You are on page 1of 116

TP48200A-AX09D3 & TP48300A-AX09D1 &

TBC800A-ACD1 Outdoor Power System


(Columbia, Claro)

Installation Guide

Issue 02

Date 2017-12-20

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2017. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: http://www.huawei.com
Email: support@huawei.com

Issue 02 (2017-12-20) Huawei Proprietary and Confidential i


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide About This Document

About This Document

Purpose
This document describes how to install and commission the power system.
The figures provided in this document are for reference only.

Intended Audience
This document is intended for:
 Installation and commissioning engineers
 Technical support engineers

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Description
Indicates an imminently hazardous situation which, if not avoided,
will result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury.
Indicates a potentially hazardous situation which, if not avoided,
could result in equipment damage, data loss, performance
deterioration, or unanticipated results.
NOTICE is used to address practices not related to personal injury.
Calls attention to important information, best practices and tips.
NOTE is used to address information not related to personal injury,
equipment damage, and environment deterioration.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential ii


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide About This Document

Change History
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.

Issue 02 (2017-12-20)
Added section 10.7 Setting the Communications Address for the PC500D Air Conditioner.
Added section 2.1 Preparing Cables
Modified section 6.6.1 Installing a 110 V AC Three-Live Wire Input Power Cable.
Modified section 6.6.2 Installing a 110 V AC Dual-Live Wire Input Power Cable.

Issue 01 (2017-09-30)
This issue is the first official release.
The SMU software version is V500R002C00.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential iii


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide Contents

Contents

About This Document .................................................................................................................... ii


1 Safety Precautions ......................................................................................................................... 1
1.1 General Safety .............................................................................................................................................................. 1
1.2 Electrical Safety ............................................................................................................................................................ 2
1.3 Battery Safety ............................................................................................................................................................... 3
1.4 Cable Layout ................................................................................................................................................................. 4
1.5 Mechanical Safety ........................................................................................................................................................ 5

2 Installation Preparations ............................................................................................................. 7


2.1 Preparing Cables ........................................................................................................................................................... 7
2.2 Tools ............................................................................................................................................................................. 8
2.3 Technical Specifications ............................................................................................................................................... 9
2.4 Requirements for Cable Routing ................................................................................................................................ 10

3 Installing Cabinets ...................................................................................................................... 11


3.1 Floor-Mounting a Cabinet........................................................................................................................................... 11
3.1.1 Floor-mounting Dimensions .................................................................................................................................... 11
3.1.2 Marking Hole Positions ........................................................................................................................................... 12
3.1.3 Drilling Holes and Installing Expansion Sleeves ..................................................................................................... 13
3.1.4 (Optional) Carrying a Cabinet ................................................................................................................................. 14
3.1.5 Hoisting a Cabinet ................................................................................................................................................... 15
3.1.6 Securing a Battery Cabinet ...................................................................................................................................... 18
3.1.7 Installing an Antitheft Enclosure Frame .................................................................................................................. 19
3.1.8 Securing a Power Cabinet ........................................................................................................................................ 25
3.2 Wall-Mounting a Cabinet ............................................................................................................................................ 27
3.2.1 Wall-mounting Dimensions ..................................................................................................................................... 27
3.2.2 Marking Mounting Holes on the Wall ..................................................................................................................... 27
3.2.3 Drilling Holes and Installing Expansion Sleeves ..................................................................................................... 28
3.2.4 Securing a Cabinet ................................................................................................................................................... 29
3.3 Pole-Mounting a Cabinet ............................................................................................................................................ 33
3.3.1 Pole-mounting Dimensions ...................................................................................................................................... 33
3.3.2 Installing Support..................................................................................................................................................... 33
3.3.3 Securing a Cabinet ................................................................................................................................................... 40

Issue 02 (2017-12-20) Huawei Proprietary and Confidential iv


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide Contents

4 Installing a Ground Cable ......................................................................................................... 44


5 Installing Components............................................................................................................... 47
5.1 Installing a Rectifier ................................................................................................................................................... 47
5.2 Installing Communications Expansion Modules ........................................................................................................ 48
5.3 Installing a SIM Card and a GPRS Antenna ............................................................................................................... 49
5.4 Installing a Smoke Sensor........................................................................................................................................... 51
5.5 Installing a Water Sensor ............................................................................................................................................ 52
5.6 Installing a Battery Temperature Sensor ..................................................................................................................... 54

6 Installing Cables ......................................................................................................................... 56


6.1 (Optional) Installing Dry Contact Signal Cables ........................................................................................................ 56
6.2 Installing a Communications Cable Between the SMU and Huawei BBU ................................................................ 57
6.3 (Optional) Installing Communications Cables ............................................................................................................ 57
6.3.1 WebUI Management ................................................................................................................................................ 57
6.3.2 Using the U2000-SPM for Management ................................................................................................................. 58
6.3.3 Using the NetEco for Management .......................................................................................................................... 58
6.3.4 Third-Party NMS Management (over SNMP) ......................................................................................................... 59
6.4 Installing Cables for the Battery Cabinet .................................................................................................................... 60
6.4.1 Installing the Door Status Sensor Cable .................................................................................................................. 60
6.4.2 Installing a PC300D Communications Cable .......................................................................................................... 61
6.4.3 Installing a PC300D Power Cable ........................................................................................................................... 62
6.5 Installing DC Output Power Cables ............................................................................................................................ 63
6.6 Installing AC Input Power Cables............................................................................................................................... 66
6.6.1 Installing a 110 V AC Three-Live Wire Input Power Cable .................................................................................... 67
6.6.2 Installing a 110 V AC Dual-Live Wire Input Power Cable ...................................................................................... 69

7 Installing ESMs and Cables ...................................................................................................... 74


8 Installing Lead-Acid Batteries and Cables ............................................................................. 80
8.1 (Optional) Installing Antitheft Baffle Plate Bases ...................................................................................................... 80
8.2 Installing Battery Strings ............................................................................................................................................ 81
8.3 Installing Copper Bars Between Batteries .................................................................................................................. 82
8.4 Installing Battery Cables ............................................................................................................................................. 83
8.5 (Optional) Installing Antitheft Baffle Plates ............................................................................................................... 84

9 Verifying the Installation .......................................................................................................... 86


9.1 Checking Hardware Installation ................................................................................................................................. 86
9.2 Checking Electrical Connections ................................................................................................................................ 86
9.3 Checking Cable Installation ........................................................................................................................................ 86

10 Commissioning.......................................................................................................................... 87
10.1 Connecting the AC Power Supply ............................................................................................................................ 87
10.2 Setting the Display Language ................................................................................................................................... 88
10.3 Setting the Date and Time ......................................................................................................................................... 88

Issue 02 (2017-12-20) Huawei Proprietary and Confidential v


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide Contents

10.4 Setup Wizard Init ...................................................................................................................................................... 88


10.5 Setting Sensor Parameters ........................................................................................................................................ 89
10.6 Setting Lead-Acid Battery Parameters ...................................................................................................................... 90
10.7 Setting the Communications Address for the PC500D Air Conditioner ................................................................... 90
10.8 Setting Communications Parameters ........................................................................................................................ 92
10.8.1 (Optional) Setting Parameters Before Using WebUI ............................................................................................. 92
10.8.2 Setting Parameters Before Using U2000-SPM ...................................................................................................... 98
10.8.3 (Optional) Setting Parameters Before Using NetEco ............................................................................................. 99
10.8.4 (Optional) Setting Parameters Before Using SNMP ............................................................................................ 101
10.8.5 Setting GPRS Communications Parameters ........................................................................................................ 102
10.9 Connecting the Lead-Acid Battery Supply ............................................................................................................. 103
10.10 Powering On the ESMs......................................................................................................................................... 104
10.11 Subsequent Operations.......................................................................................................................................... 105

11 Lock the Antitheft Enclosure Frame .................................................................................... 106


A Associations Between Alarms and Dry Contacts on the UIM ........................................ 108
B Acronyms and Abbreviations ................................................................................................ 109

Issue 02 (2017-12-20) Huawei Proprietary and Confidential vi


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 1 Safety Precautions

1 Safety Precautions

1.1 General Safety


 Ensure that the product is used in an environment that meets the product design
specifications such as the grid power, input voltage, temperature, and humidity. Using
the product in an incompatible environment may cause malfunctions, damage
components, or invalidate the warranty.
 Follow the precautions and special safety instructions provided by Huawei when
operating this product. Personnel who plan to install or maintain Huawei equipment must
receive thorough product training, understand all necessary safety precautions, and be
able to correctly perform all operations. Huawei will not be liable for any consequences
that are caused by the violation of general safety regulations and equipment usage safety
standards.
 The upstream power distribution box for the cabinet should be equipped with a
protection switch that has the same specifications as or higher specifications than the
input switch of the cabinet.
 Comply with local laws and regulations. The safety instructions in this document are
only supplemental to local laws and regulations.
 Do not operate the product or handle cables during thunderstorms.
 Do not expose the equipment to flammable or explosive gas or smoke. Keep batteries
away from strong infrared radiation, organic solvents, and corrosive gas.
 Do not use water to clean the product's internal or external electrical components.
 To avoid electric shock, do not connect safety extra-low voltage (SELV) circuits to
telecommunication network voltage (TNV) circuits.
 Do not place any irrelevant objects on batteries.
 Before using the product, remove any conductors such as jewelry or watches.
 Use insulated tools for all operations that involve electrical connections.
 Bolts should be tightened with a torque wrench and marked using red or blue color.
Installation personnel mark tightened bolts in blue. Quality inspection personnel confirm
if the bolts are tightened and then mark them in red.
 Follow specified procedures during installation and maintenance. Do not attempt to alter
the product or deviate from the recommended installation procedures without prior
consent from the manufacturer.
 Disconnect the AC power supply before maintaining AC power distribution.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 1


