Equipment Sizing
Heat Loss Calculations
Total required supply CFM
Conduction Loss Qs = HL/[(1.08)(te-t)]
Walls 210093.25/[1.08x(130-70)] = ~3500 CFMs
Hw = (A)(U)(ti-to)
525.19 ft^2 x 0.076 x 60 = 2394.87 BTUH 14 Registers in Assembly Hall
Roof 3500/14 = 250 CFM per register
Hr = (A)(U)(ti-to)
6349.9619 ft^2 x 0.17 x 60 = 64769.61 BTUH Registers
Two-way 3
Glazing Four-way 11
Hg = (A)(U)(ti-to)
3120.3102 ft^2 x 0.24 x 60 = 44932.47 BTUH
Total required return CFM*
Slab Edge Qr = CFM(1.5)
He = (P)(F)(ti-to) 6500 CFM x 1.5 = 9750 CFMr
328.12 x 0.55 x 60 = 10827.96 BTUH
5 Registers in Assembly Hall
Slab/Bsmt 9750/5 = 1975 CFM per register
Hs = (A)(F)
5426.4389 ft^2 x 4.0 = 21705.76 BTUH Zoning
Z1 – Adj. to Glazing (4-way)
Convection Loss Z2 – Central Area (4-way)
Infiltration Z3 – Rear Wall (2-way)
Hi = (.018)(ACH)(V)(ti-to)
0.018 x 0.85 x 71310 ft^3 x 60 = 65462.58 BTUH
Z3 Z2 Z1
* = accidentally used 6500 instead of 3500, all return duct sizing corresponds to 9750 CFM as a result