Self-diagnosis function
Error Indicator
ˍG{GGG GGGGTGGGGGGG.
ˍGlGGG GGsnt}GGGGGU
ˍGpGGGGGG SGGGGGGGG .
ˍGhGGSGGGGSGGslkGGGG .
lG G
ˍGlGG GGG.
ˍGpGGGG GGpk|GSGGGG GGvGpGGGGGU
ˍGpGGSGGGGGGGGGU
Master outside unit inverter compressor DC link DC voltage is not charged after master outside unit operating relay is
2 3 1 under-voltage
turned on
Slave1 outside unit inverter compressor DC link DC voltage is not charged after slave1 outside unit operating relay is
2 3 2 under-voltage
turned on
Slave2 outside unit inverter compressor DC link DC voltage is not charged after slave2 outside unit operating relay is
2 3 3 under-voltage
turned on
2 4 1 Master outside unit high pressure switch Compressor maintenance by master outside unit high pressure switch
Flow rate insufficiency or flow switch trouble of master outside unit
2 4 2 Slave1 outside unit high pressure switch Compressor maintenance by slave1 outside unit high pressure switch
Flow rate insufficiency or flow switch trouble of slave1 outside unit
2 4 3 Slave2 outside unit high pressure switch Compressor maintenance by slave2 outside unit high pressure switch
Flow rate insufficiency or flow switch trouble of slave2 outside unit
Master outside unit GG over- GtGGGGGG[_^}GGGGY^W}GG
2 5 1 voltage/under-voltage
error current
Slave1 outside unit inverter CT under-current Compressor turned off due to slave1 outside unit inverter CT under-
3 1 2
error current
Slave1 outside unit inverter CT under-current Compressor turned off due to slave1 outside unit inverter CT under-
3 1 3
error current
Compressor turned off due to master outside unit inverter compressor
Master outside unit inverter compressor dis-
3 2 1 discharge temperature over-rise
charge temperature over-rise
Flow rate insufficiency or flow switch trouble of master outside unit
Compressor turned off due to slave1 outside unit inverter compressor
Slave1 outside unit inverter compressor dis-
3 2 2 discharge temperature over-rise
charge temperature over-rise
Flow rate insufficiency or flow switch trouble of slave1 outside unit
Compressor turned off due to slave2 outside unit inverter compressor
Slave2 outside unit inverter compressor dis-
3 2 3 discharge temperature over-rise
charge temperature over-rise
Flow rate insufficiency or flow switch trouble of slave2 outside unit
Master outside unit static speed compressor Compressor turned off due to master outside unit static speed com-
3 3 1
discharge temperature over-rise pressor discharge temperature over-rise
Slave1 outside unit static speed compressor Compressor turned off due to slave1 outside unit static speed com-
3 3 2
discharge temperature over-rise pressor discharge temperature over-rise
Slave2 outside unit static speed compressor Compressor turned off due to slave2 outside unit static speed com-
3 3 3
discharge temperature over-rise pressor discharge temperature over-rise
Compressor turned off due to master outside unit high pressure over-rise
3 4 1 Master outside unit high pressure over-rise
Flow rate insufficiency or flow switch trouble of master outside unit
Compressor turned off due to slave1 outside unit high pressure over-rise
3 4 2 Slave1 outside unit high pressure over-rise
Flow rate insufficiency or flow switch trouble of slave1 outside unit
Compressor turned off due to slave2 outside unit high pressure over-rise
3 4 3 Slave2 outside unit high pressure over-rise
Flow rate insufficiency or flow switch trouble of slave2 outside unit
4 3 3 Slave2 outside unit over-voltage sensor error Slave2 outside unit over-voltage sensor disconnection or short circuit
Master outside unit air temperature sensor Master outside unit air temperature sensor disconnection or short cir-
4 4 1
error cuit
Slave1 outside unit air temperature sensor Slave1 outside unit air temperature sensor disconnection or short cir-
4 4 2
error cuit
Slave2 outside unit air temperature sensor Slave2 outside unit air temperature sensor disconnection or short cir-
4 4 3
error cuit
Master outside unit heat exchange temperature Master outside unit heat exchange temperature sensor (A) disconnec-
4 5 1
sensor (A) error tion or short circuit
Slave1 outside unit heat exchange temperature Slave1 outside unit heat exchange temperature sensor (A) disconnec-
4 5 2
sensor (A) error tion or short circuit
