Operation
Setting Levels Diagram
This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some
parameters are not displayed depending on the protect level setting and the conditions of use.
Control stops when you move from the operation level to the initial setting level.
Basic Type
E5CN/E5CN-U/E5AN/E5EN/E5GN
Power ON
Start in manual mode.
*4
Press the PF Key Press the O Key for at
least 3 s. (Display will flash
Manual for at least 1 s.
Control Level
c
25 after 1st second.)
Press the 100 Protect Level
O Key for
at least 1 s. *1
Note: The time taken to
move to the protect
Communica- level can be adjusted
Initial Setting tions Setting by changing the
Control stops. Level “Move to protect level
Press the
Level
time” setting.
O Key for less than 1 s.
Advanced Function
Setting Level
Control in progress
Input password.
Control stopped
Turn the power OFF then back ON again. If the display remains the same, the controller
Memory
e111 (E111) error
must be repaired. If the display is restored to normal, then a probable cause can be
external noise affecting the control system. Check for external noise.
OFF OFF
Note: If the input value exceeds the display limit (-1999 to 9999), though it is within the control range, will be displayed under -1999 and
above 9999. Under these conditions, control output and alarm output will operate normally.
For details on the control range, refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156).
*1. If the control output is assigned to the transfer output and the transfer output type is set to the present value, the upper limit value will be output
for the present value when there is an input error.
*2. Errors are shown only when the display is PV, PV/SV, or PV/MV. Errors are not shown for any other status.
1
Operation for E5@N/E5@N-H/E5@N-HT
Advanced Type
E5CN-H/E5AN-H/E5EN-H
Power ON
Start in manual mode.
Communica-
Control stops. Initial Setting tions Setting
Level Level
Press the
O Key for less than 1 s.
Control stopped
*2
Calibration Level Not displayed for some models
Level change
*1. You can return to the operation level by executing a software reset.
*2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel.
It can be done only by first turning OFF the power.
*3. From the manual control level, key operations can be used to move to the operation level only.
*4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H).
*5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H).
2
Operation for E5@N/E5@N-H/E5@N-HT
Programmable Type
E5CN-HT/E5AN-HT/E5EN-HT
Power ON
Start in manual mode.
Press the O+
Operation Program M Keys for at
Level Setting Level Press least 1 s.
Press the the O +
O Key less than 1 s. M Keys
a-m Press the
O Key less
for at
c
25.0
Press the least 3 s. 100.0
than 1 s.
O Key less than 1 s. (Display
Press the O Key will flash
for at least 3 s while after 1st
a-m is displayed. PID Setting Adjustment second.)
(a-m will flash after
Manual 1st second.) Level Level
mode Press the
O Key less
than 1 s.
Press the PF Key
Manual for at least 1 s. Protect Level
Control Level Monitor/Setting
Item Level
Note: The time taken to
move to the protect
level can be adjusted
Press the O Key for at by changing the
Press the O Key least 3 s. (Display will flash “Move to protect level
after 1st second.)
for at least 1 s. c
25.0 time” setting.
100.0
Communica-
Control stops. Initial Setting tions Setting
Level Level
Press the
O Key for less than 1 s.
Advanced Function
Setting Level
Control stopped
3
Operation for E5@N/E5@N-H/E5@N-HT
Parameters
Basic Type
E5CN/E5CN-U/E5AN/E5EN/E5GN
Some parameters are not displayed depending on the
model of the Controller and parameter settings.
PF Key *2
For details, refer to the E5CN/E5AN/E5EN/E5GN
Power ON
Digital Temperature Controllers User's Manual Basic
Type (Cat. No. H156). Starting in manual mode.
Starting in Press the O Key for at least 3 s. PF Key *2
Manual Control Level automatic Other than the Auto/Manual Switch display
mode. Initial Setting Level
Press the PF Key for Press the O
at least 1 s. *1 PID Key or the PF
C
25 Control Key for at least Press the Press the O Key less than 1 s.
only 1 s. O Key for
*1 at least 1 s.
