FLUOR PIPE STRESS ANALYST DESIGN GUIDE yewsen 3.21
DESIGN
GUIDES
DESIGN CRITERIA FOR FIRED HEATER PAGE lof 50
DATE 4-76
2.0
HEATER NOZZLE FORCE, MOMENT AND STRESS LIMITATION
wal
Pipe stress at the heater terminal shall be within the allowable stress
range as designated by ANSI 831.3 (latest revision) for the material of
construction.
Moment on flanges shall not exceed those permitted in section 2.0 of
the Stress Group Charts and Tables, to insure that leakage will not
In the absence of vendors' limitations, forces shall be limited to
200 Ibs. per inch of nominal pipe size, or 2000 Ibs. which ever is
jess. Cold spring may be credited in accordance with ANSI B31.3.
Forces, nozzle deflections, and moments mutually agreed upon by Fluor
and heater manufacturer.
Forces, deflections and moments shall be transmitted to the
heater vendor for their comment and approval at the earliest
time possible. Preliminary layout and sketches can be used
for this particular purpose.
b. Supporting steel for piping from heater shell or structure
shall be reviewed, designed and approved by the heater manu-
facturer. The loads on supports shall also be transmitted to
the heater vendor during the early stage of the job.
HEATER DESIGN AND LAYOUT
2.2
‘The most important consideration in laying out heater piping is to
use the heater tube as a flexible element to minimize the amount of
flexibility required in the process piping. By locating the heater
tubes in the most advantageous position, the length and number. of
fittings required in the process piping may be minimized.
TYPES OF HEATERS
Basically there are three types of heaters. They are:
1. Box-type
2. Vertical
3. Helical CoilFLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3-11
DESIGN CRITERIA FOR FIRED HEATER PAGE «2
DESIGN
GUIDES DATE 4-76
3.1 Box-Type Heaters: A box-type heater is considered to be any heater
in which the tubes are horizontal. There are numerous designs of
box-type heaters.
In this type of heater, it is possible to have locations or zones
of different heat densities. The shock or shield tubes usually
receive the highest heat density because they absorb both radiant
and convection heat.
Tubes in the radiant section of the furnace are called "radiant tubes.
The heat pickup in these tubes is mainly by direct radiation from the
heating flame and incandescent refractories
‘The zone of lower heat density is the convection section. The tubes
in this section are called “convection tubes." The heat pickup in the
convection section is obtained from the combustion gases, primarily by
convection
‘The size and arrangement of tubes in a box-type heater are determined
by the type of operation (crude oil distillation, cracking, etc.),
the amount of heating surface required, and the flow rate through
the tubes.
Box-type heaters may be updraft or downdraft, with gas-or oil-fired
burners located in the end or side walls, floor, roof, or any combin-
ation thereof.
Auxiliary tubes are often installed in the convection section after
the oil convection tubes, to preheat air for the burners or to generate
or superheat steam for process and other uses.
3.2 Vertical Heaters: ‘The vertical heater is either cylindrical or rec~
tangular. The entire heating coil, or major portion, consists of
vertical tubes. The radiant tubes are vertical, but the upper ends
of these tubes may be in a convection zone where gas velocity is
increased by restricting flow area. The tubes in the convection
section are always horizontal.
In some installations an oil economizer section or an air-heating
section, or both, are used above the main vertical heating section.
‘The auxiliary tubes in the oil economizer or air-heating sections may
be either horizontal or vertical, depending on the particular design.
The purpose of an oil economizer or air-heating section is to improve
the economy of operation.
‘The majority of vertical tube heaters are bottom-fired, with the stack
mounted directly on top of the heater. Downdraft vertical heaters
have also been used.
ee)FLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3.12
pesion DESIGN CRITERIA FOR FIRED HEATER PAGE 3
GUIDES DATE 4-76
3.3. Helical Coil Heaters: ‘The helical coil heater is cylindrical in
shape, with the radiant section surface in the form of a coil which
spirals up the wall of the heater. Heaters of this type usually do
not have a convection section; but, if included, the convection
surface is in the form of a flat spiral or bank of horizontal tubes.
‘The stack is almost always mounted directly on the heater.
4.0 THE RADIANT SECTION
4.1 Consider the vertical heater first since it is the simplest of the
three. All vertical heaters have vertical tubes in the radiant section
and horizontal tubes in the convection section if one is required.
The tubes in the radiant section are arranged in even or odd numbers.
Tubes are frequently added to reduce the height of the heater while
elimination of a tube will increase the height of the heater. Even
numbers of tubes will place the inlet and outlet nozzles at the same
end of the heater. See Figure 4.1.
1 Pass
2 Tubes,FLUOR PIPE STRESS ANALYST DESIGN GUIDE
NUMBER 3.22
DESIGN CRITERIA FOR FIRED HEATER
Desion pace 4
GUIDES DATE 4-76
4.2 Odd number of tubes place the inlet and outlet at opposite ends
of the heater. See Figure 4.2.1.
1 Pass B.
1 Tube 3 Tubes 3 Tubes
[77>
[t---,
—-~-—4
=
ro}
1
I
|
|
1
x
'
Figure 4.2.1 Tube & Pass Arrangements
4.3 Occasionally there is an option to increase or decrease the height
of the heaters and consequently reposition the nozzles to the
advantage of the piping system. (3-40' tubes = 4-30" tubes).
However, when there is a convection section involved with a direct
tie to the radiant section, the support and nozzle locations for
the interconnecting pipe will invariable be set by the heater
vendor with little option for change. see Figure 4.3.1.FLUOR PIPE STRESS ANALYST DESIGN GUIDE
NUMBER 3.11.
DESIGN CRITERI) Fu
pesict ESIGN A FOR PIRED HEATER PAGES
GUIDES DATE 4-76
4.3 (Continued)
stack
convection
Section
crossover Piping mee f
i £ $
‘Tube Support
inlet:
‘Tube Guide
{ ‘Tube Guide
4.4 Normally the supports in this case are located at the top of
the radiant section to minimize growth into the crossover
piping which minimizes the length and number of fittings re~
quired in the crossover piping for flexibility purposes.
