Professional Documents
Culture Documents
Poonam Kaur
Lecturer
EE Department
Baddi University
What is a circuit breaker?
A circuit breaker is an automatically-operated
electrical switch.
Overload:
An overload current is where too much current is drawn down an
electrically healthy circuit e.g. too many appliances are plugged in;
there is no fault in the circuit. A properly designed circuit will
interrupt an overload before any damage is done to the circuit.
Short Circuits
This is where a fault of negligible impedance (resistance) occurs
between live conductors. The value of current, which will flow, will
depend on where the fault occurs.
Circuit Breakers
10kV Supply
MCB Tripping:
Thermal Tripping
Magnetic Tripping
Types of MCB
MCB Characteristics
Thermal tripping:
In this type of tripping mechanism the current is passed through a bimetal strip
connected in series with a magnetic coil.
Magnetic tripping:
When a short circuit occurs, the heavy current in the magnetic coil produces a
strong magnetic field which instantly opens the breaker
Arc Extinction:
Facilitated by guiding the arc on splitter plates .The metal splitter plates increase
the length of the arc, splits it up, cools it.
MCB Characteristics
Thermal-Magnetic Tripping
Arc Extinction
Advantages of MCB’s over Fuses
Advantages of MCB’s :
Tamperproof
Ratings of MCB
1A
2A
3A
4A
6A
10A
16A
20A
32A
40A
50A
63A
100A
Earth Fault Breakers
The ELCB
Under normal conditions, the total current flowing from the supply to
the load will be the same as the total current flowing back to the supply
from the load. As the current in both directions is equal but opposite, it
has no effect on the CT. However, if some current flows to earth after
the ELCB, possibly due to an earth fault, the current flowing to the load
and from the load will be different.
This differential current will cause a resultant output from the CT. This
output is detected and if above a predetermined safe level, it will cause
the ELCB to trip and disconnect the supply from the load.
Residual Current Devices (RCD’s)
Single Phase RCD
Phase
LOAD
Detection Coil
Neutral
Relay
Test Button
Test Resistor
LOAD
L1
L2
L3
Earthed
Neutral Metalwork
Detection Coil
Magnetic Core
10,30,100,300
GE 6~40A 6kA B&C
mA
6 kA
Legrand 6-40A 30,300mA C
B&C
Schneider 6-40A 30mA 6kA
Moving Moving
contact
contact
OPERATING
PRINCIPLE OF
BREAKER IN A CIRCUIT BREAKER
OVERVIEW OF ARCS IN BREAKERS-:
35
1) Axial blast Air blast circuit breaker
2) Cross-blast air breaker
Advantages
The risk of fire is eliminated.
The arcing products are completely removed by the blast
The growth of dielectric strength is so rapid that final
contact gap needed for arc extinction is very small. This
reduces the size of device.
The arcing time is very small due to the rapid build up of
dielectric strength between contacts
Due to lesser arc energy, ABCB are very suitable for
conditions where frequent operation is required
The energy supplied for arc extinction is obtained from high
pressure air & independent of the current to be interrupted
Disadvantages
Air has relatively inferior arc extinguishing properties.
1. Increased safety
2. Reduced size
3. Easy installation
4. Low maintenance
SF6 breakers are costly due to high cost of SF6
SF6 gas has to be reconditioned after every operation
of the breaker, additional equipment is
required for this purpose
Compressed air
132 kV, 220 kV
4. Air blast C.B. (pressure 20 to 30
400 kV, 760 kV
atmospheres)
132 k V, 220 kV
5. SF6 C.B. SF6 gas
400 kV, 760 kV.