Slave2 outside unit heat exchange temperature Slave2 outside unit heat exchange temperature sensor (A) disconnec-
4 5 3
sensor (A) error tion or short circuit
Master outside unit suction temperature sensor Master outside unit suction temperature sensor disconnection or short
4 6 1
error circuit
Slave1 outside unit suction temperature sensor Slave1 outside unit suction temperature sensor disconnection or short
4 6 2
error circuit
Slave2 outside unit suction temperature sensor Slave2 outside unit suction temperature sensor disconnection or short
4 6 3
error circuit
Master outside unit static speed compressor Master outside unit static speed compressor discharge temperature
4 7 1
discharge temperature sensor error sensor disconnection or short circuit
Slave1 outside unit static speed compressor Slave1 outside unit static speed compressor discharge temperature
4 7 2
discharge temperature sensor error sensor disconnection or short circuit
Slave2 outside unit static speed compressor Slave2 outside unit static speed compressor discharge temperature
4 7 3
discharge temperature sensor error sensor disconnection or short circuit
5 0 1 Master outside unit 3 phase power missing Master outside unit power line phase missing
5 0 2 Slave1 outside unit 3 phase power missing Slave1 outside unit power line phase missing
5 0 3 Slave2 outside unit 3 phase power missing Slave2 outside unit power line phase missing
Over-capacity (Indoor unit capacity sum is Excessive connection of indoor unit connection display value
5 1 -
excessive) connection (Different from outside unit)
Communication error with master outside unit When the inverter controller signal is not received from the master
5 2 1
inverter controller outside unit inverter controller
Communication error with slave1 outside unit When the inverter controller signal is not received from the slave1
5 2 2
inverter controller outside unit inverter controller
Communication error with slave2 outside unit When the inverter controller signal is not received from the slave2
5 2 3
inverter controller outside unit inverter controller
Outside unit
Communication error with master outside unit When the indoor unit control signal is not received from the mas-
5 3 -
controller and indoor unit ter outside unit controller
Master outside unit 3 phase power reverse
5 4 1 Master outside unit 3 phase power reverse phase connection
phase
Slave1 outside unit 3 phase power reverse
5 4 2 Slave1 outside unit 3 phase power reverse phase connection
phase
Slave2 outside unit 3 phase power reverse
5 4 3 Slave2 outside unit 3 phase power reverse phase connection
phase
Master Outdoor Unit Communication Master Outdoor Unit Controller part cannot receive inverter
5 7 1
Error with Inverter Controller control signals (usually happens after onboarding)
Slave1 Outdoor Unit Communication Slave1 Outdoor Unit Controller part cannot receive inverter
5 7 2
Error with Inverter Controller control signals (usually happens after onboarding)
Slave2 Outdoor Unit Communication Slave2 Outdoor Unit Controller part cannot receive inverter
5 7 3
Error with Inverter Controller control signals (usually happens after onboarding)
Wrong setting between master and slave out- When the dip switch(No.8) setting is different between master and
5 9 -
side unit slave outside unit
Master outside unit inverter PCB EEPROM
6 0 1 Master outside unit inverter PCB EEPROM ACCESS error
error
Slave1 outside unit inverter PCB EEPROM
6 0 2 Slave1 outside unit inverter PCB EEPROM ACCESS error
error
Slave2 outside unit inverter PCB EEPROM
6 0 3 Slave2 outside unit inverter PCB EEPROM ACCESS error
error
Slave2 outside unit static speed CT sensor Slave2 outside unit static speed CT sensor disconnection or short
7 0 3
error circuit
Master outside unit inverter PCB input instant Master outside unit inverter PCB input instant over-current (Peak)
7 3 1
over-current (Peak) exceeded
Slave1 outside unit inverter PCB input instant Slave1 outside unit inverter PCB input instant over-current (Peak)
7 3 2
over-current (Peak) exceeded
Slave2 outside unit inverter PCB input instant Slave2 outside unit inverter PCB input instant over-current (Peak)
7 3 3
over-current (Peak) exceeded
Master outside unit inverter PCB phase imbal- When the master outside unit inverter PCB input current is differ-