4.5 The location of the nozzles has a direct bearing on the loca~
tion of the tube supports as related to the piping system.
Therefore, an understanding of the type of supporting arrange~
ments available is necessary before continuing with the layout.
5.0 BOTTOM SUPPORTS
5.1 Tubes supported at the bottom of the heater have advantages
which may or may not be of value in the layout of the piping
system. Each must be considered on its own merit and evaluated
with respect to the effect on that particular system of piping.
See Figure 5.1.PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3-12
DESIGN CRITERIA FOR FIRED HEATER PAGE 6
DATE 4-76
5.1 (Continued)
Arvax. exp. (#2)
(pn SSS
Ss ae ST
= 4
f oe PW ty we ah I
es | Guides
tt ame fh tl Woh AP nme Ny |
= tle. Support He A i S Support Nhe fe
=
i ST TYR le. oo
RR Sect
rawtet
&
5.2 The long unstable tube columns require guiding to avoid buckling
from their own weight and any external load applied parallel to
the center line of the pipe. Columns under compressive loads
are much more critical than columns in tension. To avoid eccentric
column loading, the deflection " A“ of the bottom support in a
horizontal direction must be minimized. The weight of the tubes
is supported at a lower elevation within the heater structure.
Expansion is tube movement into the piping system. Lateral dis~
placement is allowable piping movement into the heater. (L-D.)
6.0 TOP SUPPORTS
6-1 As with bottom supported tube arrangements, top supports have
decided advantages which must be evaluated for each individual
piping application.
(1) Avin. Exp. = Tube change in length is minimum for
thermal expansion growth.
(2) Avax. pxp.= Tube change in length is maximum for
thermal expansion growth.FLUOR PIPE STRESS ANALYST DESIGN GUIDE
NUMBER 3.12,
DESIGN CRITERIA FOR FTi Pi
pees RED HEATER AGE
GUIDES 4-76
6.1 (Continuea)
«3) Atv. = Tube deflection is a limited dis-
placement due to eccentric load, tube
bending stress, and physical design of
the heater compents.
The ideal case would provide enough
lateral displacement in the installed
condition to take a cold pull equal to
the piping growth from thermal expansion.
Anin. Exp. (#1)
te Anax . . \
sencmens is
———
re sutbee
“
[a tube SS I
support
The long tubes are in tension and are in no danger of buckling!
Horizontal displacement is limited by the stress in the tube and
the limit accepted by the heater vendor. The weight of the tube
is located at the top of the radiant section. See Figure 6.1.
~
1
1 |
| |
LJ
KY XN NA Exp. (#2)
Figure 6.1
7.0 FLOATING COILS
7.1 ‘This is by far the most expensive method of absorbing displacement
into the heater. There are many instances where the floating coil
is the only solution to absorbing growth of the piping system and
is in actuality a must because of limited pressure drop.FLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3.11
DESIGN CR: Pact 8
a CRITERIA FOR FIRED HEATER E
eae DATE 4-76
7.2 Methods of floating the coil employ either the use of spring
hangers or counterweights. The most common approach used by
heater vendors is the counterweighted piping system. The
code demands that all counterweights are installed with fail
safe devices for personnel protection in the event that the
counterweight assembly fails. Usually the counterweights are
attached to the headers supporting the heater tubes. The
counterweight is a weight lifting the tube through a cable
and pulley system or a weight lifting the tube through a
cantilever beam system. See Figures 7.2.1 and 7.2.2.
cable
(typ)
Weight
(typ)
tl
tl
rasa van —_/ | |! ws
inet
ty
i
ee ‘| BEAM SYSTEM
Figure 7.2.1 Floating CoilFLUOR PIPE STRESS ANALYST DESIGN GUIDE NemseR 3.12
DESIGN DESIGN CRITERIA FOR FIRED HEATER PAGE = 9
GUIDES DATE 4-76
7.2 (Continued)
Displacement limited in all directions only by heater vendor and
pipe thermal expansion (displacement) .
ore er zo
I
\
I
i
\
Cable
(typ)
5
!
|
|
|
|
{ a Weight f =)
(typ) 8
Failsafe
column
PULLEY SYSTEM BEAM SYSTEM
Figure 7.2.2 Floating Coils
co — -
The other method of floating the coil is with the use of spring
hangers. See Figure 7.2.3.
Hanger Spring
Displacement limited in all
directions only by heater
vendor and pipe thermal expansion
(displacement)
Limited Horizontal Movements —e
Base Spring
Foundation
Figure 7.2.3 Floating CoilsFLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3.22
DESIGN CRITERIA FOR PAGE = 10
Seca FIRED HEATER
GUIDES DATE 4-76
8.0 THE CONVECTION SECTION
‘The length of tubes in the convection section of the vertical heater
are generally very short because of the limited area available on
top of the radiant section. (6' to 12"). They may be controlled
easily by the addition of directional anchors on the face of the
convection section. Normally, the heater vendor will only supply
controls on request. The standard approach is to rely on friction
to provide a natural anchor in the center allowing the tube to
expand outward from that point. Since the commodity in the line
is heated as it flows from one end of the tube to the other, the
tube metal will generally be hotter at the outlet end than on the
inlet end and the metal temperature is 100°F to 200°F hotter than
the flowing commodity. See Figure 8.1.
Convection Section Tubes
Vertical Supports
pee Lye,
[Ye cusses
€ HEATER
Figure 6.1
eFLUOR PIPE STRESS ANALYST DESIGN GUIDE NuMBER 3.21
DESIGN CRITERIA FOR FIRED HEATER
foo PAGE LL
GUIDES DATE 4-76
8.2 The same phenomena will occur regardless of the number of passes
or the length of the tube although to a lesser degree on shorter
tubes. See Figure 8.2.1.
convection Section Tubes
« 7 Vertical Supports
¢ eater
Figure 8.2.1
8.3 A reliable frictional restraint such as is described is a figment
of the imagination. There are too many factors which tend to
control the direction of the expansion if positive methods are
not utilized; i-e., weld splatter, crooked supports, crooked guides,
etc. The correct approach is to add restraints to the tube. This
action will have the additional benefit of providing effective wind
and seismic stops which is definitely lacking in the frictionally
restrained state. The three locations available for providing
control on the tube are the front face of the convection section,
the rear face of the convection section and the internal supports
for the tubes. Any one of these locations may be selected.