PV/MV in-t Input Type
Press the O Key less than 1 s. 5
Adjustment M
Level Operation Level Scaling Upper Limit
in-h
Press the O Key less than 1 s. 100
C
Process Value r-s RUN/STOP M
25 Added when Additional
PV display is ON. run in-l Scaling Lower Limit
Adjustment Level 0
M M
Note: The time taken to move to the protect Note: Displayed only for models with communications.
M M level can be adjusted by changing the Changes are effective after cycling power or 0.2
Hysteresis
"Move to protect level time" setting. after a software reset.
C
sp-0 SP 0 mv-s MV at Stop
M
0.0
0 pmov Move to Protect Level:
M Displayed only when a password
0 is set. Restricts moving to protect psel Protocol Setting:
M MV at PV Error
Switches between
cwf CompoWay/F (SYSWAY)
level.
C
sp-1 SP 1 mv-e M and Modbus.
0.0 M
0 Operation/Adjustment Protect:
M
SP used by
M oapt Restricts displaying and u-no Communications Unit No.
multi-SP modifying menus in operation,
0 adjustment, and manual control 1
C
sp-2 SP 2
C
sprt SP Ramp Set Value levels.
0 off M Initial Setting/ M
Communications
M M icpt Communications Protect: bps Baud Rate
This protect level restricts movement CompoWay/F
MV Upper Limit 1 to the initial setting, communications 9.6
C
sp-3 SP 3 ol-h (SYSWAY) only
*1. When the PF Setting
105.0 M levels.
setting, and advanced function setting M
0
M M wtpt Setting Change Protect: len Communications parameter is set to A-M for a
Protects changes to setups by Data Length
ol-l MV Lower Limit off operating the front panel keys. 7 Controller with a PF Key
-5.0 M M (E5AN/E5EN).
M pfpt PF Key Protect sbit Communications
Stop Bits
4
Operation for E5@N/E5@N-H/E5@N-HT
25
C
Monitor/Setting PF Monitor/Setting PF Monitor/Setting PF Monitor/Setting PF Monitor/Setting
Item Display 1 Item Display 2 Item Display 3 Item Display 4 Item Display 5
0
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).
stop
Assignment 2
M M M M
st-b ST Stable Range a2on Alarm 2 ON Delay sub3 Auxiliary Output 3
svst SV Status Display
C
M Assignment Function
15.0 0 alm3 (E5AN/E5EN only) off
sqr Extraction of Square
Root Enable
off M M M M
alfa α d.ref Display Refresh
M a3on Alarm 3 ON Delay csel Character Select Period
0.25
amov Move to Advanced
Function Setting Level:
0.65 0 on
0 Displayed when initial M M M M
setting/communications
M protect is set to 0. at-g AT Calculated Gain a1of Alarm 1 OFF Delay t-u Soak Time Unit ra1m Control Output 1
ON/OFF Count
0.8 0 m 0 Monitor
Move by setting password (−169).
M M M M
Control Output 2
C
at-h AT Hysteresis a2of Alarm 2 OFF Delay alsp Alarm SP Selection ra2m ON/OFF Count
0.8 0 sp-m 0 Monitor
M M M
M Control Output 1
lcma Limit Cycle MV
a3of Alarm 3 OFF Delay manl Manual MV ra1 ON/OFF Count
Limit Enable
Amplitude
0 0 Alarm Set Value
20.0 off
M M M M
istp Input Shift Type ra2 Control Output 2
inf Input Digital Filter pvrp PV Rate of Change ON/OFF Count
0 Alarm Set Value
ins1 Calculation Period
0.0 4
M M M
M
pvad Additional PV Display mvse MV at Stop and Error
csca
Automatic Cooling rac ON/OFF
Reset
Counter
Addition Coefficient Adjustment
off off 0
off
M M M M
o-dp MV Display amad Auto/Manual Select
ocu Heater Overcurrent cmov Move
Level
to Calibration
Addition Use
off on 0
off
M M M
M
ret Automatic Display rt RT ocl Heater Overcurrent exfn Expansion Functions
Return Time Latch 0
off off off
M M M M
Heater Overcurrent
och Hysteresis
0.1
M
5
Operation for E5@N/E5@N-H/E5@N-HT
Advanced Type
E5CN-H/E5AN-H/E5EN-H
Some parameters are not displayed
depending on the model of the Controller and
parameter settings.
