Professional Documents
Culture Documents
Geunir DL GB3 PDF
Geunir DL GB3 PDF
V.1
GE UNI RS DL
GE UNIR DL
CONTROL UNIT FOR TWO-LEAF GATES
Page 1
STANDARD INSTALLATION
Energy Saving
In order to save energy, we have introduced the function
Energy Saving. 10 minutes after the end of programmation of the control board, the LED
of the keyboard go out and it is no more possible to use the control board. To get the control
board working again, switch it off and on.
Page 2
GEBOX ASSEMBLY INSTRUCTIONS.
1
2
mm
3 .1
84
4
mm. 250
min cm 40
Page 3
1.2 List of electric cables
The cables needed may vary depending on the installation and type and quantity of devices installed.
Tx Photo 2x1 mm2 cable a)F1 protects the secondary 24v supply against
transformer overload
Rx Photo 4x1 mm2 cable Technical: Mini fuses 5x20 T1.6A certificated by IEC
60127 or EN 60127
Selector 3x1 mm2 cable
1.2.1 Setting up the electric system and connection to the mains supply
This manual does not describe how the electrics system should be prepared for connection to the mains. It does, however, give the following warnings:
• The electricity supply line must be installed and connected by an authorised electrician or professional fitter.
• The electricity supply must be adequately protected against short circuits and static discharge.
• The power supply network must contain an omnipolar circuit breaker with a contact opening distance equal to or greater than 3.5 mm that
assures the complete disconnection of the power supply.
• Once the connections to the control unit have been made, the Fitter must use bands to join adjacent wires into groups of 2, 3 or 4 in order to prevent
them coming away from the terminal board: bands must be attached as close as possible to the terminals, no more than 10mm away, taking care not
to damage wire insulation. No cable may remain unpaired.
• The bands are only for unsheathed cables (sheathed cables are held in place by the sheath).
• Pay careful attention not to pair wires with voltages higher than 50 Volt RMD with lower voltage wires.
• The wiring performed internally by the manufacturer is already equipped with clamping bands.
There is a row of 6 LEDs on the right hand side of the board, under the terminals. L7
the NC inputs, stop and photo, the corresponding LEDs L7, L11 and L12 are
normally lit; for the NO inputs open, close and step, the corresponding LEDS L8
L8, L9 and L10 are normally off. These LEDs therefore indicate any malfunction
of the connected devices.
L9
L10
L11
L12
Page 4
GE UNI R DL
1
1 AERIAL
2 RG58-50ohm
1
2
6 6
N.C.
7
N.O.
8 8
9
10
N.O.
N.O. STEP
9
COM
NO
NC
12 Vac 15VA
13 ELECTRIC LOCK
24 Vac 3W max INDICATOR LIGHT 10
14
15
16
OUTPUT 24 Vac 200 mA max
17
CAPACITOR
MOTOR2 OPEN 3 RX TX
C OM
18 COMMON MOTOR2
24V
12V
24V
1 2V
NO
NC
0V
0V
19 MOTOR2 CLOSE
6
20 MOTOR1 OPEN
12
CAPACITOR
21 COMMON MOTOR1
15
22 MOTOR1 CLOSE 16
230 Vac 25W max
23 FLASHING
230 Vac 40W max
24 COUTESY LYGHT
25 4
L2
L1
230 Vac
L1 14
24 Vac 3w max
16
230aV
ORANGE
BROWN
BLACK
BLUE
4! 5
1-2 Aerial: aerial cable input 1 sheath, 2 cables. Use a RG58- 50ohm cable 24
230 Vac 40W max
6 Common: for stop, open, close, step and photo inputs. 25
6-7 STOP* : programmable NC input, commands gate stoppage. Can be connected to safety devices such as an emergency stop button.
When the command is released automatic closure never occurs and a new movement command must be given.
Leave jumpered if no device is envisaged
6-8 OPEN: NO input, commands gate opening.
6-9 CLOSE: NO input, commands gate closure.
