You are on page 1of 11

Journal of Marine Engineering & Technology

ISSN: 2046-4177 (Print) 2056-8487 (Online) Journal homepage: http://www.tandfonline.com/loi/tmar20

Introducing a classification method of Voltage dips


in ship electric energy systems

J Prousalidis & E Styvaktakis

To cite this article: J Prousalidis & E Styvaktakis (2008) Introducing a classification method of
Voltage dips in ship electric energy systems, Journal of Marine Engineering & Technology, 7:1,
1-10

To link to this article: http://dx.doi.org/10.1080/20464177.2008.11020205

Published online: 01 Dec 2014.

Submit your article to this journal

Article views: 133

View related articles

Full Terms & Conditions of access and use can be found at


http://www.tandfonline.com/action/journalInformation?journalCode=tmar20

Download by: [195.29.81.98] Date: 25 July 2016, At: 22:40


Introducing a classification method of Voltage dips in ship electric energy systems

Introducing a classification
method of Voltage dips in ship
electric energy systems
J Prousalidis and E Styvaktakis, National Technical University of Athens, School of Naval
Architecture and Marine Engineering, Division of Marine Engineering

This paper presents an introduction to the analysis and classification of voltage dips, in a
Downloaded by [195.29.81.98] at 22:40 25 July 2016

ship electric power system. The method followed covers the variety of dips occurring
on shipboard installations in its entity. Thus although it has been primarily developed
only for dips due to short circuit faults, it is shown that it can include the cases of sags
due to motor starting, transformer energizing inrush or even pulsed loads. This method
focuses on emerging and characterising the severeness of the event depending on the
consequences on the operating equipment. Therefore, besides an implement of asses-
sing the significance of each situation it can be easily assimilated in system power quality
monitoring units, in protection scheme design and evaluation processes or even in event
identification tools. Where simulations are required, the software package PSCAD is
used to simulate a number of case studies in the power system of actual vessels with
electric propulsion.

AUTHORS’ BIOGRAPHIES Vmin: minimum value of voltage waveform at modulation


Dr J Prousalidis (Electrical Engineer from NTUA/1991, PhD Vn: nominal system voltage
from NTUA/1997) is Assistant Professor at the School of Z F : impedance between the power grid and the fault
Naval and Marine Engineering of National Technical Univer- (including any fault impedance)
sity of Athens, dealing with electric energy systems and ZS : source impedance
electric propulsion schemes on shipboard installations. ˜f: fluctuation of frequency at modulation
˜V: fluctuation of voltage at modulation

Dr E Styvaktakis (Electrical Engineer from NTUA/1995, MSc


in Electrical Engineering from UMIST/1996, PhD from Chal-
mers/2002) is currently with the Hellenic Transmission Sys- INTRODUCTION
lectric power plant onboard has always been a

E
tem Operator dealing with power system studies.
rather complicated power system, comprising sub-
systems of several operation frequency and voltage
levels with increased number of motors nearby
NOMENCLATURE
limited number of generators, especially in sophisticated
E : pre-fault voltage structures with electric propulsion. The aforementioned
fmax : maximum value of frequency waveform at complicacy is expected to worsen further still in the All
modulation Electric Ship (AES) buildings1-5 with full electric propul-
fmax : minimum value of frequency waveform at modulation sion and extended electrification of all shipboard installa-
fn : nominal system frequency tions.
Vdip: voltage dip magnitude On the other hand, similar to continental grids several
Vmax: maximum value of voltage waveform at modulation steady- and transient-state phenomena emerge, particularly

No. A11 2008 Journal of Marine Engineering and Technology 1

Article number = K010


Introducing a classification method of Voltage dips in ship electric energy systems

those concerning power quality problems, and their conse- of the prime movers (often 4-stroke diesel engines) are
quences have to be thoroughly studied, analyzed and inves- small
tigated. • The total power installed per volume unit is large
The scope of the paper is to study and classify voltage especially in the electric propulsion applications. The
dips (or sags), due to several causes in a ship electric power installed power system can be of 40-80MVA in an area
system. In continental grids, classification methods for the of few dozen m2 .
abovementioned problems have already been created and • The largest amount of energy is demanded by electric
further developed6 . The most commonly used is the ‘ABC’ motors (acting either as main propulsion or as drivers
classification method while the most theoretical approach is of auxiliary engines). Furthermore, besides rotating
done by the Symmetrical Component Classification method. electric motors comprising dynamic loads, there is a
However, they can not be easily nor directly applied to ship significant amount of non-linear loads with non-con-
electric systems due to their special network configuration, ventional behavior e.g. pulsed loads of weapon or navi-
as described in6 , where a classification method for fault gation systems
induced voltage dips, particularly developed for ship sys- • There is no significant power transmission-distribution
tems, has been presented. cabling system as the electric power grid is composed
Thus, in order to identify the nature of voltage dips of cables of small length (50-1000m)
onboard, a large number of short circuit simulations have • There is limited number of transformers installed
been performed for all fault types at all the three main • Adopting insulated neutral, i.e. ‘unearthed’ systems is a
operation profiles of a vessel7-8 . This method takes into common practice. Generators, motors and distribution
account the particularities of ship electric energy systems transformer windings are either ungrounded wye- or
with emphasis on making the information easy to assimi- delta- connected, whereas the great majority of conti-
Downloaded by [195.29.81.98] at 22:40 25 July 2016

