Medium-Voltage

Switchgear
Switchgear Catalog HA 41.21
2003
Type SIMOSEC up to 24 kV,
Air-Insulated, Extendable Supersedes:
Catalog HA 41.21 · 2002
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Contents Application

Page Typical uses

Application, Requirements
Typical uses, features 2 and 3

R-HA41-082 eps
Technical Data
Electrical data, pressure values,
temperature 4 and 5
Switchgear installation 6
Shipping data 7

Product Range
Product range overview, equipment
features 8 and 9
Panels 10 to 15

Design
Panel design 16 and 17

Components
3AH vacuum circuit-breakers 18 to 20 Example
Three-position switches 21 4-panel transfer switchgear with
Busbars, HV HRC fuse assembly 22 and 23 integrated low-voltage niche
Operating mechanisms 24
Indicating and measuring equipment 25
Interlocking systems and locking devices 26
Transformers 27 to 29
Cable connection 30 and 31
Low-voltage equipment 32

Dimensions
Panels 33 to 39
Floor openings, fixing points 40

Standards
Standards, specifications, guidelines 41 to 43

Notes
43
R-HA41-055 eps

Utilities transfer substation


© Siemens AG 2003 for industrial plants

2 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Application, Requirements

Features
SIMOSEC switchgear is a Technical features Reliability • Mechanical switch position
factory-assembled, type- • Air-insulated indoor • Type and routine-tested indications integrated in
tested, three-phase, metal- switchgear mimic diagram
enclosed, metal-clad indoor • Standardized and manu-
• Gas-insulated, maintenance- factured using numerically • Switchgear interlocking
switchgear according to system with logical
IEC 60 298 / VDE 0670, free switching functions for controlled machines
the three-position switch mechanical interlocks
Part 6 for single busbars. • Quality management system
• Three-pole primary enclosure according to DIN EN ISO 9001 Reavailability
Typical uses
• Phases arranged one behind • More than 350,000 switchgear • Three-position switch discon-
SIMOSEC switchgear is the other components in operation nector with gas-insulated,
used for power distribution in worldwide for many years maintenance-free quenching
• No cross-insulation between
distribution systems with principle
feeder currents up to 1250 A. phases • No cross-insulation between
• Busbar system at top phases • Metal compartmentalization
Modular space-saving design between busbar compart-
allows use in • Air-insulated busbar and cable Personal safety ment, switching devices and
• Substations, customer trans-
connection system cable connection compart-
• All switching operations can
fer substations, distribution • Three-position switch, metal- be performed with closed ment
substations and switching enclosed, with air-insulated panel front • Separate pressure relief for
substations of power supply primary terminals and gas- each compartment
insulated switching functions • Metal-enclosed, cubicle-type
and public utilities
or metal-clad switchgear • Cable testing without the
• Public buildings, such as • Vacuum circuit-breaker 3AH5,
• HV HRC fuses and cable seal- need to isolate the busbar
high-rise buildings, railway metal-enclosed, up to 630 A,
stations, hospitals fixed-mounted in gas-insulated ing ends are only accessible • Mounting location of three-
switchgear vessel when the outgoing feeders are phase current transformer for
• Industrial plants earthed selective disconnection of
• Vacuum circuit-breaker 3AH6,
• Logical mechanical interlocking circuit-breaker feeders
Typical examples air-insulated, up to 1250 A,
• Wind power stations
easy to withdraw after loose- • Capacitive voltage detection
Cost-efficiency
ning the fixing bolts system for verification of safe
• High-rise buildings isolation from supply Extremely low life-cycle costs
• Hermetically-sealed by
• Airports and extremely high availability
welding, stainless-steel • Earthing of outgoing feeders
throughout the entire product
• Underground railway stations switchgear vessel, by means of make-proof service life cycle as a result of:
– For switching devices earthing switches
• Sewage treatment plants – With welded-in bushings • Three-position switch with
• Port facilities (for electrical connections and Security of operation gas-insulated quenching
mechanical components) principle
• Traction power supply • Components, e.g. operating
systems – With insulating gas SF6 mechanisms, three-position • 3AH vacuum circuit-breaker
• Automobile industry • Cubicle-type or metal-clad switches, vacuum circuit- • Minimum space requirement
panel design breakers proven for years
• Petroleum industry • Easy switchgear extension
• Pressure relief • Metal-clad panels (metal com-
• Chemical industry – To the rear and upwards partmentalization between • Standard protection relays,
– Separately for each busbar and switching device e.g. multifunction protection
• Unit-type heating power
compartment and between switching device SIPROTEC 4
stations
• Air-insulated cable connection and cable connection compart-
• Textile, paper and Electrical features
system for conventional cable ment)
food industry • Rated voltages up to 24 kV
sealing ends • Cubicle-type panels with
• Emergency power supply
• Three-phase current trans- metal compartmentalization • Rated short-time withstand
installations between switching device and current up to 25 kA
former, factory-assembled on
the feeder bushings busbar compartment • Rated normal current of
Modular design
• Integrated low-voltage niche • Three-position switch metal- feeders
• Individual panels, for free
(standard) for installation enclosed with gas-insulated – Up to 630 A, e.g. for
combination and extension switching functions ring-main, metering and
of, e.g.
• Option: low-voltage compart- – Welded sealed-for-life circuit-breaker panels
– Terminals, MCBs, push-
ments can be supplied in buttons switchgear vessel – Up to 1250 A, for
two overall heights – Protection devices – No cross-insulation between circuit-breaker and bus
phases sectionalizer panels
• Option: Top-mounted low- – With welded-in bushings for
voltage compartment • Rated normal current of
cable connection, busbar and busbar up to 1250 A
• Option: Panel heating for operating mechanism
severe ambient conditions, • Switch operating mechanisms
e.g. condensation outside switchgear vessel
• Maintenance-free operating
mechanism parts (IEC 60 694/
VDE 0670 Part 1000 *)

* Standards see page 41

Siemens HA 41.21 · 2003 3


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Technical Data

Electrical data of panels, pressure values, temperature


Common details on electrical data, filling pressure and temperature
Rated insulation level Rated voltage Ur kV 7.2 12 15 17.5 24
Rated short-dur. power-freq. withstand voltage Ud kV 20 28 35 38 50
Rated lightning impulse withstand voltage Up kV 60 75 95 95 125
Rated frequency fr 50/60 Hz
Rated normal current Ir 1) Standard 630 A
of busbar Option 1250 A
Rated short-time for switchgear with tk = 1 s up to kA 20 25 20 25 16 20 25 16 20 25 16 20
withstand current Ik for switchgear with tk = 3 s up to kA 20 – 20 – – 20 – – 20 – – 20
Rated peak withstand current Ip up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Rated filling pressure pre 2) for insulation 1500 hPa (absolute) at 20 °C
Minimum operating pressure pme 2) for insulation 1300 hPa (absolute) at 20 °C
Ambient temperature T for panels without secondary equipment – 25 °C to +55 °C
for panels with secondary equipment – 5 °C to +55 °C

Ring-main panel type RK and cable connection panel type K


Rated normal current Ir 1) for feeder and transfer, panel type RK 400, 630 A
for feeder, panel type K 400, 630 A
for feeder, panel type K1 400, 630, 1250 A
Rated short-circuit making current Ima up to kA 50 63 50 63 40 50 63 40 50 63 40 50

Transformer panel type TR


Rated normal current Ir 1) for feeder 3) 200 A
Rated peak withstand current Ip 3) up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Rated short-circuit making current Ima 3) up to kA 25 25 25 25 25 25 25 25 25 25 25 25
Reference dimension “e“ for HV HRC fuse links mm 292 4) 292 442 442 442

Circuit-breaker panel type LS for feeder for transfer with


Rated normal current Ir 1) f. panel type LS1 and LS1-U 3AH5 * 630 A
f. panel type LS11 and LS11-U 3AH6 * 630 A
f. panel type LS31, LS32 and LS31-U 3AH6 * 1250 A
Rated short-circuit making current Ima up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Rated short-circuit breaking current Isc for 3AH vacuum circuit-breaker up to kA 20 25 20 25 16 20 25 16 20 25 16 20

Busbar earthing panel type SE


Rated short-circuit making current Ima up to kA 50 63 50 63 40 50 63 40 50 63 40 50

Busbar voltage metering panels type ME3 and type ME31-F


Rated peak withstand current Ip 3) up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Rated short-circuit making current Ima 3) up to kA 25 25 25 25 25 25 25 25 25 25 25 25
Reference dim. “e“ in panel type ME31-F for HV HRC fuse links 292 mm

Billing metering panels type ME1


Rated normal current Ir 1) for transfer, panel types ME1 and ME1-H 630 A, 1250 A
for feeder as cable-connection panel type ME1-K 630 A, 1250 A
for busbar connection, panel type ME1-S 630 A, 1250 A
for bus riser panel type HF 630 A, 1250 A

Bus sectionalizer panels type LT


Rated normal current Ir 1) for panel types LT10 and HF, with 3AH5 * 630 A
for panel type LT1, with 3AH5 *: On request 630 A
for panel types LT11 and HF, with 3AH6 * 630 A
for panel types LT2 and LT22 630 A
for panel types LT31 and HF, with 3AH6 * 1250 A
Rated short-circuit making current Ima up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Rated short-circuit breaking current Isc for 3AH vacuum circuit-breaker up to kA 20 25 20 25 16 20 25 16 20 25 16 20
Electrical service life for 3AH vacuum circuit-breaker:
at rated normal current Ir 1) 10,000 operating cycles
at rated short-time breaking current Isc 50 breaking operations, 35 breaking operations on
3AH6 * with 25 kA

1) The rated normal currents apply to ambient tempera- 3) For panel types TR and ME31-F depending on the max. * Type designation
tures of 40 °C. The 24-hour-mean value is max. 35 °C cut-off current of the HV HRC fuse link of the vacuum
(according to IEC 60 694 / VDE 0670 Part 1000) 4) With reference dimension e = 192 mm, an extension tube circuit-breaker
2) Pressure values for SF6-insulated vessels (100 mm long) is additionally required for fuse mounting 292 mm

4 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Technical Data

Electrical data * of the switching devices


Three-position switch-disconnector
Rated voltage Ur kV 7.2 12 15 17.5 24
Rated insulation Rated short-duration power-frequency withstand volt. Ud kV 20 28 36 38 50
level
Rated lightning impulse withstand voltage Uw kV 60 75 95 95 125
Rated frequency fr Hz 50/60 50/60 50/60 50/60 50/60
Rated normal ring-main feeders Ir A 400, 630 400, 630 400, 630 400, 630 400, 630
current for
transformer feeders 1) Ir A 200 200 200 200 200
Rated short-time for switchgear with tk (ttk)**= 1 s Ik (Ith)** up to kA 25 25 25 25 20
withstand current
for switchgear with t k (ttk)**= 3 s Ik (Ith)** kA 20 20 20 20 20
Rated peak withstand current Ip up to kA 63 63 63 63 50
Rated short-circuit transformer feeders 2) Ima kA 25 25 25 25 25
making current for
ring-main feeders Ima up to kA 63 63 63 63 50

Switching capacity of general-purpose switches (class E3) according to IEC 60 265-1 / VDE 0670 Part 301 (Standards see page 41)
Test duty 1 Rated mainly active for 100 switching operations I1 A 630 630 630 630 630
load breaking current for 20 switching operations I1 A 31.5 31.5 31.5 31.5 31.5
Test duty 2a Rated closed-loop breaking current I2a A 630 630 630 630 630
Test duty 3 Rated transformer breaking current I3 A 40 40 40 40 40
Test duty 4a Rated cable-charging breaking current I4a (IC or I6)** A 68 68 68 68 68
Test duty 4b Rated line-charging breaking current I4b A 68 68 68 68 68
Test duty 5 Rated short-circuit making current Ima up to kA 63 63 63 63 50
Test duty 6a Rated earth-fault breaking current I6a (Ie)** A 60 60 60 60 60
Test duty 6b Rated cable-charging breaking current and line- I6b A 35 35 35 35 35
charging breaking current under earth-fault conditions (HJ3 v ICL)**
– Cable-charging breaking current under IL + HJ3 v ICL A 630+50 630+50 630+50 630+50 630+50
earth-fault conditions with superimposed load current

Switching capacity of switch-disconnector/fuse combination (Standards see page 41)


Rated transfer current I4 A 1150 1150 830 830 830

Earthing switch
Rated voltage Ur kV 7.2 12 15 17.5 24
Make-proof earth- Rated short-circuit making current Ima up to kA 63 63 63 63 50
ing function of
the three-position Rated short-time withstand current Ik (Ith)** up to kA 25 25 25 25 20
switch-disconnector
HA41-29a eps

Make-proof Rated short-circuit making current Ima up to kA 63 63 63 63 50


earthing function
in panels LS11, Rated short-time withstand current Ik (Ith)** up to kA 25 25 25 25 20
LS31, LS32
Earthing function Rated short-time withstand current Ik (Ith)** up to kA 25 25 25 25 20
of the three-position
disconnector

3AH5 and 3AH6 vacuum circuit-breakers


Rated voltage Ur kV 7.2 12 15 17.5 24
Rated insulation Rated short-duration power-frequency withstand volt. Ud kV 20 28 36 38 50
level
Rated lightning impulse withstand voltage Up kV 60 75 95 95 125
Rated frequency fr Hz 50/60 50/60 50/60 50/60 50/60
Rated normal current of feeders for 3AH5 Ir A 400, 630 400, 630 400, 630 400, 630 400, 630
for 3AH6 Ir A 630, 1250 630, 1250 630, 1250 630, 1250 630,1250
Rated short-time withstand current Ik (Ith)** up to kA 25 25 25 25 20
Rated short-circuit duration tk (tth)** s 3 3 3 3 3
Rated peak withstand current Ip up to kA 63 63 63 63 50
Rated short-circuit breaking current Isc up to kA 25 25 25 25 20
Rated short-circuit making current Ima up to kA 63 63 63 63 50
Electrical service life at rated normal current – – 10,000 operating cycles

* Higher values of electrical data available on request 1) Depending on the HV HRC


** Indications in parenthesis acc. to previous standards fuse links
2) Depending on the cut-off
current of the HV HRC fuse

Siemens HA 41.21 · 2003 5


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Technical Data

Switchgear installation
Room planning
Room planning
Switchgear installation
19 7
Wall-standing arrangement
– Single row 20
Switchgear room Switchgear room
– Double row (for face-to-face >1000
21
arrangement) 1

2
Room dimensions
10

See opposite dimension 3


drawings

>2400
>2400
4
2100*

Door dimensions 5
1750

The door dimensions 1080 6 1080


depend on the 7 7
– Number of panels in a 1230 >1000 1230 >1000
transport unit 8
– Design with or without 9
low-voltage compartment
10
Switchgear fastening

600**
600**

60 850 90 60 850 90
• For floor openings and 11
fixing points of the switch- Cable basement Cable basement
gear, see page 40
• Foundations: Wall-standing arrangement (side view) Free-standing arrangement (side view)
– Steel structure 12 17
– Steel-reinforced concrete 150 150
13
Panel dimensions
See pages 34 to 39
³50
10

Weight 14

The weight of a panel depends 3 18


on the extent to which it is
equipped (e.g. with motor
operating mechanism, voltage
transformer). For details,
please refer to page 7.