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 1 Safety Precautions

 Measure contact point voltage with a multimeter before handling a conductor surface or
terminal. Ensure that the contact point has no voltage or the voltage is within the
specified range.
 When installing or removing power cables, ensure that the corresponding circuits are
disconnected to prevent electric arcs or sparks.
 If AC input power cables need to be routed from the top, bend the cables in a U shape
outside the cabinet and then route them into the cabinet.
 Performing maintenance or replacing components may interrupt power to the loads if
batteries are not connected or the battery reserve is insufficient. Ensure that the switches
for primary loads are in the ON position and do not turn off the battery switch and the
AC input switch at the same time.
 Cables stored at subzero temperatures must be stored at room temperature for at least 24
hours before they are laid out.
 Perform routine maintenance as described in this manual; replace faulty components at
the earliest.
 After maintenance is completed, lock cabinet doors and seal cable holes to prevent
rodents from entering the cabinet.

1.2 Electrical Safety


Grounding
 When installing a device, install the ground cable first. When uninstalling a device,
remove the ground cable last.
 Before operating a device, ensure that the device is properly grounded. Ensure that the
ground cable is installed securely (the ground resistance should be less than 0.1 ohm).
Inappropriate grounding may cause device damage and personal injury.

AC and DC Power

 The power system is powered by high-voltage power sources. Direct or indirect contact
(through damp objects) with high-voltage power sources may result in serious injury or
death.
 Non-standard and improper operations may result in fire or electric shocks.
 Before making electrical connections, turn off the protection switch on the upstream
device to cut the power supply.
 Before connecting the AC power supply, ensure that electrical connections are complete.
 Before connecting cables to loads or battery cables, check cable and terminal polarities
to prevent reverse connections.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 2


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 1 Safety Precautions

ESD
 To prevent electrostatic-sensitive components from being damaged by static from human
bodies, wear a grounded electrostatic discharge (ESD) wrist strap or ESD gloves when
touching circuit boards.
 When holding a board, hold its edge without touching any components, especially chips.
 Package boards with ESD packaging materials before storing or transporting them.

Liquid Prevention
 Do not place the product in areas prone to water leakage, such as near air conditioner
vents, ventilation vents, or feeder windows of the equipment room.
 Ensure that there is no condensation inside the product or equipment room.
 Ensure that no liquid enters the product. Otherwise, short circuits will occur and may
result in serious injury or death.
 If any liquid is detected inside the product, immediately disconnect the power supply and
contact the administrator.

1.3 Battery Safety


Before installing, operating, or maintaining the batteries, read the battery manufacturer's
safety instructions. Observe the safety precautions provided in this section, which are
supplemental to the safety instructions provided by the battery manufacturer.

Basic Requirements
 Avoid skin contact with battery electrolyte. Before handling batteries, wear goggles,
rubber gloves, and protective clothing.
 When handling a battery, ensure that its electrodes always point upward. Do not tilt or
overturn batteries.
 Before installing or maintaining batteries, switch off the battery circuit breaker or
remove the battery fuse.
 Install batteries in a dry, clean, and ventilated environment that is free from sources of
ignition. Do not expose batteries to sunlight or water.
 Ensure that the load-bearing capacity of the floor in the installation area is sufficient.
Install additional supports if required.
 Secure battery cables to the torque specified in the battery documentation. Loose
connections will result in excessive voltage drop or cause batteries to burn out in the case
of excessive current.
 Ensure that battery cables do not come in contact with water.

Battery Short Circuit

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 3


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 1 Safety Precautions

High short circuit currents or electric shocks can cause equipment damage, personal injury, or
death.

To prevent short circuit or electric shock, disconnect the batteries before performing any
operation or maintenance.

Flammable Gas

 Do not use unsealed lead-acid batteries.


 Lead-acid batteries emit flammable gas. Therefore, place and secure lead-acid batteries
horizontally to prevent fire or corrosion.

Store lead-acid batteries in a place with good ventilation, and take fire safety precautions.

Battery Leakage

High temperatures may result in battery distortion, damage, and electrolyte overflow.

If the battery temperature is higher than 60°C, battery electrolyte may overflow. If the
electrolyte overflows, wear goggles, rubber gloves, and protective clothing and absorb the
leaking electrolyte using sodium bicarbonate (NaHCO3) or sodium carbonate (Na2CO3). Do
not transport or move batteries if there is an electrolyte leakage.

Battery Overdischarge
After connecting the batteries, remove the battery fuse or turn the battery circuit breaker OFF
and then power on the power system. This prevents battery overdischarge. After the power
system is on, replace the battery fuse or turn the battery circuit breaker ON.

1.4 Cable Layout


 When routing cables, ensure that a sufficient distance exists between the cables and the
DC busbar, shunt, and fuse. This prevents damage to the insulation layer of the cables.
 Route and bind signal cables and power cables separately.
 Ensure that cables meet the VW-1 testing requirements.
 Do not route cables behind the air exhaust vents of rectifiers in the cabinet.
 Ensure that all cables are securely bound.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 4


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 1 Safety Precautions

1.5 Mechanical Safety


Hoisting Devices

Do not walk under hoisted objects.


 Only trained and qualified personnel should perform hoisting operations.
 Check that all hoisting tools are available and in good condition.
 Before hoisting objects, ensure that hoisting tools are firmly fixed onto a load-bearing
object or wall.
 Ensure that the angle formed by each hoisting cable is less than 90 degrees.
 If metal hoisting cables are used, place protective pads between the cables and the
cabinet to prevent scratches to the cabinet surface.

Figure 1-1 Hoisting heavy objects

Drilling Holes

Do not drill holes into a cabinet without permission. Incorrect drilling operations may affect
the electromagnetic shielding of the cabinet and damage cables inside. Metal shavings from
drilling may short-circuit boards inside the cabinet.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 5


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 1 Safety Precautions

 Before drilling holes into a cabinet, wear goggles and protective gloves. Remove cables
from inside the cabinet.
 After drilling, clean up any metal shavings that have accumulated inside or outside the
cabinet.

Moving Heavy Objects


 Only trained personnel are allowed to move heavy objects.
 Wear protective gloves and shoes before moving heavy objects.
 Be cautious to prevent injury when moving heavy objects.
 At least two people are required to move heavy objects.
 When you transport cabinets, ensure that there is no excessive tilt and no sudden jolt.
The maximum allowed tilt angle when loading and unloading a cabinet is 15 degrees.
Secure the cabinet to a pallet truck before you transport it.
 When you move a cabinet, ensure that it does not bump into other objects or fall down.

Figure 1-2 Transportation gradient

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 6


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 2 Installation Preparations

2 Installation Preparations

2.1 Preparing Cables


The cross-sectional area of a power cable depends on the current that will flow through the
cable and the voltage drop allowed for the cable.

Table 2-1 TP48200A-AX09D1

Cable Type Maximum Minimum Maximum


Current (A) Cross-Section Cross-Sectional
al Area (mm2) Area (mm2)

Cabinet ground cable NA 16 35


AC input Live wire 45 16 25
power cable
(three-live PE wire NA 16 25
wire)
AC input Live wire 68 16 25
power cable
(dual-live wire) PE wire NA 16 25

DC output power cable 6 1 16


16 4 16
50 6 16
63 10 16
ESM ground cable NA 6 25
ESM activation cable 1 1 2.5
ESM power cable 50 10 25
NOTE:
 The data listed in the table is the cable sizes applicable when the ambient temperature is 25°C. Use
cables with larger cross-sectional areas if the ambient temperature is much higher or lower.
 The battery cables should be able to resist a temperature of 90°C at least. Double-insulated
flame-retardant copper cables are recommended.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 7


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 2 Installation Preparations

Table 2-2 TP48300A-AX09D1 and TBC800A-ACD1

Cable Type Maximum Minimum Maximum


Current (A) Cross-Sectional Cross-Sectional
Area (mm2) Area (mm2)

Cabinet ground cable NA 16 35


AC input Live wire 45 16 25
power cable
(three-live PE wire NA 16 35
wire)
AC input Live wire 68 16 25
power cable
(dual-live PE wire NA 16 35
wire)
DC output power cable 6 1 16
16 4 16
50 6 16
63 10 16
Battery cable 80 16 25
NOTE:
 The data listed in the table is the cable sizes applicable when the ambient temperature is 25°C. Use
cables with larger cross-sectional areas if the ambient temperature is much higher or lower.
 The battery cables should be able to resist a temperature of 90°C at least. Double-insulated
flame-retardant copper cables are recommended.