Never more than one. Furthermore, the stop may only be provided
‘on the first or the last pass only because of the difference in
the metal temperature of the tubes. See Figure 8.3.1.PIPE STRESS ANALYST DESIGN GUIDE
DESIGN CRITERIA FOR FIRED HEATER
8.3 (Continuea)
b= 10-0"
stop
Gxiald
cane M_ _rones oe __ ans
B00°F Le #2 Outlet Tube eee
a ee
A, - 26
€ Heater
J——convection
Section
Stop (Axial)
Heater
Figure 8.3.1PIPE STRESS ANALYST DESIGN GUIDE
DESIGN CRITERIA FOR FIRED HEATER
NUMBER 3.11
PAGE = 13
DATE 4-76
8.3 (Continued)
Assuming linear heat buildup and a tube metal temperature 00°F
higher than the conmodity-321SS tubes. See calculations below:
Calculations For Figure 8.
Temp. @ inlet = 100°F + 600°F = 700°F
Temp. @ return bend = 800°F (avg.)
Temp. @ outlet = 100°F + 00°F = 900°F
Average temperature of tube fone = 750°R
(e @ 750°F = .0815"/Ft.)
Average temperature of tube #two = 850°F
(e @ 850°F = .0941"/Ft.)
Ay [no x .0815) - (20 x .0941]) .126" our (Direction Due To
A, . fac x .0815) - Go x -0941)] = .126" IN} Location of Stop
See Figure 8.3.1.
stop
s stop
815
Ay us 4,
—_— NN _ i
5 ar
= Fe oo Ng
Ay 940 7-7 : ~~ >A
Stub Through Wall
4a
10 x -0815 = .815";
2 a
Tube Bend Through Wall.
10 x -0941 = .941"FLUOR
DESIGN
GUIDES
PIPE STRESS ANALYST DESIGN GUIDE
DESIGN CRITERIA FOR FIRED HEATER
NUMBER
PAGE
DATE
3.11
14
4-76
Installation of internal guides and anchors is not desireable
because the support steel and piping attachment are exposed
to the direct heat in the section and have no flowing commodity
to cool then.
|. See Figure 8.4.1.
-3915" 70°F
sto"
—— bab
-5175" 900°F|
H 750° Fa
_
50°F
Figure 8.4.1
stop nor Allowed
G wearer
Large forces must be restrained by face of plates.
Temp. Inlet
‘Temp. Stop
‘Temp. Return Bend = 800°
‘Temp. certer
‘Temp. Outlet
700°
= 750°
850°
900°
Avg = 725°
Avg = 775°
Avg = 825°
avg
-S x .0848
45 x .0911
5 x .0972
Floating coils in the convection section are not considered
because of the extreme difficulty in supporting the long
horizontal tubes on springs or counter-weights.
‘The coils may be displaced normal to the centerline of
the tube with only the tube stress level as a limit.
ment of the coil parallel to the centerline of the tube is not
allowed. Vertical displacement is limited to the upward direc-
tion so that the tube is lifted off of the pipe support.
The
2426"
+.4555"
486"
Displace-FLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3.12
DESIGN CRITERIA FOR FIRED HEATER
a PAGE 15
GuIpes DATE 4-76
8.6 (Continued)
additional weight from loss of the supports must be absorbed
by the first internal and external support that is effective.
See Figure 8.5.1.
8.7 Tf a directional control is required at the center of the tube
(Fig. 8.4.1) the same effect can be achieved by placing a stop
at both ends of the tube and providing a gap equal to half the
thermal expansion of the tube
Maximum Displacement
A
" Displacemen 4a 4a
ae : Maximum Displacenent —¥|
Operating Position - Pipe is Hor
Me ‘Thermal exp. is directed from vert. supt. @ "A"
|__ a7 Tube is lifted off support*
Tgeate cellar eee Tesupt's_
4
4
First Effective Support
Installed Position - Pipe is COLD
}—— “a” vertical support
Figure 8
‘The amount of lift of€ is proportional to vert. exp., which
is dependent on: Line Temp., Pipe Mat'l & Dim. “L", to
first vertical support.FLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3.12
pesien DESIGN CRITERIA FOR FIRED HEATER PAGE 16
GUIDES DATE 4-76
8.7. The weight resting on the first four supports inside the con~
vection section must now be added as additional load on the
third internal support and on the external support. The new
unsupported span must also be considered. See Figure 8.6.1.
9.0 REGENERATION
9-1 During catalyst regeneration and especially during decoking
operations the line temperature may increase considerably.
‘The effect on the line expansion, whether the decoking-regen-
eration system is independent of the process system or not,
must be taken into account in the design of the heater. The
decoking temperature generally is in the vicinity of 1300°F,
and will affect the displacement required at the heater tube
nozzles. See Figure 9.1.
Pipe Mat‘l: Stainless Steel
Temp. : Normal oper. Des. = 800°F, /\ ,
130°. /\,
Temp. + Decoking
Anchor
--4
--4
1.056"
Doe
‘Thermal exp. is from the anchor point
to the heater, thus deflecting the
tubesFLUOR
DESIGN
GUIDES
otch at joint
cx
PIPE STRESS ANALYST DESIGN GUIDE
DESIGN CRITERIA FOR FIRED HEATER
NUMBER 3.11
PAGE 17
DATE 4-76
‘The heater tube in the decoking operation is displaced nearly
twice as much as in the design condition. The allowable,pipe
spans and the pipe material are severely limited at 1300°F.
Because of these factors, water quenches are introduced into
the lines to reduce the temperature. Invariably these quenches
require mixing gees to recude the temperature rapidly to a
maximum of 1000°F or less. See Figure 9.2.1
\q—"Mixing Tee" (Designed by Stress Eng.)
Pipe may require “Liner” to reduce
thermal shock, fatigue & erosion
Erosion
Point
Hivy. wall because
RETICAL LENGTH
Figure 9.2.1
, Critical length determined by Process Eng. & Mechanical Eng. Consultant.