7 4 1
ance ent
Slave1 outside unit inverter PCB phase imbal- When the slave1 outside unit inverter PCB input current is differ-
7 4 2
ance ent
Slave2 outside unit inverter PCB phase imbal- When the slave2 outside unit inverter PCB input current is differ-
7 4 3
ance ent
Communication error between master outside unit master MICOM
8 6 1 Master outside unit master PCB EEPROM error
and EEPROM or EEPROM missing
Communication error between slave1 outside unit master MICOM
8 6 2 Slave1 outside unit master PCB EEPROM error
and EEPROM or EEPROM missing
Communication error between slave2 outside unit master MICOM
8 6 3 Slave2 outside unit master PCB EEPROM error
and EEPROM or EEPROM missing
Slave1 outside unit liquid pipe temperature sen- Slave1 outside unit liquid pipe temperature sensor disconnection
1 1 3 2
sor error or short circuit
Slave2 outside unit liquid pipe temperature sen- Slave2 outside unit liquid pipe temperature sensor disconnection
1 1 3 3
sor error or short circuit
Master outside unit over-cooling inlet tempera- Master outside unit over-cooling inlet temperature sensor discon-
1 1 4 1
ture sensor error nection or short circuit
Slave1 outside unit over-cooling inlet tempera- Slave1 outside unit over-cooling inlet temperature sensor discon-
1 1 4 2
ture sensor error nection or short circuit
Slave2 outside unit over-cooling inlet tempera- Slave2 outside unit over-cooling inlet temperature sensor discon-
1 1 4 3
ture sensor error nection or short circuit
Master outside unit over-cooling outlet tempera- Master outside unit over-cooling outlet temperature sensor dis-
1 1 5 1
ture sensor error connection or short circuit
Slave1 outside unit over-cooling outlet tempera- Slave1 outside unit over-cooling outlet temperature sensor dis-
1 1 5 2
ture sensor error connection or short circuit
Slave2 outside unit over-cooling outlet tempera- Slave2 outside unit over-cooling outlet temperature sensor dis-
1 1 5 3
ture sensor error connection or short circuit
1 5 1 - Outside unit 4 way valve switch failure Outside unit 4 way valve switch error
Outside unit
Master outside unit static speed compressor Master outside unit static speed compressor burn, locking and
1 7 3 1
error over-current
Slave1 outside unit static speed compressor Slave1 outside unit static speed compressor burn, locking and
1 7 3 2
error over-current
Slave2 outside unit static speed compressor Slave2 outside unit static speed compressor burn, locking and
1 7 3 3
error over-current
1 8 0 - Plate type heat exchanger freeze prevention Plate type heat exchanger freeze prevention error
1 8 2 - Communication error between MICOMs Communication error between main MICOM and sub MICOM
Error
Error Type Error Point Main Reasons
No.
Is sensor properly No
Connect properly to PCB
connected to PCB?
Yes
Yes
** In case the value is more than 100kΩ (open) or less than 100Ω (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature(±5% margin) ! Normal
Air temp sensor: 10°C = 20.7kΩ : 25°C= 10kΩ : 50°C= 3.4kΩ
Pipe temp sensor: 10°C = 10kΩ : 25°C= 5kΩ : 50°C= 1.8kΩ
Error
Error Type Error Point Main Reasons
No.
Is sensor properly No
Connect properly to PCB
connected to PCB?
Yes
Yes
** In case the value is more than 100kΩ (open) or less than 100Ω (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature(±5% margin) ! Normal
Air temp sensor: 10°C = 20.7kΩ : 25°C= 10kΩ : 50°C= 3.4kΩ
Pipe temp sensor: 10°C = 10kΩ : 25°C= 5kΩ : 50°C= 1.8kΩ
Error
Error Type Error Point Main Reasons
No.
Yes
Yes
* If there is no remote controller to replace : Use another unitʼs remote controller doing well
** Check cable : Contact failure of connected portion or extension of cable are main cause
Check any surrounded noise ( check the distance with main power cable)
! make safe distance from the devices generate electromagnetic wave
*** After replacing indoor unit PCB, do Auto Addressing & input unitʼs address if connected to central controller.
(All the indoor units connected should be turned on before Auto Addressing
Error
Error Type Error Point Main Reasons
No.
Mn
Drain pump blocked by Bgdbjsgdcq`hmgd`cgdhfgs
foreign particles? `mcrknod)))
Yes Bgdbjhmfekn`s
rvhsbg
'Knvonrhshnmˌ rgnqs /ngl(
Error
Error Type Error Point Main Reasons
No.