2.2 Tools

Use insulated tools. The following figure is for reference only.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 8


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 2 Installation Preparations

Figure 2-1 Tool description

2.3 Technical Specifications


Table 2-3 Technical specifications

Model Item Dimensions (H x W x D) Weight


TP48200A- Power 900 mm x 650 mm x 650 mm < 120 kg (excluding
AX09D3 cabinet (excluding the 100 mm high rectifiers and batteries)
base and the protruding part of
TP48300A- the door) < 120 kg (excluding
AX09D1 rectifiers)
TBC800A- Battery 1600 mm x 650 mm x 650 mm < 120 kg (excluding
ACD1 cabinet (including the 100 mm high batteries)
base, excluding the protruding
part of the door)

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 9


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 2 Installation Preparations

Model Item Dimensions (H x W x D) Weight


R4850G2 Rectifier 40.8 mm x 105 mm x 269 mm ≤ 2 kg
(excluding edge connectors)

2.4 Requirements for Cable Routing


 Ensure that cables are more than 20 mm away from heat sources to prevent damage
(melting, aging, or breakage) to the cable insulation layer.
 Ensure that the bending radius of each cable is at least five times the diameter of the
cable.
 Bind cables of the same type together. When routing cables of different types, ensure that
they are at least 30 mm away from each other.
 Route and bind cables so that they appear neat and tidy and their cable sheaths are intact.
 Route and bind ground cables and signal cables separately.
 Route and bind AC power cables, DC power cables, signal cables, and communications
cables separately.
 When routing power cables, ensure that there is no coiling or twisting. Do not join or
weld power cables. If necessary, use a longer cable.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 10


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

3 Installing Cabinets

The power cabinet TP48300A-AX09D1 and battery cabinet TBC800A-ACD1 can be


floor-mounted side by side. The TP48200A-AX09D3 power cabinet can be floor-, wall-, or
pole-mounted.

3.1 Floor-Mounting a Cabinet


3.1.1 Floor-mounting Dimensions
Figure 3-1 Floor-mounting dimensions (TP48200A-AX09D3)

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 11


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-2 Floor-mounting dimensions (TP48300A-AX09D1 and TBC800A-ACD1)

3.1.2 Marking Hole Positions


Prerequisites
 The installation environment is clean and dry.
 The concrete floor on which cabinets are to be installed is level.

Procedure
Step 1 Locate the marking-off template in the packing case.
Step 2 Mark hole positions based on the marking-off template, as shown in Figure 3-3.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 12


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-3 Marking hole positions (TP48200A-AX09D3)

Figure 3-4 Marking hole positions (TP48300A-AX09D1 and TBC800A-ACD1)

----End

3.1.3 Drilling Holes and Installing Expansion Sleeves


Procedure
Step 1 Drill holes to a depth of 52 mm to 60 mm using a hammer drill.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 13


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Step 2 Partially tighten each expansion bolt, place it vertically into the hole, and use a rubber mallet
to hammer it in until the expansion sleeve completely enters the hole.
Step 3 Partially tighten the expansion bolts.
Step 4 Remove the bolts, spring washers, and flat washers.

Figure 3-5 Drilling holes and installing expansion sleeves

(1) M12 bolt (2) Spring washer (3) Flat washer


(4) Expansion sleeve (5) Expansion nut (6) Concrete floor

----End

3.1.4 (Optional) Carrying a Cabinet


Procedure
Step 1 At least two persons are required to carry the cabinet, as shown in Figure 3-6.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 14


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-6 Carrying a cabinet

----End

3.1.5 Hoisting a Cabinet


Hoisting After Binding
Step 1 Bind the cabinet using lifting ropes and then hoist the cabinet to the target position, as shown
in Figure 3-7.

For safety, a lifting rope for carrying a cabinet should be able to bear a weight that is more
than three times the maximum weight of the cabinet.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 15


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-7 Hoisting a cabinet (using the TP48200A-AX09D3 as an example)

Step 2 Remove the lifting ropes.


----End

Hoisting Using the Lifting Eyes


Step 1 Install the lifting eyes, as shown in the following figure.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 16


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-8 Installing a lifting eye (TP48300A-AX09D1)

Step 2 Hoist the cabinet and place it to the target position, as shown in the following figure.

For safety, a lifting rope for carrying a cabinet should be able to bear a weight that is more
than three times the maximum weight of the cabinet.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 17


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-9 Hoisting a cabinet (TP48300A-AX09D1)

Step 3 Remove the lifting ropes and lifting eyes, and reinstall the screws in the holes for mounting
lifting eyes.
----End

3.1.6 Securing a Battery Cabinet


Procedure
Step 1 Place the cabinet onto the concrete floor and align the mounting holes in the cabinet with
those in the concrete floor.
Step 2 Place flat washers, spring washers, and expansion bolts into the cabinet mounting holes.
Step 3 Tighten expansion bolts to secure the cabinet.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 18


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-10 Securing a battery cabinet

----End

3.1.7 Installing an Antitheft Enclosure Frame


Prerequisites
The steel measuring tape and required tools are available.

Procedure
Step 1 Install the cabinet sealing plates.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 19


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-11 Install the cabinet sealing plates.

Step 2 Install supports for the antitheft enclosure frame.


1. Tighten the screws at the bottom of the supports.
2. Install the support bracket and tighten the screws.
3. Install the support side bracket and tighten the screws.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 20


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-12 Installing supports

Step 3 Adjust the size of the antitheft enclosure frame based on the cabinet size.
1. Loosen the size adjustment screws on the antitheft enclosure frame.
2. Adjust the antitheft enclosure frame to the appropriate size based on the cabinet size (650
mm deep, 650 mm wide), and then tighten the screws.

Figure 3-13 Adjusting the size of the antitheft enclosure frame

Step 4 Install the supports on the antitheft enclosure frame.


1. Determine the support installation positions on the antitheft enclosure frame based on the
support mounting holes on the cabinet.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 21


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

2. Install the long support on the left side of the antitheft enclosure frame.
3. Install the short support at the symmetric position on the right side of the antitheft
enclosure frame.
Supports on the right and left sides of the antitheft enclosure frame are installed in the same
way. The following figure shows how to install the support on the left.

Figure 3-14 Installing supports on the antitheft enclosure frame (top view)

Step 5 Unlock the antitheft enclosure frame.


1. Remove the lock baffle plate from the antitheft enclosure frame.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 22


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-15 Removing the lock baffle plate from the antitheft enclosure frame (bottom view)

Put away the removed lock baffle plate and reinstall it after the antitheft enclosure frame is installed on
the cabinet.
2. Unlock with a key and remove the latch.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 23


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-16 Removing the latch (top view)

Step 6 Install the antitheft enclosure frame on the cabinet.

Insert the support on the left side of the antitheft enclosure frame into the cabinet and then the support on
the right.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 24


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-17 Installing the antitheft enclosure frame on the cabinet

----End

3.1.8 Securing a Power Cabinet


Procedure
Step 1 Place the cabinet onto the concrete floor and align the mounting holes in the cabinet with
those in the concrete floor.
Step 2 Place flat washers, spring washers, and expansion bolts into the cabinet mounting holes.
Step 3 Tighten expansion bolts to secure the cabinet.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 25


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-18 Securing a power cabinet

----End

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 26


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

3.2 Wall-Mounting a Cabinet


3.2.1 Wall-mounting Dimensions
Figure 3-19 Wall–mounting dimensions (TP48200A-AX09D3)

3.2.2 Marking Mounting Holes on the Wall


Prerequisites
 Keep the installation environment clean and dry.
 Ensure that the wall for installing the support is flat.

Procedure
Step 1 Locate the marking-off template for wall-mounting the cabinet in the cabinet packing case.
Step 2 Use a level to measure levelness of mounting holes.
Step 3 Mark the mounting holes using a marker based on the marking-off template, as shown in
Figure 3-20.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 27


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-20 Marking mounting holes on the wall

(1) Level (2) Marker (3) Marking-off template


(4) Wall (5) Mounting hole

----End

3.2.3 Drilling Holes and Installing Expansion Sleeves


Procedure
Step 1 Drill holes in the wall with a depth range of 52 mm to 60 mm using a hammer drill.
Step 2 Partially tighten the expansion bolts and vertically insert them into holes. Knock the
expansion bolts by using a rubber mallet until the expansion sleeves are fully inserted into the
holes.
Step 3 Partially tighten the expansion bolts.
Step 4 Remove the bolt, spring washer, and flat washer.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 28


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-21 Drilling holes and installing expansion sleeves

(1) M12 bolt (2) Spring washer (3) Flat washer


(4) Expansion sleeve (5) Expansion nut (6) Solid wall

----End

3.2.4 Securing a Cabinet


Prerequisites
Choose an appropriate method move the cabinet. This section uses hoisting as an example.