Power ON
For details, refer to the E5CN-H/E5AN-H/
E5EN-H Digital Controllers User's Manual
Advanced Type (Cat. No. H157). Manual Control
Level
Communica-
Initial Setting tions Setting
Level Level
Advanced
Function Setting
Level
d.pid PID8
d.bnk Bank7
8 7
M
c
1.p PID 1 Proportional Band
M M
8.0 c
8.p PID 8 Proportional Band c
0.lsp M
M 8.0 c
0.a 2h
Set either of these parameters
0.0 c
7.lsp Bank 7 SP
1.i PID 1 Integral Time M M 0.0 0.0 c
7.a-2 Bank 7
233.0 8.i PID 8 Integral Time M M 0.0 Alarm Value 2
0.pid
M 233.0
1 M
c
0.a2l 7.pid Bank 7 PID
1.d PID 1 Derivative Time M 0.0 Set No. Bank 7
M 1 c
7.a 2h Alarm Value
40.0 8.d PID 8 Derivative Time M 0.0 Upper Limit 2
c
0.spr M
M 40.0 c M
off 0.a-3 c
7.spr Bank 7 SP
1.olh PID 8 MV Upper Limit M Bank 7
M 0.0 off Ramp Set Value c
7.a2l Alarm Value
105.0
8.olh PID 8 MV Upper Limit
M M 0.0 Lower Limit 2
c
0.a-1
Set either of these parameters
M 105.0
Set either of these parameters
0.0 c
0.a3h c
7.a-1 Bank 7 M
1.oll PID 1 MV Lower Limit M 0.0
M 0.0 Alarm Value 1 c
7.a-3 Bank 7
-5.0
8.oll PID 8 MV Lower Limit c
0.a1h M M 0.0 Alarm Value 3
M -5.0
0.0 c
0.a3l c
7.a1h Bank 7 M
c
1.aut PID 1 Automatic Selection M M 0.0 Alarm Value Bank 7
1320.0 Range Upper Limit
0.0 Upper Limit 1 c
7.a3h Alarm Value
c
8.aut PID 8 Automatic Selection M 0.0 Upper Limit 3
M
c
0.a1l M
1320.0 Range Upper Limit
0.0 0.sok Bank 7
c
7.a1l M
1.csc PID 1 Cooling Coefficient M M 1
Alarm Value Bank 7
1.00
0.0 Lower Limit 1 c
7.a3l Alarm Value
8.csc PID 8 Cooling Coefficient M 0.0 Lower Limit 3
M 1.00
c
0.a-2 M
0.0 c
0.wtb M
1.lba PID 1 LBA Detection Time M off
0
M 7.sok Bank 7 Soak Time
8.lba PID 8 LBA Detection Time M 1
M 0
M
M c
7.wtb Bank 7 Wait Band
off
M
6
Operation for E5@N/E5@N-H/E5@N-HT
Power ON
Press the O
and M Keys for
at least 3 s.
Press the O Key less than 1 s.
M M M M
soak lcr1 al3h Alarm Value
ct2 Heater Current 2
Soak Time Leakage Current 1
0.0 Upper Limit 3
0.0 Value Monitor 1 0.0 Monitor
M M M M
hb2 wt-b Wait Band lcr2 Leakage Current 2
al3l Alarm Value
Heater Burnout
0.0 Detection 2 off 0.0 Monitor 0.0 Lower Limit 3
M M M
M
oc2 mv-s MV at Stop prst Program Start o
Heater Overcurrent MV Monitor (Heating)
50.0 Detection 2 0.0 rset 0.0
M M M M
lcr1 mv-e MV at PV Error sktr Soak Time Remain c-o MV Monitor (Cooling)
Leakage Current 1
0.0 Monitor 0.0 0.0
0
M M M
M
hs1 sprt SP Ramp Set Value v-m Valve Opening
HS Alarm 1 off Monitor
50.0 0.0
M M M
lcr2 ol-h MV Upper Limit
Leakage Current 2
0.0 Monitor 105.0
M M
hs2 ol-l MV Lower Limit
HS Alarm 2 -5.0
50.0
M M PF Key *2
orl
c
ins Temperature Input Shift
MV Change Rate Limit
Monitor/Setting Item Level (E5AN-H/E5EN-H only)
0.0
0.00
M 1-point shift
M
Set either
c
insh db Position Proportional
Upper Limit
Temperature
of these
param- 2.0
Dead Band 25.0 Monitor/Setting
Item Display 1
PF Monitor/Setting
Item Display 2
PF Monitor/Setting
Item Display 3
0.00 Input Shift Value eters. 0.0
M 2-point shift M
PF
c
insl Lower Limit oc-h Open/Close Hysteresis
Temperature 0.8
0.00 Input Shift Value Monitor/Setting PF Monitor/Setting
M M Item Display 4 Item Display 5
Extraction of Square
sqrp Root
0.0 Low-cut Point Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to
5 parameters (advanced function setting level).
