Trouble Shooting Guide

Error Indicator
• This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
• Error mark is displayed on LGMV as shown in the table.
• If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurrence, if error is released, error LED is also released simultaneously.

Error Display
• Error is displayed with unit number.
• Indoor unit error is displayed on IDU info, outside error is displayed on Operation Info located on right upper side.
• If error occurs, click the error and trouble shooting guide is provided.

Display Title Cause of Error

0 1 - Air temperature sensor of indoor unit Air temperature sensor of indoor unit is open or short

0 2 - Inlet pipe temperature sensor of indoor unit Inlet pipe temperature sensor of indoor unit is open or short
Communication error : wired remote controller
0 3 - Failing to receive wired remote controller signal in indoor unit PCB
↔indoor unit
Indoor unit related Error

0 4 - Drain pump Malfunction of drain pump

0 5 - Communication error : outside unit ↔ indoor unit Failing to receive outside unit signal in indoor unit PCB

0 6 - Outlet pipe temperature sensor of indoor unit Outlet pipe temperature sensor of indoor unit is open or short

0 7 - Different operation mode Operation mode between indoor unit and outside unit is different

In case when the serial number marked on EEPROM of Indoor unit is


0 9 - Indoor EEPROM Error
0 or FFFFFF
Disconnecting the fan motor connector/Failure of indoor fan motor
1 0 - Poor fan motor operation
Lock
Communication error: indoor unit → main PCB of
1 1 - PCB Damage
outside.
2 1 1 Master outside unit inverter compressor IPM Fault Master outside unit inverter compressor drive IPM error

2 Slave1 outside unit inverter compressor IPM Fault Slave1 outside unit inverter compressor drive IPM error

3 Slave2 outside unit inverter compressor IPM Fault Slave2 outside unit inverter compressor drive IPM error

4 Slave3 outside unit inverter compressor IPM Fault Slave3 outside unit inverter compressor drive IPM error
Inverter Board Input Over Current(RMS) of Master
2 2 1 Master Outside unit Inverter Board Input Current excess (RMS)
outside unit
Inverter Board Input Over Current(RMS) of Slave1
2 Slave1 Outside unit Inverter Board Input Current excess (RMS)
outside unit
Inverter Board Input Over Current(RMS) of Slave2
3 Slave2 Outside unit Inverter Board Input Current excess (RMS)
outside unit
Inverter Board Input Over Current(RMS) of Slave3
4 Slave3 Outside unit Inverter Board Input Current excess (RMS)
outside unit
Outside unit related Error

Master outside unit inverter compressor DC link DC voltage is not charged after master outside unit operating relay is
2 3 1
under-voltage turned on
Slave1 outside unit inverter compressor DC link DC voltage is not charged after Slave1 outside unit operating relay is
2
under-voltage turned on
Slave2 outside unit inverter compressor DC link DC voltage is not charged after Slave2 outside unit operating relay is
3
under-voltage turned on
Slave3 outside unit inverter compressor DC link DC voltage is not charged after Slave3 outside unit operating relay is
4
under-voltage turned on
Compressor maintenance by master outside unit high pressure
2 4 1 Master outside unit high pressure switch switch Flow rate insufficiency or flow switch trouble of master outside
unit

Compressor maintenance by Slave1 outside unit high pressure


2 Slave1 outside unit high pressure switch switch Flow rate insufficiency or flow switch trouble of master outside
unit

Compressor maintenance by Slave2 outside unit high pressure


3 Slave2 outside unit high pressure switch switch Flow rate insufficiency or flow switch trouble of master outside
unit

Compressor maintenance by Slave3 outside unit high pressure


4 Slave3 outside unit high pressure switch switch Flow rate insufficiency or flow switch trouble of master outside
unit
1
Display Title Cause of Error
Master outside unit input voltage over-voltage/und
2 5 1 Master outside unit input voltage over-voltage or under-voltage
er-voltage
Slave1 outside unit input voltage over-voltage/und
2 Slave1 outside unit input voltage over-voltage or under-voltage
er-voltage
Slave2 outside unit input voltage over-voltage/und
3 Slave2 outside unit input voltage over-voltage or under-voltage
er-voltage
Slave3 outside unit input voltage over-voltage/und
4 Slave3 outside unit input voltage over-voltage or under-voltage
er-voltage
Master outside unit inverter compressor operation Initial operation failure due to master outside unit inverter compressor
2 6 1
failure error error
Slave1 outside unit inverter compressor operation Initial operation failure due to Slave1 outside unit inverter compressor
2
failure error error
Slave2 outside unit inverter compressor operation Initial operation failure due to Slave2 outside unit inverter compressor
3
failure error error
Slave3 outside unit inverter compressor operation Initial operation failure due to Slave3 outside unit inverter compressor
4
failure error error
Master outside unit inverter DC link over-voltage Compressor turned Off due to master outside unit inverter DC voltage
2 8 1
error over-charge
Slave1 outside unit inverter DC link over-voltage Compressor turned Off due to Slave1 outside unit inverter DC voltage
2
error over-charge
Slave2 outside unit inverter DC link over-voltage Compressor turned Off due to Slave2 outside unit inverter DC voltage
3
error over-charge
Slave3 outside unit inverter DC link over-voltage Compressor turned Off due to Slave3 outside unit inverter DC voltage
4
error over-charge
Master outside unit inverter compressor over Master outside unit inverter compressor error or operating component
2 9 1
current (IPM) error operation
Slave1 outside unit inverter compressor over Slave1 outside unit inverter compressor error or operating component
2
current (IPM) error operation
Slave2 outside unit inverter compressor over Slave2 outside unit inverter compressor error or operating component
3
current (IPM) error operation
Slave3 outside unit inverter compressor over Slave3 outside unit inverter compressor error or operating component
4
current (IPM) error operation
Compressor turned off due to master outside unit inverter compressor
Master outside unit inverter compressor discharge
Outside unit related Error

3 2 1 discharge temperature over-rise Flow rate insufficiency or flow switch


temperature over-rise
trouble of master outside unit
Compressor turned off due to Slave1 outside unit inverter compressor
Slave1 outside unit inverter compressor discharge
2 discharge temperature over-rise Flow rate insufficiency or flow switch
temperature over-rise
trouble of Slave1 outside unit
Compressor turned off due to Slave2 outside unit inverter compressor
Slave2 outside unit inverter compressor discharge
3 discharge temperature over-rise Flow rate insufficiency or flow switch
temperature over-rise
trouble of Slave2 outside unit
Compressor turned off due to Slave3 outside unit inverter compressor
Slave3 outside unit inverter compressor discharge
4 discharge temperature over-rise Flow rate insufficiency or flow switch
temperature over-rise
trouble of Slave3 outside unit
Compressor turned off due to master outside unit high pressure over-
3 4 1 Master outside unit high pressure over-rise rise
Flow rate insufficiency or flow switch trouble of master outside unit

Compressor turned off due to Slave1 outside unit high pressure over-
2 Slave1 outside unit high pressure over-rise rise
Flow rate insufficiency or flow switch trouble of Slave1 outside unit

Compressor turned off due to Slave2 outside unit high pressure over-
3 Slave2 outside unit high pressure over-rise rise
Flow rate insufficiency or flow switch trouble of Slave2 outside unit

Compressor turned off due to Slave3 outside unit high pressure over-
4 Slave3 outside unit high pressure over-rise rise
Flow rate insufficiency or flow switch trouble of Slave3 outside unit
Compressor turned off due to master outside unit low pressure over
3 5 1 Master outside unit low pressure over-drop.
drop.
Compressor turned off due to Slave1 outside unit low pressure over
2 Slave1 outside unit low pressure over-drop.
drop.
Compressor turned off due to Slave2 outside unit low pressure over
3 Slave2 outside unit low pressure over-drop.
drop.
Compressor turned off due to Slave3 outside unit low pressure over
4 Slave3 outside unit low pressure over-drop.
drop.
Master Outside unit Low Compression Ratio
3 6 1 Master Outside unit stayed under low Compression limit for 3 minutes
limited
Slave1 Outside unit Low Compression Ratio
2 Slave1 Outside unit stayed under low Compression limit for 3 minutes
limited
Slave2 Outside unit Low Compression Ratio
3 Slave2 Outside unit stayed under low Compression limit for 3 minutes
limited
Slave3 Outside unit Low Compression Ratio
4
limited
Slave3 Outside unit stayed under low Compression limit for 3 minutes 2
Display Title Cause of Error
Master Outside unit Communication error between Master Outside unit inverter compressor current detection (CT)
3 9 1
Master outside unit PFC and inverter board sensor disconnection or short circuit
Slave1 Outside unit Communication error between Slave1 Outside unit inverter compressor current detection (CT)
2
Slave1 outside unit PFC and inverter board sensor disconnection or short circuit

