You are on page 1of 1

Amps X 100 (Plot Ref. kV=0.

415)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 500

300 300

100 100

50 50

30 30

SS6-PCC-FD2A - P
10 OC1 10
P14NB
CT Ratio 1000:1
5 IEC - Standard Inverse 5

Seconds
Seconds

Pickup = 0.8
Time Dial = 0.27
3 3

SS6-MCC305-IC1 - P
OC1
1 REF 615 1
SS6-MCC305-FS1
CT Ratio 1000:1
100A Group 1
.5 IEC Normal Inverse .5
∆ 0.207 s
Pickup = 0.8
Time Dial = 0.18
.3 SS6-MCC305-BC - P .3
∆ 0.201 s
OC1
P143
CT Ratio 1000:1
IEC - Standard Inverse
.1 Pickup = 0.8 .1
Time Dial = 0.09

.05 .05

.03 .03

SS6-PCC-FD2A - 3P
SS6-MCC305-IC1 - 3P
SS6-MCC305-BC - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 (Plot Ref. kV=0.415)


ETAP Star 18.1.1C

Project: Power Sytem Study Date: 28.01.2020


Location: IOCL, Bongaigaon Rev: R2
Contract: 25585806 dt. 27/07/2018 Fault: Phase

You might also like