Professional Documents
Culture Documents
Error Indicator
• This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
• Error mark is displayed on LGMV as shown in the table
• If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
- Error is displayed with unit number.
- Indoor unit error is displayed on IDU info, outdoor error is displayed on Operation Info located on right upper
side.
- If error occurs, click the error and trouble shooting guide is provided
0 2 - Inlet pipe temperature sensor of indoor unit Inlet pipe temperature sensor of indoor unit is open or short
Communication error : wired remote con- Failing to receive wired remote controller signal in indoor
Indoor unit related error
0 3 -
troller £ indoor unit unit PCB
0 4 - Drain pump Malfunction of drain pump
Communication error : outdoor unit £
0 5 - Failing to receive outdoor unit signal in indoor unit PCB
indoor unit
Outlet pipe temperature sensor of indoor Outlet pipe temperature sensor of indoor unit is open or
0 6 -
unit short
In case when the serial number marked on EEPROM of
0 9 - Indoor EEPROM Error
Indoor unit is 0 or FFFFFF
Disconnecting the fan motor connector/Failure of indoor
1 0 - Poor fan motor operation
fan motor lock
1 7 - Inlet Air temperature sensor of FAU Air temperature sensor of indoor unit is open or short
Master Outdoor Unit Inverter Compressor
1 Master Outdoor Unit Inverter Compressor Drive IPM Fault
IPM Fault
Slave1 Outdoor Unit Inverter Compressor
2 Slave1 Outdoor Unit Inverter Compressor Drive IPM Fault
IPM Fault
Outdoor unit related error
2 1
Slave2 Outdoor Unit Inverter Compressor
3 Slave2 Outdoor Unit Inverter Compressor Drive IPM Fault
IPM Fault
Slave3 Outdoor Unit Inverter Compressor
4 Slave3 Outdoor Unit Inverter Compressor Drive IPM Fault
IPM Fault
Inverter Board Input Over Current(RMS) of Master Outdoor Unit Inverter Board Input Current excess
1
Master Outdoor Unit (RMS)
Inverter Board Input Over Current(RMS) of Slave1 Outdoor Unit Inverter Board Input Current excess
2
Slave1 Outdoor Unit (RMS)
2 2
Inverter Board Input Over Current(RMS) of Slave2 Outdoor Unit Inverter Board Input Current excess
3
Slave2 Outdoor Unit (RMS)
Inverter Board Input Over Current(RMS) of Slave3 Outdoor Unit Inverter Board Input Current excess
4
Slave3 Outdoor Unit (RMS)
1
Display Title Cause of Error
Master Outdoor Unit Inverter Compressor DC charging is not performed at Master Outdoor Unit after
1
DC link Low Voltage starting relay turn on.
Slave1 Outdoor Unit Inverter Compressor DC charging is not performed at Slave1 Outdoor Unit after
2
DC link Low Voltage starting relay turn on.
2 3
Slave2 Outdoor Unit Inverter Compressor DC charging is not performed at Slave2 Outdoor Unit after
3
DC link Low Voltage starting relay turn on.
Slave3 Outdoor Unit Inverter Compressor DC charging is not performed at Slave3 Outdoor Unit after
4
DC link Low Voltage starting relay turn on.
System is turned off by Master Outdoor Unit high pressure
1 Master Outdoor Unit High Pressure Switch
switch.
System is turned off by slave1 Outdoor Unit high pressure
2 Slave1 Outdoor Unit High Pressure Switch
switch.
2 4
System is turned off by slave2 Outdoor Unit high pressure
3 Slave2 Outdoor Unit High Pressure Switch
switch.
System is turned off by slave3 Outdoor Unit high pressure
4 Slave3 Outdoor Unit High Pressure Switch
switch.
Master Outdoor Unit Input Voltage High/ Master Outdoor Unit input voltage is over 487V or below
1
Low Voltage 270V
Slave1 Outdoor Unit Input Voltage High/ Slave1 Outdoor Unit input voltage is over 487V or below
2
Low Voltage 270V
2 5
Outdoor unit related error
Slave2 Outdoor Unit Input Voltage High/ Slave2 Outdoor Unit input voltage is over 487V or below
3
Low Voltage 270V
Slave3 Outdoor Unit Input Voltage High/ Slave3 Outdoor Unit input voltage is over 487V or below
4
Low Voltage 270V
Master Outdoor Unit Inverter Compressor The First Start Failure by Master Outdoor Unit Inverter
1
Start Failure Compressor Abnormality
Slave1 Outdoor Unit Inverter Compressor The First Start Failure by Slave1 Outdoor Unit Inverter
2
Start Failure Compressor Abnormality
2 6
Slave2 Outdoor Unit Inverter Compressor The First Start Failure by Slave2 Outdoor Unit Inverter
3
Start Failure Compressor Abnormality
Slave3 Outdoor Unit Inverter Compressor The First Start Failure by Slave3 Outdoor Unit Inverter
4
Start Failure Compressor Abnormality
Master Outdoor Unit Inverter DC link High System is turned off by Master Outdoor Unit DC Voltage
1
Voltage Over Charging
Slave1 Outdoor Unit Inverter DC link High System is turned off by Slave1 Outdoor Unit DC Voltage
2
Voltage Over Charging
2 8
Slave2 Outdoor Unit Inverter DC link High System is turned off by Slave2 Outdoor Unit DC Voltage
3
Voltage Over Charging
Slave3 Outdoor Unit Inverter DC link High System is turned off by Slave3 Outdoor Unit DC Voltage
4
Voltage Over Charging
Master Outdoor Unit Inverter Compressor Master Outdoor Unit Inverter Compressor Fault OR Drive
1
Over Current Fault
Slave1 Outdoor Unit Inverter Compressor Slave1 Outdoor Unit Inverter Compressor Fault OR Drive
2
Over Current Fault
2 9
Slave2 Outdoor Unit Inverter Compressor Slave2 Outdoor Unit Inverter Compressor Fault OR Drive
3
Over Current Fault
Slave3 Outdoor Unit Inverter Compressor Slave3 Outdoor Unit Inverter Compressor Fault OR Drive
4
Over Current Fault
2
Display Title Cause of Error
Master Outdoor Unit Constant Speed System is turned off by Master Outdoor Uunit Constant
1
Compressor2 High Discharge Temperature Speed Compressor2 High Discharge Temperature
Slave1 Outdoor Unit Constant Speed System is turned off by Slave1 Outdoor Unit Constant
2
Compressor2 High Discharge Temperature Speed Compressor2 High Discharge Temperature
3 0
Slave2 Outdoor Unit Constant Speed System is turned off by Slave2 Outdoor Unit Constant
3
Compressor2 High Discharge Temperature Speed Compressor2 High Discharge Temperature
Slave3 Outdoor Unit Constant Speed System is turned off by Slave3 Outdoor Unit Constant
4
Compressor2 High Discharge Temperature Speed Compressor2 High Discharge Temperature