6 -10 STEP: NO input, commands gate movement according to the following cycles:
SEMI-AUTOMATIC MODE: Open, stop, close, stop.
4-STEP MODE Open, pause, close, pause.
4-STEP with stop : OPEN-STOP-CLOSE-STOP
6
CONDOMINIUM MODE: Open.
6 -11 PHOTO 1*: programmable NC input for photocells or safety devices. Causes gate stoppage during both opening and closure. Motion
resumesduring opening when the photocell or safety device is disengaged.Leave jumpered if no device is envisaged.
PHOTO: NC input for photocells or safety devices. Does not intervene during gate opening; during closure causes reversal of gate motionuntil open.
23
6 - 12 25
Leave jumpered if no device is envisaged.
16 - 13 ELECTROLOCK 12 V ac output for connection of the 12 Vac 15 VA electrolock.
INDICATOR LIGHT: 24Vac 3W max output, for connecting an indicator light that copies the function of the flashing light during movement
16 - 14
and that remains on when the gate is open.
16 - 15 24 V ac OUTPUT : power supply for various devices, 200 mA max.
16
17
ELECTROLOCK, INDICATOR LIGHT AND 24 V ac OUTPUT COMMON.
PHASE 1, CAPACITOR
7
18 COMMON OPERATOR 2 POWER SUPPLY: 230 Vac 50 Hz output 300 W max.
13
19 PHASE 2, CAPACITOR 16
20 FASE 1, CONDENSATORE
21 COMMON OPERATOR 1 POWER SUPPLY: 230 Vac 50 Hz output 300 W max.
22 FASE 2, CONDENSATORE
23 - 25 FLASHING LIGHT: 230 Vdc 25W max output for connecting a SPLENDOR SRL flashing light characterised by three flashing modes:
1) slow during door opening; 2) fast (flashing times halved) during closure. 3) three flashes and a pause to indicate a fault state or travel identification.
24 - 25 COURTESY LIGHT: 230 Vdc 40W max. output for connecting a courtesy light that switches on at the start of each movement (opening
or closure) and is characterised by an adjustable on time. -
25 FLASHING OR COURTESY LIGHT POWER SUPPLY COMMON.
L1
230Vac 50Hz POWER SUPPLY, fusable input L2.
L2
Page 5
PROGRAMMING THE CONTROL BOARD
STOP PLATES - Ensure
PROGRAMMING THEthat the open and
CONTROL UNITclose stop plates are set to the correct position
SINGLE MOTOR - In the case of a single gate installation connect the motor into terminals 20-21-22
ENGLISH
DEFINING THE STOP PLATESbefore programming enter the options menu 2 and select single motor activated (led 4 on)
ISOLATION
Ensure that the automation’s opening and closure stop plates have been fixed.
SWITCH - A means of isolation must be connected to the incoming supply cable, local to the control
board, to aid programming.
PHASE 1
PHASE 1 1
1 2
2 3
3 ON
ON
ON
OFF
ON
OF
OF
F
F
OFF OF
OF
F
F
Once programming
Once programming is complete, the iskeycomplete the START button acts as a step command
acts as a STEP command.
1
Page 6
DELETING
2 RADIORADIO CONTROL
CONTROL TRANSMITTERS
MANAGEMENT
ENGLISH
The control unit is fitted with a built-in radio receiver with a 1 channel 1000-code memory, with a 433.92 MHz frequency with LIFE Rolling
Code and Auto code encoding.
seconds. The left green led will light and
))Secs
then start flashing.
start flashing.
P • b) Hold down the button on the transmitter you
Hold down the key on the radio control until all five LEDs
45"35 45"35 wish to delete until all the top 5 led’s light.
The
light transmitter has , the been
remotedeleted
control has been reset.
• To exit wait 25 seconds or push the radio
c) icon button
Wait 25 once.
seconds or press again to quit.
PHOTOCELL FUNCTIONS
Photo Input
Opening - No effect, continues to open.