M
PF Key *2
*1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H).
*2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H).
7
Operation for E5@N/E5@N-H/E5@N-HT
M 20
s-hc Standard or M
Heating/Cooling
M stnd ev-b Bank Numbers Used
M 1
st ST (Self-tuning) M
For input type of
on temperature, ev-1 Event Input
standard control, or Assignment 1
M PID none
M
Move to Advanced Function
amov Setting Level:
Displayed when initial
0 setting/ communications
protect is set to 0.
M
Move by setting password (−169).
8
Operation for E5@N/E5@N-H/E5@N-HT
Power ON
Manual Control
Level
Communica-
Initial Setting tions Setting
Level Level
Advanced
Function Setting
Level
c
st-b ST Stable Range
M 8.0 M M
15.0 manl
colr PV Change Color M Manual MV
Limit Enable svst SV Status Display
M red off off
Function
c
lbab LBA Band
alfa α M
M 3.0 M
0.65 c
pv-b PV Stable Band M pmvd Direct Setting of
d.ref Display Refresh
M 5.0 off Position Proportional MV Period
out1 Control Output 1 0.25
Assignment
at-g AT Calculated Gain
M o M M
1.0 PV Rate of Change
a1on Alarm 1 ON Delay M pvrp ra1m Control Output 1
M 0 17 Calculation Period ON/OFF Count
0 Monitor
out2 Control Output 2
Assignment
c
at-h AT Hysteresis
M none M M
0.8 csca Automatic Cooling
a2on Alarm 2 ON Delay M ra2m
Control Output 2
M 0 off Coefficient Adjustment ON/OFF Count
0 Monitor
sub1 Auxiliary Output 1
lcma Limit Cycle MV
M Assignment M
Amplitude alm1 M
20.0
a3on Alarm 3 ON Delay
M ocu Heater Overcurrent
ra1 Control Output 1
Use ON/OFF Count
M 0
sub2 Auxiliary Output 2
on
0 Alarm Set Value
Assignment
inf Input Digital Filter M alm2 M M
0.0
a1of Alarm 1 OFF Delay M ocl Heater Overcurrent
ra2
Control Output 2
ON/OFF Count
M 00 off Latch
csel Character Select 0 Alarm Set Value
pvad Additional PV Display M on M M
off a2of Alarm 2 OFF Delay och Heater Overcurrent
M rac ON/OFF Counter
M 0 0.1
Hysteresis Reset
t-u Soak Time Unit 0
M m M M
a3of Alarm 3 OFF Delay pf
M PF Setting
cmov Move to Calibration
0 a-m Level
0
M M M
exfn Expansion Functions
0
M
9
Operation for E5@N/E5@N-H/E5@N-HT
Programmable Type
E5CN-HT/E5AN-HT/E5EN-HT
Some parameters are not displayed
depending on the model of the Controller and
parameter settings.
For details, refer to the E5CN-HT/E5AN-HT/ Power ON
E5EN-HT Digital Controllers User's Manual
Programmable Type (Cat. No. H169). Manual
Control Level
Communica-
Initial Setting tions Setting
Level Level
Advanced
Function Setting
Level
Adjustment Level
Press the O Key less than 1 s.
Press the O Key less than 1 s.
Adjustment Level
Display
Displayed only MV at PV Error
PID Setting Level once when
mv-e
l.adj entering 0.0
Press the O Key less adjustment level. hs2 HS Alarm 2 M
than 1 s. M 50 0
.
ol-h MV Upper Limit
at AT Execute/ M 105 0
.
