phase and insulation
resistance of motor output Resistance 15 ± 7 % Ω 13 ± 7 % Ω
terminal normal? 2. Check insulation resistance between ODU fan motor terminal(U,V,W) and pipe (over 100M )
→ Replace fan motor if abnormality found
Yes
No
Is Fan PCB assembly normal? 1. Check fan PCB assembly IPM normal
→ Replace Fan PCB assembly
Yes
45
Error No. Error Type Error Point Main Reasons
No
Is fan motor assemble Check ODU fan motor assemble condition and locking
condition normal? → Reassemble or replace if abnormality found
Yes
1.Check resistance between each motor output terminal
Are the resistance No Chassis UXA UXB
Between each phase and insulation
resistance of motor output Resistance 15 ± 7 % Ω 13 ± 7 % Ω
terminal normal?
2. Check insulation resistance between ODU fan motor terminal(U,V,W) and pipe (over 100M )
→Replace fan motor if abnormality found
No
Is fan motor connection
1. Check if color of motor output terminal(U,V,W) connector matched with PCB’s
condition normal?
2. Check wire disconnection and wiring
→ Reassemble or replace if abnormality found
No
Check fan PCB assembly IPM normal
Is fan PCB assembly normal?
→ Replace Fan PCB assembly
Yes
46
Error No. Error Type Error Point Main Reasons
86*
Master 861
1. No EEPROM
Slave1 862 Main PCB EEPROM EEPROM Access Error
Slave2 863 2. EEPROM wrong insertion
Slave3 864
No
Is EEPROM assemble
Reset after checking EEPROM assemble condition
condition normal?
Yes
No
Correct check sum Replace Correct EEPROM
Yes
47
Error No. Error Type Error Point Main Reasons
87*
Master 871 Error occurs when checking the 1.EEPROM bad contact/wrong insertion
Fan PCB EEPROM
Slave1 872 EEPROM checksum as initializing 2.EEPROM Version is different
Error
Slave2 873 after power is supplied 3.ODU fan PCB assembly damage
Slave3 874
Yes
No
Is Fan PCB assembly normal? Replace fan PCB assembly
Yes
48
Error No. Error Type Error Point Main Reasons
104*
Master
1041
Slave1 Communication Master displays ODU number 1.Loose connection of power cable/ communi-
1042 Error Between which is not communicated. cation cable¸(Open/Short)
Slave2 Outdoors Slave displays own error number 2.Defect of each outdoor unit PCB
1043
Slave3
1044
Is communication No
cable installed Connect communication cable
normally?
Yes
Yes
Yes
Slave1 setting
Slave2 setting
Slave3 setting
49
Error No. Error Type Error Point Main Reasons
105*
Master
1051 1. Wrong connection between Comp and Fan
Slave1 Communication error
Fan controller didn't receive signal PCB
1052 (Fan PCB £ Inverter
Slave2 from Inverter PCB 2. Fan PCB power not supplied
PCB)
1053 3. ODU Comp/Fan PCB defect
Slave3
1054
Yes
Is Inverter PCB No
communication LED(yellow) Check communication cable between Inverter PCB and fan PCB
blinking normally? → Reconnect or replace wire if abnormality found
Yes
No
No
Is fan PCB assembly normal? Fan PCB assembly
Yes Yes
50
Error No. Error Type Error Point Main Reasons
106*
Master 1. Overload operation (Pipe clogging/Covering/EEV
1061
Slave1 defect/Ref. overcharge
ODU Fan PCB IPM protection circuit activation
1062 2. ODU fan motor assemble condition abnormal
Slave2 IPM Fault (over current)
(Coil disconnection/Short/Insulation damage)
1063
Slave3 3. Fan PCB assembly defect
1064
No
Is fan motor assemble Check ODU fan motor assemble condition and locking
condition normal? → Reassemble or replace if abnormality found
Yes
No 1.Check fan motor U,V,W connector connection condition
Is fan motor wire connection → Reassemble wire if abnormality found
condition normal? 2.Check fan motor wire disconnection
→ Replace ODU fan motor if abnormality found
Yes
No
Yes
51
Error No. Error Type Error Point Main Reasons
107*
Master 1. Overload operation (Pipe clogging/Covering/EEV
1071
Slave1 Fan Control part defect/Ref. overcharge
Fan PCB not received the data
1072 communication 2. ODU fan motor assemble condition abnormal
Slave2 from Main PCB
defect (Coil disconnection/Short/Insulation damage)
1073
Slave3 3. Fan PCB assembly defect
1074
No
Is fan motor assemble Check ODU fan motor assemble condition and locking
condition normal? → Reassemble or replace if abnormality found
Yes
No 1.Check fan motor U,V,W connector connection condition
Is fan motor wire connection → Reassemble wire if abnormality found
condition normal? 2.Check fan motor wire disconnection
→ Replace ODU fan motor if abnormality found
Yes
No
Yes
52
Error No. Error Type Error Point Main Reasons
No
Is wiring between fan motor 1. Check DC_Link Wire connection
and PCB normal? 2. DC_Link
→ Replace wire if abnormality found
Yes
No
Measure DC_Link voltage
Is DC_Link voltage normal?
