You are on page 1of 5

24th International Conference & Exhibition on Electricity Distribution (CIRED)

12-15 June 2017

Session 1: Network components

Frequency response analysis for exact


power transformer impedance
ISSN 2515-0855
doi: 10.1049/oap-cired.2017.0296
Masaya Hiraide 1 ✉, Takashi Nakajima 1, Tadashi Koshizuka 1, www.ietdl.org
Hisatoshi Ikeda 2, Yasuhiko Taniguchi 2, Eiichi Haginomori 2,
Noureddine Harid 3, Naji Al Sayari 3, Braham Barkat 3,
Anurag Devadiga 3
1
Tokyo Denki University, Faculty of Engineering, Department of Electrical and Electronic
Engineering, Tokyo, Japan
2
The University of Tokyo, Center for Advanced Power & Environmental Technology (APET),
Tokyo, Japan
3
The Petroleum Institute, Sas Al Nakhl, Abu Dhabi, UAE
✉ E-mail: 16kmj43@ms.denida.ac.jp

Abstract: The frequency response analysis (FRA) of the transformer impedance is known as a diagnosis method for the
damages in a transformer. It is reported the transfer function as FRA. However, the impedance of the transformer cannot
be measured correctly in the high-frequency range when the influence by the stray capacitance becomes large. Also, it is
not obvious the influences of residual flux to the transfer function or the impedance. Here, the exact measurement method
for the FRA of transformer impedance is described. The authors proposed the measurement circuit diagram in which the
influence of the stray capacitance to the earth can be included. In the circuit diagram, the resistance for the current
measurement is connected between the power supply and the transformer terminal. Therefore, it can measure the exact
transformer impedance. The magnetic flux remains in the iron core after the transformer was interrupted. In the FRA
measurement, the residual flux has an effect on the impedance. The residual flux can be removed by supplying attenuated
rectangle voltage waveform. It is cleared the difference of the impedance at the frequency range from DC to resonance
point. The exact transformer impedance will be derived by this proposed measurement method and de-magnetising.

1 Introduction voltage and the current. This is called as FRA hereafter.


The measurement was also conducted by the LCR meter. This is
There are several failure modes in the power transformer. They are called as LCR hereafter. The results of two methods will be
damages caused during the transportations, due to the compared. The new circuit diagram for the FRA measurement is
electromagnetic forces caused by a short-circuit current, caused on proposed. In the new one, the resistor for the current measurement
conductors and insulating materials by over-voltages and due to is connected to the transformer terminal of the voltage application
ages. When the damage is seen from outside and is judged as a and the resistance value is changed. Furthermore, on FRA
failure, it can be removed by repairing. However, the large measurement, it is necessary to take into consideration the
capacity transformer has an iron core and a coil in a tank and the influence of residual magnetic flux (RMF) in the measurement
medium and low capacity transformer has a moulded coil. The using the open-circuit of FRA. The experimental result about the
constructions make the recognition of the damages difficult. influence of RMF in the impedance measurement using the
The frequency response analysis (FRA) of the transformer open-circuit of FRA is described.
impedance is known as a diagnosis method for the damages in a
transformer [1]. The measured result is acquired for the sound one
and compared with the result measured after a transporting, a 2 Transformer failure with reference to frequency
commissioning test, or an operation. The comparison will be the domain
possible diagnosis of the transformer. It is known for measuring
the transformer impedance that the circuit diagram is constructed There are several failure modes for the transformer. The appearances
with a resistor of 50 Ω between the terminal of the transformer differ dependently on the frequency. The failure appearances are
and the earth and the power source of the function generator is summarised for the frequency region in Table 1 [3–5]. The
connected to the other terminal of the transformer and the earth failure mode of the transformer might possibly be estimated by
[2, 3]. The impedance is derived from the current deduced from comparing the frequency response of the measured impedance to
the voltage drop of the resistor and the terminal voltage drop of the one measured for the sound transformer. This method can
the transformer. In the circuit diagram, the current which flows contribute to the diagnosis of the transformer soundness.
through the stray capacitance of transformer does not flow through
the 50 Ω resistance. Therefore, by the circuit diagram, the
impedance cannot be measured correctly in the high-frequency 3 Measurement and experimental method of
range when the influence by the stray capacitance becomes large. impedance
In this paper, the measurement method for the FRA of transformer
impedance and the measured result for the two winding transformer 3.1 Transformer equivalent circuit
as an example are described. The measurement was conducted by
applying the sinusoidal wave with changing the frequency from Fig. 1 shows the equivalent circuit for the two winding transformer.
the function generator and deducing the impedance from the From Fig. 1, it can be seen that the magnetising characteristics are

CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 189–193
This is an open access article published by the IET under the Creative Commons 189
Attribution License (http://creativecommons.org/licenses/by/3.0/)
Table 1 Frequency and failure mode
Frequency range Failure modes

LF < 20 kHz

† core defects
† turn-to-turn short circuit
† degradation of insulation

MF 20 k–400 kHz

† axial winding deformation


† radial winding deformation
† bulk winding movement Fig. 3 Measurement circuit [1]
† turn-to-turn short circuit

between V1 and V2 is obtained. In the low-frequency domain, (1)


HF > 400 kHz is proved correct as the influence of the stray capacitances is
limited [6, 7].
† axial winding deformation The signal of V2 in Fig. 2 is input to an oscilloscope with the input
† radial winding deformation impedance of 50 Ω. It can be converted to the current. When V1 is
† winding looseness
† tum-to-tum short circuit measured by the same way, the impedance can be calculated.
However, in the high-frequency domain, the error becomes large
in the calculation by (1), as the impedance is a few to 10 s kHz near
the resonance frequency domain.

3.3 Experimental results

Fig. 4 shows the measured result of the impedance on the


single-phase transformer of 110 V–3 kV and 60 VA, when the
110 V winding is short-circuited and the high-voltage winding is
connected to the function generator. The measurement diagram is
shown in Fig. 3. The frequency was changed from 10 Hz to
1 MHz. The measured result by using the LCR meter (NF/
Fig. 1 Transformer equivalent circuit ZM2376) is shown in Fig. 4 as well.
Following observations are deduced from Fig. 4:

measured when the secondary winding is open and the voltage (i) Below 100 Hz, the impedance value is constant along with the
applied to the primary winding. This is deduced as the inductance frequency in both measurements. This will be caused by the winding
L0 is far large compared with the leakage impedance l1, due to resistance.
magnetising characteristics. (ii) The impedance increases along with the frequency above
On the other hand, the leakage impedance and the coil resistance 200 Hz. It is caused by the inductance.
can be measured when the secondary winding is short-circuited, as (iii) The local resonances are seen at 20 and 40 kHz.
the voltage is hardly applied to the iron core. (iv) The resonance appears at 300 kHz, above which the impedance
decreases. This is caused due to the capacitance which becomes
dominant.
3.2 Measurement method of impedance (v) The measured data by two methods coincide with each other.
The impedance at the resonance frequency 300 kHz differs. The
Fig. 2 shows the measuring methods schematically. In the IEEE circuit diagram was basically same as the one shown in Fig. 3 for
guide [3], the diagram shown in Fig. 3 is adopted as a circuit the LCR measurement. The reason is considered as follows. The
measuring the frequency response resistance for the current measurement is changed according to the
measured impedance value in the LCR meter measurement case.
 
V  50
k = 20 log10  2   20 log10 (1)
V1 |z + 50|

of impedance. The impedance is calculated by (1) from the voltages


V1 and V2 measured by the circuit shown in Fig. 3. The impedance
change along the frequency is obtained by repeating the
measurement at the different frequencies. From (1), the ratio of k

Fig. 2 Two types of measurement scheme Fig. 4 Measurement results by FRA and LCR meter

CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 189–193
190 This is an open access article published by the IET under the Creative Commons
Attribution License (http://creativecommons.org/licenses/by/3.0/)
However, the resistance is constant as 50 Ω in the measurement case result, the impedance is not correct near and above the resonance
by the function generator. frequency for the transformer used in the experiment of Fig. 4.
The measurement way is basically same as the one shown in
Fig. 3 for the LCR meter. This means that the impedance
3.4 Discussion measurement will not be correct in the high-frequency domain for
the LCR meter measurement.
The influence of the stray capacitance of the transformer is discussed for Fig. 7 shows the measurement circuit diagram in which the
the measurement by the function generator shown in Fig. 3. The influence of the stray capacitance to the earth can be included. In
impedance of the transformer measured from the primary terminal is the diagram, the resistance for the current measurement is
calculated by the Frequency Scan software in the Electro Magnetic connected between the power supply and the transformer terminal.
Transient Program, EMTP, for the circuit of Fig. 5, where the In addition, the resistance value is increased along with the
transformer circuit is expressed by the inductance, the stray capacitance increment of the transformer impedance. The current flows
between the windings, and the stray capacitance from winding to the through the capacitance to the earth can flow the resistance and the
earth. The result is shown in Fig. 6, in which the transformer measurement error is made small around the resonance frequency
impedance is shown when it is measured without the resistance of 50 Ω. when the transformer impedance is big.
Following facts can be deduced from Fig. 6: The relationship of V1 and V2 is shown in Fig. 8 in the circuit of
Fig. 7. The equation to calculate the transformer impedance is
(i) The impedance shows same tendency for the two conditions. described in (2).
(ii) The results are same at the resonance frequency of ‘A’. The transformer impedance can be calculated by measuring V1
(iii) The results differ significantly at the resonance frequency of and V2 with the phase difference between them:
‘B’. When the resistance of 50 Ω is connected from the
transformer terminal to the earth, the resonance becomes unclear. IR = V1 cos u1 − V2 cos u2
(iv) The results by two ways differ in the ‘C’ frequency domain.  
= V1 cos u1 − V2 cos u + u1
The reason is that the current flow through the resistance of 50 Ω  
becomes small as the large current flows through the stray V1 sin u1 = V2 sin u2 = V2 sin u + u1
capacitance to the earth of 100 pF. = V2 sin u cos u1 + V2 cos u sin u1

From the facts, it can be said that the measurement way does not V2 sin u
tan u1 = (2)
give a correct value for the impedance near and above the resonance V2 − V2 cos u
frequency. V2 sin u
u1 = tan−1
V1 − V2 cos u
V2
4 Proposal of measurement method and result by it Z =R·  
V1 cos u1 − V2 cos u + u1
4.1 Proposed method

As is shown in Fig. 5 and discussed previously, the known


measurement way restricts the current through the resistance as the 4.2 Experiment
current flows through the stray capacitance to the earth. As a
The measured results of impedance along with the frequency are
shown in Fig. 9 as R input side where the resistance for the

Fig. 5 Calculation circuit for EMTP frequency scan

Fig. 7 Propose measurement circuit arrangement for FRA

Fig. 6 Calculated results by EMTP frequency scan Fig. 8 Relation between V1 and V2 at Fig. 9

CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 189–193
This is an open access article published by the IET under the Creative Commons 191
Attribution License (http://creativecommons.org/licenses/by/3.0/)
current measurement is connected between the function generator
and the transformer terminal and its value is varied as 50, 470,
and 1 kΩ. The results of Fig. 4 are also shown as R earth side in
Fig. 9.
The following are seen from Fig. 9:

(i) Both data agree almost in the frequency range below 10 kHz.
(ii) The impedance by the resistance of the generator side is lower
than that of the earth side.
(iii) The tendency of (ii) was obtained since the impedance is
calculated correctly by changing the resistance according to the
impedance value with the resister of the generator side.
(iv) In the frequency domain above the resonance frequency, the
impedance is smaller with the resistance of the generator side than
that with the resister of the earth side. This means that the current Fig. 11 Waveform for demagnetisation
through the stray capacitance to earth is measured correctly.
(v) The resonance frequency differs in both cases. One with the
resistance of the earth side is larger than that of the generator side.
The resonance frequency is decided by the transformer inductance
L and the stray capacitance C as shown in Fig. 10. When the
resistance is connected to the earth, the current through the stray
capacitance does not flow in the resistance. The stray capacitance
is small equivalently and the resonance frequency becomes large.

5 Demagnetisation of RMF

The influence on the impedance measurement by RMF is described.


The test transformer is 110 V–3 kV, 60 VA and single-phase type.