Yes
Yes
Check if the
transmission cable is
properly connected No
Re connect transmission cable
to indoor / outdoor
terminal block?*
Outdoor PCB fault
Replace after checking
Yes
Indoor PCB fault
Replace after checking
Error
Error Type Error Point Main Reasons
No.
Indoor unit outlet pipe Indoor unit outlet pipe Refer to CH02
06 temperature sensor temperature sensor open
error or short
Is sensor properly No
Connect properly to PCB
connected to PCB?
Yes
Yes
** In case the value is more than 100kΩ (open) or less than 100Ω (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature(±5% margin) ! Normal
Air temp sensor: 10°C = 20.7kΩ : 25°C= 10kΩ : 50°C= 3.4kΩ
Pipe temp sensor: 10°C = 10kΩ : 25°C= 5kΩ : 50°C= 1.8kΩ
Error
Error Type Error Point Main Reasons
No.
- Replace the indoor unit PCB, and then make sure to perform Auto addressing and input the address of central control
Error
Error Type Error Point Main Reasons
No.
Indoor unit BLDC fan motor Indoor BLDC fan motor 1. Motor connector connection fault
10 failure feedback signal is absent 2. Indoor PCB fault
(for 50 sec.) 3. Motor fault
Is connector No
connection proper? Connect properly
Yes
Is fan motor No
Replace indoor unit fan motor
normal?*
Yes
Error
Error Type Error Point Main Reasons
No.
Yes
1. Check inverter PCB assembly U,V,W connector
connection condition
Is compressor
No 2. Check wire disconnection and wiring
Wire connection
3. Check compressor terminal connection condition
condition normal?
(bad contact)
→ Reassemble if abnormality found
Yes
Yes
Check
R~S/S~T/T~R phase voltage is 380V 10%
No R~N/S~N/T~N phase voltage is 220V 10%
Is input voltage normal?
→ Check connection condition and wiring if power is
abnormal
Yes
Yes
Error
Error Type Error Point Main Reasons
No.
23*
1. DC Link terminal misconnection/terminal
contact fault
Master
2. Starting relay damage
231 Inverter Compressor DC DC Voltage isn't charged
3. Condenser damage
Slave1 Link Low Voltage after starting relay on
4. Inverter PCB assembly damage
232 (DC Link voltage sensing part)
Slave2 5. GG low
283
Check
R~S/S~T/T~R phase voltage is 380V 10%
No
Is GG normal? R~N/S~N/T~N phase voltage is 220V 10%
→ Check connection condition and wiring if power is
abnormal
Yes
Yes
Yes
Error
Error Type Error Point Main Reasons
No.
No
Is SVC valve open? Open SVC Valve
Yes
Yes
Is high pressure of No
LGMV similar as at Replace high pressure sensor
manifold gage?
Yes
Error
Error Type Error Point Main Reasons
No.
25*
pGG
is over limited 1. pGG abnormal (T-N)
Master pGG}GG value of the product (173V 2. Outdoor unit inverter PCB assembly
251 GV or less, 289V or more) damage (input voltage sensing part)
Slave1
252
Check
R~S/S~T/T~R phase voltage is 380V 10%
No
Is GG normal? R~N/S~N/T~N phase voltage is 220V 10%
→ Check connection condition and wiring if power is
abnormal
Yes
No
Is inverter PCB assembly normal? Replace inverter PCB assembly
Yes
Error
Error Type Error Point Main Reasons
No.
Yes
Error
Error Type Error Point Main Reasons
No.
28*
Check
R~S/S~T/T~R phase voltage is 380V 10%
No R~N/S~N/T~N phase voltage is 220V 10%
Is GG normal?
→ Check connection condition and wiring if power is
abnormal
Yes
Yes
Error
Error Type Error Point Main Reasons
No.
29*
1. Overload operation
(Pipe clogging/Covering/EEV defect/Ref.
Master overcharge)
291 Inverter compressor over Inverter compressor input
2. Compressor damage(Insulation
Slave1 current current is over 30A
damage/Motor damage)
292 3. pGG low
Slave2 4. ODU inverter PCB assembly damage
293
Check
No R~S/S~T/T~R phase voltage is 380V 10%
Is GG normal? R~N/S~N/T~N phase voltage is 220V 10%
˧ Check connection condition and wiring if power is
abnorma
Yes
Yes
Error
Error Type Error Point Main Reasons
No.
