COMMENTS SHOULD BE READ IN CONJUCTION

WITH COMMENTS MADE ON THE SHOP


DRAWINGS

ALL COLUMN
LONGITUDINAL
REINFORCEMENT
NEEDS TO COG TO
THE TOP
REINFORCEMENT
OF THE BEAM

ADDITIONAL N32
BARS

4-SIDE FACE BARS


AS PER SDA.

N32 BARS COGGED


CONTRACTOR'S DOCUMENT REVIEW
Review of this document has been carried out only for general
TO THE TOP
conformance with the design intent and general compliance with
contract documents. Such review does not relieve the Contractor of EXTEND GROUT REINFORCEMENT
contractual obligations including ensuring that the work is compliant,
complete, accurate and correct. This review indicates that the TUBES FOR 4 IN THE BEAM
document is considered:
NUMBER STARTER
Satisfactory BARS (2 EACH 1300 LONG WITHIN
Satisfactory subject to comments being incorporated SIDE) INTO THE PRECAST
PRECAST COLUMN COLUMN.
✔ Satisfactory subject to comments being incorporated, amend
and resubmit BELOW.
Not Satisfactory - check comments, amend and resubmit

CHECKED BY MR DATE 9/25/2019