Master Outdoor Unit Inverter Compressor System is turned off by Master Outdoor Unit Inverter
1
High Discharge Temperature Compressor High Discharge Temperature
Slave1 Outdoor Unit Inverter Compressor System is turned off by Slave1 Outdoor Unit Inverter
2
High Discharge Temperature Compressor High Discharge Temperature
3 2
Slave2 Outdoor Unit Inverter Compressor System is turned off by Slave2 Outdoor Unit Inverter
3
Discharge High Temperature Compressor High Discharge Temperature
Slave3 Outdoor Unit Inverter Compressor System is turned off by Slave3 Outdoor Unit Inverter
4
High Discharge Temperature Compressor High Discharge Temperature
Master Outdoor Unit Constant Speed System is turned off by Master Outdoor Uunit Constant
1
Compressor1 High Discharge Temperature Speed Compressor1 High Discharge Temperature
Slave1 Outdoor Unit Constant Speed System is turned off by Slave1 Outdoor Unit Constant
2
Compressor1 High Discharge Temperature Speed Compressor1 High Discharge Temperature
3 3
Outdoor unit related error
Slave2 Outdoor Unit Constant Speed System is turned off by Slave2 Outdoor Unit Constant
3
Compressor1 High Discharge Temperature Speed Compressor1 High Discharge Temperature
Slave3 Outdoor Unit Constant Speed System is turned off by Slave3 Outdoor Unit Constant
4
Compressor1 High Discharge Temperature Speed Compressor1 High Discharge Temperature
System is turned off by excessive increase of high pressure
1 High Pressure of Master Outdoor Unit
of Master Outdoor Unit
System is turned off by excessive increase of high pressure
2 High Pressure of Slave1 Outdoor Unit
of Slave1 Outdoor Unit
3 4
System is turned off by excessive increase of high pressure
3 High Pressure of Slave2 Outdoor Unit
of Slave2 Outdoor Unit
System is turned off by excessive increase of high pressure
4 High Pressure of Slave3 Outdoor Unit
of Slave3 Outdoor Unit
System is turned off by excessive decrease of low pressure
1 Low Pressure of Master Outdoor Unit
of Master Outdoor Unit
System is turned off by excessive decrease of low pressure
2 Low Pressure of Slave1 Outdoor Unit
of Slave1 Outdoor Unit
3 5
System is turned off by excessive decrease of low pressure
3 Low Pressure of Slave2 Outdoor Unit
of Slave2 Outdoor Unit
System is turned off by excessive decrease of low pressure
4 Low Pressure of Slave3 Outdoor Unit
of Slave3 Outdoor Unit
Master Outdoor Unit Low Pressure Ratio Master Outdoor Unit stayed under low pressure limit for 3
1
Limited minutes
Slave1 Outdoor Unit Low Pressure Ratio Slave1 Outdoor Unit stayed under low pressure limit for 3
2
Limited minutes
3 6
Slave2 Outdoor Unit Low Pressure Ratio Slave2 Outdoor Unit stayed under low pressure limit for 3
3
Limited minutes
Slave3 Outdoor Unit Low Pressure Ratio Slave3 Outdoor Unit stayed under low pressure limit for 3
4
Limited minutes
3
Display Title Cause of Error
Master Outdoor Unit Inverter Compressor Master Outdoor Unit Inverter Compressor CT Sensor open
1
CT Sensor Fault or short
Slave1 Outdoor Unit Inverter Compressor Slave1 Outdoor Unit Inverter Compressor CT Sensor open
2
CT Sensor Fault or short
4 0
Slave2 Outdoor Unit Inverter Compressor Slave2 Outdoor Unit Inverter Compressor CT Sensor open
3
CT Sensor Fault or short
Slave3 Outdoor Unit Inverter Compressor Slave3 Outdoor Unit Inverter Compressor CT Sensor open
4
CT Sensor Fault or short
Master Outdoor Unit Inverter Compressor Master Outdoor Unit Inverter Compressor Discharge
1
Discharge Temperature Sensor Fault Temperature Sensor open or short
Slave1 Outdoor Unit Inverter Compressor Slave1 Outdoor Unit Inverter Compressor Discharge
2
Discharge Temperature Sensor Fault Temperature Sensor open or short
4 1
Slave2 Outdoor Unit Inverter Compressor Slave2 Outdoor Unit Inverter Compressor Discharge
3
Discharge Temperature Sensor Fault Temperature Sensor open or short
Slave3 Outdoor Unit Inverter Compressor Slave3 Outdoor Unit Inverter Compressor Discharge
4
Discharge Temperature Sensor Fault Temperature Sensor open or short
Outdoor unit related error
4
Display Title Cause of Error
Master Outdoor Unit Heat Exchanger Master Outdoor Unit Heat Exchanger Temperature
1
Temperature Sensor (Front side) Fault Sensor(Front side) open or short
Slave1 Outdoor Unit Heat Exchanger Slave1 Outdoor Unit Heat Exchanger Temperature Sensor
2
Temperature Sensor (Front side) Fault (Front side) open or short
4 5
Slave2 Outdoor Unit Heat Exchanger Slave2 Outdoor Unit Heat Exchanger Temperature
3
Temperature Sensor (Front side) Fault Sensor(Front side) open or short
Slave3 Outdoor Unit Heat Exchanger Slave3 Outdoor Unit Heat Exchanger Temperature
4
Temperature Sensor (Front side) Fault Sensor(Front side) open or short
Master Outdoor Unit Suction Temperature Master Outdoor Unit Suction Temperature Sensor open or
1
Sensor Fault short
Slave1 Outdoor Unit Suction Temperature Slave1 Outdoor Unit Suction Temperature Sensor open or
2
Sensor Fault short
4 6
Slave2 Outdoor Unit Suction Temperature Slave2 Outdoor Unit Suction Temperature Sensor open or
3
Sensor Fault short
Slave3 Outdoor Unit Suction Temperature Slave3 Outdoor Unit Suction Temperature Sensor open or
4
Sensor Fault short
Master Outdoor Unit Constant Speed
Master Outdoor Unit Constant Speed Compressor1
1 Compressor1 Discharge Temperature
Discharge Temperature Sensor open or short
Sensor Fault
Outdoor unit related error
5
Display Title Cause of Error
Omitting connection of R, S, T power of
1 Omitting connection of Master outdoor unit
Master Outdoor Unit
Omitting connection of R, S, T power of
2 Omitting connection of Slave1 Outdoor Unit
Slave1 Outdoor Unit
5 0
Omitting connection of R, S, T power of
3 Omitting connection of Slave2 Outdoor Unit
Slave2 Outdoor Unit
Omitting connection of R, S, T power of
4 Omitting connection of Slave3 Outdoor Unit
Slave3 Outdoor Unit
Excessive connection of indoor units compared to capacity
1 Excessive capacity of indoor units
of Outdoor Unit
5 1
Excessive capacity of indoor units from Excessive connection of indoor units compared to capacity
2
zoning branches of zoning branches of HR Unit
Communication error : inverter PCB ¡ Failing to receive inverter signal at main PCB of Master