Slave2 Outside unit Communication error between Slave2 Outside unit inverter compressor current detection (CT)
3
Slave2 outside unit PFC and inverter board sensor disconnection or short circuit
Slave3 Outside unit Communication error between Slave3 Outside unit inverter compressor current detection (CT)
4
Slave3 outside unit PFC and inverter board sensor disconnection or short circuit

Master outside unit inverter compressor CT sensor Master outside unit inverter compressor current detection (CT)
4 0 1
error sensor disconnection or short circuit

Slave1 outside unit inverter compressor CT sensor Slave1 outside unit inverter compressor current detection (CT)
2
error sensor disconnection or short circuit

Slave2 outside unit inverter compressor CT sensor Slave2 outside unit inverter compressor current detection (CT)
3
error sensor disconnection or short circuit

Slave3 outside unit inverter compressor CT sensor Slave3 outside unit inverter compressor current detection (CT)
4
error sensor disconnection or short circuit

Master outside unit inverter compressor discharge Master outside unit inverter compressor discharge temperature
4 1 1
temperature sensor error sensor disconnection or short circuit

Slave1 outside unit inverter compressor discharge Slave1 outside unit inverter compressor discharge temperature
2
temperature sensor error sensor disconnection or short circuit

Slave2 outside unit inverter compressor discharge Slave2 outside unit inverter compressor discharge temperature
3
temperature sensor error sensor disconnection or short circuit
Outside unit related Error

Slave3 outside unit inverter compressor discharge Slave3 outside unit inverter compressor discharge temperature
4
temperature sensor error sensor disconnection or short circuit

4 2 1 Master outside unit Low Pressure Sensor Fault Master outside unit Low Pressure Sensor open or short

2 Slave1 outside unit Low Pressure Sensor Fault Slave1 outside unit Low Pressure Sensor open or short

3 Slave2 outside unit Low Pressure Sensor Fault Slave2 outside unit Low Pressure Sensor open or short

4 Slave3 outside unit Low Pressure Sensor Fault Slave3 outside unit Low Pressure Sensor open or short

4 3 1 Master outside unit High Pressure Sensor Fault Master Outside unit High Pressure Sensor open or short

2 Slave1 outside unit High Pressure Sensor Fault Slave1 Outside unit High Pressure Sensor open or short

3 Slave2 outside unit High Pressure Sensor Fault Slave2 Outside unit High Pressure Sensor open or short

4 Slave3 outside unit High Pressure Sensor Fault Slave3 Outside unit High Pressure Sensor open or short
Master Outside unit air temperature sensor disconnection or short
4 4 1 Master Outside unit air temperature sensor error
circuit
Slave1 Outside unit air temperature sensor disconnection or short
2 Slave1 Outside unit air temperature sensor error
circuit
Slave2 Outside unit air temperature sensor disconnection or short
3 Slave2 Outside unit air temperature sensor error
circuit
Slave3 Outside unit air temperature sensor disconnection or short
4 Slave3 Outside unit air temperature sensor error
circuit
Master outside unit suction temperature sensor disconnection or
4 6 1 Master outside unit suction temperature sensor error
short circuit
Slave1 outside unit suction temperature sensor disconnection or
2 Slave1 outside unit suction temperature sensor error
short circuit
Slave2 outside unit suction temperature sensor disconnection or
3 Slave2 outside unit suction temperature sensor error
short circuit
Slave3 outside unit suction temperature sensor disconnection or
4 Slave3 outside unit suction temperature sensor error
short circuit
Master out side unit IGBT temperature sensor disconnection or
4 9 1 Master outside unit IGBT temperature sensor error
short circuit
Slave1 out side unit IGBT temperature sensor disconnection or
2 Slave1 outside unit IGBT temperature sensor error
short circuit
Slave2 out side unit IGBT temperature sensor disconnection or
3 Slave2 outside unit IGBT temperature sensor error
short circuit
Slave3 out side unit IGBT temperature sensor disconnection or
4 Slave3 outside unit IGBT temperature sensor error
short circuit

3
Display Title Cause of Error
5 0 1 Master outside unit 3 phase power missing Master outside unit power line phase missing
2 Slave1 outside unit 4 phase power missing Slave1 outside unit power line phase missing
3 Slave1 outside unit 5 phase power missing Slave2 outside unit power line phase missing
4 Slave1 outside unit 6 phase power missing Slave3 outside unit power line phase missing
Over-capacity (Indoor unit capacity sum is Excessive connection of indoor unit connection display value (Different
5 1 1
excessive) connection from outside unit)
Communication error with master outside unit When the inverter controller signal is not received from the master
5 2 1
inverter controller outside unit inverter controller
Communication error with Slave1 outside unit When the inverter controller signal is not received from the Slave1
2
inverter controller outside unit inverter controller
Communication error with Slave2 outside unit When the inverter controller signal is not received from the Slave2
3
inverter controller outside unit inverter controller
Communication error with Slave3 outside unit When the inverter controller signal is not received from the Slave3
4
inverter controller outside unit inverter controller
Communication error with master Outside unit When the indoor unit control signal is not received from the master
5 3 1
controller and indoor unit outside unit controller
Communication error between Master outside Failing to receive inverter controller signal at Master outside unit
5 7 1
unit inverter controller controller
Communication error between Slave1 outside Failing to receive inverter controller signal at Slave1 outside unit
2
unit inverter controller controller
Communication error between Slave2 outside Failing to receive inverter controller signal at Slave2 outside unit
3
unit inverter controller controller
Communication error between Slave3 outside Failing to receive inverter controller signal at Slave3 outside unit
4
unit inverter controller controller
5 9 1 Mixing Installation of Sub outside unit Mixing Installation of Old Sub outside unit and New Slave outside unit
6 0 1 Master outside unit inverter PCB EEPROM error Master outside unit inverter PCB EEPROM ACCESS error
2 Slave1 outside unit inverter PCB EEPROM error Slave1 outside unit inverter PCB EEPROM ACCESS error
3 Slave2 outside unit inverter PCB EEPROM error Slave2 outside unit inverter PCB EEPROM ACCESS error
Outside unit related Error