1. Temperature sensor defect of inverter
32* Over-increase discharge Compressor is off compressor discharge pipe
Master 321 temperature of inverter because of over-increase 2. Refrigerant shortage / leak
Slave1 322 compressor at main outdoor discharge temperature of
3. EEV defect
Slave2 323 unit inverter compressor
4. Liquid injection valve defect
Yes
* Resistance value of discharge temperature sensor
10C = 362k, 25C= 200k, 50C= 82k, 100C= 18.5k
Is EEV in
outdoor unit normal No
at heating operation? Replace outdoor unit EEV
[refer electric
component part]
Yes
Replace strainer
Error
Error Type Error Point Main Reasons
No.
Yes
* Resistance value of discharge temperature sensor
10C = 362k, 25C= 200k, 50C= 82k, 100C= 18.5k
Is EEV in
outdoor unit normal No
at heating operation? Replace outdoor unit EEV
[refer electric
component part]
Yes
Replace strainer
Error
Error Type Error Point Main Reasons
No.
1. Defect of high pressure sensor
2. Defect of indoor or outdoor unit fan
34* 3. Deformation because of damage of refrigerant pipe
Error happens
because of 3 times 4. Over-charged refrigerant
Master successive 5. Defective indoor / outdoor unit EEV
341 Over-increase of
discharge pressure compressor off due to 6. When blocked
Slave1 over-increase of high
of compressor - Outdoor unit is blocked during cooling
342 pressure by high
- Indoor unit filter is blocked during heating
Slave2 pressure sensor
7. SVC valve is clogged
343
8. PCB defect of outdoor unit
10. Indoor unit pipe temperature sensor defect
Yes
Yes
Is refrigerant No
amount normal? Adjust refrigerant amount
[refer refrigerant part]
Yes
Is fan normal?
(Indoor fan during heating No Replace related parts
Outdoor fan during cooling) (Refer to Error 105~107)
Yes
Is filter blocked
(Heating:indoor, No Clean indoor filter (heating)
Cooling:outdoor /outdoor heat exchanger (cooling)?
heat exchanger)?
Yes
Yes
Error
Error Type Error Point Main Reasons
No.
1. Defective low pressure sensor
2. Defective outdoor/indoor unit fan
35* Error happens 3. Refrigerant shortage/leakage
because of 3 times 4. Deformation because of damage of refrigerant pipe
Master Excessive drop of successive 5. Defective indoor / outdoor unit EEV
351 discharge pressure compressor off due to 6. Covering / clogging
Slave1 of compressor excessive drop of low (outdoor unit covering during the cooling mode/
352 pressure by the low
indoor unit filter clogging during heating mode)
Slave2 pressure sensor
7. SVC valve clogging
353
8. Defective outdoor unit PCB
9. Defective indoor unit pipe sensor
Yes
No
Are transmission cable/ check transmission/
piping normal? piping correction.
Yes
Is amount of refrigerant No No
Is there pipe crack or trace Adjust the amount of
normal?
of refrigerant leakage? refrigerant (Additive charge)
[refer refrigerant part]
Yes Yes
No
Is strainer Ok?* Replace the strainer
Yes
Yes
* If the temperature difference between inlet and outlet of strainer
Check indoor / outdoor unit LEV is so large that frost or ice formation can be seen or confirmed
Check Indoor unit PCB
Check indoor / outdoor unit then clogging of strainer should be checked
installation conditions (Notice: it is not full ice forming of strainer, in case that there is
not at inlet portion but at outlet portion)
Error
Error Type Error Point Main Reasons
No.
40*
Master
Micom input voltage isn't 1. GG abnormal (T-N)
401 Inverter compressor CT
within 2.5V ±0.3V at initial 2. ODU inverter PCB damage
Slave1 sensor error state of power supply (CT sensing part)
402
Slave2
403
Check
R~S/S~T/T~R phase voltage is 380V 10%
No
Is GG normal? R~N/S~N/T~N phase voltage is 220V 10%
→ Check connection condition and wiring if power is
abnormal
Yes
Yes
Yes
Is the resistance of No
Replace sensor
sensor normal?*
Yes
Is sensor resistance No
value same as temperature Replace corresponding outdoor PCB
value of LGMV?