late. The paper also includes case studies of voltage dips nental grids are grounded, either directly, or via resis-
due to: tive elements
• The power system is completely autonomous, thus its
• motor starting reliability is of high priority. The only available back
• transformer energizing up power is the emergency generator supplying only
• pulse load operation. few loads critical for the vessel survivability
It is shown, that all cases can be categorized in terms of
• A considerable number or electronic devices installed
onboard (automation systems, controllers, navigation
voltage quality and more specifically according to:
systems) are sensitive to power quality and EMI problems
• symmetry among the three AC phases provoked, in particular, by the extensive use of power
• rms magnitude electronics. Hence, the power quality problems are of
• waveshape. extreme importance and have to be analyzed thoroughly
• Referring to short-circuit calculations, as IEC-
While some extra features characterizing certain voltage dip 6136311-12 pinpoints, generators can not but be always
types are also highlighted and discussed. considered nearby the faults, resulting in fairly high
The electric grid of a car-passenger ferry with electric fault currents. Consequently, the voltage sags due to
pod propulsion as well as bow thrusters driven by electric short-circuit faults are expected to be more severe.
motors, has been used for the case studies considered.
Furthermore, for the simulation of the complete power Power quality problems onboard are of different significance
system, the power system simulation software PSCAD has compared to the same problems that occur on a continental
been exploited8-10 . power grid. For inland, power quality problems, apart from
the fact that they result in a problematic production process,
it is possible to have a significant impact on the pricing
relations (tariffs applied and penalties) between the utility
PARTICULARITIES OF SHIPBOARD and its clients. This is meaningless onboard, where the most
INSTALLATION important issue is the continuous operation of the system
The electric power grid of a ship can be regarded as a small and its redundancy. A possible malfunction in a critical load
scale, autonomous, industrial type compact power system, may lead to a total loss of the whole vessel, resulting in
although several differences between a conventional conti- possible human casualties and environmental pollution.
nental grid and a shipboard installation can be enumerated
as follows:
INTRODUCING POWER QUALITY
• The nature of a ship electric energy system is highly
hybrid comprising DC and AC subsystems operating at CLASSIFICATION ON SHIPBOARD
various voltage and frequency levels GRIDS
• Referring to prime movers, their relative rotational in-
ertia with respect to electric load demand is fairly Fault-induced voltage dips
small. However, the operating frequency of 50 or 60Hz Faults (due to the short circuit current) lead to voltage dips
is controlled via fast regulators, as the time constants of a magnitude that depends on the impedance of the source

2 Journal of Marine Engineering and Technology No. A11 2008


Introducing a classification method of Voltage dips in ship electric energy systems

(system’s strength), system configuration, fault impedance,


fault type and distance to the fault. Fault-induced events
present the most severe characteristics. Their duration de-
pends mainly on the protection system operation. That var-
ies from half-cycle (fuse operation) to several cycles
(operation of circuit breakers).
Advanced classification methods have been proposed
that consider all three phases, motivated by the fact that the
relation between the phases is important for the equipment
performance3 or by the fact that valuable information can
be extracted considering all three phases5 .
The calculation of the dip magnitude for a fault some-
where within a radial distribution system requires the point
of common coupling (PCC) between the fault and the load
to be found. The dip magnitude (%) at the load position
Fig 2: Voltage dip due to a 3-phase fault
equals the voltage at the PCC (neglecting all load currents):
ZF
V dip ¼ E (1)
Z F þ ZS seen that voltage drops to approximately 0.4pu (identical
for all three phases) although voltage in the 4kV system
where ZS is the source impedance at the PCC, Z F is the becomes zero at the fault point. The influence of the motor
impedance between the PCC and the fault (including any
Downloaded by [195.29.81.98] at 22:40 25 July 2016