15
16
HA41-2392c eps

HA41-2391c eps
³50
10

Plan view Plan view

1 Relief opening 12 Wall distance


2 Direction of pressure relief 13 Side wall distance
3 Pressure relief of switchgear 14 Installation flush with rear wall
4 Room height 15 Panel width
5 Individual panel depth 16 End wall
6 Panel depth including end wall 17 Depth of pressure relief duct
7 Control aisle 18 Option: For free-standing arrangement
pressure relief duct for each panel
8 Option: Floor cover
for rated short-time withstand current Ik w 20 kA
9 Cable
19 Option: Front cover
10 Foundation
20 Option: Low-voltage compartment
11 Height of cable basement corresponding to
21 Option: High end wall
cable bending radius

* Switchgear height 2100 mm if height of ** Depending on bending radius of cable


low-voltage compartment 350 mm;
switchgear height 2300 mm if height of
low-voltage compartment 550 mm

6 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Technical Data

Shipping data
Transport units Individual panel Panel Panel or panel Transport unit (including packing)
for shipping (plan view) or combinations type combination for standard panels (without pressure relief duct)
thereof for standard switchgear
(without pressure relief duct) Width Net Width Height Depth Volume Gross
T2 B1 weight 1) B2 T2 weight
T1 1 mm approx. kg m m m m3 approx. kg
3 with- / with with- / with with- / with with- / with
out out out out
LVC*/LVC* LVC*/LVC* LVC*/LVC* LVC*/LVC*
HA41-2284b eps

2
B1
B2

Transport of individual panels


Ring-main panel RK 375 190 / 250 0.7 1.9 / 2.3 1.40 1.86 / 2.25 250 / 310
RK1 500 210 / 270 0.7 1.86 / 2.25 270 / 330
With individual panel
Ring-main panel for panel combinations RK-U 375 260 / 320 0.7 1.86 / 2.25 320 / 380
Cable panel K, K-E 375 190 / 250 0.7 1.86 / 2.25 250 / 310
K1, K1-E 500 190 / 250 0.7 1.86 / 2.25 250 / 310
T2 Transformer panel TR 375 210 / 270 0.7 1.86 / 2.25 270 / 330
T1 1 TR1 500 230 / 290 0.7 1.86 / 2.25 290 / 350
Circuit-breaker panel 630 A LS1 750 340 / 400 1.08 2.87 / 3.48 410 / 460
LS11 750 340 / 400 1.08 2.87 / 3.48 410 / 460
Circuit-breaker panel 1250 A
3 – For connection of max. 2 cables LS31 750 400 / 460 1.08 2.87 / 3.48 470 / 520
2 – For connection of 3 cables LS32 875 460 / 520 1.08 2.87 / 3.48 530 / 580
B1

Bus sectionalizer panel 1250 A LT31 750 450 / 510 1.08 2.87 / 3.48 520 / 570
Bus sectionalizer panel 630 A LT10 750 320 / 380 1.08 2.87 / 3.48 390 / 440
4 with vacuum circuit-breaker LT11 750 320 / 380 1.08 2.87 / 3.48 390 / 440
B2
B3

Bus sectionalizer panel with LT2 750 250 / 310 1.08 2.87 / 3.48 320 / 370
2
B1

5 1 three-position switch-disconnector LT2-W 750 310 / 370 1.08 2.87 / 3.48 380 / 430
Bus sectionalizer panel with LT22 750 290 / 350 1.08 2.87 / 3.48 360 / 410
2 three-position switch-disconnectors LT22-W 750 350 / 410 1.08 2.87 / 3.48 420 / 470
HA41-2285c eps

2
B1

Billing metering panel ME1.... 750 270 / 330 1.08 2.87 / 3.48 340 / 390
ME1-H 750 330 / 390 1.08 2.87 / 3.48 400 / 450
Busbar ME3 375 210 / 270 0.7 1.86 / 2.25 270 / 330
With combinations of different voltage metering panel ME31-F 500 270 / 330 0.7 1.86 / 2.25 330 / 390
individual panels Bus riser without transformers HF 375 170 / 230 0.7 1.86 / 2.25 230 / 290
panel with transformers HF 375 260 / 320 0.7 1.86 / 2.25 320 / 380
Busbar SE1 375 190 / 250 0.7 1.86 / 2.25 250 / 310
1 T1 = Depth of individual panel earthing panel SE2 500 270 / 330 0.7 1.86 / 2.25 330 / 390
2 Individual panel For individual panel Panel Additional
dimension B1 x T1 width weight
3 Transport unit, mm approx. kg
dimension B2 x T2 Pressure relief duct 375 30
4 B3 = Overall width of for free-standing arrangement 500 40
combination of different of switchgear
750 60
individual panels
875 70
5 B2 = Width of the
transport unit
Transport of combinations of different individual panels
Transport unit: Overall width B3 B2 T2
– Standard: As individual panels arranged
w 875 mm 1.08 1.9 / 2.3 1.40 2.87 / 3.48 2) + 70 **
side by side and not screwed together
– Option: As multi-panel transport unit, w 1125 mm 1.20 1.9 / 2.3 1.40 3.19 / 3.86 2) + 80 **
panels screwed together w 1500 mm 1.70 1.9 / 2.3 1.40 4.52 / 5.47 2) + 100 **

w 2000 mm 2.33 1.9 / 2.3 1.40 6.20 / 7.50 2) + 120 **

Packing, transport (examples)


Packing Version For supply Transport
Panels mounted on wooden floor Open In Europe Rail, truck
and covered with PE protection sheeting In container Overseas Ship + truck

1) The net weight depends on the 2) Sum of the * Low-voltage compartment, ** Packing
extent to which it is equipped net weights of 350 mm high, weight approx. weight
(e.g. current transformers, motor individual panels 60 kg depending on the
operating mechanisms) and is panel type and on the extent
therefore given as mean value to which it is equipped

Siemens HA 41.21 · 2003 7


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Product Range

Product range overview

Panel designation Panel Panel


Standard panels type width
R-HA41-073 eps

R-HA41-076 eps

Column No.
Ring-main as RK 375 mm
panel 1) feeder RK1 500 mm
as RK-U 375 mm
transfer
Ring-main panel Circuit-breaker panel Transformer as TR 375 mm
type RK type LS1 panel 1) feeder TR1 500 mm
Cable panel as K 375 mm
feeder K1 500 mm
Cable panel 1) 2) as K-E 375 mm
R-HA41-074 eps

R-HA41-077 eps

feeder K1-E 500 mm


Circuit-breaker panel 630 A 1) as LS1 750 mm
with 3AH5 3) feeder
as LS1-U 750 mm
transfer
Circuit-breaker panel 630 A as LS11 750 mm
with 3AH6 3) feeder
as LS11-U 750 mm
transfer
Circuit-breaker panel 1250 A as LS31 750 mm
with 3AH6 3) feeder LS32 875 mm
as LS31-U 750 mm
transfer
Bus sectionalizer panel 630 A 1) LT10 750 mm
with 3AH5 3), for panel type HF
Bus sectionalizer panel 630 A LT11 750 mm
with 3AH6 3), for panel type HF
Bus sectionalizer panel 1250 A LT31 750 mm
with 3AH6 3), for panel type HF
Transformer panel Circuit-breaker panel Bus sectionalizer panel 630 A 1) 4)
LT2 750 mm
type TR type LS11 LT2-W 750 mm
5)
LT22 750 mm
LT22-W 750 mm
R-HA41-075 eps

R-HA41-078 eps

Billing metering Standard ME1 750 mm


panel ME1-S 750 mm
as ME1-K 750 mm
end panel ME1-KS 750 mm
Billing metering panel ME1-H 750 mm
for additional current transformer
Busbar voltage metering ME3 375 mm
panel 1) ME31-F 500 mm
Busbar earthing SE1 375 mm
panel 1)
6)
SE2 500 mm

Bus riser panel HF 375 mm

1) Metal-clad
2) With additional make-proof earthing switch
3) Type designation of vacuum circuit-breaker
4) With 1 three-position switch-disconnector
Cable panel Billing metering panel
5) With 2 three-position switch-disconnectors
type K type ME1
6) With voltage transformer for busbar metering

8 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Product Range

Equipment features
2)
• Basic equipment 1)
h
h itc
° Additional equipment (option),
further additional itc
h
r tc
fo swi sw
n um er
O g itio er acu cov
equipment on request sw 2N hin 2 ) s
ea
k v t
n d t ) po br AH6 en er
itc
h io an ear h1 e- it- rtm ak
– Not available
w o sit tc h “ o f itc h re cu f 3 c h a re
s -p i ED o sw . of
t
cir “ o itch swi
t p t-b
io
n
ee sw TH -pr om ui
o sit ent thr ical ion AR ake ition ch u um SED sw ing le c circ )
tr sit e
e or os . m een vac LO ition arth cab
E m 3
-p ac rtm D/ d
h
ee ver pl rf ec o -p / itc um AH itch
hr pa to el e-p SE an ree erat etw H... “C pos of e ion er w acu 3
t o in
om
a e e h n - t tt s n sw tor
r
fo ent
c d di
c ot hr CLO itc th op el b 3A itio ree -pro nec shu tion or v se i ion
m c ke alc in em or t “ sw for tor n d os th e n r si f a it di
ca
o in e r f r a n p k o o o e s
a ni
s
a rtm er l rm e rvic for ion C fo tion nism r m
o
er p 2 ) a ch hed ma e c ent e -p nism rel -po lt in
ec
h m
p v
co et te eas r-se O) icat 1N osi ha fo ak 1 ) w ar
it t r
fo in t rtm thr
h e ha te
d
re
e
fa
u nt
m e co ent
s
ck he a t re y-fo
l N
(1 ind O + ee-
p ec itch t-bre itch or s th e out w pa for ec era r th rth- pme
g l ra m i f i - o m p f o a i
tin cab n d h e r w u w k m t g o e u
ra rtm e b c
ni shu rea itc rvic (2N r th ting e s circ n s vice er w loc in
d
co -ou atin c.t.- ice or eq r4 ) ting ble
pe fo
r pa abl ge as al g sw -se itch ) fo e ra ot in siti
o e ak ing n
w ge ck per s ev cuit dary ove ea ca
o m c t a i c r p m d r e o ta lo a d h d
ua
l ck co as ol e n
-v leas cha nall dy-f x. s PEN tor
in o w ” o re lock -po king it-b arth ecti -vol ing o e g cir con or c el nte ps
lo le il al r ee or leas ckin ort- n u m
an nter ab r- a w e g a o c te r c
Lo cir
c u -e sp w o s ot e
S F P lo a o
M I C C Lo Re M Si re Au “O M Lo In th De In Lo Cl M Re Lo Sh – – – M cla
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Panel type

• • – • • – – – – – – RK
° ° ° ° ° ° ° ° ° ° ° ° ° ° RK1
• • – – • – – – –– – – • – – RK-U
° ° ° ° ° ° ° ° ° °
• • – • • – – – – – – TR
° ° ° ° ° ° ° • ° ° ° ° ° ° TR1
• – • • • – – – – – – – – – – – – – K
° ° ° ° ° ° ° K1
– • – • • – – – – – – – • K-E
° ° ° ° ° ° ° ° ° ° ° ° K1-E
• • – • • – – – LS1
° ° ° ° ° ° ° ° ° ° ° ° ° ° ° ° °
• • – – • – – – • – – LS1-U
° ° ° ° ° ° ° ° ° ° ° ° ° °
5) 6) LS11
• • – • • –
° ° ° ° ° ° ° ° ° ° ° ° ° ° ° ° ° ° °
• • – – • – – • – – LS11-U
° ° ° ° ° ° ° ° ° ° ° ° ° ° °
• • – • • • • 5) – 6) LS31
° ° ° ° ° ° ° ° ° ° ° ° ° ° ° ° ° LS32
– – – – LS31-U
• • •
° ° ° ° ° ° • •
° ° ° ° ° – ° ° ° –

• • – – • – – – 7) • – – LT10
° ° ° ° ° ° ° ° ° ° ° ° ° °
• • – – • • – – – 7) • – – LT11
° ° ° ° ° ° ° ° ° ° ° ° °
– – – – – 7) LT31
• • •
° ° ° ° ° ° • •
° ° ° ° – ° ° ° –

• • • – • – – – – – – – • – – LT2
° ° ° ° ° ° ° ° ° ° LT2-W
• • – – • – – – – – – – • – – LT22
° ° ° ° ° ° ° ° ° ° LT22-W
– – • – • – – – – – – – – – – – – – – – ME1
° ° ° ° ° ME1-S
– – • • • – – – – – – – – – – – – – – ME1-K
° ° ° ° ° ° ME1-KS
– – • – • – – – – – – – – – – – – – – – ME1-H
° ° ° ° °
• • – – • – – – – – – – – – ME3
° ° ° ° ° ° ° ° ° ° ° ° ME31-F
• • – – • – – – – – – – – – – • – – SE1
° ° ° ° ° ° °
• • – – • – – – – – – – – – • – – SE2
° ° ° ° ° ° ° °
– – • – • – – – – – – – – – – – – – – – – HF
° ° ° °

1) Three-position switch as three-position switch-disconnector 5) Not to be applied for versions with separate feeder earthing switch in
2) Three-position switch as three-position disconnector in panel panel types LS11, LS31 and LS32
types LS31, LS31-U, LS32 and LT31 6) Inspection window is a standard equipment in panel types LS11, LS31
3) Type designation of the vacuum circuit-breaker and LS32 for versions with separate earthing switch
4) In special cases, deeper floor cover required 7) Option (on request): Closing lock-out possible for panels LT11 or LT31
in combination with the adjacent panel type HF

Siemens HA 41.21 · 2003 9


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Product Range

Ring-main panels

Ring-main panels Ring-main panel 4)


as feeder panels as transfer panel for attachment
to panel types ME1... or ME1-H 3AH5 vacuum
circuit-breaker
Standard:
Option Option transfer

HA41-2350a eps
HA41-2348b eps

to the 5)
right
Option *
Option: 3AH6 vacuum
Option * Option transfer circuit-breaker
to the
3) 3)
optional

left
Option *
Option
Three-position
switch-disconnector
1)

Capacitive
Type RK Type RK-U voltage detection
375 mm wide 375 mm wide system

1)

Cable-type
current transformer
For other panel combinations e.g. 4MC703 . . .
Option Option
With 2)
HA41-2465a eps