Closing - Re opens.
Photo1 input
Opening - Stops and continues opening when
photocells are cleared.
Closing - Stops and then reopens when photocells
are cleared.
Page 7
PROGRAMMING MENUS
3.1.2 Automatic reclosure AUTOMATIC CLOSING
In this mode by pressing the start button or
Automatic reclosure is activated after a preset PAUSE TIME.
radio transmitter the automation changes it
motion as follows
In this mode, by pressing the ‘STEP’ key, the automation changes its motion according to the sequence 1 – OPEN 2 – PAUSE 3 – CLOSE 4 - PAUSE;
for example, if the automation is opening and one selects the step command on the remote OPEN-PAUSE- CLOSEstops
control, the automation – PAUSE
in pause; conversely, if the
automation is closed, when the step command is given it opens. PAUSE TIME is intended as the pause time before automatic re-closure.
Pressthe right green
the green led switches
LED (RIGHT) switches on.
on:
•• if none
If none of the top 5 led’s
of the LEDs are lit on, automatic
is switched
automatic
reclosure closure
is not enabled, is notit press
to enable enabled. ;
45"35 45"35 45"35
•• if atPress
least one theof +
thebutton
LEDs to increaseis or the on,
switched
– button
automatic to isdecrease
reclosure enabled, tothe pauseit time.
deactivate press
• untilWait
all the25 Seconds
LEDs or press the time but-
switch off.
ton to quit
Press and to set the various PAUSE TIME values.
5s
OPTION MENU 1
Press the option button (bottom right) once, then press in sequence to scroll through the options as shown by the five
led’s at the top. The flashing of the led indicates the option selected. The + button is used to select the function indicated
by the led staying lit without flashing. The – button will de select the option, led off. To exit continue to scroll through to
option 5.
LEDS OPTIONS 1
No function is active.
Residential : The automation closes automatically after the
set PAUSE TIME
Functioning mode as OPEN – STOP – CLOSE – STOP.
OPTION MENU 2
Press the option button (bottom right) for 5 seconds, then press in sequence to scroll through the options as shown by
the five led’s at the top. The flashing of the led indicates the option selected. The + button is used to select the function
indicated by the led staying lit. The – button will de select the option. To exit continue to scroll through to option 5.
LEDS OPTIONS 2
No function is active.
Preflashing
55” Secs
Single motor activated (connect on terminals 20-21-22)
Soft Start
Page 8
• Press the force button (bottom left) and the
FORCE
3.2.3 Force left red led switches on.
ENGLISH
• Press the + and - buttons to set the force
The force function regulates the thrust and the speed of the automation. values.
• The force value is indicated by the 5 led’s at
the top ofthethe
Press redboard.
LED (LEFT) switches on.
• Wait 25 and
seconds orthe
press theforce
force button
Press to set various values.
again to quit
45"35 45"35 LEDS ON FORCE VALUE
Minimum
Maximum
Wait 25 seconds or press again to quit.
OBSTACLE DETECTION
3.2.4 Obstacle detection
The automation is fitted with an obstacle detection system. The automation inverts its movement when it strikes an
obstacle during
The automation the with
is fitted opening and detection
an obstacle closing phases.
system: the automation inverts its movement when it strikes an obstacle during the opening and
1.During the closure phase, if the control unit identifies an obstacle, the automation inverts the motion and performs
closure phases.
aSensitivity
complete opening.
regulation If the
consists obstacle
in greater is detected
or lesser 3 timestoconsecutively,
rapidity in response the obstacle. the automation stops in the open position
awaiting
1) During thea command.
closure phase, if the control unit identifies an obstacle, the automation inverts motion and performs complete opening. If the obstacle is
2.Ifdetected
the control
3 timesunit identifies
consecutively, the an obstacle
automation oninopening,
stops the
a completely automation
open performs
position awaiting a short reversal of motion, before
a command.
stopping awaiting
2) If the control a command.
unit identifies an obstacle, the automation performs a short reversal of motion, before stopping awaiting a command.