1
Main PCB Outdoor Unit
Communication error : inverter PCB ¡ Failing to receive inverter signal at main PCB of Slave1
2
Main PCB Outdoor Unit
5 2
Communication error : inverter PCB ¡
Outdoor unit related error
5 9 1 Error of series installation In the case of installing smaller outdoor unit as master unit
6
Display Title Cause of Error
Inverter PCB EEPROM Error of Master
1 Access Error of Inverter PCB of Master Outdoor Unit
Outdoor Unit
Inverter PCB EEPROM Error of Slave1
2 Access Error of Inverter PCB of Slave1 Outdoor Unit
Unit
6 0
Inverter PCB EEPROM Error of Slave2
3 Access Error of Inverter PCB of Slave2 Outdoor Unit
Unit
Inverter PCB EEPROM Error of Slave3
4 Access Error of Inverter PCB of Slave3 Outdoor Unit
Unit
1 Master Outdoor Unit Fan Lock Restriction of Master Outdoor Unit
2 Slave1 Outdoor Unit Fan CT Sensor Error Slave1 Outdoor Unit Fan CT Sensor open or short
7 5
3 Slave2 Outdoor Unit Fan CT Sensor Error Slave2 Outdoor Unit Fan CT Sensor open or short
4 Slave3 Outdoor Unit Fan CT Sensor Error Slave3 Outdoor Unit Fan CT Sensor open or short
7
Display Title Cause of Error
Master Outdoor Unit Fan DC Link High
1 Master Outdoor Unit Fan DC Link High Voltage Error
Voltage Error
Slave1 Outdoor Unit Fan DC Link High
2 Slave1 Outdoor Unit Fan DC Link High Voltage Error
Voltage Error
7 6
Slave2 Outdoor Unit Fan DC Link High
3 Slave2 Outdoor Unit Fan DC Link High Voltage Error
Voltage Error
Slave3 Outdoor Unit Fan DC Link High
4 Slave3 Outdoor Unit Fan DC Link High Voltage Error
Voltage Error
Master Outdoor Unit Fan Over Current
1 Master Outdoor Unit Fan Current is over 5A
Error
Slave1 Outdoor Unit Fan Over Current
2 Slave1 Outdoor Unit Fan is over 5A
Error
7 7
Slave2 Outdoor Unit Fan Over Current
3 Slave2 Outdoor Unit Fan is over 5A
Error
Slave3 Outdoor Unit Fan Over Current
4 Slave3 Outdoor Unit Fan is over 5A
Error
Outdoor unit related error
8
Display Title Cause of Error
Communication Error Between Master Failing to receive Slave Unit signal at main PCB of Master
1
Outdoor Unit and Other Outdoor Unit Outdoor Unit
Communication Error Between Slave1 Failing to receive master and other Slave Unit signal at
2
Outdoor Unit and Other Outdoor Unit main PCB of Slave1 Outdoor Unit
1 0 4
Communication Error Between Slave2 Failing to receive master and other Slave Unit signal at
3
Outdoor Unit and Other Outdoor Unit main PCB of Slave2 Outdoor Unit
Communication Error Between Slave3 Failing to receive master and other Slave Unit signal at
4
Outdoor Unit and Other Outdoor Unit main PCB of Slave3 Outdoor Unit
Master Outdoor Unit Fan PCB
1 Failing to receive fan signal at main PCB of master unit.
Communication Error
Slave1 Outdoor Unit Fan PCB
2 Failing to receive fan signal at main PCB of Slave1 unit.
Communication Error
1 0 5
Slave2 Outdoor Unit Fan PCB
3 Failing to receive fan signal at main PCB of Slave2 unit.
Communication Error
Slave3 Outdoor Unit Fan PCB
4 Failing to receive fan signal at main PCB of Slave3 unit.
Communication Error
Outdoor unit related error
1 Master Outdoor Unit FAN IPM Fault Error Instant Over Current at Master Outdoor Unit Fan IPM
2 Slave1 Outdoor Unit FAN IPM Fault Error Instant Over Current at Slave1 Outdoor Unit Fan IPM
1 0 6
3 Slave2 Outdoor Unit FAN IPM Fault Error Instant Over Current at Slave2 Outdoor Unit Fan IPM
4 Slave3 Outdoor Unit FAN IPM Fault Error Instant Over Current at Slave3 Outdoor Unit Fan IPM
Master Outdoor Unit Fan DC Link Low Master Outdoor Unit Fan DC Link Input Voltage is under
1
Voltage Error 380V
Slave1 Outdoor Unit Fan DC Link Low Slave1 Outdoor Unit Fan DC Link Input Voltage is under
2
Voltage Error 380V
1 0 7
Slave2 Outdoor Unit Fan DC Link Low Slave2 Outdoor Unit Fan DC Link Input Voltage is under
3
Voltage Error 380V
Slave3 Outdoor Unit Fan DC Link Low Slave3 Outdoor Uni Fan DC Link Input Voltage is under
4
Voltage Error 380V
Master Outdoor Unit Liquid pipe Liquid pipe temperature sensor of Master Outdoor Unit is
1
Temperature Sensor Error open or short
Slave1 Outdoor Unit Liquid pipe Liquid pipe temperature sensor of slave1 Outdoor Unit is
2
Temperature Sensor Error open or short
1 1 3
Slave2 Outdoor Unit Liquid pipe Liquid pipe temperature sensor of slave2 Outdoor Unit is
3
Temperature Sensor Error open or short
Slave3 Outdoor Unit Liquid pipe Liquid pipe temperature sensor of slave3 Outdoor Unit is
4
Temperature Sensor Error open or short
9
Display Title Cause of Error
Master Outdoor Unit Subcooling Outlet Master Outdoor Unit Subcooling Outlet Temperature
1
Temperature Sensor Error Sensor open or short
Slave1 Outdoor Unit Subcooling Outlet Slave1 Outdoor Unit Subcooling Outlet Temperature
2
Temperature Sensor Error Sensor open or short
1 1 5
Slave2 Outdoor Unit Subcooling Outlet Slave2 Outdoor Unit Subcooling Outlet Temperature
3
Temperature Sensor Error Sensor open or short
Slave3 Outdoor Unit Subcooling Outlet Slave3 Outdoor Unit Subcooling Outlet Temperature
4
Temperature Sensor Error Sensor open or short
Failure of operation mode conversion at
1 Pressure unbalance between Outdoor Units
Master Outdoor Unit
Failure of operation mode conversion at
2 Pressure unbalance between Outdoor Units
Slave1 Outdoor Unit
1 5 1
Failure of operation mode conversion at
3 Pressure unbalance between Outdoor Units
Slave2 Outdoor Unit
Failure of operation mode conversion at
4 Pressure unbalance between Outdoor Units
Slave3 Outdoor Unit
Master upper part heat exchanger temper- Master Outdoor Unit upper part temperature sensor
1
ature sensor error open/short
Slave1 upper part heat exchanger temper- Slave1 Outdoor Unit upper part temperature sensor
2
ature sensor error open/short
1 5 3
Outdoor unit related error
Slave2 upper part heat exchanger temper- Slave2 Outdoor Unit upper part temperature sensor
3
ature sensor error open/short
Slave3 upper part heat exchanger temper- Slave3 Outdoor Unit upper part temperature sensor
4
ature sensor error open/short
Master lower part heat exchanger tempera- Master Outdoor Unit lower part temperature sensor
1
ture sensor error open/short