Option Option 3AH5 Block-type


HA41-2349a eps

vacuum current transformer


Option Option circuit-
optional

4MA,
4)
breaker, cast-resin insulated
Option 3) 3) fixed-
mounted
2) Option Option optional 3)
P2 P2
optional

Option Three-phase
Option 2) 2)
P1 P1 current transformer
optional

4MC63 . . .
1) 3) Option
The ring-main transfer
panel RK-U can be
attached on the left or Voltage transformer
Type RK1 either: Type LT10 Type RK-U right of the bus section- e.g. 4MR, 1-pole,
500 mm wide Version with 750 mm wide 375 mm wide alizer panel LT10 cast-resin insulated
transformers Bus sectionalizer panel type LT10 with
ring-main transfer panel type RK-U

Option Option Cable (not


With
HA41-2466a eps

Option included in the


3AH6
scope of supply)
HA41-2351b eps

vacuum
Option Option circuit-
Option
breaker,
3) 3)
with-
drawable 2nd cable (not
optional

included in the
optional

5) Option
Option P2 scope of supply)
Option
2) P1
HA41-2390b eps

1) Option
Surge
arrester

Type RK1 or: Type LT11 Type RK-U


500 mm wide Version with 750 mm wide 375 mm wide
connection Bus sectionalizer panel type LT11 with
fittings ring-main transfer panel type RK-U
(non-interchangeable arrangement)

P1 and P2
are terminal
designations
of the current
transformer

* On request
up to 12 kV

10 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Product Range

Transformer and cable panels

Transformer panels Cable panels Cable panels


as feeder panels as feeder panels, 630 A as feeder panels with
make-proof earthing switch Three-position
switch-disconnector
Option Option *
HA41-2353a eps

HA41-2356c eps

HA41-2358b eps
Option * Option * HV HRC fuse
Option Option

3)

optional

optional
Capacitive

optional
Option * Option * voltage detection
Option ** Option Option
system
1) 1) 1)

Earthing
switch
Type TR Type K Type K-E
375 mm wide 375 mm wide 375 mm wide
Make-proof
earthing switch

Fixed
as feeder panels earthing point
630 A and 1250 A
Option 1)
HA41-2354a eps

Option Option Cable-type


HA41-2359b eps
HA41-2357b eps

current transformer,
e.g. 4MC703 . . .
optional

optional
Option
Option Option Option
2)

2) 2) Block-type
Option ** current transformer
optional

optional
Option Option Option Option 4MA,
1) cast-resin insulated
1) 3) 1) 3)
3)

Type TR1 Three-phase


500 mm wide either: Type K1-E either: current transformer
Type K1
Version with 500 mm wide Version with 4MC63 . . .
500 mm wide
transformers transformers

Voltage transformer
e.g. 4MR, 1-pole,
HA41-2444a eps

HA41-2445a eps

cast-resin insulated
Option Option *
Option

Cable (not
optional
optional

Option included in the


Option
Option Option scope of supply)

1) 1)

2nd cable (not


included in the
Type K1 or: Type K1-E or: scope of supply)
500 mm wide Version with 500 mm wide Version with
connection connection
HA41-2390b eps

fittings fittings
Surge
arrester

* On request
up to 12 kV
** Current
transformer
located partly
underneath
the panel

Siemens HA 41.21 · 2003 11


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Product Range

Circuit-breaker panels

Circuit-breaker panels 630 A Circuit-breaker panels 1250 A 4)


as feeder panels as feeder panels
3AH5 vacuum
Option Option circuit-breaker
for

HA41-2467b eps
Option Option connection
HA41-2360b eps

of max. 5)

optional
Option Option ** 2 cables

optional
4) 3AH6 vacuum
Option Option circuit-breaker

optional
3)

3) Option 5) Option
optional

Option 2)
P1 Option Option Three-position

optional
optional
switch-disconnector
P2 2) Option
1) Option

1)
Type LS1 With 3AH5 vacuum circuit-breaker, Type LS31 With 3AH6 Three-position
750 mm wide fixed-mounted 750 mm wide vacuum circuit-breaker, withdrawable disconnector

Option Option Option Option


for 1)
HA41-2468 eps
HA41-2362a eps

connection Cable-type
optional

of max.

optional
current transformer
Option Option ** Option Option ** 3 cables e.g. 4MC703 . . .
(4 cables *)
optional

3) 3)
optional

2)

Option 5) Option Option 5) Option Option Block-type


current transformer
2) 2) 1) 4MA,
optional

cast-resin insulated

optional
optional

optional

Option Option
Option Option Option
3)

1) 1) Three-phase
Type LS11 With 3AH6 Type LS32 With 3AH6 current transformer
750 mm wide vacuum circuit-breaker, 875 mm wide vacuum circuit-breaker, 4MC63 . . .
withdrawable withdrawable

as transfer panels for attachment as transfer panel for attachment


Voltage transformer
to panel types ME1... or ME1-H to panel types ME1... or ME1-H
e.g. 4MR, 1-pole,
cast-resin insulated
Option Option Standard: Option Option Transfer
transfer
HA41-2361c eps

HA41-2364e eps

possible
3) to the 3) only to
4) right the right Cable (not
Option Option Option: Option B Option included in the
P1 transfer P1 scope of supply)
2) to the 2) 5)
P2 P2
optional

left
Option Option
Addit. cables (not
included in the
scope of supply)

Type LS1-U With 3AH5 Type LS31-U With 3AH6


750 mm wide vacuum circuit-breaker, fixed-mounted 750 mm wide vacuum circuit-breaker, withdrawable
Surge
arrester

Option Option Transfer


HA41-2363d eps

possible Capacitive
3) only to voltage detection
the right system
Option B Option
Footnotes for the left and right columns:
P1
P2 2) 5) * On request
Make-proof
optional

** Standard: Feeder earthing earthing switch


Option via the 3AH6 vacuum circuit-breaker
HA41-2390b eps

with interlocks (without earthing switch)


B Mounting position of the current
Fixed
transformer with terminal P1 at the top only
earthing point

Type LS11-U With 3AH6 P1 and P2 are terminal designations


750 mm wide vacuum circuit-breaker, withdrawable of the current transformer

12 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Product Range

Bus sectionalizer panels

Bus sectionalizer panels 630 A Bus sectionalizer panels 630 A 4)


in combination with bus riser panel with 1 three-position switch-disconnector
3AH5 vacuum
Option Option circuit-breaker
With
HA41-2367b eps

3AH5 Option Option


vacuum 5)

HA41-2371a eps
Option Option circuit-
Panel type HF attached

breaker, 3AH6 vacuum


4)
3) fixed- circuit-breaker
mounted
Option Option
on the left

P2 P1
P1 2) 2) P2 Three-position
optional

switch-disconnector
Option Option

Type HF Type LT10 Type LT2 corresponds to type RK-U Three-position


375 mm 750 mm wide 750 mm wide with type HF disconnector

Option Option Option


With 2)
HA41-2368b eps

3AH5 Option Block-type


vacuum current transformer
HA41-2372b eps

Option Option circuit- Option 4MA,


Panel type HF attached

4)
breaker, cast-resin insulated
3) fixed- Option
mounted 3)
Option Option 3) Option
P1 P2 P2
on the right

Three-phase
P2 2) 2) P1 2) P1 current transformer
optional

4MC63 . . .
Option Option Option

Voltage transformer
Type LT10 Type HF Type LT2-W corresponds to type RK-U e.g. 4MR, 1-pole,
750 mm wide 375 mm wide 750 mm wide with type HF cast-resin insulated

Option
With
Capacitive
Option 3AH6
with 2 three-position switch-disconnectors
vacuum voltage detection
HA41-2369d eps

circuit- system
Option
be attached on the right
Panel type HF can only

breaker Option Option

HA41-2390b eps
Option
HA41-2373a eps

with-
drawable Fixed
3) 5) Option earthing point
P2 Option
Option 2) P1
Option

Type LT11 Type HF


750 mm wide 375 mm wide

Type LT22 corresponds to type RK-U


Bus sectionalizer panel 1250 A 750 mm wide with type RK-U
in combination with bus riser panel
Option Option
With
Option 3AH6 Option
vacuum
HA41-2365c eps

HA41-2374c eps

Option circuit- Option


be attached on the right

breaker
Panel type HF can only

Option with- Option 3)


drawable
3) 5) Option 3) Option
P2 P2
Option 2) 2) P1
P1
optional

Option Option
P1 and P2
are terminal
designations
Type LT31 Type HF Type LT22-W corresponds to type RK-U of the current
750 mm wide 375 mm wide 750 mm wide with type RK-U transformer

Siemens HA 41.21 · 2003 13


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Product Range

Billing metering panels

Billing metering panels Billing metering panels Billing metering panels


630 A and 1250 A 630 A and 1250 A 630 A and 1250 A Capacitive
Standard for busbar connection for additional current transformer voltage detection
system
2)
Option Option Option Option
HA41-2450 eps

HA41-2454 eps
HA41-2446 eps

2) 2)

optional
Block-type
Option P2 P2 current transformer
Option Option Option
P1 P2 4MA,
2) 2)
P1 P1 cast-resin insulated
2)

Option *

optional
On request:
Voltage transformer,
e.g. 4MR,
Scheme 1 Scheme 1 Scheme 1 cast-resin insulated
with HV HRC fuse
Type ME1 Standard **: Type ME1-S Standard **: Type ME1-H Standard **:
750 mm wide Transfer to the right 750 mm wide Transfer to the right 750 mm wide Transfer to the right

Voltage transformer,
2) e.g. 4MR,
Option Option Option Option 1- or 2-pole,
HA41-2451 eps

HA41-2455 eps
HA41-2447 eps

cast-resin insulated

optional
Option Option Option Option
P1 P2 Fixed
2) earthing point
P2 P2

HA41-2390b eps
Option *

optional
2) 2)
P1 P1
Fixed earthing
point for
Transformer Transformer Transformer
busbar earthing
terminals terminals terminals
interchanged Scheme 2 interchanged Scheme 2 interchanged Scheme 2
Type ME1 Standard **: Type ME1-S Standard **: Type ME1-H Standard **:
750 mm wide Transfer to the right 750 mm wide Transfer to the right 750 mm wide Transfer to the right

2)
Option Option Option Option
HA41-2452 eps
HA41-2448 eps

HA41-2456 eps

optional

Option Option Option Option


P2 P1
2)
P1 P1
Option *
optional

2) 2)
P2 P2

Scheme 3 Scheme 3 Scheme 3

Type ME1 Standard **: Type ME1-S Standard **: Type ME1-H Standard **:
750 mm wide Transfer to the right 750 mm wide Transfer to the right 750 mm wide Transfer to the right

2)
Option Option Option Option
HA41-2453 eps

HA41-2457 eps
HA41-2449 eps

optional

Option P1 Option Option P1 Option


2) P2 P1 2)
P2 P2 P1 and P2
2) are terminal
designations
Option *
optional

of the current
transformer
Transformer Transformer Transformer
terminals terminals terminals * On request
interchanged Scheme 4 interchanged Scheme 4 interchanged Scheme 4
** Option:
Type ME1 Standard **: Type ME1-S Standard **: Type ME1-H Standard **: Transfer
750 mm wide Transfer to the right 750 mm wide Transfer to the right 750 mm wide Transfer to the right to the left

14 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Product Range
Billing metering panels, busbar voltage metering panels,
busbar earthing panels and bus riser panels

Billing metering panels Billing metering panels Busbar voltage Bus riser panels
630 A and 1250 A ** 630 A and 1250 A ** metering panels 630 A and 1250 A
for cable connection for busbar connection Three-position
Option switch-disconnector

HA41-2458 eps
Option HA41-2379a eps Option Option
HA41-2375a eps

HA41-2383a eps
Option * Make-proof
P2 P2 earthing switch
Option Option
2) 2)
P1 P1
Option
P2 Make-proof
2) earthing switch
P1
Option
Earthing switch
Scheme 1 Scheme 1 Scheme 1

Type ME1-K Standard B): Type ME1-KS as right or left Type ME3 Type HF BB) 2)
750 mm wide Transfer to the right 750 mm wide end panel 375 mm wide 375 mm wide Block-type
current transformer
Option 4MA,

HA41-2459 eps
cast-resin insulated
Option Option Option
HA41-2384a eps
HA41-2380a eps
HA41-2376a eps

Option *
Voltage transformer,
Option Option e.g. 4MR,
1- or 2-pole,
Option Option cast-resin insulated
P2 P2 (on
2) 2)
request)
P1 P1

Option Voltage transformer,


Transformer Transformer
P2 e.g. 4MR,1-pole
terminals terminals
2)
cast-resin insulated
interchanged Scheme 2 interchanged Scheme 2 P1 Scheme 2

Type ME1-K Standard B): Type ME1-KS as right or left Type ME31-F Type HF BB)
750 mm wide Transfer to the right 750 mm wide end panel 500 mm wide 375 mm wide
HV HRC fuse

Busbar
earthing panels
Option Capacitive
voltage detection
HA41-2460 eps

Option Option system


HA41-2385a eps
HA41-2381a eps
HA41-2377a eps

HA41-2390b eps
Option *
Fixed
Option Option
earthing point
Option
P1 P1
2) 2)
P2 P2

Option
P1 P1 and P2
Scheme 3 Scheme 3 P2 2) Scheme 3 are terminal
designations
Type ME1-K Standard B): Type ME1-KS as right or left Type SE1 Type HF BB) of the current
750 mm wide Transfer to the right 750 mm wide end panel 375 mm wide 375 mm wide transformer
Option
HA41-2461 eps

Option Option Option * On request


up to 12 kV
HA41-2378a eps

HA41-2382a eps

HA41-2386a eps

Option * ** Connection
for 3 cables
Option P1 Option P1 possible
2) 2)
P2 P2 B Option:
Option Transfer
P1 to the left
P2 2)
BB For
Option attachment
Transformer Transformer to left or
terminals terminals right
interchanged Scheme 4 interchanged Scheme 4 Scheme 4
ring-main
Type ME1-K Standard B): Type ME1-KS as right or left Type SE2 Type HF BB) panels
750 mm wide Transfer to the right 750 mm wide end panel 500 mm wide 375 mm wide type RK-U

Siemens HA 41.21 · 2003 15


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Design

Panel design (examples)

Ring-main panel as feeder Transformer panel as feeder

HA41-2393d eps

HA41-2394d eps
1 60 1 60
2 2 2 2
3 23 23
4 24 24
5 11 19 5 11 19
6 12 58 6 12 58
7 13 7 13
26
8 14 25 8 14
15 15 27
9 9
10 16 18 10 16 18
17 17
27
18 18
59 57 59
20 20 57
21 21 34 34
61 28 35 35
61 31
29 31 33
22
22 32 29
33
61
56 22 22
23
30
30
Type RK Section Type TR Section

