UNIVERSAL CABLES LTD. SATNA (MP.)
TECHNICAL PARTICULAR
S.No. DESCRIPTION 40x 400,
1_ [Manufacturers name & address Unwversal Cables Lia., Satna (WIP)
2_ [Voltage Grade. "19/33 KV
‘3 [Core & cross section (Nox Nom Area in Sq.mm) iC x.400
“4_ [Type & Designation (2s per ISS) ‘aaxWaY
5 [List of standards applicable TS:7088MV2014
6_[Suitablo for systom with
a) Service Voltage SK
[b) Neutral earthing
Eifecively Earthed system
7_[Maximum Conductor Temperature
(a) Continuous (in°c)
90°C
(o) Short tme (in °C)
250°C.
[Conductor
[a] Material to 15-8130 (Clase/Grade)
Tid grade Aluminium (Class-2)
(b) Size (Sq.mm) (Nom. Area)
400.
ic) Nom. No.Nominal diameter of wires in each
|conductor(no./mm) (Before stranding)
5972.97
[(@) Form of conductor (Gircuiar/shaped)
‘Stranded Compacted Circular
[e) Cross sectonal area
‘400 mm* (Nom)
[Maximum allowable temperature conductor during
8. Jovertcading at 25% overioad to 100 hours per year or
1500 hoursinlfe of a cable
Cable can be safely overloaded upto a conductor temp. 130°C for not
more than 100 Hrs. in any 12 consecutive months and not more than
1500 Hrs. during the lfe time of cable
70 |Shielding/screening on conductor
(a) Material
Black Extruded semi-conducing compound
(0) Type.
Extruded
(c) Whether thermosetting? (Ves No)
Yes (Thermoseting)
70 [Insulation
lwith Radiant Curing Process?
(a) Material XLPE as per 1S: 7oseii2011
to) Type Dry cured
(€) Min, Thickness (mm 28 mm.
|G) Whether triple co-extrusion under Single crosshead te
77 |Shielding/screening on insulation
[a) Material ‘Black extruded semi-conducing compound followed by black semi
Ito) Type. ‘conducting tape
[o) Tmexness (mm)
i Non-metallic (Aprox) (Extruded layer) Min. 03 mam
i) Metalic Please refer S. No. 13 (Amour)
[inner shoath
(@) Material
(o) Type,
(c) Thickness (mm) (Min)
(@) ExirudedWrapped
(@) Approx. outside diameter over sheath (Tm)
Not Applicable
73_|Amouring
(a) Material “Single layer of Hard drawn round aluminium wire as par 156130
() Sze (mm) ‘Nom. Diameter of wre - 2.5 mm
(@) Max .G. resistance af 20°O(O/K) 0.124
(9) Max A.G-resistance at 20°C(a/Km) o.124
(| Caealation Enclosed
4 [Overall sheath
(a) Material Exruded PVC (Black colour)
\) Type Type S72 as per 'S'5631/84
[@) Thickness (rm) (Min 2.04
75 [Approx. overall diametor of cable (mm) 540
76_[Stondarg crum length with tolerance of +59 (Mir) TOO ms +/ Se el
“T_|Nel weight of cable (Approx) Ka/Km~ 3530
ai nt rating for standard 1S condition, laid
[a] In ground Temp. 30°C (Amps) 400
b) induct attemp. 30°C (Amps) us
c)Inairat temp. 40°C Amps) 600)
Tp [Charaing current at raed system votage (Amp) Gas
(Approx) (at 19 KV)
NPCL Greater Noida (151019) R1-GTP/Shubham
Revit 18-1015UNIVERSAL CABLES LTD. SATNA (MP.)
TECHNICAL PARTICULAR,
(Sno! DESCRIPTION iexa00
20 [Short circuit current for conductor (Max.)
(a) for 1 sec. (KA) 377
[(b) for 3 sec. (KA) 218
2 [Electrical Parameters
ner 86 reson of Craver aac sana
(e) A.C esisancenmn of Conductor at 90°6 ee
\cuKmApprox.