load can be seen both during the fault and after fault clear-
fault impedance), while E the corresponding pre-fault vol- ing. Fault clearing causes a fast voltage increase to 0.80pu
tage. and then the voltage increases gradually towards the normal
Motors that experience a voltage drop will temporary voltage due to the motor load influence.
operate as generators supporting voltage. This shows up in Voltage dips propagate in the system and their charac-
the voltage recording as a slow decay in voltage magnitude, teristics change as they propagate through transformers. Fig
during the fault. After fault clearing, motors re-accelerate 3 shows the voltage dip in the generators terminals caused
delaying the full recovery of voltage and creating a post- by a 2-phase fault in the 4kV voltage level. The delta-star
fault dip as described in 3 that could cause motor stalling. transformer that connects the two voltage levels transforms
The electrical power system of a car-passenger ferry the relationship of the voltage drop in the three phases. A
with electric pod propulsion and bow thrusters, (see Fig 1) characterization method has been proposed in3 for voltage
has been simulated in order to investigate the characteristics dips due to faults that takes into account the different
of fault-induced voltage dips in naval systems. This system transformer connections. An extensive analysis of voltage
consists of four generators and three different voltage levels dips in naval systems, based on this classification, has been
(6kV, 4kV and 0.38kV). Induction motor load is a signifi- presented by the first author in6 .
cant part of the available generation. Considering Equation 1, it should be mentioned that the
Faults in the lower voltage level effect mainly loads fed magnitude of the drop depends on the available source
by the same busbar as the resulting voltage dips do not impedance.
propagate upwards in the system (the impedance of the Therefore, the number of generators in operation affects
transformer is large compared to the source impedance in significantly the magnitude of the voltage dip experienced
medium voltage). by the loads.
Fig 2 shows the voltage dip in the generators terminals
caused by a 3-phase fault in the 4kV voltage level. It can be

Fig 1: Simulated Ship Power System Fig 3: Voltage dip due to a 2-phase fault

No. A11 2008 Journal of Marine Engineering and Technology 3


Introducing a classification method of Voltage dips in ship electric energy systems

Finally, single-phase faults consist a specific case of It is worth noting that I0, I3 and IV could refer to more
voltage dips in most ship power systems due to their un- symmetrical operating conditions, although in I3 and IV the
grounded nature. In case of a faulted phase, the load is still three phases can be within the limits but of different values.
supplied via the healthy ones –which is the main reason of On the other hand, the other cases refer to highly unba-
installing the ungrounded system onboard- but at a signifi- lanced ones with at least one zero value - due to short
cantly higher voltage level for both phases, namely ˇ3 or circuit fault. Moreover, while I0 corresponds to balanced
1.73p.u (see Fig 4). Therefore, the system suffers from a three-phase faults, category III mainly refers to single-phase
voltage swell rather than a dip, which stresses equipment fault conditions in the unearthed ship grounding system,
insulation. which as mentioned leads to an overvoltage to the remain-
Summarizing, voltage dips due to faults are: ing healthy phases.
Furthermore, as it can be observed, there is also an
• rectangular: voltage recovers fast after fault clearing
inherent hierarchy introduced in terms of how significant -
operation
in descending order - each situation is. Therefore the classi-
• symmetrical or asymmetrical: depending on the type of
fied categories, can be written in the following order:
fault that caused them.
I0 . I1 . I2 . I3 . II1 . II2 . III . IV (2)

CLASSIFICATION METHOD OF FAULT This method can be extended and include other types of
INDUCED VOLTAGE DIPS voltage dips as explained in the following.
The ‘Classification Method’ developed in6 , for the system of
Fig 1, is summarized in Table 1. There are eight different
Induction Motor Dips
Downloaded by [195.29.81.98] at 22:40 25 July 2016

categories introduced based on symmetry among phases and


voltage rms magnitude in all three phases. This classification The start-up of an induction motor takes current five to six
approach aims to provide the system operator with a practi- times larger than normal. This current remains high until
cal tool to quickly form a clear picture of the system state. the motor reaches its nominal speed; this lasts from several
The limit value of 80% has been rather arbitrarily set as the seconds to one minute. The characteristics of the corre-
minimum voltage level required for the affordable operation sponding voltage dip depend on the induction motor data
of most electric equipment (including both static and rotary, (size, starting method, load, etc) and the strength of the
three- phase and single-phase loads), but is subjected to system at the point the motor is connected. The magnitude
modification. Thus, common practice suggests that this of the dip depends strongly on the system parameters. The
threshold value could vary from 75% up to even 90%. duration of the voltage dip due to motor starting depends on
a number of motor parameters with the most important
being the motor inertia3 . The duration of the dip is pro-
longed if other motor loads are connected to the same
busbar, as they keep the voltage further down.
Fig 5 shows a voltage dip caused by the starting of a
medium voltage auxiliary propulsion motor of 1.4 MW by
an 8MVA generator. It can be seen that voltage drops to
0.85pu and gradually recovers approximately 1 sec after.
The voltage dip is the same for all three phases.
Large power motors starting consecutively during ship
maneuvering (e.g. driving thruster systems) can cause such
severe voltage dips.