Billing metering panel Legend for pages 14 and 15


1 Option: Low-voltage compartment
HA41-2395e eps

2 Niche for optional low-voltage equipment,


cover can be unscrewed
3 Option: CAPDIS voltage detection system
1 60 4 Option: Short-circuit /earth-fault indicator
2 5 Option: Ready-for-service indicator
37 for switching device
23
2 6 Switch position indication for load-break
24
function “CLOSED – OPEN“
10 33 7 Switch position indication for earthing
function “OPEN – EARTHED“
38 8 Feeder designation label
38
9 Mimic diagram
8
16 10 Option: Sockets for capacitive voltage detection system
57 (depending on arrangement)
9 11 Option: Momentary-contact rotary control switch
33 “CLOSED – OPEN“ for motor operating mechanism
33 with local-remote switch
for three-position switch-disconnector
12 Option: Locking device for three-position
40 40 switch-disconnector
13 Pressure relief device for switching device
65 14 Manual operation for the mechanism of
the earthing function
15 Manual operation for the mechanism of
39 the load-break function
39
16 Rating and type plate
17 Gas-insulated vessel for switching device
30
18 Interlocking of the cable compartment cover

Type ME1 Section 19 Bushing-type insulator for busbar


20 Bushing-type insulator for feeder

16 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Design

Panel design (examples)

Circuit-breaker panel (with 3AH5 vacuum circuit-breaker) 21 Insulating sleeve *


22 Cable bracket with clamps (option) for fastening cables

HA41-2396e eps
23 Busbar
24 Insulating cap ** on busbar
25 Spring-operated mechanism for
1 60 three-position switch-disconnector
2 2 26 Spring-operated/stored-energy mechanism for
51 23 three-position switch-disconnector
24 27 Three-position switch-disconnector
5
51
45 28 Cable connection
11 19
46
12 58 29 Cable compartment cover
44 13 30 Earthing connection (for location see dimension drawings)
8 14 25
47 6 31 Earthing switch for cable connection
43
10 7 32 Inspection window
48 15 64
16 33 Post insulator
41
17 34 Insulating sleeve
64 57 35 Option: HV HRC fuse link
59
50 36 Option only for panel types LS11 ... and LT11 ...:
49
20 Logical mechanical interlocking between circuit-breaker
9 20
“OPEN“ and three-position switch-disconnector and
21 21 locking device for three-position switch-disconnector

28 37 Option: Part of the low-voltage equipment

61 38 Cover, screwed on
29
39 4MR voltage transformer
61 40 4MA7 block-type current transformer
22
22 Vacuum circuit-breaker:
41 3AH5 vacuum circuit-breaker, fixed-mounted

30 42 3AH6 vacuum circuit-breaker, withdrawable


43 Operating mechanism box
Type LS1 Section
44 Manual operation
– for closing with manual operating mechanism
– for emergency operation with motor operating
mechanism
Circuit-breaker panel (with 3AH6 vacuum circuit-breaker) 45 Mechanical “OFF“ pushbutton
46 Mechanical “ON“ pushbutton
HA41-2397d eps

(not supplied with spring-operated mechanism)


47 “Spring charged“ indicator
1 48 Operating cycle counter
60
55 49 Switch position indication
2
3 23 50 Option: Three-phase current transformer 4MC63 53
2 24 51 Option: Overcurrent-time protection relay
52 52 SIPROTEC easy 7SJ45
11 19
5 36 58 52 Option: Multifunction protection relay SIPROTEC 4 7SJ62
6 17 53 Insulating cap * for cable connection
7 25
14
8 27 54 Insulating cap * on bushing-type insulator
15
9 55 Option: Wiring duct, removable,
10 16 64
for control cables and/or bus wires
54 13 50
20 56 Logical mechanical interlocking for three-position switch
64
56 57 57 Earthing busbar
59
50 54
36 58 Metal compartmentalization of busbar compartment
43
43 59 Metal compartmentalization of cable
44 connection compartment
29
45 60 Busbar compartment cover for panel extension
53
46 42
33 61 Cable sealing end (not included in scope of supply)
47
62 Option: Feeder earthing via make-proof earthing switch
48 62
33 63 or feeder earthing via vacuum circuit-breaker (= locking
49 63
61 device for feeder earthed when circuit-breaker “CLOSED“)
61 64 Interlocking of cable compartment cover in
22 circuit-breaker panels
56 30 65 Cover for transformer connection compartment

Type LS11 Section * For example for Ur = 24 kV


** For example for Ur > 12 kV

Siemens HA 41.21 · 2003 17


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

3AH5 and 3AH6 vacuum circuit-breakers


Common features 3AH5 vacuum circuit-
• Circuit-breakers with breaker
vacuum interrupters • Metal-enclosed
• Stored-energy spring- • Up to 630 A 2
operated mechanism for • Pole parts with vacuum
10,000 operating cycles interrupters fixed-mounted
• Maintenance-free for in- in hermetically welded,
door installation according gas-filled switchgear vessel
to IEC 60 694 / VDE 0670 • System-conforming use 3
Part 1000, subsequently 1
with three-position switch
IEC 62 271-1* in gas-insulated switchgear
• Individual secondary vessel
equipment • Operating mechanism 4

R-HA41-066 eps
arranged outside the
Switching duties and switchgear vessel and
operating mechanisms behind the control board
The switching duties of the • Air-insulated primary
vacuum circuit-breaker are terminals
dependent, among other 3AH5 5
factors, on its type of oper- Installation in metal-clad vacuum circuit-breaker
ating mechanism. Three (operating mechanism box open)
panels
operating mechanism 6
versions are available: • Feeder panels type LS1,
panel width 750 mm
• Motor operating stored- 1 Operating mechanism box 4 Spring-operated mechanism of
energy mechanism • Transfer panels type LS1-U, three-position switch-disconnector
2 Bushing-type insulator for busbar
– For auto-reclosure (K), panel width 750 mm 5 Bushing-type insulator for feeder
3 Switchgear vessel, gas-filled, with
– For synchronization and • Bus sectionalizer panels 3AH5 vacuum circuit-breaker and 6 Location for three-phase current
rapid load transfer (U) type LT10 (for adjacent bus three-position switch-disconnector transformer (option)
• Manual operating stored- riser panel type HF),
energy mechanism panel width 750 mm
– For auto-reclosure (K)
3AH6 vacuum circuit-
• Manual spring-operated breaker
mechanism
(= spring CLOSED, • Withdrawable 1) lateral-
stored-energy OPEN) mechanism circuit-breaker, 11
– Not for auto-reclosure (K) air-insulated
– For normal closing and • Up to 1250 A
– For storage of one 8
• Circuit-breaker poles
opening
arranged one behind the
Trip-free mechanism other 7
• Operating mechanism in
• The vacuum circuit-
breakers are fitted with a separate box behind lower
trip-free mechanism panel cover
according to IEC 60 056 • Logical mechanical inter-
and VDE 0670. locking between 3AH6 10
vacuum circuit-breaker and
three-position switch
• Installation in: 9
R-HA41-068 eps

– Feeder panel type LS11,


* Standards see page 41 panel width 750 mm
– Transfer panel type LS11-U,
1) Withdrawable after loosening
the respective contact panel width 750 mm
connections and fixing bolts – Bus sectionalizer panels
type LT11 and LT31 (for 10 Locking device for the
adjacent bus riser panel 3AH6 vacuum circuit-breaker
Abbreviations for switching type HF), panel width in switch position “CLOSED”
duties and applications: 750 mm 3AH6 with earthed three-position switch
– Feeder panel type LS31 vacuum circuit-breaker in switch position “EARTHED“
U = Synchronization and
rapid load transfer (for connection of 11 Logical mechanical interlocking
(make time w 90 ms) max. 2 cables), (standard when earthing the
7 Operating mechanism box with control feeder with closed vacuum
K = Auto-reclosure panel width 750 mm elements circuit-breaker) in panel types:
– Feeder panel type LS32 – 630 A: LS11, LS11-U and LT11
8 Circuit-breaker poles with vacuum
For further details, please refer (for connection of 3 cables; interrupters – 1250 A: LS31, LS31-U, LS32
also to Catalog HG 11.11 4 cables on request), and LT31
“3AH Vacuum Circuit-Breakers“ 9 Truck
panel width 875 mm

18 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

3AH5 and 3AH6 vacuum circuit-breakers


Operating mechanism
functions

Motor operating mechanism 1)


(M1 *)
In the case of the motor operat-
ing mechanism, the closing 1
spring is charged by means of 6
2
a motor and latched in the
charged position (the “spring 7
charged” indication is visible). 3
Closing is effected either by
means of an ON pushbutton or 4
a closing solenoid. The closing
spring is recharged automati- 5 8
cally (for auto-reclosure).
R-HA41-080 eps

Operating mechanism
Manual operating stored- elements of the
energy mechanism 3AH5 vacuum circuit-breaker

The closing spring is charged


by means of the supplied hand Operating mechanism elements
crank until latching of the 1 Gear
closing latch is indicated 2 Coupling on gear for operation
(= “spring charged” indication). 1 with hand crank
– For closing with manual
Subsequently the vacuum 2 spring-operated mechanism
circuit-breaker can be closed 6
– For charging the closing spring
either manually or electrically. 3 with stored-energy mechanism
The closing spring can be re- 7 3 Closing spring
charged manually. The “possibil- 4
4 Motor (M1 *)
ity to close” is thus stored once
5 “Closing spring charged” indicator
more (for auto-reclosure).
6 Circuit-breaker “OPEN”
5 8
Manual spring-operated 7 Circuit-breaker “CLOSED”
mechanism 8 Operating rod
(= spring CLOSED,
stored-energy OPEN)
The closing spring of the vacuum
circuit-breaker is charged by
means of the supplied hand
crank until the vacuum circuit-
R-HA41-069 eps

breaker closes. Subsequently Operating mechanism


either manual or electrical open- elements of the
3AH6 vacuum circuit-breaker
ing is possible.
Vacuum circuit-breakers with
spring-operated mechanism are Differences between the vacuum circuit-breakers depending on the operating mechanism version
not suitable for auto-reclosure. Operating Motor operating Manual operating Manual spring-operated
mechanism version stored-energy mechanism stored-energy mechanism mechanism
Typical uses Utility substations Classic transfer substations Simple utility substations
and industrial plants and substations without (circuit-breaker as
auxiliary voltage supply transformer switch)
1) Motor rating at
24 V to 220 V DC: 350 W Mechanism Stored-energy CLOSED, Stored-energy CLOSED, Spring CLOSED,
110 V and 220 V AC: 400 VA function stored-energy OPEN stored-energy OPEN stored-energy OPEN
2) With closing solenoid Mechanism With motor 1), manual With hand With hand
* Equipment code operation (emergency) operation crank crank
at the panel including
anti-pumping
Abbreviations:
Closing the Electrically 2) or Mechanically at the panel Mechanically at the panel
O = OPEN operation vacuum mechanically at the panel with pushbutton, option: with hand crank
CO = CLOSE operation with subse- circuit-breaker with pushbutton electrically 2) (charging process)
quent OPEN operation at the Closing solenoid, Always provided, with Option Without
shortest internal close-open time e.g. for remote electrical signal
of the vacuum circuit-breaker electrical closing “closing spring charged”
t = Dead time 0.3 s
Rated switching O-t-CO or O-t-CO O or CO
t ‘ = Dead time 3 min sequence O-t-CO-t’-CO
Auto- Suitable (multiple Suitable (only with closing –
For further details, please refer also to reclosure (K) auto-reclosure possible) solenoid)
Catalog HG 11.11 “3AH Vacuum
Circuit-Breakers“

Siemens HA 41.21 · 2003 19


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Secondary equipment of the 3AH5 and 3AH6 vacuum circuit-breakers


The scope of the secondary Anti-pumping (standard)
equipment of the 3AH vacu- (mechanical and electrical)
um circuit-breaker depends • Function: If CLOSE and

R-HA41-080 eps
on the type of application OPEN commands are ap-
and offers a wide range of plied simultaneously and
variations, thus allowing continuously to the vacuum 1
even the highest require- circuit-breaker, this reverts
ments to be satisfied. to its OPEN position after
closing. The circuit-breaker
Closening solenoid remains in this position until
• Type 3AY15 10 (Y9 *) the OPEN command is eli- 3

• For electrical closing minated and a new CLOSE


command is given. Thus
Shunt releases continuous closing and ope-
ning (= pumping) is avoided. 4
• Types:
2
– Standard: 3AY15 10 (Y1 *) Breaker tripping signal
– Option: 3AX11 01 (Y2 *), (standard)
with energy store
• For electrical signalling 5
• Tripping by protection re- (as pulse > 10 ms), e.g. to
lay or electrical operation remote control systems,
in the case of automatic
Current transformer- Secondary equipment of the 3AH5
tripping (e.g. protection) vacuum circuit-breaker (typical example)
operated release
• Via NO contact (S6 *)
• Type 3AX11 04 (Y6 *) for and cut-out switch (S7 *)
tripping pulse W 0.1 Ws in
conjunction with suitable Varistor module
protection systems, e.g.
7SJ4 protection relay, • As overvoltage protection 1
SEG relay (other designs for protection devices in
on request) conjunction with inductive
devices in the vacuum
• Used where no external circuit-breaker (limiting to 3
auxiliary voltage is avail- approx. 500 V)
able, tripping by protec-
tion relay • Recommended for auxil-
iary voltages W 60 V DC
4 6
Undervoltage release
Auxiliary switch
• Type 3AX11 03 (Y7 *) 2
• Type 3SV9 (S1 *)
• Comprising:
– Energy store and • Standard: 6NO+6NC,
5
unlatching mechanism of which 2NO+2NC
– Electromagnetic system, +2 changeover contacts
to which voltage is perma- are free 1) 7
nently applied in the • Option: 12NO+12NC, of
CLOSED position of the which 7NO+4NC+2 change-
vacuum circuit-breaker; over contacts are free 1)
tripping is initiated when
this voltage drops Mechanical interlocking
• Connection to voltage • Dependent on the type
R-HA41-046 eps

transformer possible of operating mechanism:


– Spring-operated
Position switch mechanism or
– Stored-energy mechanism Secondary equipment of the 3AH6
• Type 3SE4 (S4 *) vacuum circuit-breaker (typical example)
• For signalling “closing • Option:
spring charged“ Switchgear interlocking Basic equipment Additional equipment
with the three-position 1 Auxiliary switch 6NO+6NC (S1 *),
• Only in conjunction with 3 Position switch (S4 *)
switch-disconnector option: 12NO+12NC
stored-energy mechanisms 4 Closing solenoid (Y9 *)
For further details concer- 2 1st release (Y1 *)
5 Operating cycle counter
ning interlocking functions,
refer to page 26. 6 2nd release
(e.g. Y2 *, Y6 * and Y7 *)
1) For utilization * Equipment Abbreviations: 7 Mechanical interlocking
by the code NO = normally-open contact with interrogation
customer NC = normally-closed contact of the three-position
switch-disconnector
For further details, please refer also to
Catalog HG 11.11 “3AH Vacuum Circuit-Breakers“