Procedure
Step 1 Take out the bolts and support in the fitting bag delivered with the support.
Step 2 Secure the support to a wall, as shown in Figure 3-22.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 29


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-22 Securing a support

Step 3 Move the cabinet slowly until it falls onto the support, as shown in Figure 3-23.

For safety, a lifting rope for carrying a cabinet should be able to bear a weight that is more
than three times the maximum weight of the cabinet.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 30


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-23 Hoisting a Cabinet

Step 4 Adjust the cabinet position so that its mounting holes align with those in the support.
Step 5 Locate the bolts for securing the cabinet in the fitting bag delivered with the cabinet.
Step 6 Place the spring washers, flat washers, and expansion bolts into the mounting holes.
Step 7 Tighten the expansion bolts to secure the cabinet, as shown in Figure 3-24.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 31


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-24 Securing a cabinet

----End

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 32


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

3.3 Pole-Mounting a Cabinet


3.3.1 Pole-mounting Dimensions
Figure 3-25 Pole-mounting dimensions (TP48200A-AX09D3)

3.3.2 Installing Support


Procedure
Step 1 Take out a fixture and upper fastener from the fitting bag, and install the fixture on the upper
fastener.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 33


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-26 Installing a fixture on the upper fastener

(1) Fixture (2) Upper fastener

Step 2 Insert a bolt into the upper fastener.


Step 3 Partially tighten the upper fastener, level it by using a level, and fasten it.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 34


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

 The pole diameter is 80 mm to 210 mm. The size and length of the configured bolt is M12
x 300 mm.
 The pole diameter is 210 mm to 350 mm. The size and length of the configured bolt is
M12 x 485 mm.

Figure 3-27 Installing an upper fastener (round pole)

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 35


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-28 Installing an upper fastener (octagon pole)

Step 4 Install a lower fastener on the support.

Figure 3-29 Installing a lower fastener on the support

Step 5 Hang the support onto the fixture, and secure the support to the upper fastener.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 36


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-30 Installing the support on an upper fastener (round pole)

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 37


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-31 Installing the support on an upper fastener (octagon pole)

Step 6 Take out the other part of the lower fastener from the fitting bag.
Step 7 Secure the lower fastener using bolts, and secure the support to the pole.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 38


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-32 Installing a lower fastener (round pole)

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 39


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-33 Installing a lower fastener (octagon pole)

----End

3.3.3 Securing a Cabinet


Prerequisites
Choose an appropriate method move the cabinet. This section uses hoisting as an example.

Procedure
Step 1 Move the cabinet slowly until it falls onto the support, as shown in Figure 3-34.

For safety, a lifting rope for carrying a cabinet should be able to bear a weight that is more
than three times the maximum weight of the cabinet.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 40


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-34 Hoisting a cabinet

Step 2 Adjust the cabinet position so that its mounting holes align with those in the support.
Step 3 Place flat washers, spring washers, and expansion bolts into the cabinet mounting holes.
Step 4 Tighten expansion bolts to secure the cabinet.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 41


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-35 Securing a cabinet (round pole)

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 42


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 3 Installing Cabinets

Figure 3-36 Securing a cabinet (octagon pole)

----End

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 43


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 4 Installing a Ground Cable

4 Installing a Ground Cable

Procedure
Step 1 Route a ground cable into the cabinet through the package entry module at the bottom of the
cabinet.
Step 2 Secure one end of the ground cable to the power cabinet ground bar, and the other end to the
site ground bar.

Ensure that the ground cable is installed securely. If devices are not properly grounded,
damage to devices or human injuries may occur.

Step 3 Secure one end of the equipotential cable to the power cabinet ground bar, and the other end
to the battery cabinet ground bar, as shown in the following figure.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 44


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 4 Installing a Ground Cable

Figure 4-1 Installing a ground cable (TP48200A-AX09D3)

(1) Cabinet ground bar (2) Site ground bar

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 45


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 4 Installing a Ground Cable

Figure 4-2 Installing a ground cable (TP48300A-AX09D1 and TBC800A-ACD1)

(1) Power cabinet ground bar (2) Site ground bar


(3) Battery cabinet ground bar

----End

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 46


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 5 Installing Components

5 Installing Components

5.1 Installing a Rectifier


Prerequisites
 The rectifier is intact after being unpacked.
 The filler panel has been removed from the rectifier slot.

 If the rectifier is damaged, contact your local Huawei office.


 The rectifier slot presents a risk of electric shock. Do not touch the slot with your hands.
 High temperature is generated around the air exhaust vent when the rectifier is running.
Do not touch the vent with your hands or cover the vent with cables or other objects.

Procedure
Step 1 Push the locking latch towards the left.
Step 2 Draw the handle downwards.
Step 3 Gently push the rectifier into its slot along the guide rails.
Step 4 Push the handle upwards.
Step 5 Push the locking latch towards the right to secure the handle.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 47


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 5 Installing Components

Figure 5-1 Installing a rectifier

----End

5.2 Installing Communications Expansion Modules


Prerequisites
 If the site requires a communications expansion module, perform the following steps to
install it.
 Wear ESD gloves during installation.

Install communications expansion modules in the upper slot and then in the lower slot.

Procedure
Step 1 Remove the filler panel from the slot for installing communications expansion modules.
Step 2 Push the handle rightwards.
Step 3 Gently insert a communications expansion module into the slot along guide rails.
Step 4 Push the handle leftwards.
Step 5 Tighten screws, as shown in the following figure.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 48


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 5 Installing Components

Figure 5-2 Installing communications expansion modules

----End

5.3 Installing a SIM Card and a GPRS Antenna


Prerequisites
If a SIM card and GPRS antenna are required, perform the following steps to install them.
Wear a pair of ESD gloves during installation.

Procedure
Step 1 Install a GPRS tray onto the base of the cabinet, as shown in the following figure.

Figure 5-3 Installing a GPRS tray (TP48200A-AX09D3 and TP48300A-AX09D1)

(1) GPRS tray

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 49


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 5 Installing Components

Step 2 Unscrew and remove the NIM01C3.


Step 3 Insert the SIM card into the SIM card slot in the NIM01C3.

The SIM card inserted into the communications expansion module (NIM01C3) should support GSM,
WCDMA, TD-SCDMA, TDD, and FDD standards, and have the SMS and data service functions
enabled.

Figure 5-4 Installing a SIM card

(1) SIM card

Step 4 Reinstall the NIM01C3 and tighten the screws.


Step 5 Attach the GPRS antenna to the tray and connect the GPRS signal cable to the ANT port on
the NIM01C3, as shown in the following figure.

Before installing the antenna, remove the plastic shell from the antenna installation base to ensure
magnetic adherence.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 50


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 5 Installing Components

Figure 5-5 Installing a GPRS antenna

----End

5.4 Installing a Smoke Sensor


Prerequisites
If the site requires a smoke sensor, perform the following steps to install it.

Procedure
Step 1 Remove screws that secure the smoke sensor to the interior of the cabinet top.
Step 2 Secure the smoke sensor base to the top of the cabinet by using the removed screws.

Ensure that the switch on the smoker sensor base faces the cabinet door.

Step 3 Secure the smoke sensor to the base, as shown in Figure 5-6.
Smoke sensor 1 and smoke sensor 2 are installed in the same way. The following picture
shows how to install smoke sensor 1.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 51


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 5 Installing Components

Figure 5-6 Installing a smoke sensor (TP48200A-AX09D3 and TP48300A-AX09D1)

Step 4 Connect one end of the signal cable to the smoke sensor and the other end to the SMOKE port
on the UIM panel, as shown in Figure 5-7.

Figure 5-7 Connecting the signal cable for the smoke sensor

----End

5.5 Installing a Water Sensor


Prerequisites
If the site requires a water sensor, perform the following steps to install it.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 52


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 5 Installing Components

Procedure
Step 1 Put the water sensor in the cable strip in the right part of the cabinet bottom, and secure the
sensor with a cable tie.

When you install a water sensor, ensure that the sensor is 5 mm to 10 mm away from the cabinet bottom.

Figure 5-8 Securing a water sensor (TP48200A-AX09D3 and TP48300A-AX09D1)

Step 2 Connect the water sensor signal cable to the WATER port on the UIM panel, as shown in
Figure 5-9.

Figure 5-9 Installing a signal cable for the water sensor

----End

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 53


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 5 Installing Components

5.6 Installing a Battery Temperature Sensor


Prerequisites
If the site requires a battery temperature sensor, perform the following steps to install it.

Procedure
Step 1 One end of the battery temperature sensor 1 cable has been connected to the BTEMP port on
the UIM02D. Route the other end of the cable into the bottom of the battery cabinet and bind
it to the middle of the battery rack using cable ties.

 l Avoid direct exposure of a battery temperature sensor to sunlight or direct contact with a
heat source, cold source, air vent, or air conditioner vent.
 The detection probe must not contact a metal surface.