Slave1 lower part heat exchanger tempera- Slave1 Outdoor Unit lower part temperature sensor
2
ture sensor error open/short
1 5 4
Slave2 lower part heat exchanger tempera- Slave2 Outdoor Unit lower part temperature sensor
3
ture sensor error open/short
Slave3 lower part heat exchanger tempera- Slave3 Outdoor Unit lower part temperature sensor
4
ture sensor error open/short
Master Outdoor Unit Constant Speed Comp locking, Check Valve leakage, comp dielectric break
1
Compressor 1 Fault down at Master Outdoor Unit
Slave1 Outdoor Unit Constant Speed Comp locking, Check Valve leakage, comp dielectric at
2
Compressor 1 Fault Slave1 Outdoor Unit
1 7 3
Slave2 Outdoor Unit Constant Speed Comp locking, Check Valve leakage, comp dielectric at
3
Compressor 1 Fault Slave2 Outdoor Unit
Slave3 Outdoor Unit Constant Speed Comp locking, Check Valve leakage, comp dielectric at
4
Compressor 1 Fault Slave3 Outdoor Unit
Master Outdoor Unit Constant Speed Comp locking, Check Valve leakage, comp dielectric break
1
Compressor 2 Fault down at Master Outdoor Unit
Slave1 Outdoor Unit Constant Speed Comp locking, Check Valve leakage, comp dielectric at
2
Compressor 2 Fault Slave1 Outdoor Unit
1 7 4
Slave2 Outdoor Unit Constant Speed Comp locking, Check Valve leakage, comp dielectric at
3
Compressor 2 Fault Slave2 Outdoor Unit
Slave3 Outdoor Unit Constant Speed Comp locking, Check Valve leakage, comp dielectric at
4
Compressor 2 Fault Slave3 Outdoor Unit
10
Display Title Cause of Error
1 Master outdoor unit Main Board Main- Master Outdoor Unit Main Board Main-Sub Micom communi-
Sub Micom communication error cation failed
Slave1 outdoor unit Main Board Main- Slave1 Outdoor Unit Main Board Main-Sub Micom communi-
2
Sub Micom communication error cation failed
1 8 2
Slave2 outdoor unit Main Board Main- Slave2 Outdoor Unit Main Board Main-Sub Micom communi-
3 Sub Micom communication error cation failed
Slave3 outdoor unit Main Board Main- Slave3 Outdoor Unit Main Board Main-Sub Micom communi-
4 Sub Micom communication error cation failed
Master Inv. oil balance pipe Temperature Master Outdoor Unit oil balance temperature Sensor open or
1 Sensor error short
Slave1 Inv. oil balance pipe Temperature Slave1 Outdoor Unit oil balance temperature Sensor open or
2 Sensor error short
1 8 4
3 Slave2 Inv. oil balance pipe Temperature Slave2 Outdoor Unit oil balance temperature Sensor open or
Sensor error short
Slave3 Inv. oil balance pipe Temperature Slave3 Outdoor Unit oil balance temperature Sensor open or
4 Sensor error short
Master const.1 oil balance pipe Master Outdoor Unit oil balance temperature Sensor open or
1 Temperature Sensor error short
Slave1 const.1 oil balance pipe Slave1 Outdoor Unit oil balance temperature Sensor open or
2 Temperature Sensor error short
1 8 5
Slave2 const.1 oil balance pipe Slave2 Outdoor Unit oil balance temperature Sensor open or
3 Temperature Sensor error short
Outdoor unit related error
Slave3 const.1 oil balance pipe Slave3 Outdoor Unit oil balance temperature Sensor open or
4 Temperature Sensor error short
Master const.2 oil balance pipe Master Outdoor Unit oil balance temperature Sensor open or
1 Temperature Sensor error short
Slave1 const.2 oil balance pipe Slave1 Outdoor Unit oil balance temperature Sensor open or
2 Temperature Sensor error short
1 8 6
Slave2 const.2 oil balance pipe Slave2 Outdoor Unit oil balance temperature Sensor open or
3 Temperature Sensor error short
Slave3 const.2 oil balance pipe Slave3 Outdoor Unit oil balance temperature Sensor open or
4
Temperature Sensor error short
1 Excessive increase of Master Outdoor Master Outdoor Unit Fan Inverter PCB Temperature is Over
Unit Fan PCB Heat Sink Temperature 95°C
Excessive increase of Slave1 Outdoor Slave1 Outdoor Unit Fan Inverter PCB Temperature is Over
2 Unit Fan PCB Heat Sink Temperature 95°C
1 9 3
Excessive increase of Slave2 Outdoor Slave2 Outdoor Unit Fan Inverter PCB Temperature is Over
3 Unit Fan PCB Heat Sink Temperature 95°C
Excessive increase of Slave3 Outdoor Slave3 Outdoor Unit Fan Inverter PCB Temperature is Over
4 Unit Fan PCB Heat Sink Temperature 95°C
Master Outdoor Unit Fan PCB Heat Sink Master Outdoor Unit Fan PCB Heat Sink Temperature
1 Temperature Sensor Error Sensor open or short
Slave1 Outdoor Unit Fan PCB Heat Sink Slave1 Outdoor Unit Fan PCB Heat Sink Temperature
2 Temperature Sensor Error Sensor open or short
1 9 4
Slave2 Outdoor Unit Fan PCB Heat Sink Slave2 Outdoor Unit Fan PCB Heat Sink Temperature
3 Temperature Sensor Error Sensor open or short
Slave3 Outdoor Unit Fan PCB Heat Sink Slave3 Outdoor Unit Fan PCB Heat Sink Temperature
4 Temperature Sensor Error Sensor open or short
11
Display Title Cause of Error
2 0 1 C+ HR unit1 Liqiud sensor error Liquid pipe sensor of HR unit open or short
#HR
C+ HR unit1 Sub Cooling Pipe In sensor
2 0 2 #HR Sub Cooling Pipe In sensor of HR unit open or short
error
C+ HR unit1 Sub Cooling Pipe Out sen-
2 0 3 #HR Sub Cooling Pipe Out sensor of HR unit. open or short
sor error
C+
2 0 4 #HR Communication error Failing to receive HR unit signal at outdoor unit
C : HR unit
# : HR unit Number
12
Error
Error Type Error Point Main Reasons
No.
Is sensor properly No
Connect properly to PCB
connected to PCB?
Yes
Yes
** In case the value is more than 100kΩ (open) or less than 100Ω (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature(±5% margin) Normal
Air temp sensor: 10°C = 20.7kΩ : 25°C= 10kΩ : 50°C= 3.4kΩ
Pipe temp sensor: 10°C = 10kΩ : 25°C= 5kΩ : 50°C= 1.8kΩ
13
Error
Error Type Error Point Main Reasons
No.
Yes
Yes
* If there is no remote controller to replace : Use another unitʼs remote controller doing well
** Check cable : Contact failure of connected portion or extension of cable are main cause
Check any surrounded noise ( check the distance with main power cable)
make safe distance from the devices generate electromagnetic wave
*** After replacing indoor unit PCB, do Auto Addressing & input unitʼs address if connected to central controller.
(All the indoor units connected should be turned on before Auto Addressing
14
Error
Error Type Error Point Main Reasons
No.