20 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Three-position switches as three-position switch-disconnectors or disconnectors


Common features Three-position
• Metal-enclosed switch-disconnector 630 A

• Located in a • Up to 630 A
gas-insulated • With gas-insulated, 1
switchgear vessel maintenance-free quench-
• Switch positions: ing principle
CLOSED-OPEN-
EARTHED Operating mechanism
2
• No cross insulation • Spring-operated mechanism
between phases with detachable lever

• Three-position switch • Manual operation with the


with air-insulated aid of a detachable lever 3 5

R-HA41-057 eps
primary connections • Options:
for busbar and feeder – Mechanical ready-for-
• Operation via a service indication
gas-tight welded-in – Auxiliary switch
bushing in the front of – Motor operating mecha-
the switchgear vessel nism for switch-disconnector 4
– Locking device
Mode of operation • Spring-operated/stored- 6
energy mechanism for Three-position
The switch shaft with the switch-disconnector
moving contact pieces transformer panel types TR,
630 A
rotates inside the cham- TR1 and ME31-F
ber containing the fixed
contact pieces. Interlocks 1 Bushing-type insulator for busbar
• Opening of lower panel 2 Switchgear vessel for gas insulation
Compression vanes,
which rotate in conjunc- cover or cable compartment 3 Three-position switch-disconnector
tion with the switch cover only in “EARTHED“ 4 Bushing-type insulator for feeder
shaft, divide the arcing position 5 Spring-operated mechanism with detachable lever
chamber into two sub- • Option: Logical mechanical 6 Mounting location for three-phase current transformer (option)
chambers each of which interlocking of three-position
changes in conjunction switch-disconnector with
with the rotation. vacuum circuit-breaker
Switch positions:
During the switching 7
movement, the compres- Three-position
HA41-2430b eps

disconnector 1250 A EARTHED


sion vanes generate a
pressure difference be- • Up to 1250 A, for panel
tween the subchambers. types LS31, LS31-U, LS32
The SF6 gas flows and LT31
through a nozzle, causes OPEN
• Metal-enclosed
a directional blow-out of
the breaking arc and Operating mechanism
quenches it rapidly.
• Spring-operated mechanism CLOSED
Interlocking is not neces- with detachable lever
sary as the “CLOSED” Detachable lever mechanism
and “EARTHED” func- • Manual operation with the with three-position switch-disconnector
tions cannot be imple- aid of a detachable lever
7 Operating lever, plugged inserted as as
mented simultaneously. • Options: three-position three-position
– Mechanical ready-for- switch- disconnector
service indication disconnector 1250 A
– Auxiliary switch 630 A
– Motor operating mecha-
nism for disconnector Switching functions of the Switching functions of the
– Locking device three-position switch-disconnector three-position disconnector
630 A 1250 A
Interlocks • Switching and disconnecting under • Disconnecting
load • Switching functions according to
• Opening of lower panel
• Switching function as general purpose – IEC 62 271-102
cover or cable compartment switch-disconnector (class E3 and M1) – VDE 0670 Part 2 / EN 60 129
cover only in “EARTHED” according to • Earthing function
position – IEC 60 265-1
– VDE 0670 Part 301 • For panel types LS31, LS31-U,
• Logical mechanical – IEC 62 271-102 LS32 and LT31
interlocking with vacuum – VDE 0670 Part 2 / EN 60 129
circuit-breaker • Make-proof earthing function
Note: Standards see page 41

Siemens HA 41.21 · 2003 21


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Busbars, HV HRC fuse assembly


Busbars HV HRC fuse assembly
Busbars
• Safe-to-touch due to • For transformer panel
metallic enclosure types TR and TR1 1 Busbar

R-HA41-061 eps
• Metal-clad busbar • For busbar voltage meter- 1 2 Insulating cap (e.g.
compartment ing panel type ME31-F for Ur > 17.5 kV) on
busbar
• Three-pole design, • HV HRC fuse links 2
3 Bushing-type
bolted from panel to acc. to DIN 43 625 (main insulator for busbar
panel dimensions) with striker 3
• Easy switchgear pin; version “medium”
extension acc. to IEC 60 282/
VDE 0670 Part 4 *
• Made of copper: – As short-circuit protec-
– Fl E-Cu for w 630 A tion before transformers
– Rd E-Cu for > 630 A to – With selectivity (depend- Busbar compartment extending over 3 panels (example)
1250 A Side view
ing on correct selection)
• For > 12 kV: to upstream and down-
With insulated busbar stream connected
equipment
– Single-pole insulation
• Requirements acc. to
IEC 60 420 * fulfilled by HV HRC fuse assembly
combination of HV HRC
fuse and three-position
R-HA41-071 eps

“CLOSED“ indi-
switch-disconnector cation, manual or
motor operation
• Fuse replacement possi-
ble only when feeder is Indication “HV
HRC fuse tripped”
earthed or “shunt
• Option: Shunt release on release tripped”
operating mechanism of “OPEN” indication
three-position switch-
disconnector
• Option: “Tripped indica-
tion” of three-position
switch-disconnector in
transformer feeder (trans-
former switch) for remote
electrical indication with
Control board of a transformer feeder
one normally-open con-
tact (1NO)

“HV HRC fuse tripped”


Following the tripping of an
R-HA41-052 eps

4 Insulating sleeve
HV HRC fuse link, the me-
5 HV HRC fuse
chanism for charging the (not included in the
4
spring must be set to the scope of supply)
“OPEN” position 6 Earthing switch (rated
Subsequently, earthing can short-circuit making
5 current Ima = 4 kA)
be implemented by means
for cable connection
of the three-position
7 Cover for bolted
switch-disconnector and
cable lug connection
e.g. the fuse can be (e.g. for rated voltage
replaced. 6 Ur = 24 kV)
8 Cable sealing end
Replacement of HV HRC 7 (not included in the
fuse links scope of supply)
• Isolating and earthing of
the transformer feeder
• Subsequent manual 8
replacement of the
HV HRC fuse link

HV HRC fuses in transformer panel type TR


Side view
* Standards see page 41

22 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Allocation of HV HRC fuses and transformers


The table opposite shows the Rated Transformer Rated normal current of the HV HRC
recommended 3GD HV HRC system fuse link at ambient temperature of 40 OC
fuse links (electrical data valid voltage Rating SN Relative Rated Lowest Highest
for ambient temperatures of up impedance current I1 value value
voltage uk
to 40 oC) for the fuse protec-
kV kVA % A A A
tion of transformers
6 to 7.2 50 4 4.8 16 16
75 4 7.2 16 16
Recommendation 100 4 9.6 20 25
The three-position switch- 125 4 12.0 25 25
disconnector in the trans- 160 4 15.4 32 32
former feeder (transformer 200 4 19.2 40 40
switch) was combined with 250 4 24.0 50 50
Siemens HV HRC fuse links 315 4 30.3 50 63
400 4 38.4 63 100
of type 3GD and tested in
500 4 48.0 63 100
accordance with IEC 60 420 *
630 4 61.0 80 100
10 to 12 50 4 2.9 10 10
Standards 75 4 4.3 10 10
HV HRC fuse links with 100 4 5.8 16 16
striker pin, “medium“ version 125 4 7.2 16 16
according to 160 4 9.3 20 20
200 4 11.5 25 25
• IEC 60 282 * 250 4 14.5 25 32
• VDE 0670 Parts 4 and 402 315 4 18.3 32 40
400 4 23.1 40 50
• DIN 43 625 main dimensions 500 4 29.0 50 63
630 4 36.4 63 80
800 5 to 6 46.2 63 80
1000 5 to 6 58.0 80 100
1250 5 to 6 72.3 100 100
13.8 50 4 2.1 6 6
75 4 3.2 10 10
100 4 4.2 10 10
125 4 5.3 16 16
160 4 6.7 16 16
200 4 8.4 16 20
250 4 10.5 20 25
315 4 13.2 25 32
400 4 16.8 32 32
500 4 21.0 40 50
630 4 26.4 50 50
800 5 to 6 33.5 50 50
1000 5 to 6 41.9 63 63
1250 5 to 6 52.4 80 80
15 to 17.5 50 4 1.9 6 6
75 4 2.9 10 10
100 4 3.9 10 10
125 4 4.8 10 10
160 4 6.2 16 16
200 4 7.7 16 20
250 4 9.7 20 25
315 4 12.2 25 25
400 4 15.5 32 32
500 4 19.3 32 40
630 4 24.3 40 50
800 5 to 6 30.9 50 50
1000 5 to 6 38.5 63 63
1250 5 to 6 48.2 63 80
20 to 24 50 4 1.5 6 6
75 4 2.2 6 6
100 4 2.9 10 10
125 4 3.6 10 10
160 4 4.7 10 10
200 4 5.8 16 16
250 4 7.3 16 16
315 4 9.2 20 20
400 4 11.6 20 25
500 4 14.5 25 32
630 4 18.2 32 40
800 5 to 6 23.1 32 32
1000 5 to 6 29.0 40 40
1250 5 to 6 36.0 50 50
1600 5 to 6 46.5 63 80
* Standards see page 41
2000 5 to 6 57.8 80 80

Siemens HA 41.21 · 2003 23


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Operating mechanisms for three-position switches


Manual operating Shunt release (option)
mechanism Operating mechanisms (examples)
Spring-operated/stored-en-
• Standard: ergy mechanisms can be
As detachable lever equipped with a shunt re-
mechanism lease. Remote electrical trip-
• Option: Design according ping of the three-position
to VDEW recommenda- switch-disconnector is possi-
ble via the magnetic coil

R-HA41-079 eps
tion – Association of
German Power Stations – of the shunt release, e.g.
VDEW e.V. transformer overtemperature
tripping.
• Spring-operated mecha-
nism To avoid thermal overloading
– For ring-main panel of the shunt release in the
event of a continuous signal Detachable lever mechanism
types RK and RK1 as spring-operated mechanism
– For all three-position that may be applied, the for ring-main feeders
switches (except in panel shunt release is switched off
types TR and TR1) via an auxiliary switch which
is mechanically coupled with
• Spring-operated- /stored- the three-position switch-
energy mechanism disconnector.
R-HA41-070 eps

1 Terminal strip located


For transformer panel in the low-voltage
types TR and TR1 as well Auxiliary switch (option) niche (optionally in
as for busbar voltage me- the low-voltage
tering panel type ME31-F Each operating mechanism 1 compartment)
of the three-position switch- 2 M.c.b. (option)
The three-position switch is disconnector can be option- 2
in the low-voltage
operated via a rocker with ally equipped with an auxil- niche
metal bellows which is 3
iary switch for the switch 3 Local-remote switch
gas-tight and welded at the position indication: (option)
switchgear vessel. 4
– 1NO + 1NC for 4 Actuation for the
“CLOSED/EARTH” 5
motor operating
Motor operating – 2NO for “OPEN” mechanism of the
mechanism (option) three-position
Separate earthing switch: 6 switch-disconnector
The manual operating me- – 2NO and 1NC for 5 Auxiliary contactors
chanisms can be equipped “EARTH” of the motor operating
with motor operating mecha- – 2NO for “OPEN” mechanism for locking
nisms both for the three- the motor
position switch-disconnector 6 Auxiliary switch
7
and for the three-position 7 Switch position
disconnector. 8 indicator for the
three-position
Operating voltages for motor
9 switch-disconnector
operating mechanisms:
8 Locking device
– 24, 48, 60, 110, 220 V DC
(standard for motor
– 50/60 Hz 110 and 230 V AC operating mechanism)
10
Electrical operation: 9 Operating mechanism
for the three-position
• Standard: Remote opera- switch-disconnector
11
tion (applied to terminal) coupled with the motor
• Option: Local operation operating mechanism
by momentary-contact Operating mechanism parts in 10 Shunt release (option)
rotary control switch transformer feeder 11 Motor operating
mechanism

Technical data of the auxiliary switch


Breaking capacity Rated switching capacity
AC operation at DC operation Rated insulation
40 Hz to 60 Hz voltage
250 V AC/DC
Operating Normal Operating Normal current Insulation group
voltage current voltage resistive inductive: C to VDE 0110
T=20 ms
Continuous current
V A V A A 10 A
up to 230 10 24 10 10
Making capacity
48 10 9 50 A
60 9 7
110 5 4
220 2.5 2
Abbreviations:
NO = normally-open contact
NC = normally-closed contact

24 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Indicating and measuring equipment


Short-circuit/earth-fault Verification of safe
indicator (option) isolation from supply Indicating and measuring equipment (examples)
The ring-main feeders can

R-HA41-072b eps
be equipped with a 3-phase Voltage detection systems Mounting locations in
the control board for
short-circuit or earth-fault For voltage detection
1 Short-circuit / earth-
indicator: according to IEC 61 243-5 / fault indicator (option)
• Optical signal when a pre- VDE 0682 Part 415 with:
2 Ready-for-service
selected pickup value is • Standard: HR system 1 indicator (option)
exceeded • Option: LRM system 3 Voltage indicator, HR
• With ring-type sensors system, plugged-in
• Option: LRM system as (standard)
• Display panel, withdraw- CAPDIS-S1 or CAPDIS-S2
able housing, depending
on the type Features of the
• Short-circuit pickup values: HR/LRM system
e.g. 400, 600, 800 or • Voltage indicator 2
1000 A – HR system (standard) or
Option: Remote electrical – LRM system (option)
indication via contact (1NO + • Verification of safe isolation
1NC contact, passing con- from supply phase by
tact), applied to terminal phase through insertion in
each socket pair
Ready-for-service indicator • For continuous operation
(option for three-position
switch) • Safe-to-touch
• Self-monitoring; easy to • Measuring system and 3
read voltage indicator can be
tested
• Independent of tempera-
ture and pressure varia- • Voltage indicator flashes
tions if high voltage is present
• Independent of site altitude • Fixed-mounted capacitive Control board of a ring-main panel
voltage divider in bushings (example)
• Only responds to changes
in gas density Features of CAPDIS-S1, -S2
• Option: Alarm switch • Maintenance-free
• Reset:
R-HA40-032 eps

“1NO contact” manual


• Without auxiliary power • For phase indications
Mode of operation L1, L2 and L3
• Self-checking
For the ready-for-service indi- • Option: With remote
cator, a gas-tight measuring indication of the voltage
box is installed on the inside state (auxiliary power Short-circuit indicator ALPHA M
of the switchgear vessel. required for CAPDIS-S2) (example)
A coupling magnet, which
is fitted to the bottom end Mounting of voltage
6 Measuring box
HA41-2462 eps

of the measuring box, trans- detection systems


mits its position to an outside 6 7 Magnetic coupling
• Standard:
armature through the stain- In all ring-main and 8 8 Red indication:
less steel switchgear vessel. not ready for service
circuit-breaker feeders 7
This armature moves the 9 Green indication:
• Option: ready for service
ready-for-service indicator of
the switchgear. In transformer feeders 9

