Professional Documents
Culture Documents
D 0003 Cube Upblast Centrifugal Rof Exhaust
D 0003 Cube Upblast Centrifugal Rof Exhaust
®
Upblast Centrifugal Roof Exhaust 1
Table of Contents IMPORTANT
Receiving, Unpacking, Handling . . . . . . . . . . . 2-3 Do not lift by the fan hood. Avoid lifting fans in a way
Storage. . . . . . . . . . . . . . . . . . . . . . . . . 3 that will bend or distort fan parts. Never pass slings or
Inspection and Maintenance During Storage . . . . . 3 timbers through the venturi of fan. Fans with special
Removing from Storage . . . . . . . . . . . . . . . . 3 coatings or paints must be protected in handling to
Dimensional Data . . . . . . . . . . . . . . . . . . . 4 prevent damage.
Installation
Handling
General Ventilation Installation . . . . . . . . . . . 4
Sidewall Mounting Installation . . . . . . . . . . . . 5 Direct and Belt Drive Units
Commercial Kitchen Installation . . . . . . . . . . . 5 Lift Direct Drive unit on to the roof utilizing hooks under
Grease Trap Installation . . . . . . . . . . . . . . . 6 the horizontal supports. Evenly space the hooks using
Hinge Installation. . . . . . . . . . . . . . . . . . . 6 a minimum of four lifting straps. Use a spreader bar to
ensure the straps do not come in contact with the unit,
UL Listed Emergency Smoke Control Installation . . 6
see Figure 1.
Pre-Starting Checks . . . . . . . . . . . . . . . . . 6-7
Operation. . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 1
Inspection . . . . . . . . . . . . . . . . . . . . . . . 8
Maintenance . . . . . . . . . . . . . . . . . . . . . . 8
Tapered Bushing Hub Installation
and Removal . . . . . . . . . . . . . . . . . . . . 8-9
Busing Installation . . . . . . . . . . . . . . . . . . 9
Belt and Bearing Maintenance. . . . . . . . . . . . 9
Bearing Lubrication Schedule . . . . . . . . . . . . 9
Parts List . . . . . . . . . . . . . . . . . . . . . . . .10
Fan Inlet Connections . . . . . . . . . . . . . . . . .11
Troubleshooting . . . . . . . . . . . . . . . . . . . .11
Mounting for Severe Duty Installation . . . . Backcover
Our Commitment. . . . . . . . . . . . . . . Backcover
Receiving
Upon receiving the product, check to ensure all Figure 2
items are accounted for by referencing the delivery Hook With
receipt or packing list. Inspect each crate or carton Safety Latch
for shipping damage before accepting delivery. Alert (Supplied by others)
the carrier of any damage detected. The customer will
make notation of damage (or shortage of items) on (2) Bearing Plate
the delivery receipt and all copies of the bill of lading Lifting Points
which is countersigned by the delivering carrier. If
damaged, immediately contact your representative. Any
physical damage to the unit after acceptance is not the
responsibility of the manufacturer.
Unpacking
(4) Drive Frame
Verify that all required parts and the correct quantity Lifting Points
of each item have been received. If any items are
missing, report shortages to your local representative to
arrange for obtaining missing parts. Sometimes it is not Figure 3
possible that all items for the unit be shipped together
Screw Screw
due to availability of transportation and truck space.
Confirmation of shipment(s) must be limited to only
items on the bill of lading.
®
Upblast Centrifugal Roof Exhaust 3
Dimensional Data 1. On the roof surface,
cut an appropriate
Direct Drive sized hole and follow
Roof *Approx.
Model Size Curb Cap Damper
Opening Weight
manufacturer’s
060, 065, 070, 075 17 (432) 8 (203) 101⁄2 (267) 29 (13)
instructions on curb
080, 085, 090, 095 19 (483) 10 (254) 121⁄2 (318) 40 (18) installation. Caulk and
099, 101, 121, 131 19 (483) 12 (305) 141⁄2 (368) 67 (30) flash the curb to ensure
141, 161 22 (559) 16 (406) 181⁄2 (470) 90 (41) a water tight seal.
180, 200 30 (762) 18 (457) 201⁄2 (521) 142 (64) 2. If unit is equipped with
• All dimensions are in inches (millimeters). *Approximate weight shown in lbs. a backdraft damper, it
(kg.) is the largest cataloged open drip proof motor.
• “Curb Cap” is the inside dimension of the curb cap
should be installed now.