Fig. 12 Comparison for with and without RMF

Voltage injection to a transformer was taken as high-voltage


winding, and low-voltage winding was set to the open-circuit.
Moreover, the state of iron core was set to two types; those were
‘without RMF’ and ‘with RMF’. The RMF can be removed by
supplying attenuated rectangle voltage waveform shown in Fig. 11
[8, 9]. The state ‘with RMF’ of an iron core was made by
injecting DC + 5 V into low-voltage winding for ∼60 s. The results
of FRA are shown in Fig. 12.
The following are seen from Fig. 12:

(i) In the range from 10 Hz to the resonance frequency, if frequency


is the same, the impedance with RMF is smaller than the impedance
without RMF.
(ii) The resonance frequency in a state with RMF is higher than a
Fig. 9 Measured result and comparison state without RMF.

The reason why the resonance frequency in a state with RMF is


higher than a state without RMF was reduction in magnetisation
inductance. That is, in (3), since the inductance L became small,
the resonance frequency fr became high:

1
fr = √ (3)
2p LC

6 Conclusions

The measuring system is investigated for the frequency response of


transformer impedance. The following conclusions are deduced.

(i) The current through the stray capacitance cannot be measured


Fig. 10 Explanation of resonance frequency by the conventional measuring system.

CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 189–193
192 This is an open access article published by the IET under the Creative Commons
Attribution License (http://creativecommons.org/licenses/by/3.0/)
(ii) The measurement of the impedance is not sufficiently correct
in the high-frequency domain where the influence of stray 7 References
capacitance becomes negligible. 1 Dick, F.P., Erven, C.C.: ‘Transformer diagnostic testing by frequency response
(iii) The new measuring system is proposed, where the current analysis’, IEEE Trans. Power Appl. Syst., 1978, 97, (6), pp. 2144–2153
through the stray capacitance can be measured. 2 CIGRE A2-26 Technical Brochure: ‘Mechanical-condition assessment of
(iv) The resistance for the current measurement is inserted between transformer windings using frequency response analysis (FRA)’, 2008
3 IEEE Std C57. 149™: ‘IEEE guide for the application and interpretation of
the function generator and the transformer terminal instead between frequency response analysis for oil-immersed transformers’, 2012
the earth and the terminal. 4 Abu-Siada, A., Hashemnia, N., Islam, S., et al.: ‘Understanding power transformer
(v) The resistance value is varied according to the transformer frequency response analysis signatures’, IEEE Electr. Insul. Mag., 2013, 29, (3),
impedance value. The system gives the correct measurement of the pp. 48–56
5 Firoozi, H., Kharezi, M., Rahimpour, H., et al.: ‘Transformer fault diagnosis using
transformer impedance in all frequency domain. frequency response analysis –practical studies’. Asia-Pacific Power and Energy
(vi) Magnetic inductance with RMF is smaller than that Engineering Conf., 2011
without RMF. In the range from 10 Hz to resonance frequency, 6 Ryder, S.A.: ‘Diagnosing transformer faults using frequency response analysis’,
if frequency is the same, the impedance with RMF is IEEE Electr. Insul. Mag., 2003, 19, (2), pp. 16–22
7 Heindl, M., Tenbohlen, S., Velásquez, J., et al.: ‘Transformer modelling based on
smaller than impedance without RMF. The resonance frequency response measurements for winding failure detection’. Proc. of the
frequency in a state with RMF is higher than a state without 2010 ICCMD, A7-3, 2010, pp. 201–214
RMF. 8 Yamagata, Y., Nakata, Y., Uchiyama, M., et al.: ‘A method of demagnetization of
(vii) In order to measure the accurate impedance, de-magnetising transformer (Japanese)’ (National Convention of the Institute of Electrical Engineers
of Japan, 1998), No. 1137
before the measurement is desirable. 9 Abeywickrama, N., Serdyuk, Y.V., Gubanski, S.M.: ‘Effect of core magnetization
(viii) The exact transformer impedance will be derived by this on frequency response analysis (FRA) of power transformers’, IEEE Trans.
proposed measurement method and de-magnetising. Power Del., 2008, 23, (3), pp. 1432–1438

CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 189–193
This is an open access article published by the IET under the Creative Commons 193
Attribution License (http://creativecommons.org/licenses/by/3.0/)

You might also like