While changes in the gas Verification of correct ter- Stainless-steel vessel Ready-for-
density during the loss of minal-phase connections filled with SF6 gas, service
gas, which are decisive for gauge pressure indicator
• Verification of correct
the insulating capacity, are 500 hPa at 20 °C
displayed, temperature- terminal-phase connec-
dependent changes in the tions possible by means of Principle of operation of gas monitoring
gas pressure are not. The a phase comparison test with ready-for-service indicator
gas in the measuring box has unit (can be ordered sepa-
the same temperature as rately)
that in the switchgear. • Safe-to-touch handling of
R-HA40-088 eps

The temperature effect is the phase comparison test


compensated via the same unit by inserting it into the
pressure change in both gas capacitive taps (socket
pairs) of the switchgear Voltage indicator, HR system
volumes. (standard)

Siemens HA 41.21 · 2003 25


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Interlocking systems and locking devices


Interlocking of connection Interlocking in circuit-
compartment breaker panel types LS1, Interlocking systems
LS1-U and LT10 (with 3AH5

R-HA41-064c eps
Ring-main and fixed-mounted vacuum
circuit-breaker panel circuit-breaker)
• Access to the cable con- • Option: Logical mechanical
nection compartment interlocking with three-po-
(e.g. for cable testing) is sition switch-disconnector
only possible provided • Earthing of feeder via
that the feeder is isolated three-position switch-
and earthed (three-posi- disconnector in
tion switch-disconnector “EARTHED” position
in “EARTHED” position)
• Option: Closing lock-out Interlocking in circuit-
This prevents the three- breaker panels (with 3AH6
position switch-disconnec- removable vacuum circuit-
tor from being switched breaker)
from “OPEN” to • Option: For 630 A panel
“CLOSED” position, types LS11, LS11-U and
when the cable compart- LT11: Logical mechanical
ment cover is removed interlocking with three-po-
sition switch-disconnector
Transformer panel
• Standard: For 1250 A
• Access to the cable con- panel types LS31, LS31-U,
nection compartment and LS32 and LT31: Logical
to the HV HRC fuse com- mechanical interlocking
partment (e.g. for replace- with three-position
ment of HV HRC fuse disconnector Interlocking for cable compartment cover
links) is only possible pro- Removed cable compartment cover
vided that the feeder is • Logical mechan. interlock- with earthed bus sectionalizer panel
isolated and earthed ing of cable compartment
(three-position switch- cover: Opening of cable
disconnector in compartment cover only
“EARTHED” position) possible provided that the
feeder is earthed
• Option: De-earthing Locking device (option)
lock-out Feeder earthing
R-HA41-081 eps

This prevents the


three-position switch- • Standard: Earthing by
disconnector from being switching of vacuum
switched from position circuit-breaker 3AH6 1) in
“EARTHED” to “OPEN”. position “CLOSED” and
of three-position switch 2)
Switchgear interlocking in position “EARTHED”
• Dependent on the va- • Option: For circuit-breaker
cuum circuit-breaker oper- panel types LS11, LS31
ating mechanism with and LS32: Earthing by
– Spring-operated or means of an additional
– Stored-energy mechanism make-proof earthing
switch at the feeder with
• Option: Switchgear-side inspection window in the
mechanical interlocking cable compartment cover
with three-position
switch-disconnector Locking devices
• Vacuum circuit-breaker The three-position switch-
cannot be closed when disconnector can be locked
three-position switch- Locking device of the detachable lever mechanism
on the operating mechanism e.g. for padlock
disconnector is in the side in any position (option).
“OPEN” position:
– Spring-operated mecha-
nism: Hand crank opening 1) With additional locking device
is blocked – optionally with signalling
– Stored-energy mechanism switch – for securing the
“CLOSED” position of the
with closing solenoid vacuum circuit-breaker for
3AY15 10: Pushbutton feeder “EARTHED”
(S12) operated by mecha- 2) Three-position switch as
nical interlock prevents – Switch-disconnector in panel
continuous command to types LS11, LS11-U and LT11
closing solenoid – Disconnector in panel types
LS31, LS31-U, LS32 and LT31
26 Siemens HA 41.21 · 2003
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

4MC63 three-phase current transformers for panel types LS ... and LT ...
Application
• For circuit-breaker panels

R-HA41-048 eps
type LS ...
• For bus sectionalizer panels
type LT ...
• Option: For ring-main panels
type RK ...

Features
• According to IEC 60 044-1/
VDE 0414 Part 1
• Designed as a three-pole
ring-core current
transformer

R-HA41-044 eps
• Free of dielectrically
stressed cast-resin parts
(due to design)
• Insulation class E
• Inductive type
• Climate-independent 4MC63 53 three-phase
current transformer
• Secondary connection by 4MC63 53 three-phase current transformer
means of a terminal strip on the bushings of the three-position
inside the panel switch-disconnector

Installation
Technical data 4MC63 53 three-phase current transformer
• Arranged outside the switch- for IN < 150 A for IN < 400 A for IN < 1000 A
gear vessel on the bushings for ID = 630 A for ID = 630 A for ID = 1250 A
• Factory-assembled
Primary data
Other designs Max. equipment operating 0.72 kV 0.72 kV 0.72 kV
(option) voltage Um
Rated current IN A 150 100 75 50 400 300 200 1000 750 600 500
Three-phase current transfor-
mers for protection equipment Rated short-duration 3 kV 3 kV 3 kV
power-frequency
based on c.t. operation: withstand voltage
• 7SJ4 protection relay as (winding test)
definite-time overcurrent Rated thermal short-time 25 kA 25 kA 25 kA
protection withstand current Ith
• Definite-time overcurrent Rated continuous thermal 630 A 630 A 1250 A
protection relay, current ID
make SEG, type WIP 1
Transient overload 1.5 x ID / 1 h 2 x ID / 0.5 h 1.5 x ID / 1 h
current
Rated peak withstand unlimited unlimited unlimited
current Idyn

Secondary data
Rated current A 1 0.67 0.5 0.33 1 0.75 0.5 1 0.75 0.6 0.5
Rating VA 5 3.33 2.5 1.67 5 3.75 2.5 5 3.75 3 2.5
Rated current (option) 5A 5A 5A
Current at ID 4.2 A 1.575 A 1.25 A
Protec- Class 10 P 10 P 10 P
tion
Overcurrent factor 10 10 10
core

Other values available on request

Siemens HA 41.21 · 2003 27


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

4MC70 33, 4MC70 31 cable-type current transformers and 4MC70 32 bus-type current transformers
Application
• For circuit-breaker panels

R-HA41-025 eps
4MC70 31 cable-type

R-HA41-049a eps
type LS ...
current transformer

H
• For ring-main panels
type RK ...
• For transformer panels
4MC70 33 cable-type
type TR ...

R-HA41-024 eps
current transformer,
4 different overall heights
Features
• According to IEC 60 044-1/

H
VDE 0414 Part 1
• Designed as a single-pole
ring-core current transformer
• Only for shielded cables
• Climate-independent

R-HA41-027 eps
• Free of dielectrically
stressed cast-resin parts
4MC70 32
(due to design) bus-type
• Insulation class E current transformer

• Inductive type
• Secondary connection by 4MC70 33 cable-type current transformers
means of a terminal strip on the cable at the panel connection
inside the panel

Installation Technical data 4MC70 33 cable-type 4MC70 31 cable-type 4MC70 32 bus-type


current transformer current transformer current transformer
• 4MC70 33 cable-type current
transformer and 4MC70 32
bus-type current transformer Primary data
for panel type LS ... Max. equipment operating 0.72 kV 0.72 kV 0.72 kV
voltage Um
• 4MC70 31 cable-type current
transformer: e.g. for panel Rated current IN A 30 A to 600 A 50 A to 600 A 200 A to 600 A
types RK ..., K ... and TR ... Rated short-duration 3 kV 3 kV 3 kV
power-frequency
• Arranged on the cable at withstand voltage
the panel connection (winding test)
• Transformers mounted on a Rated thermal short-time 25 kA 25 kA 25 kA
supporting plate at our withstand current Ith
factory; final assembly on Rated continuous thermal max. 1.2 x IN max. 1.2 x IN max. 1.2 x IN
the cables on site current ID

Transient overload 1.5 x ID / 1 h or 1.5 x ID / 1 h or 1.5 x ID / 1 h or


current 2 x ID / 0.5 h 2 x ID / 0.5 h 2 x ID / 0.5 h
Rated peak withstand unlimited unlimited unlimited
current Idyn

Secondary data
Rated current 1 A (option: 5 A) 1 A (option: 5 A) 1 A (option: 5 A)
Meas- Class 0.2 0.5 1 1 0.2 0.5 1
uring
Overcurrent factor FS10 (option: FS5) FS5 (option: FS10) FS10 (option: FS5)
core
Rating 2.5 VA to 10 VA 2.5 VA to 10 VA 2.5 VA to 10 VA
Pro- Class 10 P 5P – 10 P 5 P (on request)
tection
Overcurrent factor 10 10 – 10 10
core
Rating 2.5 VA to 10 VA – 2.5 VA to 15 VA
Option: Secondary tap 1:2 1:2 1:2
(e.g. 150 A – 300 A) (e.g. 150 A – 300 A)

Dimensions

* Depending on the core data Overall height H ** mm 50* 100* 170* 285* 89 80 * 150 *

** Available installation height Outside diameter Ø 145 mm 85 mm x 114 mm Ø 125 mm


inside panel types RK or RK1: Inside diameter Ø 55 mm Ø 40 mm Ø 55 mm
Approx. 285 mm, depending on
make, type and cross-section of For cable diameter Ø 50 mm Ø 36 mm Ø 50 mm
sealing end
Other values available on request

28 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

4MA7 block-type current transformers and 4MR voltage transformers


Application
• For billing metering panels
type ME1 ...

R-HA41-060a eps

R-HA41-030a eps
• For bus riser panel
type HF …
• For mounting at the
feeder
4MA7 block-
Features type current
transformer,
• 4MA7 current transformer single-pole
• According to IEC 60 044-1/
VDE 0414 Part 1

R-HA41-029a eps
• Dimensions according to
DIN 42 600 Part 8
• Designed as a single-pole
indoor block-type current
transformer
• Cast-resin insulated 4MR14 voltage
transformer,
• Insulation class E single-pole
• Secondary connection by
4MR voltage transformer and
means of screw-type 4MA7 block-type current transformer installed in
terminals billing metering panel type ME1

4MR voltage transformer


• According to IEC 60 044-2/ Technical data
VDE 0414 Part 2 4MA7 single-pole block-type current transformer 4MR single-pole voltage transformer

• Dimensions according to Primary data Primary data


DIN 42 600 Part 9 (small Max. equipment operating 12 kV 24 kV Max. equipment operating 12 kV
model) voltage Um voltage Um (= 1.2 x UN)
• Designed as an indoor Rated short-duration 38 kV 50 kV Rated voltage UN at max. 3.3/ 3 kV at 10 kV
voltage transformer: power-frequency rated short-duration 3.6/ 3 kV at 10 kV
– Type 4MR, single-pole withstand voltage power-frequency
4.8/ 3 kV at 20 kV
– Option: Type 4MR, two-pole withstand voltage Ud
Rated lightning impulse 95 kV 125 kV 5.0/ 3 kV at 20 kV
withstand voltage 6.0/ 3 kV at 20 kV
• Cast-resin insulated 6.6/ 3 kV at 20 kV
Rated current IN 25 A to 1250 A
• Insulation class E 7.2/ 3 kV at 20 kV
Rated thermal short-time up to 25 kA
10.0/ 3 kV at 28 kV
• Secondary connection by withstand current Ith
11.0/ 3 kV at 28 kV
means of screw-type Rated continuous thermal up to 1.2 x IN
terminals Rated lightning impulse 75 kV
current ID
withstand voltage Up
Rated voltage factor 1.9 x UN
Rated peak withstand max. 2.5 x Ith
(8 h)
current Idyn
Max. equipment operating 24 kV
voltage Um (= 1.2 x UN)
Rated voltage UN at max. 13.8/ 3 kV at 38 kV
rated short-duration 15.0/ 3 kV at 38 kV
power-frequency
17.5/ 3 kV at 50 kV
withstand voltage Ud
20.0/ 3 kV at 50 kV
22.0/ 3 kV at 50 kV
Rated lightning impulse 125 kV
withstand voltage
Rated voltage factor 1.9 x UN
(8 h)

Secondary data Secondary data


Rated current 1 A or 5 A Rated voltage 100/ 3 V
110/ 3 V
Meas- Class 0.2 0.5 1
uring 120/ 3 V
Overcurrent factor FS5 or FS10
core Rated voltage for auxiliary 100/3 V
Rating 10 VA to 15 VA winding (option) 110/3 V
Pro- Class 5 P or 10 P 120/3 V
tection Overcurrent factor 10 Rating 20 VA 50 VA 100 VA
core
Rating 5 VA or 15 VA Class 0.2 0.5 1
Other values available on request Other values available on request

Siemens HA 41.21 · 2003 29


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Cable connection
General features
Cable connection (examples)
• Connecting lugs for sealing ends
arranged one behind the other L3 L2 L1 L3 L2 L1
• Uniform cable connection height

R-HA41-050 eps

R-HA41-051 eps
for the respective panel types
• With cable bracket, e.g. type C40
according to DIN EN 50 024 1
• Access to the cable connection
2 5
compartment only if feeder has
been isolated and earthed 4
3
Special features
– In ring-main panels
– In circuit-breaker panels
– In cable panels
• For thermoplastic-
insulated cables
• For paper-insulated mass-
impregnated cables with Ring-main panel type RK Cable connection compartment with cable
adapter systems Cable connection compartment as delivered sealing ends (options: A, B, C 1) and D 1), see below)
• For connection cross- L1 L1
sections up to 300 mm2 L2 L3 L2 L3
• Cable routing downwards
R-HA41-053 eps

R-HA41-052 eps
– In transformer panels:
• For thermoplastic-
insulated cables
• For connection cross-
sections up to 120 mm2:
Cable lug max. 32 mm wide
6
• For rated normal currents
of 200 A
7
For options see figures
8
Cable cross-sections 9
Panel type Connectable cables x
connection cross-sections
No. x mm2 Transformer panel type TR Cable connection compartment with cable
for rated voltage Cable connection compartment as delivered sealing ends (option: A 2), see below)

12 kV 17.5 kV 24 kV
R-HA41-055 eps

K Standard 1x300 1x300 1x300


on request 2x300 – –
11
K1 2x400 2x400 2x400
L1 L2 L3
RK, K-E 2x300 1x300 1x300
R-HA41-067 eps