4 Slave3 outside unit inverter PCB EEPROM error Slave3 outside unit inverter PCB EEPROM ACCESS error
Master outside unit inverter IGBT when the temperature rises above
6 2 1 Master outside unit inverter IGBT over-rise error
110 ℃
Slave1 outside unit inverter IGBT when the temperature rises above
2 Slave1 outside unit inverter IGBT over-rise error
110 ℃
Slave2 outside unit inverter IGBT when the temperature rises above
3 Slave2 outside unit inverter IGBT over-rise error
110 ℃
Slave3 outside unit inverter IGBT when the temperature rises above
4 Slave3 outside unit inverter IGBT over-rise error
110 ℃
Master outside unit inverter IGBT temperature Master outside unit inverter IGBT temperature sensor disconnection or
6 5 1
sensor error short circuit
Slave1 outside unit inverter IGBT temperature Slave1 outside unit inverter IGBT temperature sensor disconnection or
2
sensor error short circuit
Slave2 outside unit inverter IGBT temperature Slave2 outside unit inverter IGBT temperature sensor disconnection or
3
sensor error short circuit
Slave3 outside unit inverter IGBT temperature
Slave3 outside unit inverter IGBT temperature sensor disconnection or
4
sensor error short circuit
7 1 1 PFC CT Sensor Error of Master outside unit Master outside unit PFC CT Sensor open or short
2 PFC CT Sensor Error of Slave1 outside unit Slave1 outside unit PFC CT Sensor open or short
3 PFC CT Sensor Error of Slave2 outside unit Slave2 outside unit PFC CT Sensor open or short
4 PFC CT Sensor Error of Slave3 outside unit Slave3 outside unit PFC CT Sensor open or short
Communication error between master outside unit master MICOM and
8 6 1 Master outside unit master PCB EEPROM error
EEPROM or EEPROM missing
Communication error between Slave1 outside unit Slave1 MICOM and
2 Slave1 outside unit Slave1 PCB EEPROM error
EEPROM or EEPROM missing
Communication error between Slave2 outside unit Slave2 MICOM and
3 Slave2 outside unit Slave2 PCB EEPROM error
EEPROM or EEPROM missing
Communication error between Slave3 outside unit Slave3 MICOM and
4 Slave3 outside unit Slave3 PCB EEPROM error
EEPROM or EEPROM missing
Communication error between master outside unit master PFC and EEP
8 8 1 PFC PCB EEPROM error
ROM or EEPROM missing
Communication error between Slave1 outside unit Slave1 PFC and EEP
2 PFC PCB EEPROM error
ROM or EEPROM missing
Communication error between Slave2 outside unit Slave2 PFC and EEP
3 PFC PCB EEPROM error
ROM or EEPROM missing
Communication error between Slave3 outside unit Slave3 PFC and EEP
4 PFC PCB EEPROM error
ROM or EEPROM missing
4
Display Title Cause of Error
Communication Error Between Master outside unit Failing to receive Slave unit signal at main PCB of Master outside
1 0 4 1
and other outside unit unit
Communication Error Between Slave1 outside unit Failing to receive Slave unit signal at main PCB of Slave1 outside
2
and other outside unit unit
Communication Error Between Slave2 outside unit Failing to receive Slave unit signal at main PCB of Slave2 outside
3
and other outside unit unit
Communication Error Between Slave3 outside unit Failing to receive Slave unit signal at main PCB of Slave3 outside
4
and other outside unit unit
Master outside unit Liquid pipe Temperature Sensor Liquid pipe temperature sensor of Master outside unit is open or
1 1 3 1
error short
Slave1 outside unit Liquid pipe Temperature Sensor Liquid pipe temperature sensor of Slave1 outside unit is open or
2
error short
Slave2 outside unit Liquid pipe Temperature Sensor Liquid pipe temperature sensor of Slave2 outside unit is open or
3
error short
Slave3 outside unit Liquid pipe Temperature Sensor Liquid pipe temperature sensor of Slave3 outside unit is open or
4
error short
Master outside unit sub-cooling Outlet Temperature Master outside unit sub-cooling Outlet Temperature Sensor open
1 1 5 1
sensor Error or short
Slave1 outside unit sub-cooling Outlet Temperature Slave1 outside unit sub-cooling Outlet Temperature Sensor open
2
sensor Error or short
Slave2 outside unit sub-cooling Outlet Temperature Slave2 outside unit sub-cooling Outlet Temperature Sensor open
Outside unit related Error

3
sensor Error or short
Slave3 outside unit sub-cooling Outlet Temperature Slave3 outside unit sub-cooling Outlet Temperature Sensor open
4
sensor Error or short
1 1 6 1 Master outside unit Oil Level Sensor Error Oil Level Sensor of Master outside unit is open or short
2 Slave1 outside unit Oil Level Sensor Error Oil Level Sensor of Slave1 outside unit is open or short
3 Slave2 outside unit Oil Level Sensor Error Oil Level Sensor of Slave2 outside unit is open or short
4 Slave3 outside unit Oil Level Sensor Error Oil Level Sensor of Slave3 outside unit is open or short
Master outside unit Main Board - External Board Master outside unit Main Board - External Board communication
1 4 5 1
communication Error Error
Slave1 outside unit Main Board - External Board Slave1 outside unit Main Board - External Board communication
2
communication Error error
Slave1 outside unit Main Board - External Board Slave1 outside unit Main Board - External Board communication
3
communication Error error
Slave1 outside unit Main Board - External Board Slave1 outside unit Main Board - External Board communication
4
communication Error error
Failure of operation mode conversion at Master Failure of operation mode conversion at Master
1 5 1 1
outside unit outside unit
1 8 0 1 Plate type heat exchanger freeze prevention Plate type heat exchanger freeze prevention error
2 Plate type heat exchanger freeze prevention Plate type heat exchanger freeze prevention error
3 Plate type heat exchanger freeze prevention Plate type heat exchanger freeze prevention error
4 Plate type heat exchanger freeze prevention Plate type heat exchanger freeze prevention error
1 8 1 1 Water temperature sensor error Water temperature sensor open/short
2 Water temperature sensor error Water temperature sensor open/short
3 Water temperature sensor error Water temperature sensor open/short
4 Water temperature sensor error Water temperature sensor open/short
1 8 2 1 Communication error between MICOMs Communication error between main MICOM and sub MICOM
2 Communication error between MICOMs Communication error between main MICOM and sub MICOM
3 Communication error between MICOMs Communication error between main MICOM and sub MICOM
4 Communication error between MICOMs Communication error between main MICOM and sub MICOM

5
Error
Error Type Error Point Main Reasons
No.
01 Indoor unit air sensor error
01(FAU) AU Outlet air sensor error 1. Indoor unit PCB wrong connection
Indoor unit sensor is
2. Indoor unit PCB failure
02 Indoor unit pipe inlet sensor error open/short 3. Sensor problem (main reason)
06 Indoor unit pipe outlet sensor error

■ Error diagnosis and countermeasure flow chart

Is sensor properly No
Connect properly to PCB
connected to PCB?

Yes

Is the resistance value No


Change the sensor
of sensor normal?*

Yes

Change the PCB

** In case the value is more than 100kΩ (open) or less than 100Ω (short), Error occurs

Refer: Resistance value maybe change according to temperature of temp sensor,


It shows according to criteria of current temperature(±5% margin) ➔ Normal
Air temp sensor: 10°C = 20.7kΩ : 25°C= 10kΩ : 50°C= 3.4kΩ
Pipe temp sensor: 10°C = 10kΩ : 25°C= 5kΩ : 50°C= 1.8kΩ

6
Error
Error Type Error Point Main Reasons
No.
The remote controller 1. Remote controller fault
No communication between
03 did not receive the signal 2. Indoor unit PCB fault
cabled
from indoor unit 3. Connector fault, Wrong connection
remote controller & indoor unit
during specific time 4. Communication cable problem

■ Error diagnosis and countermeasure flow chart

Does the error happens No Replace cabled remote


again if the remote controller
controller is replaced?*

Yes

Does the error occurred No Check connection &


when the cable of remote
communication cable **
controller is replaced?

Yes

Replace indoor unit PCB ***

* If there is no remote controller to replace : Use another unit’s remote controller doing well

** Check cable : Contact failure of connected portion or extension of cable are main cause
Check any surrounded noise ( check the distance with main power cable)
➔ make safe distance from the devices generate electromagnetic wave

*** After replacing indoor unit PCB, do Auto Addressing & input unit’s address if connected to central controller.
(All the indoor units connected should be turned on before Auto Addressing

7
Error
Error Type Error Point Main Reasons
No.
Float switch is open due to
1. Drain pump/float switch fault
rising of condensate water
2. Improper drain pipe location, clogging
04 Drain pump error level because of drain
of drain pipe
pump fault or drain pipe
3. Indoor unit PCB fault
clogging

■ Error diagnosis and countermeasure flow chart


Is thedrain panfilled Is Float switch short
No No
half with condensate On measuring its Replace float switch
water? (half levelof
resistance?
float switch)*
Yes
Yes
Replace float switch

In indoor unit PCB


Is drainpumpworking? No Does the terminal voltage No Replace indoor unit
(Sound/drainnoise/ for drain pump has
contact etc.) PCB
220V output?**
Yes
Yes
Replace Drain
Pump

Drain pumpblockedby No Check the drain head height


foreign particles? and slope***

Yes
Remove it & clean
the pump

8
Error
Error Type Error Point Main Reasons
No.
1. Auto addressing is not done
2. Communication cable is not connected
No signal communication 3. Short circuit of communication cable
Indoor & Outdoor unit
05 between indoor & outdoor 4. Indoor unit communication circuit fault
communication error
units. 5. Outdoor unit communication circuit fault
6. Not enough distance between power and
communication cable?