[c) ReaciancerKiometer (/KR)_(Approx) on
[(d) Capacitance/Kilometar (Approx.) (mF) (Approx) 024
le) Di-electrc losses at rated (Uo/U) system KV, 50
lcycles/sec.in Watvkm/Phase
108.8 (tand = 0,004)
‘1 Tan-detta at 0.5 U,
i) Tandela at Us
iy Tan-delta at 1.5 Us
iv) Tan-detta at 2U,
‘Max. tanb at Uo =0.004
Max. increment of tan6 between 05 Uo and 2 Uo = 0,002
22 |Volume Resistivity at 27°C (Gem)
Min. 1x10"
23, [Recommended min. bending radius (am
20 x overall dia of cable
‘24 [Detatng factors for folowing ambient temp. in
lAidGround ae sou
a) at 30°C Tt 0
(b) at 35°C. 7106 0.94
fc) at asic 0.94 0.87
a) at 50°C. 0.88 0.82
25 | T¥Pe test results of the similar cable to be furnished wit
tender (as specification under Clause-9 of the spec.)
Clause-9 is not applicable for testing. However we refer clause 10.1.
‘of tender specification for type test reports.
[@)_Tests on conductor:
() Tensile test for aluminium)
i) Wrapping test (or aluminivy
[i] Resistance test
(b) Test for Armouring wires [strips
(c) Test for thickness of ingulation and sheath (as
applicable)
()_Tensile stength & elongation at break
(i) Ageing in air oven.
(i) Hottest
[iv Shrinkage test
(v)_Water absorption (Gravimetric)
d) Di-electric power factor test
) As a function of voltage
i AS a function of temperature
[At room temperature
[at oo
[o) Insulation resistance test (Volume resistivity t
NPCL Greater Noida (151019) R1-GTP/ShubhamUNIVERSAL CABLES LTD. SATNA (MP.)
TECHNICAL PARTICULAR,
Eo] DESCRIPTION 7x00
[At 27°C
[at 90°C
(Hosting Gye tat
ig) impulse with standst
[n) High vorage test
i) Flammability fst
2 [abe Drume
(a Length per a (a), TanGS Sau TOR TSE
(B)Terate dum a6 (nn) 2100x650 000
[c)Approx: Siping welt wi cae 704
27 |Safe pulling force (Kg) 30 Nimm* When pulled by pulling eye on conductor
Tax TOPE a 173 Uo for utnelacopince fst and 5 Peat 173U0
28 [Paria diecharge value ae
aaiona data
EE [Wickes of exuded cna aseanig Appoci a
~The weighi mentioned above isthe approx. valve given Tor general guidance of reload Thal may be required tobe handled during
transhipment,Isalation and service. This would Inno way form te criterion for acceptance of the materi
Note Voltage grade is not clear in tender specification hence we have offered cables with 33 KV (E) grade voltage as per email and
attached technical specification
Comment on customer's commented GTP -
$.12 of GTP - Please note that 2s per technical specification and data sheet inner sheath isnot required for single core cable
hence same shall not be applicable.
NPCL Greater Noida (151018) R1-GTP/Shubham aes “UNIVERSAL CABLES LTD. SATNA (M.P.)
CALCULATION OF MAX. RESISTANCE OF ARMOUR
Resistance of armour depend upon
- Number of wire, i.e. 51 wires
- Armour material resistivity at 20°C, Al armour = 28.264 Ohm/Km
~ Lay factor, ie. 1-1
For finding max resistance of armour we use following formula i.e.
fe Resistivity of armour material X Lay factor
f ‘Armour area (No. of wire x Area of one wire) een
Now, we put the value in above formuta,
28. 44
51 x 4.90625
= 0808
: 31.0004 ‘ohmiKm
0.1242 Ohmn/Km
124 OhmiKm
NPCL Greater Noida (151019) R1-GTP/Shubham tat