RK1, K1-E 2x300 2x300 2x300


LS1 2x300 2x300 2x300
LS11, LS31 2x400 2x400 2x300
LS32 Standard 3x400 3x400 3x300 14
Option 4x300 4x300 –
on request – – 4x300 10 13
ME1-K, ME1-KS 3x400 3x400 3x300
12
1) Only with ring-main panel type RK1
2) Cable clamps with transformer
panels type TR ... partly mounted
underneath the panel in the cable
basement
3) Make Siemens, type 3EK7, Circuit-breaker panel type LS11 Cable connection compartment with cable
other makes on request Cable connection compartment as delivered sealing ends (options: A, B, C and D, see below)
Note
Cable sealing ends and cable clamps Options A Mounted cable clamps 2) C Double cable connection
are not included in the scope of supply B Short-circuit / earth-fault indicator D Suitable for connection of surge arresters 3)

30 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Selection data for various cable sealing ends

Cable sealing end, e.g. for panel types RK..., LS1..., LS11..., LS31..., LS32 Connection height **
Cable sealing ends and TR ...1) (for connection heights of cables see opposite dimension drawings) of cables above
(examples) Make Type Cross-section floor or above
mm2 lower edge of panel:
1 As-delivered condition, prepared
for cable sealing end w 12 kV
2 As-delivered condition, prepared Single-core thermoplastic-insulated cables for < 12 kV (6/10 kV)

HA41-2432b eps
for cable sealing end > 12 kV, w 24 kV,
Euromold 35 MSC 16–300 (500*)
additionally with insulating sleeve
35 MSC (option 3)) 25–300 (500*)
3 Phase L1: AIN 10 25–300 (500*)
Make: Corning Cables (RXS)
Type IAEM 20, ITK / S 212 35–300 (400*)
240 mm2 (20 kV) Pirelli ELTI mb-1C-12 35–240
4 Phase L2: ELTI-1C-12 25–300

785**
Make: Tyco Electronics Raychem Tyco Electronics IXSU-F 16–300 (500*)
Type EPKT 24 C / 1X, Raychem TFTI 25–300 (400*)
185 mm2 (24 kV),
as shrink-on sealing end, EPKT 1) 16–300
for severe ambient conditions Corning Cables (RXS) IAEM 10 25–300
Panel type RK ...
5 Phase L3: IAES 10 25–300 (500*)
Make: Pirelli 3M 92-EP 6xx-1 35–300 (400*)

HA41-2433b eps
Type ELTI mb-1C-2h-C-T3,
240 mm2 (24 kV) ABB Energiekabel SEHDI 10.2 35–300 (500*)
Nkt cables TI 12 25–240
AV 10 C 25–300 (500*)

645**
AV 10 E 25–300 (500*)
6 As-delivered condition, prepared
for cable sealing end Single-core thermoplastic-insulated cables for > 12 kV to < 24 kV (12/20 kV)
7 Phase L1: Euromold 35 MSC 25–70 Panel type LS1 ...
Make: Corning Cables (RXS) 35 MSC (option 3)) 25–185

HA41-2434a eps
Type IAEM 20, Euromold 36 MSC 2) 95–300 (500*)
95 mm2 (20 kV) 36 MSC (option 3)) 95–300 (500*)
8 Phase L2: AIN 20 25–300 (630*)
Make: Tyco Electronics Raychem
Type TFTI/5131, ITK / S 224 35–240
95 mm2 (24 kV), Pirelli ELTI mb-1C-24 35–240

480
as push-on sealing end Pirelli ELTI-1C-24 25–300
9 Phase L3: Tyco Electronics IXSU-F 25–300 (500*)
Make: Euromold Raychem TFTI 25–300 (400*) Panel type LS11 ...
Type AIN, 95 mm2 (24 kV)
EPKT 16–300 (500*)
HA41-2435a eps

Corning Cables (RXS) IAEM 20 25–300


IAES 20 25–300 (500*)
3M 93-EP 6xx-1 25–300 (400*)
ABB Energiekabel SEHDI 20.2 35–300 (500*)
Nkt cables TI 24 25–240
~380

AV 20 E 25–300 (500*)
AV 10 E 25–300 (500*)
Panel type TR ...
10 As-delivered condition, prepared
for cable sealing end w 12 kV Three-core thermoplastic-insulated cables for < 12 kV (6/10 kV)
11 As-delivered condition, prepared Euromold AIN 10 25–300
for cable sealing end > 12 kV, w 24 kV, (500*) Note
additionally with insulating cap
SR-DI 12 35–300 Depending on make and
12 Phase L1: (500*) type, the termination of the
Make: Corning Cables (RXS) Pirelli ELTI-3C-12 25–300 cable sealing end (= shield
Type IAES 20, earth) for the 3-core thermo-
240 mm2 (20 kV) Tyco Electronics IXSU-F 16–300
Raychem (500*) plastic-insulated cable and
13 Phase L2: the fitted cable clamp (option)
Make: Pirelli may be located underneath the
Type ELTI 1C-24-D-T3, Three-core thermoplastic-insulated cables for > 12 kV to < 24 kV (12/10 kV) panel in the cable basement.
240 mm2 (24 kV), This must be taken into
Euromold SR-DI 24 2) 35–300 (500*)
as indoor sealing end, account in panels with
for severe ambient conditions Corning Cables (RXS) GHKI 25–300 (500*) floor cover (option).
14 Phase L3:
Make: Euromold
Type AIN 20,
240 mm2 (24 kV) 1) Transformer panel types TR ...: 3) Cable sealing **Due to the installation of
– Lower edge of sealing end below panel end type with 4MA cast-resin insulated
– Cable lugs of sealing ends up to 32 mm width insulation shields block-type current trans-
– Owing to the various sealing end lengths, some of * On request: formers in panels RK1
the mounted cable clamps are underneath the panel Max. connection and LS1, the connection
2) Circuit-breaker panel types LS11, LS31 and LS32: cross-section of height of the cables is
– Lower edge of sealing end below panel cable sealing end reduced to 380 mm
types

Siemens HA 41.21 · 2003 31


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Low-voltage equipment
Low-voltage niche Electronic functions
(standard) Low-voltage niche (examples)
Multifunction protection
• Screwed-on cover as relay SIPROTEC 4 7SJ62 13
1 LED indications
– Cover (available mounting or 7SJ63 with the following 5
1 2 LCD
depth behind of features:
approx. 184 mm) 2 6 3 Navigation keys
1 User-programmable
– Frame cover, approx. LEDs with application- 3 7 4 Function keys
46 mm deeper version specific label, for display- 5 Option:
(available mounting 4 8 Short-circuit/
ing any desired process earth-fault
depth behind of and equipment data indicator
approx. 230 mm)
2 LCD for process and 6 Frame cover of
• For accommodation of equipment data, e.g. for: low-voltage niche
9
terminals and standard – Measuring and metering (can be unscrewed)

R-HA41-062a eps
protection devices, e.g. values 7 Momentary-contact
in circuit-breaker panels – Binary information on the rotary control switch
combined with frame ON-OFF for motor
status of switching point operating mechanism
cover for panels and device In bus sectionalizer panel type LT11 of the three-position
– Type LS1: Protection – Protection data (low-voltage niche closed) switch-disconnector
relays (with max. 75 mm – General indications 8 Local-remote switch
wide mounting frame), – Alarms for three-position
e.g. type 7SJ45, 7SJ46 switch-disconnector
and 7SJ60, 3 Keys for navigation in 10
14 9 Control board
option: Protection relay menus and for entering
values 10 Low-voltage niche
make SEG open
– Type LS11: Protection 4 Four user-programmable 11 11 Option:
relays (with max. 150 mm function keys for Installed equipment
wide mounting frame), frequently performed 12 Panel front
e.g. type 7SJ4..., 7SJ60 actions
and 7SJ61 (on request 13 Option:
9 Multifunction
type 7SJ62), option: Pro- Low-voltage cables protection relay
tection relay make SEG

R-HA41-083 eps
• Control cables of the SIPROTEC 4 7SJ61
• For bus wires and/or con- on swing-out frame
panel to the low-voltage
trol cables; niche open at compartment are con- 14 Option:
the side to the adjacent Protection device
nected via multi-pole, In circuit-breaker panel type LS1 make SEG,
panel coded module plug (low-voltage niche open) type WIC
• Safe-to-touch, separated connectors
from high-voltage part of • Option: Plug-in bus wires
the panel from panel to panel inside
• Degree of protection the low-voltage niches, 10
IP 3X (standard) optionally in separate
cable duct on the panel
11
Low-voltage
compartment
(option)
• Heights 12
– 350 mm
– 550 mm
R-HA41-059a eps

• Available mounting depth:


442 mm
• For mounting on the In billing metering panel type ME1
panel (low-voltage niche open)

• Dependent on the pa-


nel-specific scope of the
secondary equipment Low-voltage compartment (option)
• For accommodation of pro- SIPROTEC 4
tection, control, measuring 1 7SJ61:
and metering equipment, 1 LED indications
2
e.g. multifunction protecti- 2 LCD
on relay SIPROTEC 4 type 3
R-HA41-058 eps

3 Navigation keys
7SJ62/ 7SJ63 or protecti-
on relay make SEG 4 4 Function keys

• For 750 mm wide panel On circuit-breaker panel type LS1


types LS31..., LS32 and for additional low-voltage equipment
LT31

32 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Dimensions

Ring-main panels, transformer panels

* * 442**

350*
~184**

360
1750

1750

785***
187.5 187.5
HA41-2407b eps

20 Ring-main
panels
375 500 150 205 210 210
Type RK Type RK1 1050
1080

*
~184**
360
1750

HA41-2408b eps

1)
Ring-main panel
20

for panel combinations


375 150
1050
Type RK-U
1080

* *
~184**
360

1) Location of voltage transformer


in left-hand panel,
e.g. in panel type
LT10 or LT11
* Option:
1750

1750

Low-voltage compartment
available in two heights:
350 mm or 550 mm
** Available mounting depth
for low-voltage equipment
*** For panel type RK1 the cable
HA41-2409b eps

connection height is reduced


~380

187.5 187.5 to approx. 380 mm for panel


20

Transformer version with 4MA block-type


panels current transformer
375 500 150 205 210 210
Type TR Type TR1 1050
1080

Siemens HA 41.21 · 2003 33


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Dimensions

Cable panels

* * 442**

350*
~184**

360
1750

1750

785
187.5 187.5
HA41-2411b eps

20
Cable panels
375 500 150 205 210 210
Type K Type K1 1050
1080

* *
~184**
360
1750

1750

785

187.5 187.5
HA41-2412b eps

Cable panels
20

(with additional make-proof


earthing switch)
375 500 150 205 210 210
Type K-E Type K1-E 1050
1080

* Option:
Low-voltage compartment
available in two heights:
350 mm or 550 mm
** Available mounting depth
for low-voltage equipment

34 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Dimensions

Circuit-breaker panels

* 442**

350*
~184**

360
~230**
1750

645***

562.5
HA41-2413c eps

Circuit-breaker panel
20

630 A
with 3AH5 1)
750 150 205 210 210
Type LS1 1050
1080

* *
~184**
360

~230**
1750

1750

2)
HA41-2414d eps

480

390 110 390 110 Circuit-breaker panels


20

630 A
with 3AH6 1)
750 750 150 205 210 210
Type LS11 (with make- Type LS11 (without 1050
proof earthing switch) earthing switch) 1080

* * 1) Type designation of the


vacuum circuit-breaker
~184** 2) Option: Inspection window
360

~230** 3) Option: With make-proof


earthing switch

* Option: Low-voltage compartment


available in two heights:
350 mm or 550 mm
** Available mounting depth
1750

1750

for low-voltage equipment


– Approx. 184 mm with cover
– Approx. 230 mm with extended
2) 3) frame cover
*** The cable connection height is
reduced to approx. 380 mm for
HA41-2470b eps

panel version with 4MA block-type


480

390 110 390 110 110 current transformer


20

750 875 150 205 210 210


Circuit-breaker panels
Type LS31 3) (for connection Type LS32 3) (for connection 1050
1250 A
of max. 2 cables) of 3 cables) 1080
with 3AH6 1)

Siemens HA 41.21 · 2003 35


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Dimensions

Bus sectionalizer panels 630 A with bus riser panel

* 442**

350*
~184**

360
~230**
1750

HA41-2416b eps

Bus sectionalizer panel


20
630 A
with 3AH5 1)
1125 150
Type LT10 + type HF 1050
1080

*
~184**
360

~230**
1750

HA41-2417c eps

Bus sectionalizer panel


630 A
20

with 3AH6 1)
1125 150
Type LT11 + type HF 1050
1080

*
~184**
360

~230**

1) Type designation of the


vacuum circuit-breaker
1750

* Option:
Low-voltage compartment
available in two heights:
350 mm or 550 mm
** Available mounting depth
for low-voltage equipment
HA41-2471a eps

– Approx. 184 mm
Bus sectionalizer panel with cover
20

1250 A – Approx. 230 mm


with 3AH6 1) with extended frame cover
1125 150
1050
Type LT31 + type HF
1080

36 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Dimensions

Bus sectionalizer panels

* * 442**

350*
~184**

360
1750

1750

HA41-2419b eps

20
Bus sectionalizer panels
without transformers
750 750 150
1050
Type LT2 Type LT22
(= type RK-U with type RK-U) 1080
(= type RK-U with type HF)

* *
~184**
360
1750

1750

HA41-2420b eps

20

Bus sectionalizer panels


with transformers
750 750 150
Type LT2-W Type LT22-W 1050
1080

* Option:
Low-voltage compartment
available in two heights:
350 mm or 550 mm
** Available mounting depth
for low-voltage equipment

Siemens HA 41.21 · 2003 37


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Dimensions

Billing metering panels

* 442**

350*
~184**

360
1750

HA41-2421b eps

20

Billing metering panel


(standard)
750 150
Type ME1 1050
1080

* *
~184** ~184**
360

360
1750

1750
HA41-2422b eps

HA41-2469 eps

480
375
20

20

750 150 750 150 250 250 250


Type ME1-S (for busbar 1050 Type ME1-K 1050
connection) 1080 (for cable connection) 1080
Billing metering panels
for busbar and cable
* connection
~184**
360
1750

* Option:
Low-voltage compartment
available in two heights:
HA41-2423b eps

Billing metering 350 mm or 550 mm


20

panel for ** Available mounting depth


2nd current transformer set for low-voltage equipment
750 150
Type ME1-H 1050
1080

38 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Dimensions

Busbar voltage metering panels, busbar earthing panels, bus riser panels

* *
~184** ~184**

360
360

1750
1750

HA41-2426b eps
HA41-2425b eps

Busbar
earthing

20
20

panels
375 150 500 150
1050 1050
Type SE1 Type SE2
without transformers 1080 1080
with voltage transformers