Figure 5-10 Installing a battery temperature sensor(TBC800A-ACD1)

If the site also requires battery temperature sensor 2, install it at the TEMP2 port of the UIM02D.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 54


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 5 Installing Components

Figure 5-11 Cable connection positions for battery temperature sensors

(1) Battery temperature sensor 1 (2) Battery temperature sensor 2

----End

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 55


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

6 Installing Cables

 Ensure that the upstream AC input circuit breaker is OFF, and attach warning labels such
as "Do not operate."
 Switch off all circuit breakers before installing cables.

6.1 (Optional) Installing Dry Contact Signal Cables


Procedure
Step 1 Press the contact plate using a flat-head screwdriver to flip the metal spring inside each dry
contact.
Step 2 Connect the signal cables to the corresponding dry contacts.
Step 3 Remove the flat-head screwdriver and check that the signal cables are connected securely.

Figure 6-1 Installing a dry contact signal cable

(1) Contact plate (2) Dry contact port

----End

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 56


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

6.2 Installing a Communications Cable Between the SMU


and Huawei BBU

If Huawei BBU is deployed, connect a communications cable between the SMU and Huawei
BBU. The U2000-SPM and NetEco network management systems (NMSs) are supported.

Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU.
Step 2 Connect the other end of the cable to the MON1 port on Huawei BBU, as shown in Figure
6-2.

Figure 6-2 Connecting a communications cable

(1) RS485/RS232 port on the SMU (2) MON1 port on Huawei BBU

----End

6.3 (Optional) Installing Communications Cables


6.3.1 WebUI Management
Procedure
Step 1 Connect the FE port on the site monitoring unit (SMU) by using a network cable, as shown in
Figure 6-3.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 57


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

Figure 6-3 Connecting a communications cable (for WebUI management)

(1) User WebUI terminal (2) FE port on the SMU

----End

6.3.2 Using the U2000-SPM for Management


For the cable connection to the NMS, see 6.2 Installing a Communications Cable Between the
SMU and Huawei BBU.

6.3.3 Using the NetEco for Management


Networking Mode 1: over FE
Step 1 Connect a network cable to the FE port on the SMU, as shown in Figure 6-4.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 58


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

Figure 6-4 Connecting a communications cable to the FE port

(1) NetEco terminal (2) FE port on the SMU

----End

Networking Mode 2: over an RS485 Port


For the cable connection to the NMS, see 6.2 Installing a Communications Cable Between the
SMU and Huawei BBU.

6.3.4 Third-Party NMS Management (over SNMP)


Procedure
Step 1 Connect the FE port on the SMU by using a network cable, as shown in Figure 6-5.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 59


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

Figure 6-5 Connecting a communications cable (over SNMP)

(1) User SNMP terminal (2) FE port on the SMU

----End

6.4 Installing Cables for the Battery Cabinet


When the power cabinet TP48300A-AX09D1 and battery cabinet TBC800A-ACD1 are
deployed together, you need to connect the cables for the door status sensor and air
conditioner of the battery cabinet to the power cabinet.

6.4.1 Installing the Door Status Sensor Cable


Procedure
Step 1 Locate the door status sensor cable bound in the battery cabinet.
Step 2 Connect the cable to the DIN4 terminal on the UIM02D.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 60


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

 The door status sensor cable should be connected to the reserved DIN port.
 In this example, the door status sensor cable is connected to the DIN4 terminal on the
UIM02D.

Figure 6-6 Installing the door status sensor cable

(1) Battery cabinet door status sensor

----End

6.4.2 Installing a PC300D Communications Cable


Procedure
Step 1 Install a communications cable between the power cabinet and battery cabinet.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 61


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

Figure 6-7 Installing a communications cable

(1) Power cabinet UIM (2) Ethernet splitter (3) Battery cabinet PC300D

----End

6.4.3 Installing a PC300D Power Cable


Procedure
Step 1 Lay out a PC300D power cable, and route it into the power cabinet through the package entry
module.

One end is secured to the PWR port on the battery cabinet PC300D, and the other end is reserved on the
battery cabinet.

Step 2 Connect the negative terminal on the other end of the power cable to the 6 A BLVD circuit
breaker.
Step 3 Connect the positive terminal on the other end of the power cable to the RTN+ busbar.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 62


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

Figure 6-8 Installing a PC300D Power Cable

(1) Battery cabinet PC300D (2) Power cabinet ground screw

----End

6.5 Installing DC Output Power Cables


Procedure
Step 1 Route DC output power cables into the cabinet through the package entry module at the
bottom or cabling channel at the rear of the cabinet.
Step 2 Secure the negative power cable to the corresponding load circuit breaker based on the actual
load capacity.
Step 3 Secure the positive power cable to the RTN+ busbar.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 63


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

Figure 6-9 Installing DC output power cables (TP48200A-AX09D3)

(1) Secondary load (2) Primary load

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 64


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

Figure 6-10 Installing DC output power cables (TP48300A-AX09D1 bottom cable routing)

(1) Primary load (2) Secondary load

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 65


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

Figure 6-11 Installing DC output power cables (TP48300A-AX09D1 rear cable routing)

(1) Primary load (2) Secondary load

----End

6.6 Installing AC Input Power Cables

 Ensure that the upstream AC input circuit breaker is OFF, and attach labels such as "No
operations allowed".
 Switch off all circuit breakers before installing power cables.

The system supports the 110 V AC three-live wire and 110 V AC dual-live wire input systems.
Install AC input power cables based on site requirements.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 66


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

6.6.1 Installing a 110 V AC Three-Live Wire Input Power Cable


Procedure
Step 1 (Applies only to TP48300A-AX09D1) Remove the protective cover plate from the rear of the
cabinet.

Figure 6-12 Remove the protective cover plate (TP48300A-AX09D1)

Step 2 Route AC input power cable into the cabinet through the package entry module at the bottom
or cabling channel at the rear of the cabinet.
Step 3 Secure the AC input power cable to the corresponding AC input circuit breakers or terminals.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 67


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

Figure 6-13 Installing a 110 V AC three-live wire input power cable (TP48200A-AX09D3)

(1) Alternating current distribution box (ACDB)

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 68


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

Figure 6-14 Installing a 110 V AC three-live wire input power cable (TP48300A-AX09D1)

(1) Alternating current distribution box (ACDB)

Step 4 (Applies only to TP48300A-AX09D1) Reinstall the protective cover plate at the rear of the
cabinet.
----End

6.6.2 Installing a 110 V AC Dual-Live Wire Input Power Cable


The AC input power systems of both the TP48200A-AX09D3 and TP48300A-AX09D1
power cabinets support dual live wires altered from three live wires onsite.

TP48200A-AX09D3
The procedure for altering three live wires into two is as follows:
Step 1 Remove the wires on the AC input circuit breaker.
Step 2 Remove the L3 wires on the AC SPD.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 69


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

Step 3 Install the 2-pole 100 A AC input circuit breaker.


Step 4 Remove the jumper between pins 2 and 3 of the L terminal.
Step 5 Short-circuit pins 1 and 2 and pins 3 and 4 of the L terminal using jumpers respectively.
Step 6 Connect the L1 and L2 AC input wires to the 2-pole 100 A circuit breaker, as shown in the
following figure.

Figure 6-15 Altering three live wires into two

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 70


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

Figure 6-16 Installing a 110 V AC dual-live wire input power cable (TP48200A-AX09D3)

(1) Alternating current distribution box (ACDB)

----End

TP48300A-AX09D1
The procedure for altering three live wires into two is as follows:
Step 1 Remove the wires on the AC input circuit breaker.
Step 2 Remove the L3 wires on the AC SPD.
Step 3 Install the 2-pole 125 A AC input circuit breaker.
Step 4 Install the end fastener on the left side of the 2-pole 125 A circuit breaker.
Step 5 Remove the jumper between pins 3 and 4 of the L terminal.
Step 6 Short-circuit pins 2 and 3 and pins 4 and 5 of the L terminal at the bottom using copper bars.
Step 7 Connect the L1 and L2 AC input wires to the 2-pole 125 A circuit breaker, as shown in the
following figure.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 71


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

Figure 6-17 Altering three live wires into two

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 72


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 6 Installing Cables

Figure 6-18 Installing a 110 V AC dual-live wire input power cable (TP48300A-AX09D1)

(1) Alternating current distribution box (ACDB)

----End

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 73


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 7 Installing ESMs and Cables

7 Installing ESMs and Cables

Prerequisites
Install ESMs in the power cabinet TP48200A-AX09D3.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 74


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 7 Installing ESMs and Cables

 Smoking and sparks are prohibited near ESMs.