Fig 4: Voltage dip (swell) due to a 1-phase fault

Category Phase A Phase B Phase C


(% Vn) (% Vn) (% Vn)
I0 0.00 0.00 0.00
I1 0.00 0.00 , 80%
I2 0.00 , 80% , 80%
I3 , 80% , 80% , 80%
II1 , 80% , 80% 100%
II2 , 80% 100% 100%
III 0.00 . 100% . 100%
IV .80% and .80% and .80% and
,100% ,100% ,100%
Table 1: Voltage dips of ‘Classification Method ‘ Fig 5: Voltage dip due to motor starting

4 Journal of Marine Engineering and Technology No. A11 2008


Introducing a classification method of Voltage dips in ship electric energy systems

Summarizing, voltage dips due to induction motor start-


ing are:
• non-rectangular: voltage recovers gradually
• symmetrical: all phases present the same behaviour.
Consequently, considering the classification method pre-
sented above, the voltage dip due to motor starting can be a
symmetrical category, i.e. either I3 or IV (symmetrical case
I0, as already mentioned, with zero voltage in all three-
phases corresponds to faults rather than other cases).

Transformer Saturation Dips


When a transformer is energised under a no-load condition, Fig 6: Voltage waveforms during transformer energizing (top)
the magnetizing current necessary to maintain the magnetic and corresponding voltage rms magnitude
flux in the core is in general only a few percent of the
nominal rated load current.
During transformer energising, a transient occurs to
change the flux in the core to the new steady state condi-
tion. In general this will cause the flux to go above the
saturation value once each cycle until the average value of
Downloaded by [195.29.81.98] at 22:40 25 July 2016

the flux over a cycle has decayed to nearly zero. This


temporary over-fluxing of the transformer core causes high
values of the magnetizing current, which is highly asymme-
trical and decays exponentially. This phenomenon is known
as magnetising inrush current and its magnitude depends on
the point on the wave where the energization switching
takes place and the core residual flux.
As the core is forced into saturation the transformer
draws a large current from the supplying network. When
the voltage reverses its polarity in the next half cycle, the Fig 7: Voltage harmonics in time due to transformer
maximum flux in the core is less than the maximum flux saturation
density in the no-load situation. The transformer inrush
current is therefore asymmetrical and contains a DC com-
ponent, which might take seconds to disappear depending Consequently considering the classification method pre-
on the damping of the system 5 . The voltage dip caused by sented above, the voltage dip due to transformer energizing
the magnetising inrush current can be long in duration and inrush can be any non-zero but also non-symmetrical cate-
drive other near-by transformers into saturation (sympa- gory i.e. I3, II1, II2 or IV (in case I3 and IV).
thetic saturation7,8 ). In general, any voltage change in the The harmonic distortion caused by transformer satura-
transformer terminals (like a voltage dip) could lead it into tion can lead to more severe dips if any system resonance is
saturation due to the resulting transient in the core. excited. Fig 8 shows the voltage dip occurring when the
Fig 6 presents a transformer saturation voltage dip same transformer as above is energized through a busbar
caused by the energizing of a transformer in the network of where a 3rd harmonic filter (single-tuned filter) is con-
Fig 1. A sharp voltage drop (approximately 0.2pu for the
worst phase) is followed by a gradual recovery. As can be
seen in Fig 7, the voltage presents temporary harmonic
distortion. The Short Time Fourier Transform has been used
for the estimation of the harmonics (from 2nd to 5th ) of the
voltage of one of the phases of Fig 6. The 2nd harmonic is
contributing the most. This increased harmonic distortion
can cause undesired protection operation.
Summarising, voltage dips due to transformer saturation
are:
• non-rectangular: voltage recovers gradually as the in-
rush current decays
• non-symmetrical: each phase presents a different de-
gree of saturation
• rich in harmonics: due to the asymmetry of the inrush Fig 8: Voltage waveforms during transformer energizing (top)
current. and corresponding voltage rms magnitude

No. A11 2008 Journal of Marine Engineering and Technology 5


Introducing a classification method of Voltage dips in ship electric energy systems

nected. The 3rd harmonic filter causes a parallel resonance eral case studies, it can be elicited 20
that, voltage dips due
in a frequency slightly lower than the 3rd harmonic and the to pulsed loads starting are:
harmonics of the transformer inrush current are amplified
leading to a more severe dip (0.1pu lower than before). • non-rectangular: voltage and frequency recover gradu-
Considering that the use of harmonic filters is extended ally
in ship systems due to the multiple use of power converters • symmetrical: all phases present the same behaviour
this example shows that these filters must be disconnected • periodical or quasi-periodical : the phenomenon is re-
during transformer energizing, a practice followed in many peated on a rather constant time basis, hence, modula-
industrial power systems. tion in frequency and voltage waveforms is noticeable.