■ Error diagnosis and countermeasure flow chart


No Replace thePCBof indoor unit
Does alltheIDUs show No Is totalnumberofindoor displayederror
same error codeCH05? units connecteddisplayed
after autoaddressing? Re-connect aftercheckthe
communicationcable of indoor
Yes unit displayed error**
Yes
END

No Replace outdoorPCBafter
Is outdoorPCBLED No Check themainpower checking
blinking? supply at theODU
terminal block? Replace TRANSafter
checking
Yes
No Check theinsulationof inverter
Is maincircuit breakeroff? / constantcompressorand
replace ifrequired
Yes Check thecapacity of main
Yes
circuit breakerandreplaceif
Improperconnectionof power required
supply cable
If all ok,
Turn on maincircuit breaker
Main powersupply problem

Check if the
communicationcable is No
properly connected Re connect communicationcable
to indoor /outdoor
terminal block?*

Yes
Outdoor PCB fault , Replace after checking

Indoor PCB fault, Replace after checking

9
Error
Error Type Error Point Main Reasons
No.
1. Indoor units are in different mode
The Indoor units started 2. PCB fault
3. cabled remote controller fault
All Indoor units are not later are operated in dif-
07 Checking ch07 method
running in same mode ferent mode from earlier
one. IDU doesn’t operate as Operation mode is
flickering at IDU wired remote controller and IDU
display window.

■ Error diagnosis and countermeasure flow chart

No Does error code disappear No


Is operationmodeof
after set operation Replace IndoorPCB
outside &Indoorunits same?
mode same?

Yes
Yes
END

Adjust outsidemainPCB
dip switchsetting

Error
Error Type Error Point Main Reasons
No.
1.Error developed in transmission between
Indoor unit EEPROM the micro- processor and the EEPROM on
09
error the surface of the PCB.
2. ERROR due to the EEPROM damage

■ Error diagnosis and countermeasure flow chart

- Replace the indoor unit PCB, and then make sure to perform Auto addressing and input the address of
central control

10
Error
Error Type Error Point Main Reasons
No.
Indoor BLDC fan motor 1. Motor connector connection fault
Indoor unit BLDC fan motor
10 feedback signal is absent 2. Indoor PCB fault
failure
(for 50 sec.) 3. Motor fault

■ Error diagnosis and countermeasure flow chart

Is connector No
Connect properly
connectionproper?

Yes

Is fanmotor No
Replace indoorunit fanmotor
normal?*

Yes

Replace indoorunit PCB

11
Error
Error Type Error Point Main Reasons
No.
Indoor unit doesn't get sig- 1. Indoor 485 transmission PCB fault
11 Indoor unit transmission error nal from ODU for 3 minutes 2. After PCB replacing, auto addressing
continuously was not done

■ Error diagnosis and countermeasure flow chart

After ODU main PCB No No Replace indoorunit 485


After Autoaddressing,
reset, errorcode transmissionPCB
error codedisappears?
disappears?

END

12
Error
Error Type Error Point Main Reasons
No.
1.Over current detection at Inverter
21
compressor(U,V,W)
Master
2.Compressor damaged (insulation
(211)
IPM self protection circuit damaged/Motor damaged)
Slave1
Comp PCB Assy IPM activation 3.IPM overheating
(212)
Fault occur (Overcurrent/IPM overheat- (Heat sink disassembled)
Slave2
ing/Vcc low voltage) 4.Inverter compressor terminal
(213)
disconnected or loose
Slave3
5.Inverter PCB assembly damaged
(214)
6.ODU input current low

■ Error diagnosis and countermeasure flow chart

Are thereany powerwire No 1. Check R/S/T/N Wiring Condition


connections normal? → Rewire them if abnormality found

Yes
1. Check resistance between each terminal of compressor
Are the resistance
No (U-V:0.26 ±7%, V-W:0.26 ±7%,W-U:0.26 ±7% (25℃))
Between eachphase and
insulationresistanceofInverter 2. Check insulation resistance between compressor
compressornormal? terminal and pipe (over 50M )
→ Replace compressor if abnormality found
Yes
1.Check Comp PCB assembly U,V,W connector connection
condition
Is compressor No 2. Check wire disconnection and wiring
Wire connection
condition normal? 3. Check compressor terminal connection condition
(bad contact)
→ Reassemble if abnormality found
Yes
1.Check Comp PCB assembly P,N connector
connection condition
Is DC_LinkWireconnection No 2.Check Converter PCB assembly P,N connector
condition normal? connection condition
3. Check wire disconnection and wiring
Yes → Reassemble if abnormality found

Is CompIPM heat sink’s No Check Comp PCB assembly Comp IPM heat sink joining
joining condition normal? condition
→ Reassemble if abnormality found
Yes

Is CompPCBassembly No Check Comp PCB assembly IPM normality.


normal? → Replace Comp PCB assembly
if abnormality found.

Yes

Recheck power and


installation condition

13
Error
Error Type Error Point Main Reasons
No.
22
1. Overload operation (Pipe clogging/
Master
Covering/EEV defect/Ref. overcharge)
(221)
Inverter PCB Assembly 2. Compressor damage(Insulation
Slave1
AC Input Current Over input 3 phase power damage/Motor damage)
(222)
Error current is over limited 3. Input voltage low
Slave2
value 4. Power Line Misconnection
(223)
5. Inverter PCB Assembly damage
Slave3
(Input current sensing part)
(224)

■ Error diagnosis and countermeasure flow chart

1. Check Pipe clogging/distortion


No 2. Check Covering (Indoor/Outdoor Unit)
Is installation
3. Check EEV connector assemble condition/normal operation
condition normal?
4. Check refrigerant pressure
→ Reassemble or manage if abnormality found
Yes
1. Check resistance between each terminal of compressor
Are the resistance
No (U-V:0.255 ±7%, V-W:0.255 ±7%, W-U:0.255 ±7%(75℃)
Between eachphase and
insulationresistanceofInverter 2. Check insulation resistance between compressor
compressornormal? terminal and pipe (over 50M )
→ Replace compressor if abnormality found
Yes
1. Check Comp PCB assembly U,V,W connector
Is compressor connection condition
No
Wire connection 2. Check wire disconnection and wiring
condition normal? 3. Check compressor terminal connection condition
(bad contact)
Yes → Reassemble if abnormality found

No Check joining condition of converter PCB assembly and


Is converterPCBassembly
bridge diode
bridge diodejoiningconditionnormal?
→ joining again if abnormality found
Yes
Check
No R~S/S~T/T~R phase voltage is 380V 10%
Is input voltage normal?
R~N/S~N/T~N phase voltage is 220V 10%
→ Check connection condition and wiring if power is abnormal
Yes

Is CompPCBassembly No Check Comp PCB assembly IPM normality


normal? → Replace Comp PCB assembly

Yes

Recheck power and


installation condition

14
Error
Error Type Error Point Main Reasons
No.
23
Master 1.DC Link terminal misconnection/
(231) terminal contact fault
Slave1 2. Starting relay damage
Inverter Compressor DC DC Voltage isn't charged
(232) 3. Condenser damage
Link Low Voltage after starting relay on
Slave2 4. Comp PCB assembly damage
(233) (DC Link voltage sensing part)
Slave3 5. Input voltage low
(234)

■ Error diagnosis and countermeasure flow chart

Are thereany powerwire No


connections normal? 1. Check R/S/T/N wiring conditions
→ Rewire them if abnormality found.

Yes

Check
No R~S/S~T/T~R phase voltage is 380V 10%
Is input voltagenormal?
R~N/S~N/T~N phase voltage is 220V 10%
→ Check connection condition and wiring if power is abnormal
Yes

No 1. Check joining condition of bridge diode and heatsink


Is bridgediodenormal? 2. Check bridge diode
→ joining again or replacing bridge diode if abnormality found
Yes
1.Check Comp PCB assembly P,N connector connection
condition
Is DC_LinkWireconnection No 2.Check Converter PCB assembly P,N connector connection
condition normal?? condition
3. Check wire disconnection and wiring
Yes → Reassemble if abnormality found

Is converterPCBassembly No Check joining condition of converter PCB assembly and


bridge diodejoiningconditionnormal? bridge diode
→ joining again if abnormality found
Yes

Is CompPCBassembly No Check Comp PCB assembly IPM normality.


normal? → Replace Comp PCB assembly if abnormality found.