No
Drain pump blocked by Check the drain head height
foreign particles? and slope***
Yes
15
Error
Error Type Error Point Main Reasons
No.
Yes
Yes
Check if the
communication cable is
properly connected No
Re connect communication cable
to indoor / outdoor
terminal block?*
Outdoor PCB fault
Replace after checking
Yes
Indoor PCB fault
Replace after checking
16
Error
Error Type Error Point Main Reasons
No.
- Replace the indoor unit PCB, and then make sure to perform Auto addressing and input the address of central control
17
Error
Error Type Error Point Main Reasons
No.
Indoor unit BLDC fan motor Indoor BLDC fan motor 1. Motor connector connection fault
10 failure feedback signal is absent 2. Indoor PCB fault
(for 50 sec.) 3. Motor fault
Is connector No
connection proper? Connect properly
Yes
Is fan motor No
Replace indoor unit fan motor
normal?*
Yes
18
Error
Error Type Error Point Main Reasons
No.
Yes
Yes
1.Check inverter PCB assembly U,V,W connector
Is compressor connection condition
No 2. Check wire disconnection and wiring
Wire connection
condition normal? 3. Check compressor terminal connection condition
(bad contact)
→ Reassemble if abnormality found
Yes
19
Error
Error Type Error Point Main Reasons
No.
22*
1. Overload operation (Pipe
Master clogging/Covering/EEV defect/Ref.
221 overcharge)
Slave1 Inverter PCB Assembly
2. Compressor damage(Insulation
222 AC Input Current Over Error input 3 phase power damage/Motor damage)
current is over limited
Slave2 3. Input voltage low
value(22A)
223 4. Power Line Misconnection
Slave3 5. Inverter PCB Assembly damage
224 (Input current sensing part)
Yes
1. Check inverter PCB assembly U,V,W connector
connection condition
Is compressor
No 2. Check wire disconnection and wiring
Wire connection
3. Check compressor terminal connection condition
condition normal?
(bad contact)
→ Reassemble if abnormality found
Yes
Yes
No Check
Is input voltage normal? R~S/S~T/T~R phase voltage is 380V 10%
R~N/S~N/T~N phase voltage is 220V 10%
→ Check connection condition and wiring if power is
abnormal
Yes
Yes
20
Error
Error Type Error Point Main Reasons
No.
23*
Master 1. DC Link terminal misconnection/terminal
231 contact fault
Slave1 2. Starting relay damage
232 Inverter Compressor DC DC Voltage isn't charged
Link Low Voltage 3. Condenser damage
after starting relay on
Slave2 4. Inverter PCB assembly damage
233 (DC Link voltage sensing part)
Slave3 5. Input voltage low
234
Yes
Check
R~S/S~T/T~R phase voltage is 380V 10%
No R~N/S~N/T~N phase voltage is 220V 10%
Is input voltage normal?
→ Check connection condition and wiring if power is
abnormal
Yes
Yes
Is inverter PCB assembly power No Check connection between inverter PCB assembly and
connection normal? bridge diode(misconnection, disconnection)
→ wiring again if abnormality found
Yes
Yes
21
Error
Error Type Error Point Main Reasons
No.
Yes
No
Is SVC valve open? Open SVC valve
Yes
Yes
Yes
Is high pressure of No
LGMV similar as Replace high pressure sensor
at manifold gauge?
Yes
22
Error
Error Type Error Point Main Reasons
No.
25*
Master
251
Slave1 Input voltage is over limited 1. Input voltage abnormal (T-N)
252 Input Voltage high/low value of the product (270V 2. Outdoor unit inverter PCB assembly dam-
Slave2 or less, 487V or more) age (input voltage sensing part)
253
Slave3
254
Yes
Check
R~S/S~T/T~R phase voltage is 380V 10%
No R~N/S~N/T~N phase voltage is 220V 10%
Is input voltage normal?
→ Check connection condition and wiring if power is
abnormal
Yes
Is inverter PCB assembly power No Check connection between inverter PCB assembly and
connection normal? bridge diode(misconnection, disconnection)
→ wiring again if abnormality found
Yes
Yes
23
Error
Error Type Error Point Main Reasons
No.
26*
Master
1. Overload operation
261
(Pipe clogging/Covering/EEV defect/Ref.
Slave1 overcharge)
262 Inverter compressor starting Starting failure because of
2. Compressor damage
failure Error compressor abnormality
Slave2 (Insulation damage/Motor damage)
263 3. Compressor wiring fault
Slave3 4. ODU inverter PCB damage (CT)
264
Yes
Yes
24
Error
Error Type Error Point Main Reasons
No.
28*
Master
281
Slave1 1. Input voltage abnormal (R,S,T,N)
282 Inverter DC link high Inv PCB DC link voltage
voltage error supplied over 780V 2. ODU inverter PCB damage
Slave2 (DC Link voltage sensing part)
283
Slave3
284
Yes
Check
R~S/S~T/T~R phase voltage is 380V 10%
No R~N/S~N/T~N phase voltage is 220V 10%
Is input voltage normal?
→ Check connection condition and wiring if power is
abnormal
Yes
Yes
25
Error
Error Type Error Point Main Reasons
No.
29*
Master
1. Overload operation
291
(Pipe clogging/Covering/EEV defect/Ref.
Slave1 overcharge)
292 Inverter compressor over Inverter compressor input
2. Compressor damage(Insulation
current current is over 30A
Slave2 damage/Motor damage)
293 3. Input voltage low
Slave3 4. ODU inverter PCB assembly damage
294
Check
No R~S/S~T/T~R phase voltage is 380V 10%
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V 10%
→ Check connection condition and wiring if power is
abnorma
Yes
Yes
26
Error
Error Type Error Point Main Reasons
No.
System is turned off by
30* Master Outdoor Unit
Master Outdoor Unit 1.Constant Speed Compressor 2 Discharge
Master 301 Constant
Constant Temperature Sensor Fault
Slave1 302 Speed Compressor 2 2. Refrigerant Short/Leakage
Slave2 303 Speed Compressor 2
Discharge Temperature 3. EEV Fault
Slave3 304 Discharge Temperature
Sensor
Sensor
Yes
* Resistance value of discharge temperature sensor
10C = 362k, 25C= 200k, 50C= 82k, 100C= 18.5k
Is EEV in
outdoor unit normal No
at heating operation? Replace outdoor unit EEV
[refer electric
component part]
Yes
Replace strainer
27
Error
Error Type Error Point Main Reasons
No.
1. Defect of high pressure sensor
34* 2. Defect of indoor or outdoor unit fan
Error happens 3. Deformation because of damage of refrigerant pipe
Master because of 3 times 4. Over-charged refrigerant
341 successive compres- 5. Defective indoor / outdoor unit EEV
Over-increase of dis-
Slave1 sor off due to over- 6. When blocked
charge pressure of
342 increase of high pres-
compressor - Outdoor unit is blocked during cooling
Slave2 sure by high pressure
- Indoor unit filter is blocked during heating
343 sensor
7. SVC valve is clogged
Slave3
344 8. PCB defect of outdoor unit
10. Indoor unit pipe temperature sensor defect
Yes
Yes
Is refrigerant No
amount normal? Adjust refrigerant amount
[refer refrigerant part]
Yes
Is fan normal?