Cancel
off c Temperature Input
Display PID Selection ins Shift M
d.pid PID1 M 0. 00
1
d.pid ol-l MV Lower Limit
cmwt Communications M 1-point shift Set -5. 0
2 PID2 off
Writing either
c
insh Upper Limit
d.pid Temperature
of these
M
3 PID3 M 0. 00 Input Shift Value param-
M 2-point shift
eters orl MV Change
irda Infrared
Communications
Rate Limit
0. 0
off Use
inslLower Limit
c
d.pid PID8 Temperature M
8 M 0. 00
Input Shift Value
db Position
spmd SP Mode M Proportional
2. 0 Dead Band
M psp c
p Proportional Band M
c
1.p PID 1 Proportional Band M M 8. 0
Fixed SP oc-h Open/Close
8. 0 c
8.p PID 8 Proportional Band fs p M 0. 8
Hysteresis
8. 0 0. 0
M i Integral Time M
PID 1 Integral Time M M 23 3 0
. Extraction of
1.i PID settings sqrp Square Root
23 3. 0 8.i PID 8 Integral Time ct1 Heater Current 1 M
Value Monitor 0. 0 Low-cut Point
0. 0
M 233. 0 d Derivative Time M
M M 400
.
1.d PID 1 Derivative Time
stb Standby Time
40. 0 hb1 Heater Burnout M
8.d PID 8 Derivative Time Detection 1 0.00
0. 0
M 40. 0 c-sc Cooling Coefficient M
M M 1.00
1.olh PID 1 MV Upper Limit psps Program SP
105. 0 oc1 Heater M Heating/cooling Shift Value
8.ol h PID 8 MV Upper Limit Overcurrent
50.0 Detection 1 c
0. 0
M 10 5. 0 c-db Dead Band M
M 0.0
1.oll PID 1 MV Lower Limit M ps0 RSP 0 before
-5. 0 ct2 Heater Current 2 M Correction
8.ol l PID 8 MV Lower Limit Value Monitor
0. 0 Manual Reset Value -200.0
M -5. 0 of-r Clear the offset during M
M 500
. stabilization of P or PD
c
1.aut PID 1 Automatic M control. ps1 RSP 1 before
13 20. 0 Selection PID 8 Automatic hb2 Heater Burnout M Correction
Range Upper Limit
c
8.aut Selection 0. 0 Detection 2 c
hys Hysteresis
-2 00.0
M 1320. 0 Range Upper Limit (Heating) M
M 1. 0
1.csc PID 1 Cooling M M
Hysteresis settings ps10 RSP 10 before
1. 00 Coefficient
oc2 Heater Correction
Overcurrent -2 00.0
8.c sc PID 8 Cooling 50. 0 Detection 2 c
chys Hysteresis
M 1. 00
Coefficient (Cooling) M
M 1.0
1.lba PID 1 LBA Detection M lcr1 Leakage Current 1 M bc0 RSP Broken-line
Correction Value 0
0 Time Monitor 0
8.lba PID 8 LBA Detection 0.0 c
wt-b Wait Band
M 0 Time
M of f
hs1 HS Alarm 1 M bc1 RSP Broken-line
M Correction Value 1
50 0
. MV at Reset 0
mv-r M
M 0. 0
lcr2 Leakage Current 2 M bc10 RSP Broken-line
Correction Value 10
Monitor
0. 0 0
M M
10
Operation for E5@N/E5@N-H/E5@N-HT
Power ON
Starting in manual mode.
Press the O
and M Keys for
at least 3 s.
Press the O Key less than 1 s.
Operation Level
Display Program Selection Press the
d.prg O Key for
d.prg
0
d.prg
1 d.prg at least 3 s.
2 7
c
25.0 PV ct 2 Heater Current 2
0.0 Value Monitor
s-n o Number of Segments
M M
8 Used, 1 to 32 c
25.0 PV/SP lcr 1 Leakage Current 1
Display Segment Selection, END or 0 to 0.0 (See note.) 0.0 Value Monitor
Number of Segments −1 M
d.seg M
d.seg
endd.seg
0 a-m Auto/Manual lcr 2 Leakage Current 2
1 d.se g Switch
7 0.0 Value Monitor
M M
prg Program Number Run/Reset
r-r Press the O
0 rst and M Keys for
M M at least 1 s.
pid PID Set No.