 Switch off the battery circuit breakers before installing ESMs.
 Do not use a metal to simultaneously touch two or more ESM terminals or simultaneously
touch an ESM terminal and an object (such as the battery compartment) that has been
grounded. Otherwise, short circuits may occur, which may further generate sparks or
explosion.
 Do not immerse ESMs in water or expose them to rain.
 Short circuits inside an ESM or on the ESM loop must be prevented to avoid fire and
personal injury.
 Comply with regulations and warnings issued by the ESM manufacturer.
 Avoid ingestion of ESM components.
 Protect ESMs from mechanical vibration, collision, punctures, and strong impact.
Otherwise, the ESMs may catch fire.
 Do not throw ESMs into fire because this may cause batteries to ignite.
 Dispose of waste ESMs in strict accordance with local laws and regulations.
 Use tools with insulated handles. Otherwise, the ESMs may burn out and personal injury
may be caused.
 Before operating the ESMs, wear goggles, rubber gloves, and protective clothes. Remove
any conductors such as jewelry or watches.
 During installation, ensure that the positive and negative ESM terminals are correctly
connected to prevent reverse polarity. First connect the negative ESM cable and then
connect the positive ESM cable.
 Secure ESM cables to a torque specified in the ESM documentation. Loose connections
will result in excessive voltage drops or cause ESMs to burn out when the current is high.
 An ESM communication failure alarm caused by reasons such as loose communications
cable connection should be handled within 72 hours (default value, configurable).
Otherwise, the ESM will be internally locked, which may affect the ESM power backup.

Procedure
Step 1 Install ESMs from the bottom up.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 75


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 7 Installing ESMs and Cables

Figure 7-1 Installing ESMs

Step 2 Install the ESM ground cable.

Figure 7-2 Install the ESM ground cable

Step 3 Install the ESM communications cables.


After ESM communications cables are installed, connect a build-out resistor to the
COM_OUT port of the last ESM.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 76


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 7 Installing ESMs and Cables

The build-out resistor must be installed for matching the communication link impedance to
ensure communication reliability.

Figure 7-3 Install the ESM communications cables

Step 4 Install the ESM activation cables.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 77


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 7 Installing ESMs and Cables

 Connect the positive and negative ESM activation cables to correct polarity. Otherwise,
the ESMs will fail to be activated.
 If there are multiple ESMs, the activation cables can be connected to the same load route.

Figure 7-4 Install the ESM activation cables

Step 5 Install the ESM power cables.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 78


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 7 Installing ESMs and Cables

Figure 7-5 Install the ESM power cables

----End

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 79


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 8 Installing Lead-Acid Batteries and Cables

8 Installing Lead-Acid Batteries and Cables

Install lead-acid batteries in the battery cabinet TBC800A-ACD1.

 Smoking and sparks are prohibited near batteries.


 Before installing batteries, ensure that battery circuit breakers are OFF or battery fuses are
disconnected.
 Comply with regulations and warnings of the battery manufacturer.
 Use the tools with an insulated handle. Otherwise, batteries may burn out and personal
injury may be caused.
 During battery operations, wear goggles, rubber gloves, and protective clothes. Remove
conductive articles such as watches, bracelets, and rings.
 If battery acid gets in the eyes, rinse with cold water for more than 15 minutes and seek
medical advice immediately. If battery acid contacts skin or clothing, wash with soap and
water immediately.
 Do not use a metal to simultaneously touch the two or more terminals of the batteries or
simultaneously touch the battery terminal and the object (such as the battery compartment)
that has been grounded. Otherwise, short circuits may occur, which may further generate
sparks or explosion.
 During battery installation, never short-circuit or reversely connect positive and negative
battery terminals. Connect the negative battery cable before the positive battery cable.
 Secure battery cables to a torque specified in battery documentation. Loose connections
will result in excessive voltage drop or cause batteries to burn out when the current is high.

8.1 (Optional) Installing Antitheft Baffle Plate Bases


Procedure
Step 1 Remove screw caps from antitheft baffle plate bases for the battery compartment.
Step 2 Install the antitheft baffle plate bases on the cabinet.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 80


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 8 Installing Lead-Acid Batteries and Cables

Figure 8-1 Installing an antitheft baffle plate base

----End

8.2 Installing Battery Strings


Prerequisites
Ensure that batteries are from the same manufacturer and of the same model and have a close
voltage. New and old batteries cannot be used together.

Procedure
Step 1 Install batteries in the battery compartment in sequence.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 81


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 8 Installing Lead-Acid Batteries and Cables

Figure 8-2 Installing battery strings

----End

8.3 Installing Copper Bars Between Batteries


Procedure
Step 1 Remove insulation covers from battery 3 and battery 4.
Step 2 Use a copper bar to connect the battery 4 positive terminal to the battery 3 negative terminal.
Step 3 Reinstall the insulation cover on battery 4.

Figure 8-3 Installing a copper bar between batteries

Step 4 Repeat the preceding steps to install copper bars between battery 2 and battery 3 and between
battery 1 and battery 2.
Step 5 If there are multiple battery strings, repeat the preceding steps to install copper bars between
the other batteries and reinstall insulation covers on all batteries.
----End

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 82


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 8 Installing Lead-Acid Batteries and Cables

8.4 Installing Battery Cables


Context

When installing battery cables, install the negative cable before the positive cable.

Procedure
Step 1 Remove the insulation cover from battery 4.
Step 2 Connect one end of the negative battery cable to the negative wiring terminal on battery 4,
and the other end to the BAT- terminal on the right side of the power cabinet.
Step 3 Reinstall the insulation cover on battery 4.
Step 4 Remove the insulation cover from battery 1.
Step 5 Connect one end of the positive battery cable to the positive wiring terminal on battery 1, and
the other end to the RTN+ busbar on the right side of the power cabinet.
Step 6 Reinstall the insulation cover on battery 1.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 83


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 8 Installing Lead-Acid Batteries and Cables

Figure 8-4 Installing battery cables

----End

8.5 (Optional) Installing Antitheft Baffle Plates


Procedure
Step 1 Install antitheft baffle plates on the antitheft baffle plate bases for the battery compartment, as
shown in Figure 8-5.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 84


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 8 Installing Lead-Acid Batteries and Cables

Figure 8-5 Installing an antitheft baffle plate

----End

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 85


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 9 Verifying the Installation

9 Verifying the Installation

9.1 Checking Hardware Installation


 Check that all screws, especially those used for electrical connections, are secured.
Check that flat washers and spring washers are installed properly.
 Check that rectifiers are completely inserted into their respective slots and properly
locked.

9.2 Checking Electrical Connections


 Check that all circuit breakers are OFF or all fuses are disconnected.
 Check that flat washers and spring washers are securely installed for all OT terminals
and that all the OT terminals are intact and properly connected.
 Check that batteries are correctly installed and that battery cables are correctly connected,
and not short circuits exist.
 Check that input and output power cables and ground cables are correctly connected, and
not short circuits exist.

9.3 Checking Cable Installation


 Check that all cables are securely connected.
 Check that all cables are arranged neatly and bound properly to their nearest cable ties,
and are not twisted or overly bent.
 Check that cable labels are properly and securely attached in the same direction.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 86


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

10 Commissioning

 Performing commissioning procedure provided in this chapter may result in power failure
or alarms. Inform the alarm center before commencing the procedure and after completing
the procedure.
 Commissioning should be performed by trained personnel according to the commissioning
instructions provided in this chapter.
 Commissioning is performed with the power on. Before you perform commissioning,
remove any conductors such as jewelry or watches, stand on dry insulating material, and
use insulated tools.
 During commissioning, do not establish contact between electrical points that have
different electric currents.
 Check that the status of a unit or component meets requirements before turning on its
switch.
 If you are maintaining or servicing equipment and do not want others to perform any
operation, attach the label "Currently being serviced. Do not switch on." to the equipment.
 During commissioning, shut down the power system immediately if any fault is detected.
Rectify the fault, start the power system, and proceed with the commissioning.

10.1 Connecting the AC Power Supply


Procedure
Step 1 Measure the input voltage on the AC input circuit breaker. The value should range from 85 V
AC to 300 V AC.
Step 2 Switch on the AC input circuit breaker and measure the output voltage of the AC input circuit
breaker. The value should range from 85 V AC to 300 V AC.
Step 3 Check that the run indicators on the rectifiers are steady on.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 87


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

Step 4 Measure the voltage between the –48 V busbar and the RTN+ busbar. The value should range
from –42 V DC to –58 V DC.
----End

10.2 Setting the Display Language


After powering on the SMU, press or on the LCD to select a display language. Then
press to enter the standby screen.

If an undesired language is selected, reinstall and restart the SMU and then select the desired language.

10.3 Setting the Date and Time


 The LCD backlight turns off if no button is pressed within 30 seconds.
 Re-login is required if no button is pressed within 1 minute.
 The preset password for login is 000001.

Set the date and time as required.

Table 10-1 Setting the date and time

Main Menu Second-Level Third-Level Default Value Settings


Menu Menu

Setting Wizard Date and Time Time Zone UTC +08:00 Set to the local time zone.
NOTE Beijing
The date and time Date and Time - Set to the local date and time.
vary with time
zones. Set the NTP Enable No Yes/No
time zone, date,
and time based on NOTE
the local Set the parameter to Yes if you
situation. need to synchronize the SMU time
and the site network server time.