→ Check Inverter PCB if voltage is below 380V
Yes
No
Is Fan PCB assembly normal? Replace fan PCB assembly
Yes
53
Error No. Error Type Error Point Main Reasons
113*
Master
1131
Slave1 Outdoor unit liquid Abnormal sensor resis- 1. Defective temperature sensor connection
1132 pipe (condenser) tem- tance value 2. Defective temperature sensor (Open / Short)
Slave2 perature sensor error (Open/Short) 3. Defective outdoor unit PCB
1133
Slave3
1134
114*
Master
1141
Outdoor Unit
Slave1 Abnormal sensor resis- 1. Defective temperature sensor connection
Subcooling Inlet
1142 tance value 2. Defective temperature sensor (Open/Short)
Temperature Sensor
Slave2 (Open/Short) 3. Defective outdoor PCB
Error
1143
Slave3
1144
115*
Master
1151
Outdoor Unit
Slave1 Abnormal sensor resis- 1. Defective temperature sensor connection
Subcooling Outlet
1152 tance value 2. Defective temperature sensor (Open/Short)
Temperature Sensor
Slave2 (Open/Short) 3. Defective outdoor PCB
Error
1153
Slave3
1154
Is temperature sensor No
connector connections Check and correct connection
are normal?
Yes
Yes
* Sensor resistance 100 kΩover (open) or 100 Ω below (short) will generate error
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ
Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ
54
Error No. Error Type Error Point Main Reasons
145*
Master
1451 Communication Error 1. Power cable or communication
Slave1 between Cycle controller of Master unit of cable is not connected
1452 Master unit can’t receive signal
Slave2 (Main PCB External 2. Defect of outdoor Cycle/External
from External controller
1453 PCB) PCB
Slave3
1454
No
Is communication cable Re-connect communication cable
connected correctly?
Yes
No
Is Main PCB normal Replace Main PCB
Yes
* The Method of checking Main PCB and External PCB (If normal, communication LED blinks)
55
Error No. Error Type Error Point Main Reasons
Yes
Yes
Is EEV connector No
Connect EEV connector
connected normally?
Yes
56
Error
Error Type Error Point Main Reasons
No.
Yes
Yes
Yes
Yes
After opposite
mode operation to present No If the same error is occurred in
mode, is the same error near future replace 4way valve
occurred again?
Yes
57
Error No. Error Type Error Point Main Reasons
182*
Master 1821 Communication Error Failure Receiving Signal
1. Failure Receiving Signal Between
Slave1 1822 Between Main and Sub Between Main and Sub
Main and Sub Micom
Slave2 1823 Micom of External PCB Micom
Slave3 1824
Communication Between
Main-Sub Micom
LED (Yellow) Blinking
No
’ the
Press
Rest Button *
No
No
Replay
Replace External PCB
On-boarding *
58
Error No. Error Type Error Point Main Reasons
193*
Master
1931 1. Fan PCBA IPM Connection Condition Abnormal
Slave1 2. Outdoor Unit Fan Motor Operation Abnormal
Fan PCB Heatsink Heatsink Temperature
1932 3. Outdoor Unit Fan PCB Assembly Defect
Temperature High is Over 90°C
Slave2 4. Overload Operation (Pipe Clogging/ Covering/EEV
1933 Defect/Ref. Overcharge)
Slave3
1934
No
Fan PCB IPM Connection 1. Check Fan PCBA Screw Connection Condition
Condition Normal? Reassemble or Manage if abnormality Found
Yes
No
1. Check Outdoor Unit Fan Motor Operation or Lock
Is ODU Fan Motor Normal?
Reassemble or Manage if abnormality Found
Yes
No
Is Fan PCB assembly 1. Reset
Normal? Replace Fan PCB Assembly
Yes
59
Error No. Error Type Error Point Main Reasons
194*
Master
1941
Slave1 Outdoor unit Fan PCB Outdoor unit Fan PCB 1. Defective temperature sensor connection
1942 heatsink temperature heatsink temperature 2. Defective temperature sensor (Open / Short)
Slave2 sensor error sensor error 3. Defective outdoor unit PCB
1943
Slave3
1944
Is temperature sensor No
connector connections Check and correct connection
are normal?
Yes
Yes
60
Error
Error type Error point Main reasons
No.
61
Error No. Error type Error point Main reasons
62
Error No. Error type Error point Main reasons
63
Error No. Error Type Error Point Main Reasons
No
Is Simple central No
controller setting 1. Set the slave mode with Simple central controller after reset.
normal?
Yes
64