Consequently considering the classification method pre-


sented above, the voltage dip due to pulsed loads can be
Voltage dips due to Pulsed Loads any symmetrical category, i.e. either I3 or IV (symmetrical
The recently introduced concept of pulsed loads can be case I0, as already mentioned, with zero voltage in all
regarded as a particular voltage dip case. More three-phases corresponds to faults rather than any other
specifically10-11,20, a limited but increasing number of loads case).
installed aboard tend to have an extremely high power (or Finally, it is highlighted that this kind of voltage dip is
current) demand for a very short time interval, followed by provoked by specific equipment type well located in the
almost zero demands for longer intervals. This behaviour is electric grid, while in all cases the pulsed load is installed
repeated on a periodic or quasi-periodic basis. As represen- along with a dedicated intermediate power supply unit (e.g.
tative examples the railguns, radars and the electromagnetic a flywheel) aiming at alleviating the adverse consequences
launchers (EMALS) can be referred. In Fig 9 a typical of the entire phenomenon.
Downloaded by [195.29.81.98] at 22:40 25 July 2016

phenomenon caused by a pulsed load is shown.


The aforementioned high valued current flowing
through the system impedances provokes a significant vol-
tage drop, in a manner similar to the one discussed in the EXPLOITATION OF DIP
previous sections. Furthermore, in this particular case, due CLASSIFICATION METHOD
to the finite ship electric energy generation capacity, the The classification method discussed so far can be exploited
high power demand affects also system frequency, resulting among others as a handy implement for assessing the opera-
thus in a frequency drop, too, (see Fig 9). The periodic tion status of the ship system based on representative meas-
fluctuation of voltage and/or frequency is often met in many urements of limited number.
shipboard standards (STANAG 1008, IEEE 45 and USA More specifically, it can be integrated into a Power
MIL-STD-1399) as ‘modulation’. Quality Monitoring (PQM) module which can be part of the
Concerning quantifying voltage or frequency modula- Electric Power Control and Management System (EP-
tion the difference between maximum and minimum value CAMS). In this way, all major electric quantities can be
is used as a percentage of the double of the nominal value monitored and recorded leading to protection scheme eva-
as shown in Equation (3): luation, damage or even maintenance assessment. Thus, any
Vmax  Vmin fmax  fmin event occurred as soon as identified, analysed and located
˜V ¼ , ˜f ¼ (3)
2Vn 2fn can trigger possible scenarios of courses of actions. For
instance, the fault induced voltage dips are the most severe
Frequency and voltage modulation may affect the operation ones as they lead to the most adverse consequences com-
of several subsystems of a ship such as radarscopes, com- prising, insulation failures, fuse blowing, equipment or net-
munication equipment, missile guidance systems, weapon work damages, etc, necessitating urgent maintenance
systems, gear systems etc 3 . Anyhow, by investigating sev- actions with several economical implications.

Fig 9: Voltage and frequency modulation

6 Journal of Marine Engineering and Technology No. A11 2008


Introducing a classification method of Voltage dips in ship electric energy systems

The other types of voltage dips which are more equip- ing the actual events via some extra features of theirs, e.g.
ment dependent, do not involve the maintenance and cost the waveshape and the symmetry among phases. Further-
components to that extent referring more to abnormal oper- more, the features in italics are the ones that can be
ating conditions rather than possible destructions. Anyhow, exploited in the easiest way as a means to identify the
the electric system operator can be assisted to assess the phenomenon causing the voltage dip. Hence, for instance,
importance of the situation locating and identifying the while transformer energization is mainly characterized by
problems due to the events monitored in conjunction with the transient 2nd harmonic developed, still only the voltage
other monitoring systems, e.g. insulation monitoring sys- waveshape in conjunction with the lack of balance among
tems which mostly help identifying single-phase faults. phases suffice for its identification. On the other hand, dips
due to pulsed loads can be uniquely traced via the periodic
nature of their associated modulation. Anyway, following
On identifying voltage dips this approach an expert system could identify the event type
In order to show how the voltage dip classification method based only on measurements of phase voltages, as figura-
presented can be further exploited e.g. by being integrated tively shown in Table 4.
in a PSQ Monitoring sytems, Table 2 summarises the dip As already mentioned, 2nd harmonic criterion is not
categories versus possible causes as presented in the pre- really necessary as the combination of non-symmetrical
vious sections. It can be seen that in most cases there more non-rectangular voltage dip suffices for identifying transfor-
than causes resulting in the same dip type. However, as mer voltage dip. Furthermore, frequency modulation identi-
shown in Table 3, there are more than one ways of identify- fication can be done fairly easy by a frequency monitoring