The critical length shown is a factor of the injected material,
temperature and velocity. It is required to prevent wear (erosion)
on the elbow from the effect of the injected material striking
the elbow at high velocity. The length must be sufficient so
that the injected material is thoroughly mixed with the flowing
commodity before the elbow. Using the weld reducer to attach the
injection line removes the thermal shock from the crotch and
allows the injection to be made without weld cracking and bowing
at the junction point. The connection at the junction point will
be designed by stress.FLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3.22.
DESIGN CRITERIA FOR FIRED HEATER PAGE 18
DESIGN
GUIDES DATE 4-76
9.4 0.8.H.A. has had a drastic effect on Fluor's attitude toward
“throw away" or “expendable” piping in decoking systems. Fluor
is now obligated to recommend material which is within the
temperature limits established by the Refinery Piping Code or
be in a position to prove the suitability of the material at
higher temperatures ~ even though this piping is used infrequently.
At temperatures above 1100°F (the Code limiting temperature of
carbon steel) Fluor will recommend alloy or stainless steel pipe
for these installations. In the event that the client insists
on using carbon steel pipe he must indicate in writing that his
decision is to override Fluor's recommendation. He must also provide
allowable stress for computing wall thicknesses, pipe spans and thermal
expansion for all temperatures beyond the range of the code. Fluor
will then design to the specific parameters dictated by the client
‘This approach is mandatory for all plants which fall under the
jurisdiction of United States federal regulations.
Note- In determining design temperatures, consider the temperature
derating allowances permitted by Code for uninsulated piping.
20.0 RING HEADERS
10.1 ‘The ring header must always be supplied by the heater vendor.
Tube connections are difficult to locate on the header, also,
the support and tube movements from the ring header expansion
are removed from the area of responsibility of the vendor when
hhe does not design and fabricate the ring. Since there is no
flexibility between the ring and the tube, the tube must absorb
the expansion of the ring header. The weight of the header is
on the tube support.
11.0 STRESS CHARTFLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER. 3.21
DESIGN CRITERIA FOR FIRED HEATER
DESIGN PAGE 19
GUIDES DATE 4-76
12.0 VERPICAL HEATER SAMPLE PROBLEM #1
20" @ Inlet from V-101
20" g outlet to pipeway
Stainless Tubes
253 Gr-B Pipe
Figure 12.1 Plan Layout:
(a) (B) (c)
options 1-40 Tube, 2-20 Tubes, 3-13" Tubes,
o Fe ae
Inlet 600°F 20 Req'd 20 Sets Req'd 20 Sets Req'd
outlet 800°F 42' Height 22" Height: 15" Height
Tube Metal = 900°F 6'-6" @ utr. 11'-6" @ Htr. 16'-6" Htr.
Commodity Avg. = 700°F 5'-6" g Ring 10'-6" g Ring 15'-6" ¢ RingFLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3.22
DESIGN CRITERIA FOR FIRED HEATER PAGE 20
DESIGN
DATE 4-76.
aA 1B 2a 2B 2D 3a 3B
Figure 12.2 Tube and Support Arrangement Sample Problem
12.1 The thermal expansion between V-101 and H-101 is 50 x .046 =
2.30" in the east-west direction which must be absorbed by
additional piping in the north-south and vertical direction
or by the heater tubes. By the Table 11.0 a 4" tube of minimum
18" length is required and would be top supported to handle the
large displacement. ‘This eliminates scheme 3A and 3B because
of the short tube length unless the coil is floated (too expen-
sive unless other schemes fail). Schemes 2D, 2B and 1B are
eliminated because bottom supported tubes allow limited dis
placement. Schemes 1A, 2A and 2C are best suited for the
layout to accommodate the horizontal displacement. However,
the top supported units impose vertical displacement into
‘the piping system. Obviously scheme 1A is the worse offender,
and it is eliminated. See Figure 12.1.1.FLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3.31
fee DESIGN CRITERIA FOR FIRED HEATER PAGE = 22
GUIDES DATE 4-76
12.1 (continued)
pats
Thea
12.2 The bottom inlet and outlet may require less piping but requires a
higher supporting structure for the heater. Ring headers on the
bottom must be raised to allow 7'-6" clearance under the pipe.
Use the bottom inlet and outlet connections.
12.3 The piping system must now be arranged and anchored to control
the movements and forces on the heater nozzle. Supports are
added to the system and loading is calculated for each. All
pertinent information is then transmitted to the heater manu-
facturer. See Figure 12.3.1.FLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3-11
DESIGN CRITERIA FOR FIRED HEATER
DESIGN PAGE = 22
Guipes DATE 4-76
12.3 (Continued)
Dummy Support
Directional Anchor
a Transmit load
to vendor
Transmit loads
and movements to
heater vendor
Ring Header
ERE
Figure 12.3.1
12.4 Information to be transmitted to heater vendor.
1. Inlet tube movement for all tubes.
+ at] 016 = 2 13/16" west
tay [fston + es0'-0
toy [fst-an] woes = 1/4" nacen and south
Sree ere ore eres rites
Bg ese eee fore ta pec en ne fcaes
13.0 VERTICAL HEATER SAMPLE PROBLEM #2
13.1 Another type installation is the vertical heater with a convection
section. In this case, consider the convection section a preheater
with crossover piping between the convection section and theFLUOR PIPE STRESS ANALYST DESIGN GUIDE
DESIGN CRITERIA FOR FIRED HEATER
Desicx
GUIDES
13.1 (Continued)
a pi 153'=0"
‘ EL :
“4 fH | 2
13.2
Material
Piping Inlet = S00°F, a53 Gr-B
Piping Outlet = 700°F, 53 Gr-B
Sp
Heater Tube = 800°F, ss
EL. 100'-0"
Figure 1
‘The vertical expansion in the inlet line is (153.0' - 101.5") x
0362 = 1.864". From the stress chart (Table 11.0) the 6" tube 12'-0
long can only be bent 5/8", therefore, the line cannot be supported
at grade. Supporting will be in the form of spring hangers at any
elevation or a solid support from the heater structure. The maximum
distance from the nozzle to. the solid support is 0.625/.0362 = 17'-3
Support the inlet line at elevation 135'-9". The support must be
designed to absorb the thermal force to bend the 12'-0" leg plus
half the weight of the 12'-0" leg plus the weight of the entire
vertical line and half the weight of the lower horizontal run to the
first support. The inlet nozzles must absorb the horizontal movement
of the intet line.FLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3.22
DESIGN DESIGN CRITERIA FOR FIRED HEATER
GUIDES
13.2 (Continued)
5 x .0362 = .181 = 3/16" North and South; and 11 x .0362
West; and the vertical expansion of 17.25 x .0362
13.3 The lower 12" manifold will grow down from the upper pipe sup-
port (135.75' - 101.5') x .0362 = 1.24" which must be absorbed
by bending the pipe between the manifold and the first solid
support. Springs may be required on the 12" line.
