33-402B
242 kV Type PMRI
· ASME pressure vessel certification for unfired
pressure vessels
· 3-cycle interrupting time
· single self-blast interrupter per phase
· three tank construction
· exterior bushing current transformers
· control cabinet houses the mechanism, current
transformer terminal blocks and the electrical
control components
· porcelain or composite bushings meet or exceed all
applicable ANSI and NEMA design specifications
· isolated gas systems provided per pole with mini-gas
monitor and pressure gauge
· design tested to meet or exceed ANSI standards
Standard Features
· dead tank design
· HMB-2S hydraulic spring operating mechanism
· independent pole operating capability
Shipping and Installation
The 242PMRI power circuit breaker is shipped fully assembled. By extending the breaker legs, mounting
the breaker on the pad and adding the required quantity of SF6 gas, the breaker is ready for testing and
service.
DIMENSION IN INCHES
A B C D E F G H I J K L M N O
171 94½ 83½ 83½ 70 54 52 19 57-7/8 62-7/8 102 159 170¼ 178 23
DIMENSION IN INCHES
P Q R S T U V W X Y Z AA
106 35 101 81¾ 68 12 61-7/16 76¾ 16-7/16 156 200¼ 102½
60 Hz BIL Chopped
Maximum Continuous Interrupting Freq. KV Wave kV Crest
Breaker kV, RMS A, RMS kA, RMS kV Crest 2µ 3µ
1200
2000 20 425 900
242PMRI 242 1160 1040
3000 40 460* 1050*
4000
* IEC performance option.
2.0 6.0
Current (kA)
Voltage (pu)
3.0
1.0
Random closing
50 -3.0
50 (worst case)
-1.0
Time (ms)
-6.0
-2.0
1.0 3.0
Greensburg, PA 15601 Synchronous
Phone: (724) 838-5204 50
-3.0
50 Closing
Fax: (724) 838-5299 -1.0
Time (ms)
-6.0
www.abbhvsg.com -2.0
Time (ms)
June 2001