Dip Phase A Phase B Phase C possible cause


Downloaded by [195.29.81.98] at 22:40 25 July 2016

Category
(% Vn) (% Vn) (% Vn) fault motor starting transformer pulsed load
I0 0.00 0.00 0.00 Yes No No No
I1 0.00 0.00 ,80% Yes No No No
I2 0.00 ,80% ,80% Yes No No No
I3 ,80% ,80% ,80% Yes Yes Yes Yes
II1 ,80% ,80% 80%-100% Yes No Yes No
II2 ,80% 80%-100% 80%-100% Yes No Yes No
III 0.00 .100% .100% Yes No No No
IV 80%-100% 80%-100% 80%-100% Yes Yes Yes Yes
Table 2: Dip categories versus possible causes

event waveshape symmetry among 2nd harmonic Voltage-Frequency Modulation


phases
fault rectangular yes/no no
motor starting non-rectangular yes no
transformer energization non-rectangular no yes
pulsed load non-rectangular yes yes
Table 3: Characteristic features of dip provoking events

Dip Category waveshape symmetry among Voltage-Frequency Event type


recognised phases Modulation
I0 Fault
I1 Fault
I2 Fault
I3 Rectangular Fault
I3 Non-Rectangular Yes Motor Start
I3 Non-Rectangular No Transformer Energization
I3 Yes Yes Pulsed Load
II1 Rectangular Fault
II1 Non-Rectangular Transformer Energization
II2 Rectangular Fault
II2 Non-Rectangular Transformer Energization
III Fault
IV Rectangular Fault
IV Non-Rectangular Yes Motor Start
IV Non-Rectangular No Transformer Energization
IV Yes Yes Pulsed Load
Table 4: Event type identification based on voltage dip classification

No. A11 2008 Journal of Marine Engineering and Technology 7


Introducing a classification method of Voltage dips in ship electric energy systems

system –always installed onboard- in the case of pulsed are also active. Anyhow, each fault situation is characterized
loads. On the other hand, the fault type can not be traced and, hence can be identified in a sole unique way by the
unless the system topology is well known and several short- combination of category type per monitored bus. For exam-
circuit conditions have been thoroughly studied. As shown ple, the case of:
in the following this thorough approach also assists in locat-
ing the fault incident. Thus, in the case-study of the car-
• Main Bus at IV
passenger ferry of Fig 1, the results of the fault induced
• Pod1 at IV
voltage dips analysis are presented in Table 5. More specifi-
• Pod2 at IV
cally, the results of voltage dip classification for all buses
• Bow thruster 1 at I0
and all fault combinations are summarized. It is noted, that
• Bow Thruster 2 at IV
letters ‘A’, ‘B’, ‘C’ stand for the corresponding phases and
• Service Load at IV
‘G’ stands for the ground, i.e. any ship hull metal part. corresponds only to three-phase fault at the bus of Bow
Moreover, in operation ‘at sea’ no thruster buses are taken Thruster 1. Furthermore, in this way, besides the fault type,
into consideration, while in ‘Harbor’ operation, no propul- the faulted point is located also.
sion buses are considered at all.
As can be deduced from Table 5, the voltage dip types
occurred are more dependent on the network topology
On integrating the voltage dip classification method
rather than the loading conditions according to the opera- in monitoring systems
tion profile. This is mainly due to the wide range of values For a shipboard system which is relatively small compared
set at the categorization. Moreover, it can be deduced that to terrestrial power systems, a small number of monitors are
the closer to the faulted bus a monitored point is, the capable to provide the necessary information for identifying
Downloaded by [195.29.81.98] at 22:40 25 July 2016

severest voltage dip is subjected to. The most representative the type and the origin of an event by combining the meas-
case is covered during manoeuvering where bow thrusters urements from different locations. Although there is a num-