• The roof curb should be 1½ in. (38 mm) less than the curb cap to allow for 3. Remove motor cover.
roofing and flashing.
Access to the motor
• Roof opening is a square dimension.
compartment is
Figure 5 - Roof Curb Installation
accomplished by
Belt Drive
Shaft Roof *Approx.
removing the screws as shown in Figure 3, page 2.
Model Size Curb Cap Damper
Bearings Opening Weight 4a. On belt drive fans, use the lifting lugs on the drive
099, 101, 101HP, frame or bearing plate to lift and place the unit on
19 (483) ⁄4 (19)
3
12 (305) 141⁄2 (368) 66 (30)
121, 131
141, 141HP, 161,
top of roof curb. Refer to Figure 2, page 2.
22 (559) ⁄4 (19)
3
16 (406) 181⁄2 (470) 87 (39)
161HP 4b. On direct drive fans, lift and place the unit on
161XP 22 (559) 1 (25) 16 (406) 181⁄2 (470) 87 (39) top of roof curb using hooks under the horizontal
180 30 (762) 3
⁄4 (19) 18 (457) 201⁄2 (521) 126 (57) supports. Refer to Figure 1, page 2.
180HP 30 (762) 1 (25) 18 (457) 201⁄2 (521) 126 (57)
200 30 (762) 3
⁄4 (19) 18 (457) 201⁄2 (521) 142 (64)
5. Secure fan to curb using a minimum of eight lag
200HP 30 (762) 1 (25) 18 (457) 201⁄2 (521) 142 (64)
screws, metal screws or other suitable fasteners.
220, 220HP, 240, Shims may be required depending upon curb
34 (864) 1 (25) 24 (610) 261⁄2 (673) 175 (79) installation and roofing material.
240 HP, 240 XP
300, 300HP, 300XP 40 (1016) 1 (25) 30 (762) 32½ (826) 313 (142) 6. Verify power line wiring is de-energized before
360, 360HP, 360XP 46 (1168) 11⁄4 (32) 36 (914) 381⁄2 (978) 440 (200)
connecting fan motor to power source.
420 52 (1321) 11⁄4 (32) 42 (1067) 441⁄2 (1130) 578 (262)
480 58 (1473) 11⁄2 (38) 48 (1219) 501⁄2 (1283) 675 (306) 7. For commercial kitchen and UL Listed emergency
• All dimensions are in inches (millimeters). *Approximate weight shown in lbs. smoke control applications, the electrical supply
(kg.) is the largest cataloged open drip proof motor. must enter the motor compartment through
• “Curb Cap” is the inside dimension of the curb cap the breather tube. For other non-flammable
• The roof curb should be 1½ in. (38 mm) less than the curb cap to allow for
roofing and flashing.
applications, the electrical supply can be routed
• Roof opening is a square dimension. through the conduit chase between the curb cap
and the bottom of the motor compartment.
8. Connect power supply wiring to the motor as
Installation indicated on the motor nameplate or terminal box
General Ventilation Installation cover. Check the power source for compatibility
with the requirements of your equipment.
Screw Screw 9. Check fan wheel for free rotation, recenter if
necessary. Check setscrew(s) for tightness.
10. Check all fasteners for tightness.
Conduit
11. Mount and wire safety disconnect switch under
Factory Wired
Chase Motor to motor cover. Wire control switches at ground level,
Disconnect
refer to Figure 6.
3/4 in.
(19 mm)
8 or 12 in. min. Wiring by
Others
(203 or 305 mm) Damper MOTOR MOTOR
Recommended
Roof Opening Figure 6 - Typical Wiring Diagram
Sidewall Mounting Installation du ventilateur non raccordée à une gaine doit comporter une
protection adaptée.
3. Lift the fan into place. Do NOT support the unit by Screw Screw
Discharge Height
screws, metal screws or other suitable fasteners. Mounting (per NFPA)
Installation
5. Follow steps 6 through 12 of General Ventilation Optional Welded Duct
by others
Optional
Vented Curb
Grease
Installation instructions on page 4. Trap minimum of
18 in. (457
Extension
Liquid Tight
mm) above Flexible Conduit
roof deck by Others
(per NFPA)
8 in. min.
Standard (203 mm)
Recommended
Roof Opening
Grease Trough
IMPORTANT
Pointed Down
Hoodband The size of the duct must be equal to or larger than
the inlet opening of the fan.
Wall
Unit
To comply with NFPA 96, the fan discharge must be a
minimum of 40 in. (1016 mm) above the roof surface
Secure standard
roof curb flange and a minimum of 10 ft. (3048 mm) from any building
to wall opening air intake.
