ROOT CAUSE ANALYSIS

Water leakage from Sprinkler line Flow Switch.

ABB INDIA PVT LTD – 01


SATPUR NASHIK

Identify Investigation by

DOUSE FIRE SYSTEM PVT LTD -- TEAM

DATE – 22-12-2019
Sr.No. Problem Corrective Root cause analysis Preventive action plan
action
01 Water Fist Switch off the (A)Before work start :- Our team has (A)ALL the Air release valves
leakage from Jockey pump and been removed the all materials in are very old in ABB plant-1.
Sprinkler line Drain the other location. Than work start
Flow Switch Sprinkler line . (B) After work completed :- At the (B) Kindly check air release
time of water testing in sprinkler line . valve its not working
When the water pressure increasing in properly .
the sprinkler line then Air must be
automatically released from air release
valves. but there was too much
pressure in the sprinkler line due to no
air release.
(C) Water leakage from gas kit of flow
switch due to air and water pressure in
sprinkler pipe.