Yes
* Error is generated if the resistance is more than 5M(open) and less than 2k (short)
Error
Error Type Error Point Main Reasons
No.
Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly?
Yes
After replacement of No
Replace corresponding
outdoor unit main PCB
pressure sensor
is the system normal?
Yes
END
Error
Error Type Error Point Main Reasons
No.
43*
Abnormal value of 1. Bad connection of high pressure connector
Master 431 Sensor error of high
sensor 2. Defect of high pressure connector (Open/Short)
Slave1 432 pressure
(Open/Short) 3. Defect of outdoor PCB
Slave2 433
Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly?
Yes
After replacement of No
Replace corresponding
outdoor unit main PCB
pressure sensor
is the system normal?
Yes
END
44*
Master 441 Sensor error of 1. Bad connection of air temperature connector
Abnormal value of
Slave1 442 outdoor air 2. Defect of air temperature connector(Open/Short)
sensor (Open/Short)
Slave2 443 temperature 3. Defect of outdoor PCB
Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly??
Yes
No
Is sensor value correct?* Replace sensor
Yes
* If value is 100k ≠(open) or 100 Ø(short), error occurs
Piping temperature
45* sensor error of heat 1. Bad connection of air temperature connector
Master 451 exchanger in Abnormal value of 2. Defect of air temperature connector(Open/Short)
Slave1 452 master & slave sensor
3. Defect of outdoor PCB
Slave2 453 outdoor unit heat (Open/Short)
exchanger (A,B)
Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly??
Yes
No
Is sensor value correct?* Replace sensor
Yes
* If value is 100k ≠(open) or 100 Ø(short), error occurs
Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly??
Yes
No
Is sensor value correct?* Replace sensor
Yes
* If value is 100k ≠(open) or 100 Ø(short), error occurs
Yes
Is the resistance of No
Replace sensor
sensor normal?*
Yes
Is sensor resistance No
value same as temperature Replace corresponding outdoor PCB
value of LGMV?
Yes
* Error is generated if the resistance is more than 5M(open) and less than 2k (short)
Piping temperature
48* sensor error of heat
Master 481 exchanger in Abnormal value of 1. Bad connection of air temperature connector
sensor 2. Defect of air temperature connector(Open/Short)
Slave1 482 master & slave
outdoor unit heat (Open/Short) 3. Defect of outdoor PCB
Slave2 483
exchanger (A,B)
Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly??
Yes
No
Is sensor value correct?* Replace sensor
Yes
* If value is 100k ≠(open) or 100 Ø(short), error occurs
Error
Error Type Error Point Main Reasons
No.
50*
Master
1. GG abnormal (R,S,T,N)
501 ODU 3phase power Omitting one or more of
2. Check power Line connection condition
Slave1 omission error R,S,T input power
3. Main PCB damage
502
Slave2
503
Check
R~S/S~T/T~R phase voltage is 380V Ź 10%
No
Is GG normal? R~N/S~N/T~N phase voltage is 220V Ź 10%
→ Check connection condition and wiring if power is
abnormal
Yes
Yes
Error
Error Type Error Point Main Reasons
No.
1. 130% more than outdoor unit rated capacity
Over-Capacity 2. Wrong connection of transmission
(Sum of indoor unit Sum of indoor unit cable/piping
51 capacity is more than capacity exceed outdoor 3. Control error of slave outdoor unit Dip switch
outdoor capacity) unit capacity specification 4. Power supply defect of slave unit PCB
5. Defect of outdoor unit PCB
Yes
Yes Yes
Is transmission
No
cables between outdoor units Re-connect
connected correctly?*
Yes
Yes
End
Error
Error Type Error Point Main Reasons
No.
Is transmission
LED (Yellow) of inverter No Is noise filter or fuse No
Replace noise filter or fuse
compressor normal?
PCB on?
Yes Yes
No
Is transmission cable
Re-connect transmission cable
connected correctly?
Yes
No
Is MAIN PCB normal? Replace MAIN PCB
Yes
Error
Error Type Error Point Main Reasons
No.
Yes Yes
End
No
Is power supplied
Supply power
to indoor units?