• Press
Press the force button (bottom left)for 5
for 5 seconds, the red LED (LEFT) will light and
seconds and the left red led switches on and
then
then goes
switch off. off.
• Press the + and
Press and to set-the
buttons to set detection
various obstacle the obstacle
values.
5 detection values.
45"35 45"35
Secs
))
• Wait 25 ON
LEDS seconds orOBSTACLE
press theDETECTION
force button
again
to quit NO OBSTACLE DETECTION
LEDS ON MINIMUM
OBSTACLE DETECTION
NO OBSTACLE DETECTION
MINIMUM
Wait 25 seconds or press again to quit.
MAXIMUM
MAXIMUM
Page 9
MANUAL PROGRAMMING
3.3.4 Programming Manual
POSITION THE GATE AT 45 DEGREES
Position the leaf gates at 45°
• Press the start button for 5 seconds, the first of the 5 top
led’s lightfor
a) Press and flash.
5 seconds, the first 5 leds light up and
after flash
•The The programming
programming candone
can be be done manually
manually with awith a radio trans-
button
mitter or a switch connected across terminal 6 & 10 .
connected to terminals 6-10 STEP BY STEP or the radio
previously stored.
LEARNING LIMIT CLOSING a) Learning door closing switch 2. Give the command
step (A) the door (2) reaches and is pushing for a moment the
switch
closing. When the door (2) learned of the switch closure
remains on only the red LED (DX).
LEARNING
b) THE
Learning end CLOSING
closing LIMIT
door 1st Giving back
the command step (A) reaches the door and push for a
• Give a command with a radio transmitter or with a switch
moment the
connected across terminals 6 & 10. Motor 2 will run closed
andclosure.
switch shut offIf when it drives
the switch against
closure has the
beenclose stop. The right
learned
1 2 1 2 red led will
successfully remain
remain on. central lit only red LED.
on the
SFAS OPEN
a) Give the command step (A) and release the shutter (1)
opens. Al reaching the point where you want to open the
door (2)
LEARNING
Opening lagTHEto theOPEN
command LIMITstep (A) and release it:
the door (2) opens.
• Give a command with a radio transmitter or with a switch
connected across terminals 6 & 10. Motor 1 will run open.
b) The twothe
To set doors shall open
required nowleaf
opening anddelay,
until reaching
give a second com-
mandfor
pushing when the first
a moment gate
their has achieved
opening theIf required
switches. the delay.
1 2 1 2 1 2 Opening switches have been properly learned about Central
•remain
The turned
two motors willthe
on only run toLEDs.
red the open stops and shut off. The
two red led’s will light.
b) When both the doors (1) and (2) reached the end of
closing to verify that flashing the two green LEDs and are fixed
If the result is not satisfactory carry out the procedure again.
the two red LEDs.
Automation is now planned. Automation is placed by default in
semiautomatic mode.
If the result is not satisfactory to reset the power and start over from scratch.
Page 10
5 GENERAL INFORMATION
ENGLISH
It is strictly forbidden to copy or reproduce this instruction manual without written permission to do so and subsequent verification by LIFE home integration. Translation into other languages of all or part
of the manual is strictly forbidden without previous written authorisation from and subsequent verification by LIFE home integration. All rights on this document are reserved.
LIFE home integration will not accept responsibility for damage or malfunctions caused by incorrect installation or improper use of products and Users are therefore recommended to read this manual
carefully LIFE home integration will not accept responsibility for damage or malfunctions caused by the use of the automation together with the devices of other manufacturers; such action will render the warranty void.
LIFE home integration will not accept responsibility for damage or injury caused by non-compliance with the installation, set up, maintenance and use indications contained in this manual and the safety
instructions described in the SAFETY INSTRUCTIONS AND WARNINGS chapter.
With the aim of improving its products, LIFE home integration reserves the right to bring about alterations to them at any time, without giving prior notice. This document conforms to the state of the
automation at which it is provided when released for sale.