Minimum of
(8) 3/8 inch Per NFPA 96, ductwork to an upblast discharge
fasteners around
the flange exhaust fan must be constructed of and supported
by carbon steel not less than No. 6 MSG (1.52 mm) or
stainless steel not less than No. 18 MSG (1.21 mm) in
thickness. Duct must also extend a minimum of 18 in.
Grease Trough (457 mm) above the roof surface.
Standard Roof Curb
Ensure that a minimum of 500 ft/min of air velocity
Figure 7 - Typical Sidewall Mounting Installation through the duct is maintained per NFPA 96, clause
8.2.1.1, 2014 edition and UL 762, Issue #7, clause 6.2,
October 14, 2013.
The following accessories may be required by
NFPA 96 depending upon installation: Grease Trap,
Hinge Kit or Hinged Base, Clean-Out Port, and Vented
Curb.
®
Upblast Centrifugal Roof Exhaust 5
IMPORTANT UL Listed Emergency
Smoke Control Installation
Minimum duct velocities must be maintained in
kitchen exhaust applications. If a speed controller is Factory
Installed
used, ensure compliance with all applicable codes. Heat Baffle
NEMA-3R
Disconnect
–Important– wired to motor
ELECTRICAL – If fan motor is NOT thermally protected, remote
through the
overload protection must be installed having adequate rating as to breather tube
Representation of voltage, frequency, horsepower, and full load current per phase.
Where connected to a circuit protected by fuses, use time delay fuses.
UL Listed For supply connection use wires rated for at least 90°C (194°F).
Exhaust Exhaust Must be installed in accordance with the requirements to NFPA 96 or Liquid Tight
Appliances must have minimum clearances of zero inches to non-combustibles, Flexible Conduit
Appliances 13G3 3 inches to limited combustibles, 18 inches to combustibles.
by Others
Maximum CAUTION – Mount with the lowest moving part at least 8 ft 8 in. (203 mm)
label Operating PDERYHÀRRURUJUDGHOHYHO1RWUHTXLUHGRQURRIPRXQWHG
minimum
Temperature ventilators or duct mounted ventilators provided with belt guards.
400°F
ATTENTION – Monter la pièce mobile la plus basse à au moins
2,5 m au-dessus du niveau du sol. Non requis pour les ventilateurs
montés sur un toit ou pour les ventilateurs montés sur gaine avec
protège-courroie. 461546
Roof Deck
• Check grease absorber (if included) every month. of a fire, the fan will ELECTRICAL – If fan motor is NOT thermally protected, remote
overload protection must be installed having adequate rating as to
voltage, frequency, horsepower, and full load current per phase.
Replace grease absorber after every cleaning and/ continue to operate. Where connected to a circuit protected by fuses, use time delay fuses.
For supply connection use wires rated for at least 90°C (194°F).
INSTALLATION – When connecting electrical power to this fan,
or as needed between cleanings. Check the local and Power
Ventilator
do not restrict motor movement for possible future belt or wheel
adjustment.
• Replacement grease absorbers (P/N 476084) can national electrical For Smoke
Control CAUTION – Mount with the lowest moving part at least 8 ft
PDERYHÀRRURUJUDGHOHYHO1RWUHTXLUHGRQURRIPRXQWHG
Systems
be ordered from your local representative. codes for emergency 76Y9 ventilators or duct mounted ventilators provided with belt guards.
ATTENTION – Monter la pièce mobile la plus basse à au moins
smoke removal fans. 2,5 m au-dessus du niveau du sol. Non requis pour les ventilateurs
montés sur un toit ou pour les ventilateurs montés sur gaine avec
NFPA 96: Upblast exhaust fans shall be supplied authorities for your 454975
G H
Figure 13
Wheel Overlap and
Gap Dimension
®
Upblast Centrifugal Roof Exhaust 7
Operation IMPORTANT
1. Before starting up or operating fan, check all Uneven cleaning of the wheel will produce an out of
fasteners for tightness. In particular, check the balance condition that will cause vibration in the fan.
setscrews in the wheel hub (or the tapered bushing Installation and maintenance are to be performed only
and pulleys if applicable). by qualified personnel who are familiar with local codes
2. While in the OFF position or before connecting the and regulations and who are experienced with this type
fan to power, turn the fan wheel by hand to be sure it of equipment.
is not striking the venturi or any obstacle.