13.4 The outlet ring header grows down (151' - 108") x .088 = 3.78".
Location of the first solid support must be at least 38 linear
horizontal feet from the ring header (see Table 11.0).
13.5 Maximum horizontal expansion which can be absorbed by the 51"
long inlet lines is more than 8 7/8" per Table 11.
13.6 Maximum horizontal expansion which can be absorbed by the 43
Jong outlet tubes is more than 16 3/16" per chart.
13.7 Tube movenents of large magnitudes such as these present prob
lems of heat loss* to the heater vendor, however, they are not
insurmountable. The best example for large magnitudes of move- (0
ments into heater tubes are applications in hydrogen and reformer
heaters.
14.0 Other typical layouts are piping arrangements to reactors and drums,
See Figure 14.1.
‘Heat loss problems in this case is concerned with the closure
of gap between the outside of the tube and the wall or floor
of the heater.PIPE STRESS ANALYST DESIGN GUIDE wumeeR 3.22
DESIGN CRITERIA FOR FIRED HEATER PAGE 25
DATE = 4-76
14.0 (Continued)
ar
800°F, A53-GrB
a EL 147'-0"
El. 144'-0"
Avg, Commodity Tem
I} 8758s tube = 975¢e
pap Tubes
950°F, A53-GrB
EL.__107'~0
Figure 14.1
14.1 In order to minimize the vertical expansion difference, the tube
support should be located as near to the reactor support as poss-
ible. When the lower tangent line of the reactor is close to the
bottom of the heater the tubes should be bottom supported. When
the lower tangent line of the reactor is near the top of the heater,
the tubes should be top supported.
14.2 Example of vertical expansion difference.
Example #1
a. Bottom supported heater tubes.
Elevation H = 107'-0"
Are fasr-on = caor-or) x 0698 = 2.792"
a:
"
[a47+-o7) = aoo-or} x sana
Net = 1.441"
4.2332"FLUOR PIPE STRESS ANALYST DESIGN GUIDE nai ert
P, 26
prin DESIGN CRITERIA FOR FIRED HEATER AGE
GUIDES DATE 4-76
14.2 (Continued)
b. Top supported heater tubes
Elevation H = 107'-0"
A
a2
[aa7'-0") = ao7'-o"] x .0698 =
fuar'-or) = aaron] x canta =
Net = 2.458"
‘a. Bottom supported heater tubes
Elevation H = 124'-0"
Ai = [far = a2at-o"] x .0698 = 1.6054"
Az = [aar'-o%) = og'-orj} x 1114 = 4.2332"
Net = 2.6278"
b. Top supported heater tubes
Elevation H = 124"-0"
Ax = [f147!-0") - (124'-o"j] x .0698 = 1.6054" @
Qa = [aa7t-or) - aaat-onmy) x .1114 = 23342"
Net = 1.2712"
14.3 In order to evaluate the heater as a whole, the lower ring
header and attached piping must be considered.
Example #3
a. Bottom supported heater tubes
Elevation # = 107"
A3 = fost-o") = ao7'-on]} x a=
fao'-07) ~ 207'-0")] x 0835 = .0277* up
Example #4
b. Top supported heater tubes
Elevation # = 107'-0"
As = [ase-o" = aor-o4) x ana
faro'-0%) = (207'-0%)) x .0835 = 3.8713" down
14.4 When large piping is involved, a floating coil may be preferred to
use the flexibility in both the inlet and outlet piping and to
absorb the heater tube expansion.FLUOR PIPE STRESS-ANALYST DESIGN GUIDE
14.4
DESIGN
GuIDes
NUMBER 3-11.
DESIGN CRITERIA FOR FIRED HEATER PAGE = 27
DATE 4-76
(Continued)
Example #5 H = Lo7*~
+ Reactor = [(247'-0") - (107!-0"]] x -0698
~ eater = [247'-0") ~ co7!-0"] x ana
+ tower Pipe = [(1i0'-0") ~ c07*-or]] x .0835
Net = 1eava"
Example #6 H = 124'-0"
+ reactor = [f247'-0") - (22at-o"j] x 0698 = 1.605"
= eater = [(247'-0") ~ (ao7'0"] x uaad = = 4.456"
+ Lower Pipe = [(110'=0") - (2o7!=0"] x .0835 250"
Net = 2.601"
15.0 BOX-TYPE HEATERS
16.0
15.1
15.2
Box heaters are generally much larger than the vertical type
heaters and present more varied and complex problems with
respect to stress analysis. The radiant section tubes can be
vertical or horizontal with connecting headers in varied forms
welded directly or with flexible “pigtails.”
Rather than discuss the radiant section as a general form,
specific units will be analyzed with the most effective layouts
presented and the reasons for their selection.
CRUDE HEATER OUTLET TO VACUUM TOWER
16.2
Do not arrange radiant tubes parallel to the major pipe run.
Heater tubes may not be moved parallel to themselves because
of the large number of tubes which are interconnected. Flex-
ibility would then be required in the piping arrangement. See
Figure 16.1.FLUOR PIPE STRESS ANALYST DESIGN GUIDE
DESIGN CRITERIA FOR FIRED HEATER
DESIGN
GUIDES
NUMBER 3.11.