The identity plate bearing the information on the Manufacturer is fixed to the control unit. The plate specifies the type and date (month/year) of manufacture of the product.
For further information on technical and/or commercial issues and technician call-out and spares requests, Clients may contact the Manufacturer or area representative from which the product was purchased.
7 INSTALLATION
ATTENTION: Important safety instructions. Follow all instructions carefully, incorrect installation may cause serious injury.
Before commencing installation we highly recommend reading the instructions and warnings contained in this manual carefully (see the SAFETY INSTRUCTIONS AND WARNINGS Chap) and observing
the instructions it contains.
Page 11
8 TESTING AND TRIAL RUN
• The testing and trial run must be performed by a COMPETENT PERSON supervised and aided by a PROFESSIONAL FITTER. It is the responsibility of the person who tests and sets up
the automation (of which the control unit is a part) to perform the checks required in accordance with the risks existing and to check conformity with the relevant legislation and standards,
in particular with EN standard 12445, which governs the methods for performing trials on gate automations and EN standard 12453 that specifies the performance requisites concerning safety of use.
• The testing and trial run are the most essential phases of installation for guaranteeing maximum operating safety.
• The checks and procedures for testing may also be used for routine checks on the automation and its devices.
• The automation may only be tested if a non-hazardous force tolerance has been set. Force tolerance must be adjusted to a minimum value so as to exclude the danger of injury during closure.
• Adjust the maximum force in line with EN standard 12445.
• Never touch the gate or moving parts when they are in motion.
• Remain at a safe distance when the gate is in motion: only pass when the gate is completely open and immobile.
• In the event of malfunctions (noisiness, jerky movements, etc.) suspend the use of the automation immediately: failure to observe this rule may entail serious hazards, risks of accidents and/or serious
damage to the gate and the automation.
• Always remember that the following residual risks exist when the gate is in movement:
a) impact and crushing against the main closure edge (against the single leaf or between the two leaves);
b) impact and crushing in the opening area;
c) cshearing between the moving and the fixed guides and support during movement;
d) mechanical risks caused by movement.
8.1 Testing
During testing, ensure that the measurement of the gate’s impact force has been performed in accordance with EN standards 12445 and 12453.
• Check that the indications given in the SAFETY INSTRUCTIONS AND WARNINGS and INSTRUCTIONS AND INDICATIONS FOR INSTALLATION chapters have been carefully observed.
• Ensure that the automation is correctly adjusted and that the protection and release systems are in good working order.
• Using the key selector or the radio control perform gate opening and closure tests and ensure that each movement of the gate corresponds to the control unit settings. Perform as many checks as
necessary to be certain of perfect operation.
• Ensure the correct operation of the LEDs on the keyboard of the control unit (see specific manual).
• In particular, for photocell checks, check that there is no interference with other devices. Pass a cylindrical tube with a diameter of 5cm and a length of approximately 30 cm through the optic axis that
connects the two photocells. Perform this check firstly close to the transmitter and then close to the receiver and lastly halfway between the two.
• In all three cases, the device must intervene by passing from the active state to the alarm state and vice versa, thus causing the action set on the control unit: for example, during a closure manoeuvre
it must cause inversion of movement.
• Perform the photocell operation test required in compliance with EN standard 12445 p. 4.1.1.6. The results must satisfy EN standard 12453 p. 5.1.1.6.