Motor maintenance is generally limited to cleaning
3. Start the fan and shut it off immediately to check and lubrication (where applicable). Cleaning should be
rotation of the wheel with directional arrow in the limited to exterior surfaces only. Removing dust buildup
motor compartment, reference Figure 14. on motor housing ensures proper motor cooling.
4. When the fan is started, observe the operation and Greasing of motors is only intended when fittings are
check for any unusual noises. provided. Many fractional horsepower motors are
5. With the system in full operation and all ductwork permanently lubricated and should not be lubricated
attached, measure current input to the motor and after installation. Motors supplied with grease fittings
compare with the nameplate rating to determine if should be greased in accordance with manufacturer’s
the motor is operating under safe load conditions. recommendations. Where motor temperatures do not
6. Keep inlets and approaches to fan clean and free exceed 104ºF (40ºC), the grease should be replaced
from obstruction. after 2,000 hours of running time as a general rule.
Wheels require very little attention when moving clean
IMPORTANT air. Occasionally, oil and dust may accumulate causing
Adjust (tighten) belt tension after the first 24-48 hours imbalance. When this occurs, the wheel and housing
of operation. should be cleaned to ensure smooth and safe operation.
All fasteners should be checked for tightness each time
Inspection maintenance checks are performed prior to restarting
unit.
Inspection of the fan should be conducted at the • When installing fans for restaurant exhaust
first 30 minute and 24 hour intervals of satisfactory applications follow NFPA 96 for cleaning fans.
operation.
• Grease containers must be emptied at regular
30 Minute Interval: Inspect bolts, setscrews and motor intervals to prevent overflow.
mounting bolts. Adjust and tighten as necessary.
A proper maintenance program will help these units
24 Hour Interval: Check all internal components. On deliver years of dependable service.
belt drive unit only, inspect belt alignment and tension.
Adjust and tighten as necessary. Tapered Bushing Hub Installation
and Removal
Maintenance For wheel hubs and shaft pulleys utilizing a tapered
bushing interface, follow this procedure for installation
DANGER and removal. There are two possible set ups for the
tapered bushing, both have the same procedure, but
Disconnect and secure to the “off” position all orientation of the hub varies.
electrical power to the fan prior to inspection or
servicing. Failure to comply with this safety precaution Tapered Bushing Removal:
could result in serious injury or death. 1. If present, loosen the setscrew holding the bushing
and shaft key in place.
WARNING
2. Loosen and remove the socket head cap screws
This unit should be made non-functional when
which fasten the bushing to the hub as shown in the
cleaning the wheel or housing (fuses removed,
section views and examples of Figures 19-22.
disconnect locked off).
3. Standard Mounting: Take the two socket head cap
DANGER screws that were removed and install them into the
Pour écarter les risques de blessure grave ou de mort, visibly threaded holes on the wheel hub.
débrancher et verrouiller l’alimentation électrique en Reverse Mounting: Install the two socket head cap
position « Arrêt » avant tout contrôle ou entretien. screws into the visibly threaded holes of the bushing
AVERTISSEMENT flange.
L’appareil doit être rendu non opérationnel lors du 4. Once both socket head cap screws are installed,
nettoyage de la turbine ou du caisson (fusibles retirés, tighten them an eighth of a turn at a time, alternating
sectionneur verrouillé). between the two until the hub comes loose from the
bushing.
8 Upblast Centrifugal Roof Exhaust ®
Standard Mounting Reverse Mounting 3. Install the two bushing socket head cap screws
into the aligned holes by hand (or without excessive
torque) until the heads of the socket head cap
screws are seated against the mating surface.
4. Adjust the height of the wheel in the fan relative to
the inlet venturi then tighten the two socket head
cap screws an eighth turn at a time in an alternating
fashion and to a torque of 10 ft-lbs.
Belt and Bearing Maintenance
1. Belts tend to stretch after a period of time. They
Figure 19 Figure 20 should be checked periodically for wear and
tightness. When replacing belts, use the same type
Hub
as supplied with the unit.
Bushing
2. Matched belts should always be used on units with
Hub multi-groove pulleys.
3. For belt replacement, loosen tensioning device
enough to allow removal of the belt by hand.
4. Once installed, adjust belts as shown in
Bushing
Washers “Pre-Starting Checks.”
Cap Screws
Washers
5. To ensure tightness, check pulley setscrews. Proper
keys must be in keyways.