Yes

Recheck power and


installation condition

15
Error
Error Type Error Point Main Reasons
No.
1.Defective high pressure switch
2. Defective fan of indoor unit or
24 outdoor unit
Master 3. Check valve of compressor clogged
(241) 4. Pipe distortion due to the pipe damage
Slave1 Excessive rise of discharge Compressor off due to the 5. Refrigerant overcharge
(242) pressure in outdoor com- high pressure switch in 6. Defective LEV at the indoor or outdoor
Slave2 pressor outdoor unit unit .
(243) 7. Covering or clogging(Outdoor covering
Slave3 during the cooling mode /Indoor unit
(244) filter clogging during the heating mode)
8. SVC valve clogging
9. Defective outdoor PCB

■ Error diagnosis and countermeasure flow chart

Is high pressureswitch No
connectorconnected Connect securely
to PCB?*

Yes
Is high pressureswitch No No
Is high pressureswitch Replace high
connectorshort
terminal short?*** pressure switch
during off time?**

Yes

Replace connecting cable

No
Is SVC valve open? Open SVC valve

Yes

No Re-check momentary
Is this error appeared
again after reset? problem or not

Yes
Is high pressure No Replace PCB
more than2500kPa CH24 : inverter compressorPCB
at manifoldgauge? CH109~154: subunitPCB

Yes
Is high pressureof No
LGMV similaras Replace high pressure sensor
at manifoldgauge?

Yes

Check pipe is blocked or


not and take measure

16
Error
Error Type Error Point Main Reasons
No.
25
Master
(251)
Slave1 Input voltage is over limited 1. Input voltage abnormal (R-N)
(252) Input Voltage high/low value of the product (173V 2. Outdoor unit Converter PCB assembly
Slave2 or less, 289V or more) damage (input voltage sensing part)
(253)
Slave3
(254)

■ Error diagnosis and countermeasure flow chart

Are thereany powerwire No 1. Check R/S/T/N wiring conditions


connections normal? → Rewire them if abnormality found.

Yes
Check
No R~S/S~T/T~R phase voltage is 380V 10%
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V 10%
→ Check connection condition and wiring if power
is abnormal
Yes

No Check joining condition of converter PCB assembly


Is converterPCBassembly
and bridge diode
bridge diodejoiningconditionnormal? → joining again if abnormality found

Yes 1.Check Comp PCB assembly P,N connector


connection condition
Is DC_Link Wire connection No 2.Check Converter PCB assembly P,N connector
condition normal? connection condition
3. Check wire disconnection and wiring
→ Reassemble if abnormality found
Yes

No
Comp PCBLEDdisplay error Replace Comp PCB assembly.

Yes

Recheck power and installation


condition

17
Error
Error Type Error Point Main Reasons
No.
26
Master 1. Overload operation
(261) (Pipe clogging/Covering/EEV defect/Ref.
Slave1 Inverter compressor overcharge)
Starting failure because of
(262) starting 2. Compressor damage
compressor abnormality
Slave2 failure Error (Insulation damage/Motor damage)
(263) 3. Compressor wiring fault
Slave3 4. ODU Comp PCB damage (CT)
(264)

■ Error diagnosis and countermeasure flow chart


1. Check Pipe clogging/distortion
2. Check Covering (Indoor/Outdoor Unit)
Is installation No 3. Check EEV connector assemble condition/normal
condition normal? operation
4. Check refrigerant pressure
→ Reassemble or manage if abnormality found
Yes

Are thereany powerwire No 1. Check R/S/T/N wiring conditions


connections normal? → Rewire them if abnormality found.

Yes
Are the resistance 1. Check resistance between each terminal of compressor
Between eachphase and No (U-V:0.255 ±7%, V-W:0.255 ±7%, W-U:0.255 ±7%(75℃)
insulationresistanceofInverter 2. Check insulation resistance between compressor
compressornormal? terminal and pipe (over 50M )
→ Replace compressor if abnormality found
Yes
1. Check Comp PCB assembly U,V,W connector
Is compressor No connection condition
Wire connection 2. Check wire disconnection and wiring
condition normal? 3. Check compressor terminal connection condition
(bad contact)
Yes → Reassemble if abnormality found

No Check Comp PCB assembly IPM normality


Is CompPCBassembly normal?
→ Replace Comp PCB assembly

Yes

Recheck power and installation


condition

18
Error
Error Type Error Point Main Reasons
No.
28
Master
(281)
Slave1 1. Input voltage abnormal (R,S,T,N)
Inverter DC link high Inv PCB DC link voltage
(282) 2. ODU Comp PCB damage
voltage error supplied over 780V
Slave2 (DC Link voltage sensing part)
(283)
Slave3
(284)

■ Error diagnosis and countermeasure flow chart

No 1. Check R/S/T/N wiring conditions


Are thereany powerwire
2. Check Noise filter wiring conditions
connections normal? → Rewire them if abnormality found.

Yes
Check
No R~S/S~T/T~R phase voltage is 380V 10%
Is input voltagenormal? R~N/S~N/T~N phase voltage is 220V 10%
→ Check connection condition and wiring if power is
abnormal
Yes

Is ConverterPCBassembly No
normal? Replace Converter PCB assembly

Yes

Is ConverterPCBassembly No
normal? Replace Converter PCB assembly

Yes

Recheck power and installation


condition

19
Error
Error Type Error Point Main Reasons
No.
29
Master 1. Overload operation
(291) (Pipe clogging/Covering/EEV defect/Ref.
Slave1 overcharge)
Inverter compressor Inverter compressor input
(292) 2. Compressor damage(Insulation
over current current is over 30A
Slave2 damage/Motor damage)
(293) 3. Input voltage low
Slave3 4. ODU Comp PCB assembly damage
(294)

■ Error diagnosis and countermeasure flow chart

1. Check Pipe clogging/distortion


Is installation No 2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal operation
condition normal?
4. Check refrigerant pressure
→ Reassemble or manage if abnormality found
Yes
1.Check resistance between each terminal of compressor
Are the resistance
No (U-V:0.255 ±7%, V-W:0.255 ±7%, W-U:0.255 ±7%(75℃)
Between eachphase and
2.Check insulation resistance between compressor terminal
insulationresistanceofInverter
and pipe (over 50M )
compressornormal?
→ Replace compressor if abnormality found
Yes
1. Check Comp PCB assembly U,V,W connector connection
Is compressor No condition
Wire connection
2. Check wire disconnection and wiring
condition normal?
3. Check compressor terminal connection condition (bad contact)
→ Reassemble if abnormality found
Yes

No Check
Is input voltagenormal? R~S/S~T/T~R phase voltage is 380V 10%
R~N/S~N/T~N phase voltage is 220V 10%
→ Check connection condition and wiring if power is abnormal
Yes

No 인버터 보드 IPM 정상유무 확인


Is CompPCBassembly normal?
→ 인버터 보드 교체

Yes

Recheck power and installation


condition

20
Error
Error Type Error Point Main Reasons
No.
32
Master
(321) 1. Temperature sensor defect of
Over-increase discharge
Slave1 Compressor is off because inverter compressor discharge pipe
temperature of inverter
(322) of over-increase discharge 2. Refrigerant shortage / leak
Compressor at main
Slave2 temperature of inverter 3. EEV defect
outdoor unit
(323) compressor 4. Liquid injection valve defect
Slave3
(324)

■ Error diagnosis and countermeasure flow chart

Is theamountof No No Change theamount of


refrigerant normal? Is therepipecrack
refrigerant
[refer refrigerantpart] or traceof leakage?
(Charge additiveamount)

Yes

Yes Weld / reconnectthecracked


portion andrechargerefrigerant

Is theresistanceof discharge No Replace discharge


temperaturesensornormal?* temperature sensor

Yes

Is EEV in
outside unit normal No
at heatingoperation? Replace outside unit EEV
[refer electric
component part]

Yes

Does liquid injection No


corresponded Check liquid injection
operate normally? corresponded

Yes

No Check another components


Is therepipe
(straineretc.)clogging? and operation conditions
/ Take measures
Yes

Replace strainer

21
Error
Error Type Error Point Main Reasons
No.
1. Defect of high pressure sensor
2. Defect of indoor or outside unit fan
34
3. Deformation because of damage of refrigerant
Master Error happens
pipe
(341) because of 3 times
4. Over-charged refrigerant
Slave1 Over-increase of dis- successive compres-
5. Defective indoor / outside unit EEV
(342) charge pressure of sor off due to over-
6. When blocked
Slave2 compressor increase of high pres-
- Outside unit is blocked during cooling
(343) sure by high pressure
- Indoor unit filter is blocked during heating
Slave3 sensor
7. SVC valve is clogged
(344)
8. PCB defect of outside unit
10. Indoor unit pipe temperature sensor defect

■ Error diagnosis and countermeasure flow chart

No Check about the water


Is circulation water
circulation system
normal?