10.4 Setup Wizard Init


After the Setup Wizard Init screen is displayed, set the following parameters.

Table 10-2 Setting parameters

Item Setting

Time Zone Set to the local time zone.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 88


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

Item Setting
Date and Time Set to the local date and time.
Battery Vendor Set the parameters based on site
requirements.
Battery Model
NOTE
In the lithium battery scenario, retain the default
values.

The SMU may restart Yes

10.5 Setting Sensor Parameters


Set sensor parameters based on site requirements.

 The dry contact parameter for the door status sensor needs to be set only when the door
status sensor of the battery cabinet is connected to a dry contact on the UIM.
 In this example, the door status sensor of the battery cabinet is connected to the DIN4 port.

Table 10-3 Sensor parameter settings

Main Second-Level Third-Level Fourth-Level Default Setting


Menu Menu Menu Menu Value
Parameters Alarm DI Dry DIN4 Alm. Close Open
Settings Parameters Contact Para. Cond.
Power System Sensor Water Sensor None Set to Yes
Config. Para. or No as
Smoke Sensor required.
Batt. Temp.
Sensor 2

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 89


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

10.6 Setting Lead-Acid Battery Parameters


Table 10-4 Setting lead-acid battery parameters (TP48300A-AX09D1)

Main Second- Third- Fourth-Level Default Setting


Menu Level Level Menu Value
Menu Menu
Parameters Acid Basic Battery1 Yes Yes/No
Settings Battery Parameters Connected NOTE
Battery2 Yes If N battery strings
are connected, set
Connected Battery 1 Connected
to Battery N
Battery3 Yes Connected to Yes,
Connected and set the other
parameters to No.
Battery4 Yes
Connected
Single-String 190 Ah Rated capacity of
Cap. the batteries in a
battery string.
NOTE
The batteries
connected to one
circuit breaker or fuse
are called a battery
string.

Other Battery Install - Set this parameter to


Parameters Time the current date.

 If battery routes 1 and 2 are respectively connected to a battery string (each battery string consists of
four 12 V, 190 Ah batteries in series), set Battery1 Connected and Battery2 Connected to Yes and
others to No, and set Single-String Cap. to 190 Ah.
 If battery route 1 is connected to two battery strings in parallel (each battery string consists of four
12 V, 190 Ah batteries in series), set Battery1 Connected to Yes and others to No, and set
Single-String Cap. to 380 Ah.

10.7 Setting the Communications Address for the PC500D


Air Conditioner
Prerequisites
If the power cabinet TP48300A-AX09D1 is installed together with the battery cabinet, the
communications address of the power cabinet air conditioner PC500D should be set to 25.
Two types of air conditioners are optional. Set air conditioner communications addresses as
required.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 90


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

Procedure
If the air conditioner display panel is the one shown in the following figure, set air conditioner
communications addresses in the following way.

Figure 10-1 Air conditioner display panel 1

Step 1 Press ENTER on the home screen of the air conditioner display panel to access the password
input screen.
Step 2 Enter the password 0001 and press ENTER to access the main menu screen.
Step 3 On the main menu screen, choose System Func and press ENTER to access the system
function screen.
Step 4 On the system function screen, choose Para Set and press ENTER to access the system
parameters screen.
Step 5 Select Addr, press ENTER, set the communications address for the power cabinet air
conditioner to 25, and press ENTER.
----End

Procedure
If the air conditioner display panel is the one shown in the following figure, set air conditioner
communications addresses in the following way.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 91


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

Figure 10-2 Air conditioner display panel 2

Step 1 After an air conditioner is powered on, hold down the M key on the home screen for 5
seconds to access the parameter setting state.
Step 2 Use the up and down keys to select the code F07 and press the set key to access the
communications address setting screen.
Step 3 Use the up and down keys to set the communications address to 25 and press the set key to
save the setting.
----End

10.8 Setting Communications Parameters


10.8.1 (Optional) Setting Parameters Before Using WebUI
Operating Environment
Operating system: Windows XP or later
Browser: Internet Explorer 8.0 or later, FireFox 13 or later, or Chrome 20

Internet Explorer is used as an example to illustrate all WebUI operations mentioned in this document.

Setting a LAN

 If the SMU is connected to a LAN and a proxy server has been selected, cancel the proxy
server settings.
 If the SMU is connected to the Internet but your computer is connected to a LAN, do not
cancel the proxy server settings. Otherwise, you cannot access the SMU.

To cancel proxy server settings, perform the following steps:


Step 1 Open Internet Explorer.
Step 2 Choose Tools > Internet Options.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 92


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

Step 3 Click the Connections tab and click LAN settings.


Step 4 Clear Use a proxy server for your LAN, as shown in Figure 10-3.

Figure 10-3 Canceling proxy server settings 1

Figure 10-4 Canceling proxy server settings 2

Step 5 Click OK.


----End

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 93


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

Setting Internet Explorer Security

Set Internet Explorer security before you perform the following operations:
 Export historical logs, historical data, statistics, and battery test records.
 Upload system configuration files.
 Download system configuration files.
 Upgrade software.

To set Internet Explorer security, perform the following steps:


Step 1 Open Internet Explorer.
Step 2 Choose Tools > Internet Options.
Step 3 Click the Security tab.
Step 4 Click Internet and click Custom level, as shown in Figure 10-5. After you specify Internet
security settings, click Local intranet and click Custom level.

Figure 10-5 Internet Explorer security

Step 5 Specify the security settings.


Enable the following:
 Initialize and script ActiveX controls not marked as safe for scripting
 Allow previously unused ActiveX controls to run without prompt

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 94


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

 Include local directory path when uploading files to a server


 Automatic prompting for file downloads

Figure 10-6 Internet Explorer security setting 1

Figure 10-7 Internet Explorer security setting 2

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 95


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

Figure 10-8 Internet Explorer security setting 3

Figure 10-9 Internet Explorer security setting 4

Step 6 Click OK.


Step 7 Click the Advanced tab, and select all of Use TLS 1.0, Use TLS 1.1, and Use TLS 1.2.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 96


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

Figure 10-10 Internet Explorer security setting 5

Step 8 Click OK.


----End

Setting SMU Parameters


Step 1 Apply to the site or equipment room network administrator for a fixed IP address.
Step 2 Set the IP address, subnet mask, and gateway on the SMU's LCD.

Table 10-5 IP parameters


Main Second-Level Third-Level Default
Menu Menu Menu Value Settings
Setting Network IP Address 192.168.0.10 Set this parameter
Wizard Parameters according to the address
provided by the network
administrator.
Subnet Mask 255.255.255.0 Set this parameter
according to the subnet
mask provided by the
network administrator.
Default 192.168.0.1 Set this parameter
Gateway according to the gateway
address provided by the
network administrator.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 97


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

Main Second-Level Third-Level Default


Menu Menu Menu Value Settings
NOTE
If the WiFi module is
installed, do not set the
default gateway to
192.168.8.1.

----End

Login Page
Enter https://local IP address for the SMU (for example, https://192.168.0.10) in the address
box of Internet Explorer and press Enter. The login page is displayed, as shown in Figure
10-11.

Figure 10-11 Login page

The preset user name is admin, and the preset password is Changeme.

10.8.2 Setting Parameters Before Using U2000-SPM


Context

If a Huawei BBU is deployed, set the Northbound and M/S Protocol parameters.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 98


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

Procedure
Step 1 Set the port mode, communications protocol type, baud rate, and communications address on
the SMU's LCD.

Table 10-6 Communications parameters

Main Second-Level Third-Level Fourth-Level Fifth-Level Default Settings


Menu Menu Menu Menu Menu Value
Parameters Comm. Serial Port Northbound Port Mode Manual Manual
Settings Parameters
Protocol Type M/S M/S
NOTE
Protocol Protocol
Protocol Type is
displayed only
when Port Mode
is set to Manual.

M/S Protocol Baud Rate - 9600 9600


Comm. - 3 3
Address

----End

10.8.3 (Optional) Setting Parameters Before Using NetEco


Networking Mode 1: FE Port
Step 1 Apply to the site or equipment room network administrator for a fixed IP address.
Step 2 Set the IP address, subnet mask, and gateway on the SMU's LCD.

Table 10-7 IP parameters

Main Second-Level Third-Level Default


Menu Menu Menu Value Settings
Setting Network IP Address 192.168.0.10 Set this parameter according to the IP
Wizard Parameters address assigned by the network
administrator.
Subnet Mask 255.255.255.0 Set this parameter according to the subnet
mask provided by the network
administrator.
Default 192.168.0.1 Set this parameter according to the
Gateway gateway address provided by the network
administrator.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 99


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

Step 3 Set the IP Addresses and Ports for the active and standby servers of the NetEco on the
SMU's LCD.