Yes
In case of CH53, almost happened with CH05, the indoor units not operated actually are normal so check with
same method of CH05. and additionally check as shown as below and above flow chart
• Although the quantity of indoor units installed is same as LGMV data there may be a few indoor units with
which the number of transmission is not increased with LGMV
• Although the quantity of indoor units installed is not same as LGMV data, and if transmission of the indoor unit
displayed at LGMV is done well then the indoor unit suspected to have some problem (and is not appear at
LGMV) may have following problems
" wrong connection of transmission cable or power cable
# fault of power / PCB / transmission cable
$ duplication of indoor unit number
• If transmission is not doing well wholly then the Auto Addressing is not done
• The case that CH53 appear at indoor unit also Auto Addressing is not done so indoor unit address may be
duplicated
* After replacement of indoor unit PCB, Auto Addressing should be done, if central controller is installed then the
central control address also should be input.
In case that only transmission PCB is replaced above process is not needed
Error
Error Type Error Point Main Reasons
No.
Yes
Is CH 54 occurred again No
after reset MAIN End
circuit breaker?
Yes
No
Is main PCB fuse normal? Replace Fuse
Yes
Error
Error Type Error Point Main Reasons
No.
Slave ODU mixed Installing old Sub ODU and Installing LGDC Slave Unit and Super sub
59
installation new slave ODU together Unit together
No
Installed 3 UNIT or more? Recheck power and installation condition
Yes
Yes
Yes
ON ON
Slave 1
1 2 3 4 5 6 7 1 2 3 4 5 6 7
1 2 3 4 5 6 7 8 9 10 11 12 13 14
ON ON
Slave 2
1 2 3 4 5 6 7 1 2 3 4 5 6 7
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Error
Error Type Error Point Main Reasons
No.
60*
Master
1. EEPROM contact defect/wrong insertion
601 Inverter PCB EEPROM EEPROM Access error and
Slave1 error 2. Different EEPROM Version
Check SUM error
602 3. ODU inverter PCB assembly damage
Slave2
603
Yes
Yes
Error
Error Type Error Point Main Reasons
No.
70*
Master
701 Constant Speed Constant Speed
1. Constant Speed Compressor CT Sensor
Slave1 Compressor CT Sensor Compressor CT Sensor
defect
702 Error Open/short
Slave2
703
Yes
Error
Error Type Error Point Main Reasons
No.
71*
Master
Micom input voltage isn't 1. GG abnormal (T-N)
711 Inverter input current CT
Slave1 sensor error within 2.5V ±0.3V at initial 2. ODU inverter PCB damage
712 state of power supply (CT sensing part)
Slave2
713
Check
R~S/S~T/T~R phase voltage is 380V 10%
No R~N/S~N/T~N phase voltage is 220V 10%
Is GG normal?
→ Check connection condition and wiring if power is
abnormal
Yes
No
Is inverter PCB assembly normal? Replace inverter PCB assembly
Yes
Check
No R~S/S~T/T~R phase voltage is 380V 10%
Is GG normal?
R~N/S~N/T~N phase voltage is 220V 10%
˧ Check connection condition and wiring if power is abnormal
Yes
Yes
No
Is inverter PCB assembly Check inverter PCB assembly IPM/IGBT normality
normal? ˧ Replace inverter PCB assembly
Yes
1. CT sensor defect
74* During operation(compressor
2. Capacity over of AVR
Master 741 frequency is over 50Hz), difference
3 Phase Power Unbalance
Slave1 742 between R & T phase is 5A for 10 3. Bridge R-N or S-N or T-N phase
Slave2 743 seconds. voltage unequally at indoor unit
etc.
No Check
R~S/S~T/T~R phase voltage is 380V 10%
Is GG normal?
R~N/S~N/T~N phase voltage is 220V 10%
˧ Check connection condition and wiring if power is abnormal
Yes
No
Does indoor unit power
bridge R,S,T phase equally? Bridge R-N,S-N,T-N voltage equally
Yes
No
Is inverter PCB
Replace inverter PCB assembly
assembly normal?
Yes
86*
Master 861 Main PCB EEPROM 1. No EEPROM
EEPROM Access Error
Slave1 862 Error 2. EEPROM wrong insertion
Slave2 863
Yes
No
Is EEPROM 24C16? Replace EEPROM with 24C16
Yes
104*
Master
11 ! 041 Master displays ODU number 1.Loose connection of power
Transmission Error
Slave1 which is not communicated. cable/transmission cable¿¸(Open/Short)
Between Outdoors
12 ! 042 Slave displays own error number 2.Defect of each outdoor unit PCB
Slave2
13 ! 043
Is transmission No
cable installed Connect transmission cable
normally?