1 styp Segment n Format seg Segment
Monitor
No.
o MV Monitor (Heating)
0 0.0
M ramp
M
M M
c
al-1 Alarm Value 1
Hold Hold
0.0
c
sp Segment n SP c- o MV Monitor (Cooling)
off 0.0
M 0.0
M M
Alarm Upper M
c
Ral1h Limit 1 adv Advance V-m Valve Opening
0.0 c
Rpr Segment n Ramp off 0.0 Monitor
0.0 Rate
M M M
Alarm Lower M Remaining Standby
Ra l1 l
c
Limit 1
stb m
0.0 time Segment n Time 0.00 Time Monitor
M 0.00 M
M
c
al-2 Alarm Value 2 prg t Elapsed Program
Time Monitor
0.0 0.00
M M
Program Link
lin k Destination rptm Program Execution
Alarm Upper
0 Repetition Monitor
c
Ral2h Limit 2
end
0.0 M M
M
ts1 s Time Signal 1 c
rsp Remote SP Monitor
Ral2l Alarm Lower 0 Set Segment 0.0
Limit 2
0.0 M
M Time Signal 1 Heater Current 1
on1 ON Time
ct1
c Alarm Value 3 0.00 0.0 Value Monitor
al-3
0.0 M M
M Time Signal 1
of1
c
Ral3h Alarm Upper 0.00 OFF Time
Limit 3
0.0 M
M ts2s Time Signal 2
Set Segment
c
al3l Alarm Lower 0
Limit 3
0.0 M
M on2 Time Signal 2
Program 0.00 ON Time
Rrp t Repetitions
0 M
Time Signal 2
PF Key *2
of2 OFF Time
0.00
Monitor/Setting Item Level (E5AN/EN-HT only)
PF
Monitor/Setting PF Monitor/Setting
Item Display 4 Item Display 5
PF Key *2
*1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/EN-HT).
*2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/EN-HT).
11
Operation for E5@N/E5@N-H/E5@N-HT
M
d-u ev-2 Event Input
Assignment 2
M c
Communications
none
Setting Change Protect sbit
wtpt 2
Stop Bits M M
off c
sl-h SP Upper Limit
M ev-3 Event Input
Assignment 3
M prty Communications Parity 1300.0 none
even M M
pfptPF Key Protect M SP Lower Limit
off
c
sl-l ev-4 Event Input
Assignment 4
sdwt Send Data Wait Time
-200.0 none
M 20
M M
Parameter Mask Enable M
pmsk cntl PID ON/OFF
on pid
clfl Closed/Floating
M flot
M
Password to Move to Standard or
M
prlp Protect Level:
Password setting
s-hc Heating/Cooling
calb Motor Calibration
0 stnd
off
M M
M
cp Control Period (Heating)
Travel Time
20
mot
30
M M
Control Period (Cooling) Extraction of Square
c-cp sqr Root Enable
20 off
M M
orev Direct/Reverse Operation Tt-u Program Time Unit
or-r h-m
M M
alh1
c Alarm 1 pru Time Unit of
Ramp Rate
Hysteresis
0.2 m
M M
Alarm 2 Type rtsm Reset Operation
alt2 stop
2
M
M
c
alh2 Alarm 2 p-on Operation after Power ON
Hysteresis cont
0.2
M
M
Alarm 3 Type eset Operation at End of Operation
alt3 rst
2
M
M
c
alh3
Alarm 3 pvst PV Start
Hysteresis sp
0.2
M M
Move to Advanced Function
Transfer Output Type amov Setting Level
tr-t 0
off
M
M
12
Operation for E5@N/E5@N-H/E5@N-HT
Power ON
Manual
Control Level
Communica-
Initial Setting tions Setting
Level Level
Advanced
Function Setting
Level
hbu HB ON/OFF a3on Alarm 3 ON Delay rspu Remote SP Enable spdp "PV/SP" Display
Screen Selection
on 0 off 3
M M M M
13