You are on page 1of 2

CHS Controls AB

Florettgatan 33
SE-254 67 Helsingborg, Sweden
Tel +46 42 38 61 00, Fax +46 42 38 61 29
chs@chscontrols.se
www.chscontrols.se

Vacuum Circuit Breakers VCP-T Drawout Medium


Product Focus Voltage Vacuum
Circuit Breakers
Up to 15 kV
Up to 25 kA

Small Without Compromise


Introducing the VCP-T drawout medium voltage circuit
breaker and cassette. Designed for use where space is at
a premium, VCP-T is ideal for applications such as power
houses, shipboard use, engine generators, restricted
access locations, and low profile areas.

● 60% smaller than comparable breakers


● 50% lighter than comparable breakers
● One compact footprint through 15 kV
● Reduction of installed space
● Reduced material and shipping costs
● Reduced installation space and weight
● Installation / startup time savings
● 3-cycle (50 ms) interrupting time
● Mechanical endurance up to 20,000 operations

True Metal-Clad Drawout Circuit Breaker Value Added Flexibility


VCP-T delivers all the features normally associated with a The VCP-T design offers unmatched flexibility, even after
true drawout metal-clad circuit breaker. installation. VCP-T simplifies design, installation and use.

● Three position drawout (Disconnect, Test, Connect) ● Thru-the-door or closed door operation
● Metal-clad insulation/isolation ● Common family of accessories
● Two step stored energy mechanism ● Field-installable accessories
● O - 0.3s - CO - 15s - CO ● Labeled and dedicated secondary contacts
● Spring loaded multi-finger primary disconnects ● Clear and concise operating panel
● Silver plated fixed primary cassette stabs ● Front access to mechanism/accessories
● Automatic steel primary safety shutters ● Visible contact erosion indicator
● Tested and proven to ANSI C37.09 ● Optional integral trip unit
● UL Listed and CSA witnessed ● One compact drawout cassette size
VCP-T Drawout Vacuum Circuit Breakers
VCP-T Features Available VCP-T Drawout Circuit Breaker and Cassette Dimensions in inches (mm)
Feature Standard Optional Top View Top View
Metal-Clad Insulation / Isolation ➀
Spring Loaded Primary Finger Disconnect
Silver Plated Primary Cassette Stabs
Manual Charging ➁
Electrical Motor Charging ➂
Integral Charging Handle
Auxiliary Switch (5a/5b) ➃
Mechanical Operations Counter
24, 48, 125 & 250V DC, 120 & 240V AC Control
Shunt Trip
Shunt Trip (2nd) ➄
Spring Release ➄
Undervoltage Release ➄
“ON” and “OFF” Pushbuttons
“ON” and “OFF” Pushbutton Cover ➅
Prevent Close Cover ➆
Key Interlock (Ronis, Castell, Kirk) ➇
Integral Lifting Means ➈
Through or Closed Door Operation
Identified / Dedicated Secondary Contacts
Secondary Umbilical Cord
Two Step Stored Energy Mechanism
Side View Side View
O - 0.3s - CO - 15s - CO
Anti-Pump VCP-T Breaker Ratings (ANSI C37.04 and C37.09)
Trip Free Identification Rated Values
Latch Check Switch Circuit Rated Insulation Level Continuous Short ➀ Short Mechanical Approx.
Breaker Maximum Current Circuit Circuit Endurance Weight
Visible Contact Erosion Indicator Type Voltage Power Impulse Breaking Making
Visible Contact Wipe Indicator Frequency Withstand Current Current
C-O
Drawout (Disconnect, Test and Connect) kV rms kV rms kV Peak Amperes kA rms kA Peak Operations (pounds)

Interlock 2 and 3 Breakers 600 20000 237


50 VCP-T16 4.76 19 60 800 16 42 20000 237
Integral Microprocessor-based Trip Unit 1200 10000 239
➀ 11 gauge grounded steel barrier ➂ Includes shunt trip and spring 600 10000 243
➁ Includes shunt trip release, field installable 50 VCP-T20 4.76 19 60 800 20 52 10000 243
➄ Field installable, viewed through ➃ Heavy duty, double break, wipe type 1200 10000 245
viewing window, maximum 3 devices - for customer use 249
600 10000
any combination ➆ Prevents access to “ON” pushbutton - 50 VCP-T25 4.76 19 60 800 25 65 10000 249
➅ Limits access to pushbuttons, metal used in conjunction with pushbutton 1200 10000 251
or plastic cover
➈ Used with standard lifting sling ➇ Prevents breaker from closing 600 20000 238
75 VCP-T16 8.25 20 60 800 16 42 20000 238
1200 10000 240
Optional Digitrip Trip Units 600 10000 244
75 VCP-T20 8.25 20 60 800 20 52 10000 244
1200 10000 246
● RMS Sensing ● Model 520V
600 10000 250
– Basic Protection 75 VCP-T25 8.25 20 60 800 25 65 10000 250
1200 10000 252
● Microprocessor- (LSIG)
600 10000 239
Based 150 VCP-T16 15 36 95 800 16 42 10000 239
● Model 1150V 1200 10000 241

● Self-Powered – Advanced Protection 600


800
10000 245
150 VCP-T20 15 36 95 20 52 10000 245
(LSIG) 1200 10000 247

● Local Testing – Metering and 600 10000 251


150 VCP-T25 15 36 95 800 25 65 10000 251
Communications 1200 10000 253

➀ Also 2 Second Short Time Current Rating

Eaton Corporation
CHS Controls AB
Cutler-Hammer business unit
Florettgatan 33
1000 Cherrington Parkway
SE-254 67 Helsingborg, Sweden
Moon Township, PA 15108
Tel +46 42 38 61 00, Fax +46 42 38 61 29
United States
chs@chscontrols.se
tel: 1-800-525-2000
www.chscontrols.se
www.cutler-hammer.eaton.com

© 2002 Eaton Corporation


All Rights Reserved
Printed in USA
Form No. SA01301002E / CSS 19377
July 2002

You might also like