PAGE = 28
DATE = 4-76
a
16.1 (Continued)
Required Loop
Alloy Piping 36" DIA
P-101
ar Supt. by vendor
vacuum
a)
—<—_ eared
Stop Tube
4 ee Expansion
Tangential aaa
Nozzle
Cold Spring Riser 100
crude Heater
(Box-Type)
Figure 16.1
An arrangement such as this requires
about a 50' deep loop
with four extra elbows.FLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3.21
DESIGN
GUIDES
DESIGN CRITERIA FOR FIRED HEATER PAGE 29
DATE 4-76,
Hanger spring
Required
6"-alloy
‘ube Leads ™ yy
Alloy Pipe
36" DIA
16.2
Eigure_ 16.2.2
An arrangenent such as this requires about 30' minimum of
vertical 6" alloy pipe per lead, two extra elbows as shown,
plus a spring support for each lead. See Figure 16.2.1.FLUOR PIPE STRESS ANALYST DESIGN GUIDE NumBeR 3.22
DESIGN CRITERIA FOR FIRED HEATER PASE
DESIGN ou
Gulpes DATE 4-76
Sup't by vendor
stop Tube
Expansion
20"-0"
Figure 16.3.1 wed
16.3 An arrangement such as this requires about a 70' offset in
the 36" B alloy pipe plus two elbows. See Figure 16.3.1.FLUOR PIPE STRESS ANALYST DESIGN GUIDE
NUMBER 3.12
fe DESIGN CRITERIA FOR FIRED HEATER PAGE = 31
GUIDES DATE 4-76
16.4 Yo minimize piping costs and maintain a tight professional
layout the heater tubes should be perpendicular to the longest
length of pipe. See Figure 16.4.1 thru 16.4.4.
stop
Nobil Joliet Layout a
T-101 60" DIA es
+ Inclined Plane Sup't (typ) Trt
trite
Cold Spring Risers 100%, to grow —
down on the tube support when oper. I>}
— z
Transmit loads &
sup't by vendor.
movements to vessels early ee
70'~0"
‘Tube Movement
Figure 16.4.1
Transmit tube movement and loads on heater structure to
heater vendor before purchase
36" DIA
Vendor sup't
Cold Spring —+ |
Risers 1008
Val 1
(|
Miia
Tubes 50' long
Figure 16.4.2PIPE STRESS ANALYST DESIGN GUIDE
DESIGN CRITERIA FOR FIRED HEATER
NUMBER 3.11
PAGE = 32
16.4 (Continued)
Sup't by vendor
NN Hanger Roa
a 1
special Inclined 4
Plane on
cold sprin
Roller Bearings Cold Spring
Stop Tube
1-101 Expansion
NTOC Layout
(tehran)
Two Units Installed 48" Lines oo
Figure 16.4.3
cold Spring —~|
Risers 100%
Stop Tube
Expansion
NIOC Abadan
36" @ tine
Figure _FLUOR PIPE STRESS ANALYST DESIGN GUIDE
DESIGN CRITERIA FOR FIRED HEATER
NUMBER 3.11
P
DESIGN ‘AGE 33
GUIDES DATE 4-76
17.0
The lines from the tube nozzle to the upper header are to have
100% cold spring so that they will be supported in the operating
position. In order for the tubes to be straight and relatively
stress free in the operating position, the main pipe header should
have 100% cold spring. See Figure 17.1.
Cold spring 1008 = 6"
OOO
a a x
Support —” 7
5
2
S
z
caer .
90000 tt
es
s 7
Support Elev. a
L
F istaitea Operating
‘Tube Positions in Heater
Figure 17.1FLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3-21
DESIG F
pEsicn SN CRITERIA FOR FIRED HEATER PAGE «34
cuines DATE 4-76
ot
14.0
‘The inlet to the heater is in the convection section and the
piping is usually in the form of a water fall. See Figure 18.1.
A-o
Stop movement in
and out
Sup't by
vendor Do not 9
Cold Spring
ADD weight of DROP,
weight of tube to
first effective
support, weight of
pipe to first support
and thermal.
Figure 1FLUOR PIPE STRESS ANALYST DESIGN GUIDE NUBER 3.12
DESIGN DESIGN CRITERIA FOR FIRED HEATER PAGE 35
GuIDes DATE 4-76
18.0 (Continued)
Supports should be located on the heater structure at a point
where springs are not necessary. Vertical expansion is mini~
mized in the lower piping system and absorbed by the convection
section.
19.0 In addition to plot arrangement, there are a mumber of items to be con-
sidered in designing the line
19.1 During start up the outlet line is filled with liguid and will
weigh several times more than in the normal operating condition
when it is in a vapor state. Consequently, a solid support is
preferred whenever possible. Where springs are required, the
piping should be arranged to sit on solid supports at installa~
tion and as they grow off the support in the operating condition
the spring hanger will handle the load in the vapor state.
19.2 Since the line has a vacuum design, the dead load at each sup-
port adds to the external pressure at that point. This condition
makes the use of a stiffening ring mandatory at the support
regardless of the stiffening requirements of the vacuum condition!
(Very Important)
19.3 Forces, loads and moments must be transmitted to the vessel department
as early as possible. (Extremely Important)
19.4 Forces, loads and moments must be transmitted to the vendor as
early as possible.
19.5 Soil conditions where settlement is a problem will force the use
‘of springs in the piping system. Because of the two phase flow,
and the vibration problems in these systems, springs are not
desireable. Exert every effort to pile the heater, vessel and
pipe supports. Do not depend on hydrotest settlement to elimi-
nate the problem. Spring back of the soil will occur and the
equipment will settle again.
19.6 To eliminate ‘thermal forces horizontally perpendicular to the
line, the center line of the heater should be in line with the
irectional anchors on the tubes at the face of the heater.FLUOR PIPE STRESS ANALYST DESIGN GUIDE HUMBER 3.22
36
neseN DESIGN CRITERIA FOR FIRED HEATER PAGE
Guipes DATE = 4-76
20.0 REFORMERS
20.1 Catalytic reformers generally have a heater-reactor system
with vertical tube heaters located opposite a series of
reactors. The interconnecting piping is most frequently
large enough that the entire heater coil must be floating.