ATTENTION: once the automation has been tested, the parameters set must not be altered. If further adjustments (e.g. alterations to the voltage value) are made, all the checks required for
testing and compliance with EN standard 12445 must be repeated.
a) Compile a technical file for the automation, which must include at least:
• a general mechanical and electrical diagram,
• risk analysis and solutions adopted for eliminating or reducing risks,
• manuals of the individual components,
• list of the components used,
• instructions for use and warnings concerning use by the owner,
• system maintenance record
• declaration of the system’s CE conformity
b) Fix a CE marking plate to the gate, bearing at least the following information:
• Name and address of the party responsible for installation and testing;
• Type of automation,
• model,
• registration number,
• year of installation,
• CE mark.
c) Fill in the declaration of conformity and give it to the owner of the automation.
d) Compile the guide with the instruction manual (EN 12635 p. 5.3 and 5.4) and give it to the owner of the automation.
e) Compile the maintenance and improvement log (EN 12635 p. 5.3) and give it to the owner of the automation.
f) Compile the guide containing the instructions for maintenance that provides instructions concerning the maintenance of all automation devices (EN 12635 p. 5.3 and 5.5) and give it to the owner
of the automation.
g) Before the first use of the automation, the owner must have been given adequate information concerning hazards and residual risks.
10
Page 12
10 MAINTENANCE
10.1 Maintenance instructions and warnings
• Once the automation has been tested, the parameters set must not be altered. If further adjustments (e.g. alterations to the voltage value) are made, ALL THE CHECKS REQUIRED FOR
TESTING AND COMPLIANCE WITH STANDARDS MUST BE REPEATED.
• The Manufacturer declines responsibility for damage or injury caused by non-compliance with the information provided in this manual and the safety instructions provided below
• The Manufacturer declines all responsibility for damage and malfunctions deriving from non-compliance with the maintenance instructions.
• In order to keep the operator efficient and safe, follow the cleaning, checking and routine maintenance procedures as described in this manual. This is the owner’s duty.
• Any checking, maintenance or repair work must be conducted by a PROFESSIONAL FITTER
• Always switch off the electricity supply in the event of malfunctions, breakdowns and before any other operations in order to avoid the gate from being activated.
• Always disconnect the operator’s power supply before performing any maintenance or cleaning operation.
• The owner is NOT authorised to remove the control unit cover as it contains live parts.
• If the power cable is damaged, it must be replaced by the Manufacturer or its technical Assistance service or in any case a person with a similar qualification in order to avoid risks.
• If the power cable is damaged, it must be replaced by the Manufacturer or its technical Assistance service or in any case a person with a similar qualification in order to avoid risks.
• Do not perform technical or programming modifications on the control unit. Operations of this type may cause malfunctions and/or risk of accidents. The manufacturer declines all responsibility for
damage caused by products that have been modified.
• In the event of intervention of automatic or fuse switches, before restoring function conditions identify and eliminate the fault. Request the intervention of a PROFESSIONAL FITTER.
• The disconnection and replacement of the pair of buffer batteries (optional) may be performed by a PROFESSIONAL FITTER only.
• If a fault that cannot be solved following the information contained in the present manual arises, contact the manufacturer’s assistance service.
• All maintenance, repair or replacement of parts must be recorded in the maintenance log, which is SUPPLIED AND INITIALLY FILLED IN BY THE FITTER.
ATTENTION: operator disconnection from the mains supply must be performed by a qualified electrician using suitable tools.
Page 13
Declaration of conformity
• EN 12445:2000 Industrial, commercial and garage doors and gates – Safety in the usage of motorised doors –
testing methods
• EN 12453: Industrial, commercial and garage doors and gates – Safety in the usage of motorised doors –
Requisites
• EN 60204-1:1997 Machinery safety – Electric equipment of the machine – Part 1: general rules.
• EN 60950 Information technology equipment - Safety - Part 1: General requisites
• ETSI EN 301489-3:2001 Electromagnetic compatibility for radio equipment and appliances.
• EN 300220-3:2000 Radio equipment and systems – short band devices – Technical characteristics and testing methods for
radio apparatus with a frequency of 25 to 1000 MHz and powers of up to 500mW.
The Manufacturer also declares that it is not permitted for the abovementioned components to be used until such time as the
system in which they are incorporated is declared conform to directive 98/37/EC.
Position: PRESIDENT
Signature:
Page 14
Address: Via Sandro Pertini,3/5 31014 COLLE UMBERTO (TV) Italia
Page 15