(Indoor fan during heating No Replace related parts
Outdoor fan during cooling) (Refer to Error 105~107)
Yes
Is filter blocked
(Heating:indoor, No Clean indoor filter (heating)
Cooling:outdoor /outdoor heat exchanger (cooling)?
heat exchanger)?
Yes
Yes
28
Error
Error Type Error Point Main Reasons
No.
1. Defective low pressure sensor
35* 2. Defective outdoor/indoor unit fan
Error happens 3. Refrigerant shortage/leakage
Master because of 3 times 4. Deformation because of damage of refrigerant pipe
351 successive compres- 5. Defective indoor / outdoor unit EEV
Excessive drop of
Slave1 discharge pressure sor off due to exces- 6. Covering / clogging
352 of compressor sive drop of low pres- (outdoor unit covering during the cooling mode/
Slave2 sure by the low pres-
indoor unit filter clogging during heating mode)
353 sure sensor
7. SVC valve clogging
Slave3 8. Defective outdoor unit PCB
354
9. Defective indoor unit pipe sensor
Yes
No
Are communication cable/ check communication/
piping normal? piping correction.
Yes
Is amount of refrigerant No No
Is there pipe crack or trace Adjust the amount of
normal?
of refrigerant leakage? refrigerant (Additive charge)
[refer refrigerant part]
Yes Yes
No
Is strainer Ok?* Replace the strainer
Yes
Yes
* If the temperature difference between inlet and outlet of strainer
Check indoor / outdoor unit LEV is so large that frost or ice formation can be seen or confirmed
Check Indoor unit PCB
Check indoor / outdoor unit then clogging of strainer should be checked
installation conditions (Notice: it is not full ice forming of strainer, in case that there is
not at inlet portion but at outlet portion)
29
Error
Error Type Error Point Main Reasons
No.
40*
Master
401
Slave1 Micom input voltage isn't 1. Input voltage abnormal (T-N)
402 Inverter compressor CT
within 2.5V ±0.3V at initial 2. ODU inverter PCB damage
sensor error
Slave2 state of power supply (CT sensing part)
403
Slave3
404
Yes
Check
R~S/S~T/T~R phase voltage is 380V±10%
No
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V±10%
→ Check connection condition and wiring if power is
abnormal
Yes
No Replace inverter PCB assembly
Is inverter PCB assembly normal?
Yes
30
Error No. Error Type Error Point Main Reasons
41*
Slave1 472 1. Defective connection of the
(Inverter)
Slave2 473
Master 411 compressor discharge pipe tem-
Slave3 474 Compressor dis-
Slave1 412 perature sensor
48* charge pipe tem- Sensor measurement
Slave2 413 2. Defective discharge pipe com-
(Constant 2) perature sensor valve is abnormal
Slave3 414 pressor sensor of the compres-
Master 481 (Open/Short)
47* error sor (open/short)
Slave1 482
(Constant 1)
Slave2 483 3. Defective outdoor PCB
Master 471
Slave3 484
Yes
Is the resistance of No
Replace sensor
sensor normal?*
Yes
Is sensor resistance No
value same as temperature Replace corresponding outdoor PCB
value of LGMV?
Yes
* Error is generated if the resistance is more than 5M(open) and less than 2k (short)
31
Error
Error Type Error Point Main Reasons
No.
42*
Master 421 Abnormal value of 1. Bad connection of low pressure connector
Slave1 422 Sensor error of low sensor 2. Defect of low pressure connector (Open/Short)
Slave2 423 pressure (Open/Short) 3. Defect of outdoor PCB
Slave3 424
43*
Master 431 Abnormal value of 1. Bad connection of high pressure connector
Sensor error of high
Slave1 432 sensor 2. Defect of high pressure connector (Open/Short)
pressure
Slave2 433 (Open/Short) 3. Defect of outdoor PCB
Slave3 434
Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly?
Yes
After replacement of No
Replace corresponding
outdoor unit main PCB
pressure sensor
is the system normal?
Yes
END
32
Error No. Error Type Error Point Main Reasons
49*
Master 491 Outdoor Unit IPM Outdoor Unit IPM 1. Bad connection of air temperature connector
Slave1 492 Temperature Temperature Sensor 2. Defect of air temperature connector(Open/Short)
Slave2 493 Sensor Fault Open or Short 3. Defect of outdoor PCB
Slave3 494
Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly??
Yes
No
Is sensor value correct?* Replace sensor
Yes
* If value is 100kΩ ↑(open) or 100Ω ↓(short), error occurs
33
Error
Error Type Error Point Main Reasons
No.
50*
Master
501 1. Input Voltage abnormal (R,S,T,N)
Slave1 ODU 3phase power omis- Omitting one or more of 2. Check power Line connection condition
502 sion error R,S,T input power 3. Main PCB damage
Slave2 4. Inverter PCB input current sensor fault
503
Slave3
504
Yes
1. Check resistance between each terminal of compressor
Are the resistance (0.34~0.35±7%)
Between each phase and No 2. Check insulation resistance between compressor
insulation resistance of Inverter terminal and pipe (over 50M )
compressor normal? → Replace compressor if abnormality found
Yes
1.Check inverter PCB assembly U,V,W connector
Is compressor connection condition
No 2. Check wire disconnection and wiring
Wire connection
condition normal? 3. Check compressor terminal connection condition
(bad contact)
Yes → Reassemble if abnormality found
Yes
34
Error
Error Type Error Point Main Reasons
No.
1. 130% more than outdoor unit rated capacity
Over-Capacity 2. Wrong connection of communication
51*
(Sum of indoor unit capaci- Sum of indoor unit capaci- cable/piping
Master ty is more than outdoor ty exceed outdoor unit 3. Control error of slave outdoor unit Dip switch
511 capacity) capacity specification 4. Power supply defect of slave unit PCB
5. Defect of outdoor unit PCB
Yes
Yes Yes
Is communication
No
cables between outdoor units Re-connect
connected correctly?*
Yes
Yes
End
* In order to check
communication
cables between outdoor units,
check in order as below
: PCB connectors ‡
terminal block ‡
communication cables
35
Error
Error Type Error Point Main Reasons
No.
Is capacity sum of Indoor units Are quantity(max:8 IDU) and Check communication cables
No No
less than 48kBtu/h each branch capacity(max:48kBtu/h) of indoor between indoor, HR and
pipe of HR unit? units over installed each branch outdoor units
pipe of HR units?
Yes Yes
Yes
Re-connect
* In order to check communication cables between outdoor units, check in order as below:
PCB connectors terminal block communication cables
36
Error
Error Type Error Point Main Reasons
No.
No
Is communication cable
Re-connect communication cable
connected correctly?
Yes
No
Is MAIN PCB normal? Replace MAIN PCB
Yes
37
Error
Error Type Error Point Main Reasons
No.