* *
~184** ~184**
360

360
1750

1750

HA41-2428b eps
HA41-2427b eps

1)
Bus
20

20

riser
panels
375 150 375 150
1050 1050
Type HF Type HF
1080 1080
without transformers with transformers

* * 442**
350*

~184**
360
1750

1750

1) Location of voltage
transformer in
left-hand panel
* Option:
Low-voltage compartment
available in two heights:
HA41-2424b eps

~ 415

Busbar 350 mm or 550 mm


20

voltage metering ** Available mounting depth


panels for low-voltage equipment
375 500 150
Type ME3 Type ME31-F 1050
with fuses 1080

Siemens HA 41.21 · 2003 39


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Dimensions

Floor openings (dimensions in red) and fixing points

375 375
1 14 x 28 14 x 28

187.5 For pa- 187.5 For pa-


20

20
150
150

60

60
58

58
nel type nel type 1 Wall distance
80

80
For panel width 375 mm

2 Fixing frame (base)


205

2 RK RK-U of an individual panel or panel block


K ME3
385

385
210

K-E HF 3 Floor opening for high-voltage cables and,


3 6 where applicable, control cables; in panel
TR SE1
857
1000
850

857
1000
850
types LS11, LS31 and LS31-K: floor opening
210

4 also possible below floor cover


58 58
385

385
4 Position of the led-in cables for the feeder
5 187.5
5 Fixing points
110

110

6 Floor opening if required for panels


HA41-2398 eps

HA41-2399 eps

without cable connection


18 169.5 28 x 14 18 169.5 28 x 14
60 255 60 255

With cable connection Without cable connection

500 500
1 14 x 28 14 x 28

250 For pa- 250 For pa-


20

20
150
150

60

60
58

58

nel type nel type


80

80
For panel width 500 mm

RK1
205

2 RK1-U
K1+ ME31-F
385

385

K1-E
210

SE2
3 TR1 6
857
1000
850

857
1000
850
210

4
58 58
385

385

5 187.5
110

110
HA41-2400 eps

HA41-2401 eps

18 232 28 x 14 18 232 28 x 14
60 380 60 380

With cable connection Without cable connection

750 750
1 14 x 28 14 x 28

187.5 375 For pa- For pa- 187.5 375 For pa-
20
20

150
150

60
60

58
58

nel type nel type nel type


80
80
For panel width 750 mm

LS11 LS1-U
205

205

2 LS1
(Dim. a LS11-U
LS31 LT10
385
385

= 562.5)
210

210

3 3 6 LT11
ME1-K LT2
857
1000
850
857
1000
850
210

210

(Dim. a 368 LT2-W


4 = 375) LT22
58 58
385
385

LT22-W
HA41-2403a eps

5 a ME1-KS 390 110 ME1


(Dim. a ME1-S
= 375) ME1-H
110

110
HA41-2404 eps
HA41-2402 eps

18 169.5 375 18 169.5 375


LS31-U
28 x 14 For dimensions not shown 28 x 14
LT31
60 630 see illustration on the left 60 630

With cable connection With double cable connection Without cable connection

875
1 14 x 28

187.5 500 For pa-


20
150

60
58

nel type
80
For panel width 875 mm

LS32
205

2
385

210

3
857
1000
850
210

4
368 58
385

5 390 110 110


110
HA41-2472a eps

18 169.5 500 28 x 14
60 755

With cable connection

40 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Standards

Standards, specifications, guidelines


Standards Overview of standards (December 2002)
The SIMOSEC switchgear IEC standard VDE standard EN standard
complies with the relevant up to now current in future current in future current
standards and specifications
Switchgear IEC 60 694 * IEC 60 694 * IEC 62 271-1 VDE 0670 Part 1000 VDE 0671-001 EN 60 694
applicable at the time of
type tests. IEC 60 298 * IEC 60 298 * IEC 62 271-200 VDE 0670 Part 6 VDE 0671-200 EN 60 298
Devices 1) IEC 60 056 ** IEC 62 271-100 IEC 62 271-100 VDE 0670 P. 101 to 106 VDE 0671-100 EN 60 056
In accordance with the
harmonization agreement
2) IEC 60 129 ** IEC 62 271-102 IEC 62 271-102 VDE 0670 Part 2 VDE 0671-102 EN 60 129
reached by the countries of the 3) IEC 60 265-1 * IEC 62 265-1 * IEC 62 271-103 VDE 0670 Part 301 VDE 0671-103 EN 60 265-1
European Community, their 4) IEC 60 420 ** IEC 62 271-105 IEC 62 271-105 VDE 0670 Part 303 VDE 0671-105 EN 60 420
national specifications 5) IEC 61 243-5 IEC 61 243-5 IEC 61 243-5 VDE 0682 Part 415 VDE 0682 Part 415 EN 61 243-5
conform to the IEC standard. 6) IEC 60 282 IEC 60 282 IEC 60 282 VDE 0670 Part 4 VDE 0670 Part 4 EN 60 282
Degree of IEC 60 529 IEC 60 529 IEC 60 529 VDE 0470 Part 1 VDE 0470 Part 1 EN 60 529
protection
Insulation IEC 60 071 IEC 60 071 IEC 60 071 VDE 0111 VDE 0111 EN 60 071
Current IEC 60 044-1 IEC 60 044-1 IEC 60 044-1 VDE 0414 Part 1 VDE 0414 Part 1 EN 60 044-1
transformers
Voltage IEC 60 044-2 IEC 60 044-2 IEC 60 044-2 VDE 0414 Part 2 VDE 0414 Part 2 EN 60 044-2
* In future, all standards for switching transformers
devices and switchgear will be
summarized in IEC 62 271 1) Circuit-breaker 3) Switch-disconnector 5) Voltage detection systems
** Withdrawn standard 2) Disconnector and earthing switch 4) Switch-disconnector / fuse 6) HV HRC fuses
combination

Type of service location Table – Insulating capacity Insulating capacity


SIMOSEC switchgear can be Rated voltage (rms value) kV 7.2 12 15 17.5 24 • The insulating capacity is veri-
used as an indoor installation in fied by testing the switchgear
accordance with IEC 61 936 Rated short-duration power-frequency withstand voltage (rms value) with rated values of short-
(Power installations exceeding – Across isolating distances kV 23 32 39 45 60 duration power-frequency
1 kV AC) and VDE 0101 withstand voltage and light-
– Between phases and to earth kV 20 28 36 38 50
• Outside lockable electrical ning impulse withstand volt-
service locations at places Rated lightning impulse withstand voltage (peak value) age according to IEC 60 694/
which are not accessible to – Across isolating distances kV 70 85 105 110 145 VDE 0670 Part 1000 (see
the public. Enclosures of table “Insulating capacity”
– Between phases and to earth kV 60 75 95 95 125
switchgear can only be • The rated values are referred
removed with tools. to sea level and to normal
Correction factor a for the site altitude atmospheric conditions
• Inside lockable electrical
service locations. A lockable (1013 hPa, 20 °C, 11 g/m3
For site altitudes 1 humidity in accordance with
HA40-2037 eps

electrical service location is


a place outdoors or indoors
above 1000 m, the IEC 60 071 and VDE 0111).
adjacent correction 0,9
Correction factor a

that is reserved exclusively for • The insulating capacity


factor a is recom-
housing electrical equipment 0,8 decreases with increasing
mended, depend-
and which is kept under lock altitude.
ing on the actual
and key. Access is restricted 0,7 For site altitudes above
site altitude above
to authorized personnel and 1000 m (above sea level)
sea level. 0,6
persons who have been prop- the standards do not provide
erly instructed in electrical any guidelines for the insula-
engineering. Untrained or 0,1 tion rating. Instead, special
unskilled persons may only regulations apply to these
0
enter under the supervision 0 1000 2000 3000 4000 5000 altitudes.
of authorized personnel or Site altitude in m above sea level
properly instructed persons. Site altitude
As the altitude increases, the
Terms Rated short-duration power-frequency withstand voltage to be selected
insulating capacity of insulation
“Make-proof earthing switches” Rated short-dur. power-fre. withstand volt. (IEC 60 694 / VDE 0670 Part 1000) in air decreases due to the
W
are earthing switches with 1.1 · a decreasing air density.
short-circuit making capacity For SIMOSEC switchgear the
Rated lightning impulse withstand voltage to be selected
according to decreasing insulating capacity
– IEC 62 271-102 Rated lightning impulse withstand volt. (IEC 60 694 / VDE 0670 Part 1000)
W must be taken into account
and 1.1 · a
for site altitudes above 1000 m
– VDE 0670 Part 2/ EN 60 129 (above sea level), see also
Example: Result:
IEC 60 694 / VDE 0670
3000 m site altitude above sea level According to the above Part 1000.
17.5 kV switchgear rated voltage table, a switchgear for a
95.0 kV rated lightning impulse withstand voltage rated voltage of 24 kV is
to be selected.
Rated lightning impulse 95 kV = 118 kV
withstand volt. to be selected 1.1 · 0.73

Siemens HA 41.21 · 2003 41


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Standards

Standards, specifications, guidelines


Cable testing Tests for resistance to • Definitions of criteria: Climate and ambient
• For circuit-breaker and internal arc faults – Criterion 1 conditions
switch-disconnector feeders • Safety of operating personnel Correctly secured doors, SIMOSEC switchgear may be
ensured by tests to verify re- shutters etc. must not open used, subject to possible addi-
• DC voltage test – Criterion 2
sistance to internal arc faults tional measures – e.g. panel
before the test: Parts of enclosed heaters or floor covers –
• Internal arc tests in accord- switchgear which may cause
Remove or disconnect any ance with IEC 60 298 / VDE under the following ambient
a hazard must not fly off conditions and climate classes:
voltage transformers at the 0670 Part 6 * by agreement – Criterion 3
cable connection in between operator and manu- No holes in the freely • Ambient conditions
SIMOSEC switchgear. facturer accessible external parts of – Natural foreign materials
SIMOSEC switchgear for • Internal arc tests performed in the enclosure as the result of – Chemically active pollutants
rated voltages up to 24 kV accordance with IEC 60 298, burning in or tearing open – Small animals
can be subjected to cable Appendix AA / VDE 0670 – Criterion 4 • Climate classes
tests at a max. DC test Part 6, Appendix AA * Vertically arranged The climate classes are
voltage of 96 kV (when indicators must not ignite classified according to
switchgear is new) or 70 kV. • The possibility of arc faults
– Criterion 5 IEC 60 721-3-3
The voltage at the busbar in SIMOSEC switchgear is Horizontally arranged
may be 24 kV in this case. much less due to: indicators must not ignite SIMOSEC switchgear is largely
– Metal-enclosed and gas- – Criterion 6 insensitive to climate and
Test voltages: insulated switching functions ambient conditions by virtue of
The effectiveness of the
Rated Max. test (e.g. of three-position earth connection must not the following features:
voltage voltage applied switch-disconnector and be detrimentally influenced • No cross insulation for
to cable 3AH5 vacuum circuit-breaker) isolating distances between
0.1 Hz acc. Standard – Logical arrangement of In the event of an arc fault at
the cable connection, pressure phases
to in many operating mechanism
IEC com- elements and mechanical relief is effected to the rear and • Metal enclosure of switching
panies upwards. devices (e.g. three-position
interlocks
AC DC DC switch) in gas-filled stainless-
– Short-circuit-proof feeder For free-standing switchgear a
kV kV kV kV earthing by means of the pressure-relief duct fitted at the steel switchgear vessel
12 19 24 48 three-position switch- rear is optionally available up to • Dry-type bearings in
24 38 48 70 disconnector 20 kA. operating mechanism
• Essential parts of the operat-
For cable testing, the ing mechanism made of
installation and operating corrosion-proof materials
instructions applicable to
• Use of climate-independent
SIMOSEC switchgear and
three-phase current trans-
the standards IEC 60 298 /
formers
VDE 0670 Part 6 – Section
5.107 * must be observed.

* Standards see page 41

42 Siemens HA 41.21 · 2003


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Standards

Standards, specifications, guidelines


Protection against solid IEC 60 529 and EN 60 529: Notes
foreign bodies, electric shock
Type of protection Degree of protection If not stated otherwise on
and ingress of water
the individual pages of this
SIMOSEC switchgear fulfills catalog, we reserve the right
acc. to the standards * to include modifications, espe-
I P 2X
ss cially regarding the stated val-
IEC 60 694 VDE 0670 Part 1000
EN 60 694 ues, dimensions and weights.
Protection against solid foreign bodies
IEC 60 298 VDE 0670 Part 6 Protected against the penetration Drawings are not binding.
IEC 60 529 EN 60 529 of solid foreign bodies, diameter W 12.5 mm All product designations used
Protection against electric shock are trademarks or product
Protected against access to dangerous parts names of Siemens AG or
the following degrees of by means of a finger (the distance between other suppliers.
protection **: a test finger with a diameter of 12 mm
to dangerous parts must be sufficient) If not stated otherwise, all
Degree of Type of dimensions in this catalog are
protection protection Protection against the ingress of water given in mm.
No definition
IP 2X Enclosure of live
(standard) parts under
high-voltage
Compartments I P 3X
IP 3X Enclosure of live ss
(option) parts under high-
voltage in switchgear Protection against solid foreign bodies
Protected against the penetration
with locking device
of solid foreign bodies, diameter W 2.5 mm
IP 3XD Enclosure of live
(on parts under high- Protection against electric shock
request) voltage in switchgear Protected against access to dangerous parts
with locking device by means of a wire (the distance between a test
rod with a diameter of 2.5 mm and a length of
IP 65 Metal enclosure 100 mm to dangerous parts must be sufficient)
of gas-filled
switchgear vessels Protection against the ingress of water
No definition
Type of installation:
Wall-standing arrangement
I P 3 XD
sss

Protection against solid foreign bodies


Protected against the penetration
of solid foreign bodies, diameter W 2.5 mm
Protection against the ingress of water
No definition

Protection against electric shock


Protected against access to dangerous parts
by means of a wire (the distance between a test
rod with a diameter of 1 mm and a length of
100 mm to dangerous parts must be sufficient)

IP 65
ss

Protection against solid foreign bodies


Dust-proof: no penetration of dust
Protection against electric shock
Protected against access to dangerous parts Responsible for
by means of a wire (test probe with a diameter of 1 mm
may not penetrate) Technical contents:
Protection against the ingress of water Christoph Maul
Protected against water jets, Siemens AG, Dept. PTD M2 S2
water which is directed towards Erlangen
the enclosure from any direction
may not have a damaging effect
General editing:
Gabriele Pollok
Siemens AG, Dept. PTD CC T
Erlangen

* Standards see page 41 Printed in Germany


KGK 06.03 10.0 VO/- 40 En 100653
** For explanations 6101/D6278
see adjacent table
Siemens HA 41.21 · 2003 43