Yes
Yes
Yes
1 2 3 4 5 6 7 1 2 3 4 5 6
1 2 3 4 5 6 7 8 9 10 11 12 13 14
ON ON
Slave2
1 2 3 4 5 6 7 1 2 3 4 5 6 7
1 2 3 4 5 6 7 8 9 10 11 12 13 14
ON ON
Slave3
1 2 3 4 5 6 7 1 2 3 4 5 6 7
1 2 3 4 5 6 7 8 9 10 11 12 13 14
113*
Master 1. Defective temperature sensor
11 ! 131 Outdoor unit liquid pipe connection
Abnormal sensor resistance value
Slave1 (condenser) temperature 2. Defective temperature sensor
(Open/Short)
12 ! 132 sensor error (Open / Short)
Slave2 3. Defective outdoor unit PCB
13 ! 133
Is temperature sensor No
connector connections Check and correct connection
are normal?
Yes
Yes
* Sensor resistance 100 kΩover (open) or 100 Ω below (short) will generate error
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ
Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ
114*
Master 1. Defective temperature sensor
11 141 Outdoor unit sub-cooling connecter connection
Abnormal sensor resistance value
Slave1 inlet / outlet temperature 2. Defective temperature sensor
(Open/Short)
12 142 sensor error (Open/Short)
Slave2 3. Defective outdoor PCB
13 143
Is temperature sensor No
connector connections Check and correct connection
are normal?
Yes
Yes
* Sensor resistance 100 kΩover (open) or 100 Ω below (short) will generate error
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ
Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ
115
Master 1. Defective temperature sensor
11 151 Outdoor unit subcooling connecter connection
Abnormal sensor resistance
Slave1 inlet/outlet temperature 2. Temperature sensor
value(Open/short)
12 152 sensor error defect(open/short)
Slave2 3. Outdoor unit main PCB defect
13 153
Yes
Yes
* Sensor resistance 100 kΩover (open) or 100 Ω below (short) will generate error
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ
Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ
Error
Error Type Error Point Main Reasons
No.
Yes
Yes
Yes
Yes
After opposite
mode operation to present No If the same error is occurred in
mode, is the same error near future replace 4way valve
occurred again?
Yes
173*
Master
1. Constant compressor damage
11 731 Defect according to constant
Constant compressor 2. Constant compressor input over
Slave1 compressor damage or
defect current
12 732 locking, over current
3. Discharge temperature sensor defect
Slave2
13 733
Is resistance value
(insulation & phase to phase)
No
of corresponding constant Replace constant compressor
compressor normal ?
[refer electric
component part]
Yes
No
Is cables’ connection
Adjust connection of cables
of compressor normal? *
Yes
Is discharge temperature No
sensor of compressor Replace discharge
normal? [refer electric temperature sensor
component part]
Yes
No
Is water flow Check Water flow rate and
rate normal? Power reset
Yes
Is temperature No
sensor Connection Connect temperature
Condition normal? * sensor on PCB
Yes
Is the resistance No
value of temperature Replace temperature sensor
sensor normal?
Yes
Is temperature sensor No
Connect temperature sensor on PCB
Connection Condition nomal?
Yes
Yes
Sub Micom No
LED Blinking? Sub Micom
Yes
No
Clear Error? Sub Micom
Yes
Sub Micom
Error
Error Contents Meaning Main Causes
Code
1) Check system setting address of central controller and actual address is matched or not
2) Re-start service program(engine) of central controller
3) Replace CNU
Error
Error Contents Meaning Main Causes
Code
1. NOISE occurs
2. CNU defect
Central controller
251 Length of received date : 0 3. Temporary error of Timing mismatch
Receive Zero Error 4. A/C product defecth
5. PI485 communication cable open or
connection defect
1) Check system setting address of central controller and actual address is matched or not
2) Re-start service program(engine) of central controller
3) Replace CNU
Error
Error Contents Meaning Main Causes
Code
1. NOISE occurs
2. CNU defect
Setting address and actual
Central controller
252 address are different each 3. Temporary error of Timing mismatch
Wrong Address Error 4. A/C product defecth
other
5. PI485 communication cable open or
connection defect
1) Check system setting address of central controller and actual address is matched or not
2) Re-start service program(engine) of central controller
3) Replace CNU