Cap Screws
Parts List
Each fan bears a manufacturer’s nameplate with model bva
number and serial number embossed. This information
CAUTION
will assist the local representative and the factory in
providing service and replacement parts. Before taking A fan manufactured with an explosion resistant motor
any corrective action, make certain unit is not capable does not certify the entire unit to be explosion proof.
of operation during repairs. Refer to UL Listing mark for the fans approved usage.
NOTE CAUTION
For replacement, the windband, vertical supports, La présence d’un moteur antidéflagrant sur un
drain trough and curb cap/venturi come as one ventilateur ne garantit pas que tout l’appareil est
complete assembly. antidéflagrant. Pour connaître les emplois autorisés
de l’appareil, voir son marquage de conformité UL.
Motor
Hoodband Hood Clip Hoodband Pulley
Disconnect
Belt
Shaft Pulley
Motor
Motor Disconnect Motor
Vibration Support Pan Switch
Isolators
Horizontal Vibration Hoodband
Support Isolators Bracket
Wheel Vertical Drive Frame Fan Shaft
Support Assembly
Conduit
Chase Horizontal
Breather Tube Vertical
Support Support
Windband Wheel
Breather Tube
Birdguard in tube
Drain
Birdguard Windband
Trough
Curb Cap/
Curb Cap/ Venturi
Venturi
Good
Poor Poor Good
Dampers must open fully. Use Avoid sharp turns or entrance Provide uniform airflow at fan inlet Provide uniform airflow at fan inlet and
motorized dampers in low airflow conditions which cause uneven to ensure optimum performance. through the damper to ensure optimum
applications to reduce losses. flow. Use turning vanes in elbows performance. Curb cap should be three
to reduce adverse effects. wheel diameters from the radius. Use
turning vanes in duct when possible.
Troubleshooting
WARNING AVERTISSEMENT
Before taking any corrective action, make certain unit Avant d’entreprendre toute action corrective, s’assurer
is not capable of operation during repairs. que l’appareil ne pourra pas fonctionner durant les
réparations.
®
Upblast Centrifugal Roof Exhaust 11
Mounting for Severe Duty Installation
IMPORTANT High Wind Ratings Seismic Ratings
Fasteners Fasteners
Only qualified installers should perform this work. Fan Curb Cap Size Per Per
Total Fan Size
Manufacturer assumes no liability for damages Size inches (millimeters) Side Side Total
resulting from installation. ≤ 17x17 to 22x22
3 12 060-240 2 8
161 (432x432 to 559x559 mm)
Installation instructions for seismic ratings are only
Steel
> 26x26 to 40x40
recommendations. Final design must be determined 4 16 300-360 3 12
161 (660x660 to 1016x1016 mm)
by Structural Engineer of Record (SEOR) including 420-480 5 20
requirements for curb construction, mounting of unit ≤ 17x17 to 22x22
3 12 060-240 2 8
161 (432x432 to 559x559 mm)
Concrete
to curb and mounting of curb to structure.
> 26x26 to 40x40
Fan to Curb Mounting: 5/16-inch (7.9 mm) self-drilling 3 12 300-360 3 12
161 (660x660 to 1016x1016 mm)
fasteners are to be installed on each side of fan with one 420-480 5 20
fastener 4-inches (102 mm) ≤ 17x17 to 22x22
3 12 060-240 2 8
from each edge and one Unit 161 (432x432 to 559x559 mm)
Wood
fastener in the center, > 26x26 to 40x40
4 16 300-360 3 12
161 (660x660 to 1016x1016 mm)
Figure 10. Fasteners are
420-480 5 20
to be equally spaced. All dimensions are in inches (millimeters).
Roof Curb
Model GPF, GPFHL, Curb to Deck Mounting: Fasteners need to be
GPFHD or Equivalent
18 ga. min. 1.25 in. located on all four sides of the curb,
1.25 in.
High Wind Ratings
42 in. Tall Max Figures 12a and 12b.
Seismic Ratings Figure 12a
24 in. Tall Max Curb Corner
Welded Steel Construction Anchor Detail Roof Curb Roof Curb
Optional Hinged Base Mounting: For installations Concrete Anchoring Steel Anchoring
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library
under Warranties.
Greenheck’s Centrifugal Upblast and Sidewall Exhaust catalog AMCA Publication 410-96, Safety Practices for Users and
provides additional information describing the equipment, fan Installers of Industrial and Commercial Fans, provides
performance, available accessories, and specification data. additional safety information. This publication can be obtained
from AMCA International, Inc. at www.amca.org.
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
12 471560 • CUE and CUBE, Rev. 10, March 2018 Copyright 2018 © Greenheck Fan Corporation