Yes Yes
End
No
Is power supplied
Supply power
to indoor units?
Yes
In case of CH53, almost happened with CH05, the indoor units not operated actually are normal so check with
same method of CH05. and additionally check as shown as below and above flow chart
• Although the quantity of indoor units installed is same as LGMV data there may be a few indoor units with
which the number of communication is not increased with LGMV
• Although the quantity of indoor units installed is not same as LGMV data, and if communication of the indoor
unit displayed at LGMV is done well then the indoor unit suspected to have some problem (and is not appear at
LGMV) may have following problems
wrong connection of communication cable or power cable
fault of power / PCB / communication cable
duplication of indoor unit number
• If communication is not doing well wholly then the Auto Addressing is not done
• The case that CH53 appear at indoor unit also Auto Addressing is not done so indoor unit address may be
duplicated
* After replacement of indoor unit PCB, Auto Addressing should be done, if central controller is installed then the
central control address also should be input.
In case that only communication PCB is replaced above process is not needed
38
Error
Error Type Error Point Main Reasons
No.
54*
Wrong connection of 3Ø Wrong connection of 3Ø 1. Main PCB defect
Master 541
power supply cable power supply cable 2. No power of R,S,T supplied
Slave1 542 (Reverse direction / miss-
(Reverse direction / missing 3. Wring connection of R,S,T cables
Slave2 543 a phase) ing a phase) 4. Main Pcb Fuse failure
Slave3 544
Yes
Is CH 54 occurred again No
after reset MAIN End
circuit breaker?
Yes
No
Is main PCB fuse normal? Replace Fuse
Yes
39
Error
Error Type Error Point Main Reasons
No.
57*
1. Bad Connection Between Inv and Main
Master 571 Communication error : Main Failing to receive inverter
2. Communication Wire Noise Effect
Slave1 572 PCB signal at main PCB of
Outdoor Unit 3. ODU Main PCB Damage
Slave2 573 --> Inverter PCB
4. ODU Inv PCB Damage
Slave3 574
Is inverter PCB No
assembly 1. Replace Inverter PCB
normal?
Yes
No
40
Error
Error Type Error Point Main Reasons
No.
Yes
Recheck installation
condition
ON ON
Slave2
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
ON ON
Slave3
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
41
Error No. Error Type Error Point Main Reasons
60*
1. EEPROM contact defect/wrong insertion
Master 601 Inverter PCB EEP- EEPROM Access error
2. Different EEPROM Version
Slave1 602 ROM error and Check SUM error
3. ODU inverter PCB assembly damage
Slave2 603
Slave3 604
Yes
Yes
42
Error No. Error Type Error Point Main Reasons
Is ODU Fan Motor Assemble No Check ODU Fan Motor assemble condition and fan locking
condition normal? → Reassemble or replace if abnormality found
Yes
Yes
Yes
43
Error No. Error Type Error Point Main Reasons
69*
Master 691 Constant 1 CT Sensor
Constant 1 CT Sensor Constant 1 CT Sensor Error
Slave1 692 open or short of Outdoor
Error of Outdoor Unit
Slave2 693 Unit
Slave3 694
70*
Constant Speed Constant Speed
Master 701 1. Constant Speed Compressor 2 CT Sensor
Compressor 2 CT Compressor 2 CT Sensor
Slave1 702 defect
Sensor Error Open/short
Slave2 703
Slave3 704
Yes
44
Error No. Error Type Error Point Main Reasons
Check
No R~S/S~T/T~R phase voltage is 380V 10%
Is input voltage normal?
R~N/S~N/T~N phase voltage is 220V 10%
’ Check connection condition and wiring if power is abnormal
Yes
Yes
No
Is inverter PCB assembly Check inverter PCB assembly IPM normality
normal? ’ Replace inverter PCB assembly
Yes
45
Error No. Error Type Error Point Main Reasons
75*
1. Input voltage is abnormal(not 15V)
Master 751 Offset of micom which senses the
Fan CT sensor error
Slave1 752 fan motor phase current is not 2.5V 2. Fan PCB assembly defect
Slave2 753 3. Power wire open and connecting fault
Slave3 754 4. Inv PCB assembly defect
Yes
No
Is Fan PCB normal? 1. Replace Fan PCB
Yes
Is there any error No
1. Replace Fan PCB
when power reset?
Yes
46
Error No. Error Type Error Point Main Reasons
76*
Master 761 Fan DC Link High Voltage Fan PCB DC link voltage supplied 1. Input power abnormal
Slave1 762 Error over 780V 2. Fan PCB assembly defect
Slave2 763 3. Power wire connecting fault
Slave3 764
No
Is DC Link power normal?
1. Check DC Link wiring conditions
→ Rewire them if abnormality found.
Yes
Yes
Recheck power and
installation condition
47
Error No. Error Type Error Point Main Reasons
Yes
1.Check resistance between each motor output terminal
Are the resistance No LG motor : 8.8Ω±10%(25℃)
Between each phase and insulation Panasonic : 8.8Ω±10%(25℃)
resistance of motor output
terminal normal? 2. Check insulation resistance between ODU fan motor terminal(U,V,W) and pipe
(over 100M )
→ Replace fan motor if abnormality found
Yes
No
Is Fan PCB assembly normal? 1. Check fan PCB assembly IPM normal
→ Replace Fan PCB assembly
Yes
48
Error No. Error Type Error Point Main Reasons
Yes
1. Check resistance between each motor output terminal
Are the resistance No LG motor : 8.8Ω±10%(25℃) Panasonic : 8.8Ω±10%(25℃)
Between each phase and insulation 2. Check insulation resistance between ODU fan motor terminal(U,V,W) and pipe
resistance of motor output
terminal normal? (over 100M)
→ Replace fan motor if abnormality found
No
Check fan PCB assembly IPM normal
Is fan PCB assembly normal?
→ Replace Fan PCB assembly
Yes
49
Error No. Error Type Error Point Main Reasons
86*
Master 861
Main PCB EEPROM 1. No EEPROM
Slave1 862 EEPROM Access Error
Error 2. EEPROM wrong insertion
Slave2 863
Slave3 864
Yes
No
Correct check sum Replace Correct EEPROM
Yes
50
Error No. Error Type Error Point Main Reasons
87*
Master 871 Error occurs when checking the 1.EEPROM bad contact/wrong insertion
Fan PCB EEPROM
Slave1 872 EEPROM checksum as initializing 2.EEPROM Version is different
Error
Slave2 873 after power is supplied 3.ODU fan PCB assembly damage
Slave3 874
Yes
No
Is Fan PCB assembly normal? Replace fan PCB assembly
Yes
51
Error No. Error Type Error Point Main Reasons
104*
Master
11 041
Slave1 Communication Master displays ODU number 1.Loose connection of power cable/ communi-
12 042 Error Between which is not communicated. cation cable¸(Open/Short)
Slave2 Outdoors Slave displays own error number 2.Defect of each outdoor unit PCB
13 043
Slave3
14 044
Is communication No
cable installed Connect communication cable
normally?