Yes

No
Is servicevalveopened ? Open service valve

Yes
Are transmission No Check and repair
cable / pipeconnection transmission
normal? cable / pipe connection
Yes
Is refrigerant No
amount normal? Adjust refrigerant amount
[refer refrigerantpart]

Yes
Is fannormal? No Replace related parts
(Indoor fanduringheating
check water duringcooling) (Refer to Error 105~107)

Yes

Is filterblocked No Clean indoor filter (heating)


(Heating:indoor, /outside heat exchanger
Cooling:outside (cooling)?
heat exchanger)?

Yes
Is valueofhighpressure No Replace sensor of high
sensorsame as Manifold
value(Is it highactually)? pressure

Yes

Check indoor unit LEV


Check indoor unit PCB
Check in/outside installation
condition
22
Error
Error Type Error Point Main Reasons
No.
1. Defective low pressure sensor
2. Defective outdoor/indoor unit fan
35
3. Refrigerant shortage/leakage
Master Error happens
4. Deformation because of damage of refrigerant
(351) because of 3 times
pipe
Slave1 Excessive drop of successive compres-
5. Defective indoor / outdoor unit EEV
(352) discharge pressure sor off due to exces-
6. Covering / clogging
Slave2 of compressor sive drop of low pres-
(outdoor unit covering during the cooling mode/
(353) sure by the low pres-
indoor unit filter clogging during heating mode)
Slave3 sure sensor
7. SVC valve clogging
(354)
8. Defective outdoor unit PCB
9. Defective indoor unit pipe sensor

■ Error diagnosis and countermeasure flow chart

Is servicevalve No
Open service valve
opened?

Yes

Are communicationcable/ No
check communication/
piping normal? piping correction.

Yes

Is amount ofrefrigerant No No Adjust the amount


normal? Is therepipecrack ortrace
of refrigerant leakage? of refrigerant
[refer refrigerantpart]
(Additive charge)
Yes

Yes Weld / reconnect the cracked


portion and recharge
refrigerant

Is fannormal? No Check andreplacerelatedparts


(in heatingoutdoorfan,
in coolingindoorfan) (error 105~108reference)

Yes

No
Is strainerOk?* Replace the strainer

Yes
Are the values ofmanifold No
and low pressuresensorsame? Replace the pressure sensor
( Is thelowpressurevalue
actually low?)

Yes

Check indoor / outdoor unit LEV Check Indoor unit PCB


Check indoor / outdoor unit installation conditions

23
Error
Error Type Error Point Main Reasons
No.
40
Master
(401)
Slave1 Micom input voltage isn't 1. Input voltage abnormal (R-N)
Inverter compressor CT
(402) within 2.5V ±0.3V at initial 2. ODU Comp PCB damage
sensor error
Slave2 state of power supply (CT sensing part)
(403)
Slave3
(404)

■ Error diagnosis and countermeasure flow chart

No 1. Check R/S/T/N wiring conditions


Are thereany powerwire
2. Check Noise filter wiring conditions
connections normal?
→ Rewire them if abnormality found.

Yes
Check
No R~S/S~T/T~R phase voltage is 380V±10%
Is input voltagenormal?
R~N/S~N/T~N phase voltage is 220V±10%
→ Check connection condition and wiring if power is abnormal
Yes

No
Is CompPCBassembly normal? Replace Comp PCB assembly

Yes

Recheck power and installation


condition

24
Error
Error Type Error Point Main Reasons
No.
41
Master
(411) 1. Defective connection of the compressor
Slave1 Compressor dis- Sensor measurement discharge pipe temperature sensor
(412) charge pipe tempera- value is abnormal 2. Defective discharge pipe compressor
Slave2 ture sensor error (Open/Short) sensor of the compressor (open/short)
(413) 3. Defective outdoor PCB
Slave3
(414)

■ Error diagnosis and countermeasure flow chart

Sensor connectiontoPCB No Insert sensor connector to PCB


is normal? properly

Yes

Is theresistanceof No
Replace sensor
sensor normal?*

Yes
Is sensorresistance No
value sameastemperature Replace corresponding outdoor
value of LGMV? PCB

Yes

Replace corresponding sensor

* Error is generated if the resistance is more than 5M(open) and less than 2k (short)

Note: Standard values of resistance of sensors at different temperatures (5% variation)


10C = 362k : 25C= 200k : 50C= 82k : 100C= 18.5k

25
Error
Error Type Error Point Main Reasons
No.
42
Master
(421)
Slave1 Abnormal value of 1. Bad connection of low pressure connector
Sensor error of low
(422) sensor 2. Defect of low pressure connector (Open/Short)
pressure
Slave2 (Open/Short) 3. Defect of outdoor PCB
(423)
Slave3
(424)

43
Master
(431)
Slave1 Abnormal value of 1. Bad connection of high pressure connector
Sensor error of high
(432) sensor 2. Defect of high pressure connector (Open/Short)
pressure
Slave2 (Open/Short) 3. Defect of outdoor PCB
(433)
Slave3
(434)

■ Error diagnosis and countermeasure flow chart

Is sensorconnected No
Connect sensor to PCB correctly
to PCBcorrectly?

Yes

After replacement of No Replace corresponding


outdoor unit mainPCB
is the systemnormal? pressure sensor

Yes

END

26
Error
Error Type Error Point Main Reasons
No.
44
Master
(441)
Slave1 Sensor error of Abnormal value of 1. Bad connection of air temperature connector
(442) outdoor air temper- sensor 2. Defect of air temperature connector(Open/Short)
Slave2 ature (Open/Short) 3. Defect of outdoor PCB
(443)
Slave3
(444)
46
Master
(461)
Slave1 Compressor suc- Abnormal value of 1. Bad connection of air temperature connector
(462) tion temperature sensor 2. Defect of air temperature connector(Open/Short)
Slave2 sensor error (Open/Short) 3. Defect of outdoor PCB
(463)
Slave3
(464)
49
Master
(491)
Slave1 Outdoor Unit IPM Abnormal value of 1. Bad connection of air temperature connector
(492) Temperature sensor 2. Defect of air temperature connector(Open/Short)
Slave2 Sensor Fault (Open/Short) 3. Defect of outdoor PCB
(493)
Slave3
(494)

■ Error diagnosis and countermeasure flow chart

Is sensorconnected No
Connect sensor to PCB correctly
to PCBcorrectly??

Yes

No
Is sensorvaluecorrect?* Replace sensor

Yes

Replace corresponding
outdoor unit PCB

* If value is 100kΩ ↑(open) or 100Ω ↓(short), error occurs


NB: Resistance value of temperature sensor change according to temperature
It is normal if value shown as below (±5% error)
Sensor of air temperature: 10°C = 20.7kΩ : 25°C= 10kΩ : 50°C= 3.4kΩ
Sensor of piping temperature: 10°C = 10kΩ : 25°C= 5Ωk : 50°C= 1.8kΩ

27
Error
Error Type Error Point Main Reasons
No.
50
Master
(501)
1. Input Voltage abnormal (R,S,T,N)
Slave1
ODU 3phase power Omitting one or more of 2. Check power Line connection condition
(502)
omission error R,S,T input power 3. Converter PCB damage
Slave2
4. Converter PCB input current sensor fault
(503)
Slave3
(504)

■ Error diagnosis and countermeasure flow chart

Are thereany powerwire No 1. Check R/S/T/N wiring conditions


connections normal? → Rewire them if abnormality found.

Yes
Check
No R~S/S~T/T~R phase voltage is 380V±10%
Is input voltagenormal?
R~N/S~N/T~N phase voltage is 220V±10%
→ Check connection condition and wiring if power is abnormal
Yes

No 1. Check R~N/S~N/T~N phase voltage is 220V±10%


Is ConverterPCBassembly
2. Check Converter PCB assembly wire
normal? disconnection and wiring
→ Reassemble if abnormality found
Yes

No
INV. PCBLED display error Replace inverter PCB assembly.