‘The following figures show typical heater tube arrangements:
‘Tube
(typ)
Inlet Har. —e ja outlet Har.
Figure 20.1.1FLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3.21
8:
pEsicn DESIGN CRITERIA FOR FIRED HEATER PAGE 37
GUIDES DATE 4-76
20.1 (Continued)
outlet Har
Inlet Hér.
ee
Figure 20.1.2
Inlet Har. outlet Har.
™ ooFLUOR PIPE STRESS ANALYST DESIGN GUIDE
DESIGN
GUIDES
NUMBER 3.11.
DESIGN CRITERIA FOR FIRED HEATER PAGE (38
pate = 4°76
20-1 (Continued)
20.2
20.3
Inlet Hare A xO
Fit
2 20.
the tubes are stubbed into the headers at close intervals (6"¢ to ¢
for 4"@ tubes) and usually consist of 80 to 120 tubes for each
header. Since the headers are large diameter pipe (28" # to
36" ) there is no flexibility in the inlet and outlet piping
systens. ‘The heater tubes must then be floating to accommodate
the thermal expansion if the plot is to be minimized and pipe
plus fitting costs held down.
A typical heater reactor train is the Mobil Joliet Reformer,
Union 0i1 Reformer and Puerto Rican Reformer Reactors. See
Figure 20.3.1.FLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3-12
DESIGN CRITERIA FOR FIRED HEATER
an PAGE 39
GUIDES DATE 4-76
20.3 (Continued)
Reactors
25" or Min. 36" 6 Pipe
1000°F
' [>_<
Q
HE eddddt-}-—. KD Vertical Ef€luent Exchangers
2
8 -
Seismic
& Wind Stop Oy (+
zi
7
WD
OD
20.4 All horizontal and vertical pipe expansion is absorbed by allow-
ing the heater tubes to move freely in the vertical direction
and to slide across the counterweights and through the heater
horizontally. The piping system provides little if any flexi~
bility and all differential thermal expansion is abosrbed by the
heater tubes. Pipe supporting is critical and should be arranged
so that the heater tubes and headers are balanced independently
of the piping system. Responsibility for proper support of theFLUOR PIPE STRESS ANALYST DESIGN GUIDE numer 3.12
DESIGN
GuIDes
DESIGN CRITERIA FOR FIRED HEATER PAGE = 40
DATE 4-76
20.4 (Continued)
20.5
20.6
20.7
20.8
20.9
heater loads is then clearly left to the heater vendor while the
piping system is the responsibility of the pipe stress engineer.
Reactor piping must be capable of standing independently when
the elbows on top of the reactor are removed (catalyst loading
conditions) .
The piping system is, however, supported from the heater structure
and must be guided so that the wind and seism‘c loads are trans-
mitted to the main heater structure. These loads must be sub-
mitted to the heater vendor along with terminal movements as
early as possible.
Stress analysis should include effects of the heater header,
tubes, guides and frictional forces to move the heater headers.
In most cases the frictional effects will exceed the thermal
effect in magnitude and will be the determining factor in design
of the reactor foundation, flanges, structure, etc.
Whenever possible the heater headers should have limit stops in
the form of horizontal guides parallel and perpendicular to the
heater header and vertical stops. The counterweights provided
by the heater vendor must be adjustable to afford a margin for od
error in erection. See Figure 20.7.1.
Flanges in the line and on the reactor are not standard rated
flanges. They must be designed to withstand the forces and
moments developed from thermal, friction, wind, seismic, dead-
weight and hydrotest loads. These loads must be transmitted
to the vessel department for incorporation in vessel design and
to the selected flange vendor -designer to be used along with
pressure considerations in the flange design. See Figure 20.8.1.
Effects of settlement will also be a determining factor in
establishing clearance and movements required in the heater and
the support structure.BK)
1
-76
3
4
4
NUMBER
PAGE
DATE
LOE eanbra
PIPE STRESS ANALYST DESIGN GUIDE
DESIGN CRITERIA FOR FIRED HEATER
DESIGN
GUIDES
FLUOR
‘aubromre3un09
eraessatpy
ain sped uotzon
woxa peoT
peed on
TS
borate |
saqny Teoy3300,
uhzFLUOR
DESIGN
GUIDES
PIPE STRESS ANALYST DESIGN GUIDE NUMBER
DESIGN CRITERIA FOR FIRED HEATER PAGE
DATE
3.1
42
4-76
20.8 (Continued)
Heater
Removable Elbow
Seismic & Wind stop
Friction Moment
NN Hanger Spring for Upper
Line
Hanger Spring on Lower
Line
Grade
Friction
Friction
Force
RIFE £ —1
Figure 20.8.1FLUOR PIPE STRESS ANALYST DESIGN GUIDE HUMBER 3.22
DESIGN
GUIDES
DESIGN CRITERIA FOR FIRED HEATER PAGE «43
DATE = 4-76
21-0 OP PLATFORMER
21.1
21.2
21.3
21.4
‘The major difference between the normal Reformer layout and the
UOP Platformer is that the reactors are stacked on top of each
other as a huge vertical vessel. A structure is built around
the reactor and the piping drops are supported from the struc-
ture. The piping from the reactors to and from the heater has
long drops which are sufficiently flexible so that the horizontal
expansion need not be taken into the heater. Vertical expansion
must be accommodated by floating the heater tubes and headers
similar to the reformer unit. Since the pipe is not required to
slide across the supports, the frictional forces are not major
design considerations.
When supporting the piping from the structure, it is adviseable
to position the spring supports in two separate locations for
drops over 100". Seismic stops will be required on the long
drops.
Flanges are specially designed to accommodate piping forces and
moments as well as the internal or external pressures. All
loads must be transmitted to the heater vender, reactor
and those responsible for flange design.
‘The same general design philosophy has been used for the Champlin
Oil Refinery, Corpus Christi, Texas; Coastal States Refiner,
Corpus Christi, Texas; BPOC Refinery, Marcus Hooke Penna; and is
being considered for the Pertamina Aromatics plant in Indonesia.