Main Bus Pod1 Pod2 Bow Thruster1 Bow Thruster2 Service Load
At Sea Fault at AG III IV IV IV
main bus AB I3 I2 I2 I2
ABG I1 I2 I2 I2
ABCG I0 I0 I0 I0
Fault at AG IV III IV IV
Pod1 bus AB I3 I3 I3 I3
ABG I3 I1 I3 I3
ABCG I3 I0 I3 I3
Fault at AG IV IV IV III
Service AB I3 I3 I3 I3
Load bus ABG I3 I3 I3 I1
ABCG I3 I0 I0 I0
Maneuvering Fault at AG III IV IV IV IV
main bus AB I3 I2 I2 I0 I2
ABG I1 I2 I2 I0 I2
ABCG I0 I0 I0 I0 I0
Fault at AG IV III IV IV IV
Pod1 bus AB I3 I3 I3 I3 I3
ABG I3 I1 I3 I3 I3
ABCG I3 I0 I3 I0 I3
Fault at AG IV IV IV III IV IV
Bow AB IV IV IV I3 IV IV
Thruster ABG IV IV IV I1 IV IV
1 bus ABCG IV IV IV I0 IV IV
Fault at AG IV IV IV IV III
Service AB I3 I3 I3 I1 I3
Load bus ABG I3 I3 I3 I1 II1
ABCG I3 I0 I0 I0 I0
Harbor Fault at AG III IV
main bus AB I3 I2
ABG I1 I2
ABCG I0 I0
Fault at AG IV III
service AB I2 I3
load bus ABG I2 I1
ABCG I0 I0
Table 5: Analysis of fault induced voltage dips in the case study of Fig 1

8 Journal of Marine Engineering and Technology No. A11 2008


Introducing a classification method of Voltage dips in ship electric energy systems

ber of reasons for measuring current, in terms of the events voltage signature by detecting points of change and by
presented in this paper, voltage measurements are adequate processing the different segments in an expert system fra-
for analysis and identification purposes. This simplifies mework. This work is presented in21 . Such methods simpli-
significantly the requirements for the equipment. fy considerably the analysis of the measurements obtained
In recent years, the developments in microprocessing by monitoring systems.
and communications led to monitoring systems of low cost. As power quality becomes critical in shipboard systems,
Fig 10 presents a monitoring system for voltage dip events a monitoring system apart from voltage events can record
for a shipboard power system. It consists of monitoring (by adding a few more elements) and store periodically:
equipment, voltage transformers (if not already available for
protection purposes), communication links for transferring
• Voltage rms
the monitoring data and a central process unit that will
• Harmonics (individual harmonics and total harmonic
distortion by performing Fourier Transform on the vol-
accommodate and process the data. Data mining software
tage waveforms)
(for example an expert system) can be used to combine the
data in order to provide decision support information (type
• Unbalance (by calculating the indices described in the
relevant standards).
of event, origin, impact of the event etc) for the system
operator.
As the cost of storing the recordings is low (the cost of
data storage technology presents a decreasing trend), the CONCLUSIONS
utilization of such a system will create a database of record- This paper presents an introduction to the analysis and
ings-measurements that can be exploited in many ways. classification of voltage dips in ship electric power systems.
Firstly, the recordings can be used to evaluate and tune the The method followed takes into account all major voltage
Downloaded by [195.29.81.98] at 22:40 25 July 2016

available models of the power system components used for dip types occurring in ship electric power systems and can
simulation purposes. By making the necessary additions- be a handy tool for assisting the system operator to assist
changes in these models more accurate results can be the operating conditions. Furthermore, it is shown that this
obtained when for example, predicting the impact of new method can be used as an implement to identify the voltage
equipment on board. dip type and location by an expert Power Quality monitor-
Furthermore, useful knowledge can be extracted by this ing system or as an evaluation tool of the protection scheme
database for the evaluation of the protection system opera- performance. The only prerequisite information is a non-
tion of the power system. Voltage dips are linked with expensive multi-phase on-line voltage monitoring system of
protection in two ways: (a) the duration of fault induced major ship network buses - recording voltage rms magni-
dips depends on the time it takes for protection system to tude and waveshape as well as symmetry among phases.
isolate the faulty part of the system (b) transformer and This monitoring system has to be accompanied by a series
motor dips can cause protection maloperation. The record- of off-line voltage dip incident simulations which help to
ings can reveal situations of slow protection operation or locate the incidents in a precise manner.
situations where protection operated under non-fault condi-
tions. This knowledge can be used to improve the protection
system performance. ACKNOWLEDGEMENTS
Voltage dip classification in terms of origin (fault, trans- The work of this paper is part of the research project
former, motor) can be automated using signal processing ‘Pythagoras-I’’’ within the ‘Operational Programme for
techniques to extract voltage rms magnitude, segment the Education and Initial Vocational Training - EPEAEK-II’-
frame. The Project is co-funded by the European Social
Fund (75%) and Greek National Resources (25%).