Yes

Recheck power and installation


condition

28
Error
Error Type Error Point Main Reasons
No.
1.130% more than outdoor unit rated
capacity
2. Wrong connection of communication
Over-Capacity
51 Sum of indoor unit capaci- cable/piping
(Sum of indoor unit capaci-
Master ty exceed outdoor unit 3. Control error of slave outdoor unit
ty is more than outdoor
(511) capacity specification Dip switch
capacity)
4. Power supply defect of slave unit
PCB
5. Defect of outdoor unit PCB

■ Error diagnosis and countermeasure flow chart

Is capacity sumof
ndoor units less than No Are quantity andcapacity No Check communicationcables
130% of outdoorunit of indoor units installed between indoorand outdoor
capacity at LGMV? same as thedataof LGMV? units

Yes

Yes 실내/외기 용량 조절
Check following
dip S/W settingison No
Slave1: No.5,7 해당 딥 스위치 조절
Slave2: No. 6,7
Slave3: No. 5,6,7

Yes
No Is mainpowerreally supplied? No
Is power of SlavePCB Supply main
On? (Check LEDblinking) (Terminal BlockT-N)
power again
Yes
Yes
Check and replace PCB,
Line Fuse, Transformer

Is communicationmission No
cables betweenoutdoorunits Re-connect
connectedcorrectly?*

Yes

Is errorcodereleased No
in order(Slave2➠Slave1➠Main) Replace Main orSlavePCB
after powerreset?

Yes

End

* In order to check communication cables between outdoor units,


check in order as below : PCB connectors ➠ terminal block ➠ communication cables

29
Error
Error Type Error Point Main Reasons
No.
52
Master
(521)
Communication error Main PCB of Master unit 1. Power cable or communication
Slave1
between of Master unit can’t cable is not connected
(522)
(Compressor PCB receive signal from 2. Defect of outdoor Main PCB or
Slave2
➔ Main PCB) Comp1/Comp2 controller compressor
(523)
Slave3
(524)

■ Error diagnosis and countermeasure flow chart

Is communication No
LED (Yellow)of Re-connect communication cable
CompressorPCBon?

Yes

Is communicationcable No
Re-connect communication cable
connectedcorrectly?

Yes

No
Is MainPCBnormal? Replace Main PCB

Yes

Replace Compressor PCB

30
Error
Error Type Error Point Main Reasons
No.
1. Communication cables are not
connected between External PCB and
indoor PCB
2. Communication cables are not connected
between Main PCB and External PCB
53 In case Main PCB can’t 3. Communication cables are not connected
Communication error
Master receive signal from between Main PCB and Communication
(Indoor unit ➔ Main PCB)
(531) Indoor unit PCB
4. Communication cables are short/open
5. Indoor PCB power off
6. Defect of outdoor Cycle/Communication/
indoor PCB
7. Communication wire connection fault

■ Error diagnosis and countermeasure flow chart

Is power supplied No
Supply power
to indoor PCB?

Yes
1. Check communication cable between External and indoor PCB
→ Re-connect communication cable
2. Check communication cable between Cycle and External PCB
Is communicationcable No → Re-connect communication cable
connectedcorrectly? 3. Check communication cable between Cycle and Communication PCB
→ Re-connect communication cable
Yes 4. Check communication cable soldering correctly
→ Replace communication cable

1. Is indoor unit quantity correct after auto addressing


Are quantity ofindoor No → Check Communication PCB
Units installedsame as 2. Check communication PCB LED blinking
The data of LGMV? → Replace communication PCB
3. Auto addressing after replace Communication PCB
Yes → Check outdoor Main PCB

Check communication cable


and installation

In case of CH53, almost happened with CH05, the indoor units not operated actually are normal so check with same
method of CH05. and additionally check as shown as below and above flow chart
• Although the quantity of indoor units installed is same as LGMV data there may be a few indoor units with which the
number of communication is not increased with LGMV
• Although the quantity of indoor units installed is not same as LGMV data, and if communication of the indoor unit
displayed at LGMV is done well then the indoor unit suspected to have some problem (and is not appear at LGMV)
may have following problems
➀ wrong connection of communication cable or power cable
➁ fault of power / PCB / communication cable
➂ duplication of indoor unit number
• If communication is not doing well wholly then the Auto Addressing is not done
• The case that CH53 appear at indoor unit also Auto Addressing is not done so indoor unit address may be duplicated

* After replacement of indoor unit PCB, Auto Addressing should be done, if central controller is installed then the
central control address also should be input.
In case that only communication PCB is replaced above process is not needed

31
Error
Error Type Error Point Main Reasons
No.
57
Master
(571) 1. Bad Connection Between Comp
Slave1 Failing to receive inverter PCB and Comp PCB
Communication error : Main
(572) signal at main PCB of 2. Communication Wire Noise Effect
PCB --> Comp PCB
Slave2 Outdoor Unit 3. ODU Main PCB Damage
(573) 4. ODU Main PCB Damage
Slave3
(574)

■ Error diagnosis and countermeasure flow chart

Are thereany No 1. Check communication wiring conditions


communicationwire 2. Check connector conditions
connections normal? → Rewire them if abnormality found.

Yes

Is CompPCB No
1. Replace Comp PCB
assembly normal?

Yes

Is thereany error No
1. Replace Main PCB
when power reset?

Yes

Recheck power and


installation condition

32
Error
Error Type Error Point Main Reasons
No.
59 Series Installation of Slave
Series Installation
Master Outdoor Unit Larger Than 1. Dip Switch Setting Error
Error
(591) Master Capacity

■ Error diagnosis and countermeasure flow chart

Is Dipswitch No
setting normal? 1. Set the most capacitor ODU for Master

Yes
Are theresettingwith No
Master→Slave1→Slave2→ Set with Master→Slave1→Slave2→Slaver3
Slaver3?

Yes

Is thereany errorwhen No
power reset? 1. Replace Main PCB

Yes

Recheck installation
condition

33
Error
Error Type Error Point Main Reasons
No.
60
Master
(601)
Slave1 1. EEPROM contact defect/wrong insertion
Comp PCB EEP- EEPROM Access error
(602) 2. Different EEPROM Version
ROM error and Check SUM error
Slave2 3. ODU Comp PCB assembly damage
(603)
Slave3
(604)

■ Error diagnosis and countermeasure flow chart

No 1.Check EEPROM insert direction/connection condition


Is EEPROMinsertionnormal? 2.Check EEPROM Check SUM
’ Replace if abnormality found

Yes

No
Is CompPCBassembly normal? Replace Comp PCB assembly

Yes

Recheck power and installation


condition

34
Error
Error Type Error Point Main Reasons
No.
62
1. Inverter PCBA IPM Connection
Master
condition Abnormal
(621)
2. Outdoor Unit Fan Motor Operation
Slave1
Inverter PCB Heatsink Heatsink Temperature abnormal
(622)
Temperature High is Over 90°C 3. Outdoor Unit Inverter PCB Assembly
Slave2
defect
(623)
4. Overload Operation (Pipe Clogging/
Slave3
covering/EEV Defect/Ref. Overcharge)
(624)

■ Error diagnosis and countermeasure flow chart

1. Check Pipe Clogging/ Distortion


2. Check Covering (Outdoor/Indoor Unit)
Is Installation No 3. Check EEV Connector Assemble Condition/Normal
ConditionNormal? Operation
4. Check Refrigerant Pressure
5. Check Power Wire/ Connection Condition
Yes → Reassemble or Manage if abnormality Found

InverterPCBIPM Connection No 1. Check Inverter PCBA Screw Connection Condition


ConditionNormal? → Reassemble or Manage if abnormality Found

Yes

No 1. Check Outdoor Unit Fan Motor Operation or Lock


Is ODUFanMotor Normal?
→ Reassemble or Manage if abnormality Found

Yes

Is InverterPCBassembly No 1. Reset
Normal? →Replace Inverter PCB Assembly

Yes

Recheck power and installation


condition

35
Error
Error Type Error Point Main Reasons
No.
65
Master
(651)
Slave1 Outdoor unit liquid Abnormal sensor resis- 1. Defective temperature sensor connection
(652) pipe (condenser) tem- tance value 2. Defective temperature sensor (Open / Short)
Slave2 perature sensor error (Open/Short) 3. Defective outdoor unit PCB
(653)
Slave3
(654)

■ Error diagnosis and countermeasure flow chart

Is temperaturesensor No
connectorconnections Check and correct connection
are normal?