See Figure 21.4.1 and Figure 21.4.2.DESIGN
GUIDES
21.4
Fa
FLUOR
PIPE STRESS ANALYST DESIGN GUIDE
DESIGN CRITERIA FOR FIRED HEATER
NUMBER 3.12
PAGE = 44
DATE 4-76
(continued)
Har.
. Har.
Upper Htr.
@-spring Ranger
Figure 21.4.1FLUOR PIPE STRESS ANALYST DESIGN GUIDE NUMBER 3.22
45
peaen DESIGN CRITERIA FOR FIRED HEATER PAGE
GuIDes DATE 4-76
21.4 (Continued)
14" vertical Growth
4
—
Exchanger
Hanger Spring ——>|
Hydraulic —_—
‘Snubber
Box Heater
la Hanger Spring—*"
Bottom Heater Har.
EE
Figure 21FLUOR PIPE STRESS ANALYST DESIGN GUIDE umen 3.21
pean DESIGN CRITERIA FOR FIRED HEATER PAGE 46,
uipes DATE = 4-76
stop all directions except
vertical.
i)
pe
Rs \E vertical stop (failsafe) with clearance SE
«typ)
Figure 21.5-1
Vertical stop Typ. With Clearance
21-5 The most critical lines to be considered are the bottom line
out of the reactor and the naptha charge to the heater both
entering and leaving the same exchanger. Since the bottom line
out of the reactor has no provision for flexibility the exchangers
are on slide pads, rollers, rod hangers or spring hangers.
Analysis is made utilizing all line to and from the exchangers
and the entire heater coil including the heater outlet line.
‘The entire unit is compact with a minimum number of elbows in
each line. No loops or dog legs are required for flexibility
if the system is given proper analysis during layout. See Figure
21.5.1 and Figure 21.5.2.FLUOR PIPE STRESS ANALYST DESIGN GUIDE
DESIGN CRITERIA FOR FIRED HEATER
NUMBER 3-12.
PAGE = 47
DATE
DESIGN
GUIDES
4-76
21.5 (Continued)
Reactor
Heater Tubes: 80 Tubes @
DIA
36" DIA
\
36" DIA
Counterweights
(typ)
lame Exchanger - Rod Hung
Figure 21FLUOR PIPE STRESS ANALYST DESIGN GUIDE
DESIGN
GuiDes
NUMBER 3.11
DESIGN CRITERIA FOR FIRED HEATER PAGE = 48
DATE 4-76
4
22.0 ULTRAFORMER ~ POWERFORMER
22.1
22.2
‘The most complex piping system found in refinery applications
today are in the ultra or powerformer units. They generally
consist of four or five reactors operating in conjunction with
three or four heaters which make up the reactor train. The
complexity of the system is caused by the necessity of using one
reactor as a swing reactor for catalyst regeneration. Each
reactor has the capability of being the swing reactor so that a
network of bypass lines is required enabling the remaining re~
actors to perform independently of the swing reactor. The re-
actors are set opposite the heaters and a structure is pro~
vided in the center to support the weight of the piping and
valves. On large diameter piping (24" +), each valve will weigh
between 10,000 and 20,000 pounds. Sprinas are usually installed
on both sides of each valve to minimize the bending moment in
the piping system. Since the valve and piping loads are so mass~
ive, the entire structural design is meaningless until the piping
design is firm and all springs and valves are located. At that
time, loads will be provided to structural department by stress.
Heaters should be positioned so that the maximum thermal expan-
sion is perpendicular to the heater tube. In most cases the
tubes in the heaters are not vertical. Attempting to slide them oa
through the heater is difficult.
23.0 HYDROGEN HEATERS
23.1
23.2
‘The major problem with hydrogen heaters is the extreme tempera~
ture in the outlet line to the waste heat boiler, and in the
heater tubes themselves. The outlet stream is about 1800°F and
the header under the heater is generally refactory lined.
Since the tubes are so hot, the heater manufacturer prefers t~
Keep the stress level as low as possible and will insist on
fixing these headers at the center of the heater. There is no
available flexibility in the refactory lined header so that the
waste heat boiler must then be mounted on slide pads or hung by
means of rods or spring heangers. The other alternate is to make
the outlet line Inconel which creates problems with expansion into
the heater tubes.
First we will explore the refactory lined header arrangement.
Initially a layout was dictated by a customer which was not a
good design but will serve as an example of poor layout. See
Figure 23.2.1.FLUOR
DESIGN
GUIDES
PIPE STRESS ANALYST DESIGN GUIDE
DESIGN CRITERIA FOR FIRED HEATER
NUMBER 3-11,
PAGE 49
DATE 4-76
23.2 (Continued)
40" pia/e"
0.0004, Refractory
Directional Anchor @ canter of Her. (typ)
Tubes (oPeN 300,000 ft-#
(Heesesss tec]
23.3
23.4
23.5
on Teflon Slide Pads
35.0008
wom —[ rn Waste Heat Boiler
Figure 23.2.1
The thrust required to move the waste heat boiler creates a
large bending moment on the pipe which could crack the refac~
tory and introduce hot spots on the carbon steel pipe. Cal~
culated pipe shell temperature was 300°F. Fluor's recommendation
to hang the waste heat boiler or reposition it to a better location
were not accepted.
Since that time, rumors of numerous hot spots have been heard
and in a more recent project the waste heat boiler has been
repositioned by the same customer to a location which minimizes
the bending moment on the pipe.
‘The horizontal expansion is absorbed by the piping between the
waste heat boiler and the steam drum mounted above it. See
Figure 23.5.1.
12,500#
Sliding or Hung Boiler
Dir. anch. (typ)PIPE STRESS ANALYST DESIGN GUIDE
DESIGN CRITERIA FOR FIRED HEATER
FLUOR
DESIGN
GUIDES
NUMBER
PAGE = 50
DATE 4-76
3.
23.6 Another approach to the problem is to locate the waste heat
boilers under the heater and route the outlet piping in a
flexible manner to the steam drum. See Figure 23.6.1.
Figure 23.6.1