Yes
Yes
Yes
ON ON
Slave2
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
ON ON
Slave3
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
52
Error No. Error Type Error Point Main Reasons
105*
Master
11 051
1. Wrong connection between Inverter and
Slave1 Communication error
Fan controller didn't receive signal Fan PCB
12 052 (Fan PCB Inverter
Slave2 PCB) from inverter controller 2. Fan PCB power not supplied
13 053 3. ODU Inv/Fan PCB defect
Slave3
14 054
Yes
Is inverter PCB No
communication LED(yellow) Check communication cable between Inverter PCB and fan PCB
blinking normally? ’ Reconnect or replace wire if abnormality found
Yes
No
No
Is fan PCB assembly normal? Fan PCB assembly
Yes Yes
53
Error No. Error Type Error Point Main Reasons
106*
Master 1. Overload operation (Pipe clogging/Covering/EEV
11 061 defect/Ref. overcharge
Slave1 ODU Fan PCB IPM protection circuit activation 2. ODU fan motor assemble condition abnormal
12 062
Slave2 IPM Fault (over current / overheating) (Coil disconnection/Short/Insulation damage)
13 063 3. Fan PCB heatsink assemble condition abnormal
Slave3
14 064 4. Fan PCB assembly defect
Yes
No 1.Check fan motor U,V,W connector connection condition
Is fan motor wire connection → Reassemble wire if abnormality found
condition normal? 2.Check fan motor wire disconnection
→ Replace ODU fan motor if abnormality found
Yes
No
Yes
54
Error No. Error Type Error Point Main Reasons
No
Is wiring between fan motor 1. Check DC_Link Wire connection
and PCB normal? 2. DC_Link
’ Replace wire if abnormality found
Yes
No
Measure DC_Link voltage
Is DC_Link voltage normal?
’ Check inverter PCB if voltage is below 380V
Yes
No
Is Fan PCB assembly normal? Replace fan PCB assembly
Yes
55
Error No. Error Type Error Point Main Reasons
113*
Master
1. Defective temperature sensor con-
11 131
Slave1 Outdoor unit liquid pipe nection
Abnormal sensor resistance value
12 132 (condenser) temperature 2. Defective temperature sensor
Slave2 (Open/Short)
sensor error (Open / Short)
13 133 3. Defective outdoor unit PCB
Slave3
14 134
115*
Master
1. Defective temperature sensor con-
11 151
Slave1 Outdoor Unit Subcooling necter connection
Abnormal sensor resistance value
12 152 Outlet Temperature Sensor 2. Defective temperature sensor
Slave2 (Open/Short)
Error (Open/Short)
13 153 3. Defective outdoor PCB
Slave3
14 154
Is temperature sensor No
connector connections Check and correct connection
are normal?
Yes
Yes
* Sensor resistance 100 kΩover (open) or 100 Ω below (short) will generate error
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ
Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ
56
Error
Error Type Error Point Main Reasons
No.
Yes
After opposite
mode operation to present No If the same error is occurred in
mode, is the same error near future replace 4way valve
occurred again?
Yes
Yes
57
*** When power is supplied in order as follow
(Slave2 Slave1 Mater)
ODU information is displayed one after another on main PCB 7-segment
1. Model Code
Model Code Unit(HP)
190 8
191 10
192 12
193 14
194 16
195 18
196 20
2. Total Capacity
Displayed with HP
3. ODU Type
Heat Recovery : 4, Heat Pump : 2, Cooling Only : 0
4. Normal mode : 25
5. Refrigerant
R410a : 41
58
***** 1. Checking method for outdoor unit of 3 units system
(Master + Slave1 + Slave2)
Close all the SVC valves of high pressure gas pipe
Operate system
Check the difference of high and low pressure with LGMV for each unit (Master, Slave1, Slave2)
If there is a unit in which the difference is not increased then the 4way valve of that unit is defective
2. Checking method for outdoor unit of single unit system
(Manual steps)
Turn on dip S/W 12,13,20(upper and low 4way valve ON)
Turn on dip S/W 13,20(low 4way valve ON)
Turn on dip S/W 12,20(upper 4way valve ON)
Turn on dip S/W 20(upper and low 4way valve OFF)
Execute 1~2times until finding defective 4way valves
Turn off all of dip S/W after finished steps.
Caution : Operate manual steps under 2.0MPa.
ON ON
upper 4way valve ON
low 4way valve ON
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
ON ON
upper 4way valve OFF
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
low 4way valve ON
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
ON ON
upper 4way valve ON
low 4way valve OFF
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
ON ON
upper 4way valve OFF
low 4way valve ON
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
59
Error No. Error Type Error Point Main Reasons
Is resistance value
(insulation & phase to phase)
No
of corresponding constant Replace constant compressor
compressor normal ?
[refer electric
component part]
Yes
No
Is cables’ connection
Adjust connection of cables
of compressor normal? *
Yes
Is discharge temperature No
sensor of compressor Replace discharge
normal? [refer electric temperature sensor
component part]
Yes
60
Error No. Error Type Error Point Main Reasons
182*
Communication Error Failure Receiving Signal
Master 11-> 821 1. Failure Receiving Signal Between
Between Main-Sub Between Main-Sub Micom of
Slave1 12-> 822 Main-Sub Micom of Master Outdoor
Micom of Master Master Outdoor unit Main
Slave2 13-> 823 unit Main PCB
Outdoor unit Main PCB PCB
Slave3 14-> 824
Sub Micom No
LED Blinking? Press the Reset Button
Yes
No
’
Clear Error? Momentary Error
*
Yes
Sub Micom
61
Error No. Error Type Error Point Main Reasons
Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly??
Yes
No
Is sensor value correct?* Replace sensor
Yes
* If value is 100kΩ ↑(open) or 100Ω ↓(short), error occurs
62
Error No. Error Type Error Point Main Reasons
193*
Master 11 931
Fan PCB heatsink Heat sink temperature is over 1. Heatsink temperature sensor defect
Slave1 12 932
Slave2 13 933 temperature high 95°C 2. Fan PCB assembly defect
Slave3 14 934
194* 1. Heatsink temperature sensor
Master 11 941 Fan PCB heatsink defect(Open/Short)
Heatsink temperature sensor
Slave1 12 942 temperature sensor 2. Wrong connection of temperature sen-
abnormal
Slave2 13 943 error sor connector
Slave2 14 944 3. Fan PCB assembly defect
No
Is temperature
’ sensor Check connection of heat sink
inserted to fan PCB? temperature connector
Yes
No
Is temperature
’ sensor Check connection condition of
attached to heat sink? heat sink and temperature sensor
Yes
Check heat sink temperature
No sensor wire disconnection
Is termperature
’ ‘ Measure temperature sensor
sensor normal? resistance(10k 5% at 25C)
‘ Replace the sensor if
Yes abnormality found
No
’ Replace fan PCB assembly
Is fan PCB assembly normal?
Yes
63
Error
Error type Error point Main reasons
No.
64
Error No. Error type Error point Main reasons
65
Error No. Error type Error point Main reasons
66
Error No. Error Type Error Point Main Reasons
No
Is Simple central No
controller setting 1. Set the slave mode with Simple central controller after reset.
normal?
Yes
67