Yes

Is thevalueof temperature No
Replace sensor
sensor resistancenormal?*

Yes

Replace outdoor unit PCB

36
Error
Error Type Error Point Main Reasons
No.
71
Master
(711)
Micom input voltage
Slave1 1. Input Voltage is abnormal (R-N)
Converter CT Sensor isn’t within 2.5V±0.3V
(712) 2. ODU Converter PCB damage (CT
Error at initial state of power
Slave2 sensing part)
supply
(713)
Slave3
(714)

■ Error diagnosis and countermeasure flow chart

No 1. Check R/S/T/N wiring conditions


Are thereany powerwire 2. Check noise filer wiring conditions
Connections normal? Rewire them if abnormality found

Yes
Check
No R~S/S~T/T~R phase voltage 380V±10%
Is input voltagenormal? R~N/S~N/T~N phase voltage 200V±10%
Check connection condition and wiring if power is
abnormal
Yes

Is ConverterPCB No
1. Replace Converter PCB
Assemblynormal?

Yes

Recheck Power and


Installation Condition

37
Error
Error Type Error Point Main Reasons
No.
86
Master
(861)
Slave1
1. No EEPROM
(862) Main PCB EEPROM EEPROM Access Error
2. EEPROM wrong insertion
Slave2
(863)
Slave3
(864)

■ Error diagnosis and countermeasure flow chart

Is EEPROMassemble No
Reset after checking EEPROM assemble condition
condition normal?

Yes

No
Correct check sum Replace Correct EEPROM

Yes

Recheck power and


installation condition

38
Error
Error Type Error Point Main Reasons
No.

104
Master
(1041)
Slave1 Communication Master displays ODU number 1.Loose connection of power cable/
(1042) Error Between which is not communicated. communication cable¸(Open/Short)
Slave2 Outdoors Slave displays own error number 2.Defect of each outdoor unit PCB
(1043)
Slave3
(1044)

■ Error diagnosis and countermeasure flow chart

Is communication No
cable installed Connect communication cable
normally?

Yes

Is SlaveUnit DipSW No
Dip SW setting
setting done?

Yes

Is MainPCBpower No
Connect power cable
supplied?

Yes

Replace Main PCB

39
Error
Error Type Error Point Main Reasons
No.
113
Master
(1131)
Slave1 Outside unit liquid pipe Abnormal sensor 1. Defective temperature sensor connection
(1132) (condenser) temperature resistance value 2. Defective temperature sensor (Open/Short)
Slave2 sensor error (Open/Short) 3. Defective outdoor PCB
(1133)
Slave3
(1134)
115
Master
(1151)
Outdoor Unit
Slave1 Abnormal sensor 1. Defective temperature sensor connection
Subcooling Outlet
(1152) resistance value 2. Defective temperature sensor (Open/Short)
Temperature Sensor
Slave2 (Open/Short) 3. Defective outdoor PCB
Error
(1153)
Slave3
(1154)

■ Error diagnosis and countermeasure flow chart

Is temperaturesensor No
connectorconnections Check and correct connection
are normal?

Yes

Is thevalueof temperature No
Replace sensor
sensor resistancenormal?*

Yes

Replace outdoor unit PCB

* Sensor resistance 100 kΩover (open) or 100 Ω below (short) will generate error

Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance
value according to outdoor unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ
Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ

40
Error
Error Type Error Point Main Reasons
No.
116
Master
(1161)
Lack of comp. oil
Slave1
Outdoor Unit Oil level Abnormal sensor 1. Lack of Comp. Oil
(1162)
Sensor Error resistance value 2. Defective oil sensor (Open/Short)
Slave2
(Open/Short)
(1163)
Slave3
(1164)

■ Error diagnosis and countermeasure flow chart

Is the oil sensor No


Check and correct connection
connection on PCB normal?

Yes

Is the oil sensor No


Check and correct connection
connection on comp normal?

Yes

Replace oil sensor

41
Error
Error Type Error Point Main Reasons
No.

145
Master
(1451)
Communication Error 1. Power cable or communication
Slave1 Cycle controller of Master unit
between cable is not connected
(1452) of Master unit can’t receive
(Main PCB → External 2. Defect of outdoor Cycle/External
Slave2 signal from External controller
PCB) PCB
(1453)
Slave3
(1454)

■ Error diagnosis and countermeasure flow chart

Is communicationLED No
(Yellow) of Re-connect Power cable
External PCBon?

Yes

Is communicationcable No
Re-connect communication cable
connectedcorrectly?

Yes

No
Is MainPCBnormal Replace Main PCB

Yes

Replace External PCB

42
Error
Error Type Error Point Main Reasons
No.

1. Wrong operation of 4way valve


because of sludge etc. inflow
151 Function error of 4way 2. No pressure difference because of
Function error of outdoor
Master (reversing valve) in Main or compressor fault
4way (reversing valve)
(1511) Slave outdoor units 3. Wrong installation of In/outdoor
common pipe
4. Defect of 4way valve

■ Error diagnosis and countermeasure flow chart


Is 4-Way valveconnecter No
connectionareproperly Reconnect it
connected?

Yes

Is 4 Way valvecoil No
Change 4 Way valve coil
resistancenormal?*

Yes

Is 4 way valvecoilconnected No
Re-insert 4 way valve coil
to 4 way valvenormally?**

Yes
In caseofmorethan
2 units, does masteroutdoor No
unit recognizeas more Refer to CH 51 & make measure
than 2 units?***

Yes
After reset, canwe
check supply voltageat PCB No
when startingheating Replace outdoor unit PCB
mode operation****
Yes

Is compressorworking No Check and replace compressor,


normally? Magnet switch, corresponding PCB
[refer electric component part]

Yes
After opposite
mode operationtopresent No If the same error is occurred in
mode, is thesameerror near future replace 4way valve
occurred again?
Yes

Replace 4 way valve

43
Error
Error Type Error Point Main Reasons
No.
180
Master
(1801)
Slave1 1. Lack of circulation water
Plate type heat exchanger
(1802) 2. Defective water temperature sensor
freeze prevention
Slave2 (Open/Short)
(1803)
Slave3
(1804)

■ Error diagnosis and countermeasure flow chart

Is circulation water No Check about the water


normal? circulation system and reset

Yes

No
Is DIP switch setting geothermalmode? Check and set geothermal mode

Yes
Is temperaturesensor No
connectorconnections Check and correct connection
are normal?

Yes

Is thevalueof temperature No
Replace sensor
sensor resistancenormal?*

Yes

Replace outdoor unit PCB

* Sensor resistance 100 kΩover (open) or 100 Ω below (short) will generate error

Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance
value according to outdoor unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ
Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ

44
Error
Error Type Error Point Main Reasons
No.

181
Master
(1811)
Slave1 Abnormal sensor 1. Defective temperature sensor connection
Water temperature
(1812) resistance value 2. Defective temperature sensor (Open/Short)
sensor error
Slave2 (Open/Short) 3. Defective outdoor PCB
(1813)
Slave3
(1814)

■ Error diagnosis and countermeasure flow chart

Is temperaturesensor No
connectorconnections Check and correct connection
are normal?

Yes

Is thevalueof temperature No
Replace sensor
sensor resistancenormal?*

Yes

Replace outdoor unit PCB

* Sensor resistance 100 kΩover (open) or 100 Ω below (short) will generate error

Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance
value according to outdoor unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ
Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ

45
Error
Error Type Error Point Main Reasons
No.
182
Master
(1812)
Slave1 Communication Error Failure Receiving Signal
1. Failure Receiving Signal Between
(1822) Between Main and Sub Between Main and Sub
Main and Sub Micom
Slave2 Micom of External PCB Micom
(1823)
Slave3
(1824)

■ Error diagnosis and countermeasure flow chart

CommunicationBetween No
Push the RESET Replay Replace External
Main-Sub Micom
LED (Yellow)Blinking button On-boarding PCB

Yes

END

46
Error
Error Type Error Point Main Reasons
No.

1. RS-485 communication wiring defect


2. Communication defect between
Network error of central remote controller and indoor unit
242 Network Error
controller 3. RS-485 dip switch setting error
4. Indoor unit addressing setting error
on central controller

■ Error diagnosis and countermeasure flow chart

Are thereany
communicationwire of No
. Reconnect RS-485 communication wire
RS-485 connections
normal?
Yes

Are thereany overlapof No


Reset the overlap of IDU address for single address
IDU address?

Yes
Is Simplecentral No Set the slave mode with Simple central controller after
controllersetting
normal? reset.

Yes

Recheck power and


installation condition

47