REFERENCES
1. Hatzilau IK, Prousalidis J, Styvaktakis E, Kanellos F,
Perros S, Sofras E. 2006. Electric power supply quality
concepts for the All Electric Ship (AES), Proceedings of
2006 World Marine Transport Technology Conference, Lon-
don (UK).
2. Hatzilau IK, Prousalidis J, Styvaktakis E, Sofras E.
2005. Voltage and Current Spikes & Transients - Power
Supply Quality aspects for the AES, Proceedings of 2005
All Electric Ship Symposium (AES2005), Paris (France).
3. Bollen MHJ. 1999 Understanding power quality pro-
blems: voltage sags and interruptions, IEEE Press, N.Y.
4. Amy JV. 2002 Considerations in the design of naval
electric power systems, Proceedings of the Power Engineer-
ing Society Summer Meeting, vol. 1, pp 331-335, 2002.
Fig 10: Monitoring system for onboard power systems 5. Styvaktakis E, Bollen MHJ. 2003 Signatures of vol-

No. A11 2008 Journal of Marine Engineering and Technology 9


Introducing a classification method of Voltage dips in ship electric energy systems

tage dips: transformer saturation and multistage dips, IEEE tional Conference on Power Systems Transients (IPST),
Trans. on Power Delivery, 18-1:265-270. New Orleans (USA).
6. Spagkouros S, Prousalidis J. 2004. Electric Power 15. Moschakis M, Prousalidis J, Hatziargyriou N. 2004.
Quality problems in ship systems: A classification method, Performance Assessment of STC used for Alternative Naval
IASME Transactions, 1-2: 337-342. Power Supplying Units , IASME Transactions, 1-2: 394-399.
7. Bronzeado HS, Brogan PB, Yacamini R. 1996. Har- 16. Whitehead D, Fischer N. 2005. Advanced Commer-
monic analysis of transient currents during sympathetic cial Power System Protection Practices Applied to Naval
interaction IEEE Transactions on PowerSystems, 11-4: Medium Voltage Power System. Proceedings of Electric Ship
2051–2056. Technologies Symposium, Philadelpia (USA).
8. Prousalidis JM, Georgopoulos AG, Hatziargyriou ND, 17. Butler KL, Sarma NDR, Whitcomb C, Do Carmo H,
Papadias BC. 1997. Investigation of Transformer Sympa- Zhang H. 1998, Shipboard systems deploy automated pro-
thetic Inrush, Proceedings of 2nd International Conference tection, IEEE Computer Applications in Power, 11-2:31-36.
on Electromagnetic Transients, IPST ’97, Seattle (USA), 18. Vallianatos P, Prousalidis J, Styvaktakis E. 2006. On
pp. 197-202. starting-up large power motors rotating high inertia loads
9. IEEE Standard 45-1998, IEEE Recommended Prac- in autonomous systems, Proceedings of International Con-
tice for Electrical Installations on Shipboard. ference on Electric Machines (ICEM-2006), Chania
10. STANAG 1008, Characteristics of Shipboard Elec- (Greece).
trical Power Systems in Warships of the North Atlantic 19. Prousalidis J, Styvaktakis E, Sofras E, Hatzilau IK,
Treaty. Muthumuni D. 2007. Voltage dips in ship systems, Proceed-
11. USA MIL-STD-1399(NAVY), Interface standard ings of 2007 Electric Ship Technology Symposium, Ana-
for Shipboard systems – Section 300A – Electric Power, heim (USA).
Downloaded by [195.29.81.98] at 22:40 25 July 2016

Alternating Current. 20. Kanellos F, Hatzilau IK, Prousalidis J, Styvaktakis


12. IEC-60092/101. 1994. Electrical installation in E. 2006. Simulation of a Shipboard Electrical Network
Ships - Definitions and General Requirements. (AES) Comprising Pulsed Loads, Proceedings of Interna-
13. TC3 of the Information Technology Industry Coun- tional Symposium Engine as a Weapon II, London (UK).
cil (ITIC). 2000. ITIC (CBEMA) Curve. 21. Styvaktakis E, Bollen MHJ, Gu IYH. 2002. Expert
14. Samineni S, Johnson B, Hess H, Law J 2003. ‘‘Mod- system for classification and analysis of power system
eling and Analysis of a Flywheel Energy Storage System events, IEEE Transactions on Power Delivery, 17-2:423–
with a Power Converter Interface, Proceedings of Interna- 428.

10 Journal of Marine Engineering and Technology No. A11 2008

You might also like