Table 10-8 NetEco parameters

Main Second-Level Third-Level Fourth-Level Default


Menu Menu Menu Menu Value Settings
Parameters Comm. Network NetEco Primary 192.168.0.10 Set an IP address for
Settings Parameters Parameters IP the active NetEco
server.
NetEco Backup 192.168.0.10 Set an IP address for
IP the standby NetEco
server.
NetEco Port 31220 31220
Number NOTE
Please contact Huawei
technical support if you
need change the port
number.

----End

Networking Mode 2: RS485 Port


Step 1 Set Port Mode to Manual, Protocol Type to M/S Protocol, Baud Rate to 9600, and Comm.
Address to 3.

Table 10-9 Communications parameters

Main Second-Level Third-Level Fourth-Level Fifth-Level Default Settings


Menu Menu Menu Menu Menu Value
Parameters Comm. Serial Port Northbound Port Mode Automatic Manual
Settings Parameters
Protocol Type M/S M/S
NOTE Protocol Protocol
This parameter is
displayed only
when Port Mode
is set to Manual.

M/S Protocol Baud Rate - 9600 9600


Comm. - 3 3
Address

----End

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 100


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

10.8.4 (Optional) Setting Parameters Before Using SNMP


Prerequisites

You can set SNMP parameters remotely or locally on the WebUI.

Before setting SNMP parameters, obtain the information listed in Table 10-10 from the NMS.

Table 10-10 Information obtained from the NMS

Information Description
SNMP version SNMP version and port number used by the SMU and
NMS. The SNMP versions include SNMPv1,
SNMP Port Number SNMPv2c, and SNMPv3.
Read Community Name If you use SNMPv1 or SNMPv2c, enter the read
community name and write community name that
Write Community Name comply with the NMS. Otherwise, the SMU will not
connect to the NMS.
The read community name must be different from the
write community name.
User Name To enhance the security, you need a user name and
password for authentication if you use SNMPv3. After
MD5/SHA Password the authentication succeeds, the SMU can
communicate with the NMS.
Trap Target Address IP address and port number reported in the alarm trap.
Trap Port
Trap community If you use SNMPv1 or SNMPv2c, community name
NOTE
used for reporting alarm trap packets.
If the SMU software version is
V500R001C00 or later, you need to
obtain the trap community name.

Procedure
Step 1 Log in to the WebUI. For details, see 10.8.1 (Optional) Setting Parameters Before Using
WebUI.
Step 2 Access the System Settings page and set SNMP.
 If the SNMP version is SNMPv1 or SNMPv2c, after you set SNMP Version in SNMP,
set SNMP Version, Read Community Name, and Write Community Name.
 If the SNMP version is SNMPv3, set SNMP Version in SNMP, click Add in SNMPv3,
and set User Name, MD5/SHA Password, and DES/AES Password. Then click
Confirm and Submit.
Step 3 In SNMP Trap, click Add and set relevant parameters such as Trap Target Address and
Trap Port.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 101


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

Step 4 In Mib files, click Export to export the Mib file and then import it into the NMS.

If there is only one NMS, perform Step 4 once only.

----End

Follow-up Procedure
You can query the power system operating status, active alarms, and the names of
user-defined dry contact inputs, and configure dry contact outputs on the NMS that is
connected over SNMP.

10.8.5 Setting GPRS Communications Parameters


Setting Parameters
Step 1 On the LCD, check whether the default GPRS parameter settings are consistent with the
network communications parameter settings of the SIM card carrier. If not, change the
parameters based on the actual carrier configurations.

Table 10-11 Checking GPRS parameters

Main Menu Second-Level Third-Level Fourth-Level Default


Menu Menu Menu Value

Parameters Comm. GPRS Access Point -


Settings Parameters Name
Access Point *99#
Number
User Name Huawei
Password Huawei

Step 2 Set IP addresses and port numbers for the active and standby NetEco servers on the LCD.

Table 10-12 Setting NetEco parameters

Main Second-Level Third-Level Fourth-Level Default Setting


Menu Menu Menu Menu Value
Parameters Comm. Network NetEco 192.168.0.10 IP
Settings Parameters Parameters Primary IP address
of the
active
NetEco
server
NetEco 192.168.0.10 IP
Backup IP address
of the
standby

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 102


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

Main Second-Level Third-Level Fourth-Level Default Setting


Menu Menu Menu Menu Value
NetEco
server
NetEco Port 31220 NetEco
Number port
number

----End

Checking Network Connections


After the SIM card and GPRS antenna are installed, the SIM card automatically connects to
the GPRS network in dial-up mode. View the network connection status on the LCD.

Table 10-13 Checking network connections

Main Menu Second-Level Third-Level Description


Menu Menu
Running Wireless Net GPRS Comm. Dialup Succeeded indicates
Information Status Status successful dial-up and normal
network connection.

10.9 Connecting the Lead-Acid Battery Supply


Prerequisites

To avoid damage to batteries, switch on the battery circuit breaker only after you correctly set
battery parameters.

Procedure
Step 1 Switch on the battery circuit breakers.
Step 2 Switch all the circuit breakers to the appropriate status based on site requirements.
Step 3 Observe the power system for 15 minutes. If no alarm (excluding door alarms) is generated on
the LCD during this period, the voltage and current for batteries and loads are normal.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 103


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

 Before delivery, the BLVD and LLVD switches are set to AUTO and the system is under
automatic control.
 If there is no AC input during commissioning, flip the switch to ON to power the BLVD
and LLVD loads.
 Flip the switches back to AUTO after the commissioning.

Figure 10-12 Battery BLVD switch and LLVD switch (TP48300A-AX09D1)

(1) BLVD switch (2) LLVD switch

----End

10.10 Powering On the ESMs


Procedure
Step 1 Switch on the battery circuit breakers and the circuit breaker connected to activation cables in
the power system.

The SMU will restart after identifying the ESMs.

Step 2 Check whether the ESMs are activated. If the run indicator on an ESM is on, the ESM is
activated. If it is off, the ESM is not activated. If so, check that the activation cable is properly
connected.
Step 3 Check whether the ESMs communicate properly. If the run indicator on an ESM is steady on,
the ESM communicates properly with the SMU. If the indicator blinks fast (4 Hz), the
communication is interrupted. In this case, check that the communications cable is properly
connected.
Step 4 Set all the circuit breakers to the appropriate status based on site requirements.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 104


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 10 Commissioning

Step 5 Observe the ESMs for 15 minutes. The ESMs are running properly if the alarm indicators are
off.
----End

10.11 Subsequent Operations


Procedure
Step 1 Reinstall the removed cover or panel (if there is).
Step 2 The paint on the surface of the cabinet should be kept intact. Therefore, any damaged paint
must be repaired.
Step 3 Put all tools back in the toolkit after they are no longer used.
Step 4 Lock the cabinet door and hand over the key to the administrator. Clean the site and leave.
----End

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 105


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 11 Lock the Antitheft Enclosure Frame

11 Lock the Antitheft Enclosure Frame

Procedure
Step 1 Lock the antitheft enclosure frame. The following figure shows a cabinet with the antitheft
enclosure frame installed.
1. Insert the latch.
2. Lock the antitheft enclosure frame using the key.
3. Reinstall the lock baffle plate on the antitheft enclosure frame.

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 106


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide 11 Lock the Antitheft Enclosure Frame

Figure 11-1 Lock the antitheft enclosure frame

----End

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 107


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro) A Associations Between Alarms and Dry Contacts on the
Installation Guide UIM

A Associations Between Alarms and Dry


Contacts on the UIM

Table A-1 Associations between dry contacts and alarms

Dry Contact Silkscreen Associated Alarm


Type

Dry contact inputs DIN1 Dry contact input 1


DIN2 Dry contact input 2
DIN3 Dry contact input 3
DIN4 Dry contact input 4
DIN5 Dry contact input 5
DIN6 Forcibly load connection
Dry contact ALM1 Battery Test Negative
outputs
ALM2 Rectifier fault, rectifier protection, rectifier
The default setting communication failure, or multi-rectifier fault
(closed: alarm;
open: normal) can ALM3 Battery Fuse Break
be modified.
ALM4 DC undervoltage
ALM5 High ambient temperature, very high ambient
temperature
ALM6 Battery Charge Failure
ALM7 AC failure, long ac failure
ALM8 SMU fault
ALM9 AC/DC surge protector fault
ALM10 Reserved
ALM11 Reserved
ALM12 Reserved

Issue 02 (2017-12-20) Huawei Proprietary and Confidential 108


Copyright © Huawei Technologies Co., Ltd.
TP48200A-AX09D3 & TP48300A-AX09D1 &
TBC800A-ACD1 Outdoor Power System (Columbia,
Claro)
Installation Guide B Acronyms and Abbreviations

B Acronyms and Abbreviations

B
BBU Building base band unit

E
ESM Energy storage module

F
FE Fast Ethernet

H
HAU Heater Assembly Unit
HTTPS Hypertext Transfer Protocol Secure

L
LCD Liquid crystal display

S
SMU Site monitor unit