Professional Documents
Culture Documents
88 95 Hoek
88 95 Hoek
Acoustic localisation
of partial discharge in
power transformers
Practical experiences with and without the help of UHF measurement technology
Introduction
ABSTRACT
Detecting partial discharges in the insulation system of a power transformer The localisation of Partial Discharge (PD)
at an early stage reduces the risk of total breakdown. One method to detect faults in transformers is often necessary
partial discharges is acoustic measurement. With this technique detection and when such incipient faults are identified.
localisation of partial discharge is possible by placing acoustic sensors on the The measurement of partial dischar-
surface of the transformer tank. The low impact of electrical interferences from ge level in accordance with IEC 60270
outside the measurement set-up constitutes one of the strengths of the acous [1] is a procedure established throug-
tic method. A further advantage is the ability to identify the position of the par- hout the world for quality assurance of
tial discharge source, which is needed to estimate the risk and to enable a fast transformers and is performed as part of
and effective repair. The sensitivity and accuracy of the PD localisation can be the today routine measurements at the
improved with a combination with conventional electrical measurement or with manufacturer‘s factory. If the occurrence
Ultra High Frequency (UHF) measurement method. Since the UHF measure- of PD in the transformer has been deter-
ment method is more advantageous for measurement environments with heavy mined during such a measurement, it is
interferences in the field, the combination with acoustic localisation proves to a matter of urgency to localize the fault,
be useful even in challenging field situations. This article describes the applica- which is often very small, as quickly and
tion of this procedure illustrating it with different practical examples. accurately as possible. Similar applies to
transformers in the field. Here, PD detec-
tion and localisation procedures are gene-
KEYWORDS rally initiated as a result of corresponding
power transformer, partial discharge, acoustic localisation, electrical trigger, indications obtained from the Dissolved
UHF range Gas-in-oil Analysis (DGA) as well as from
„
can harm the insulation and might lead to ween the various materials (pressboard, ly through oil and a good signal quality is
a total destruction of the asset over time.
To prevent such a sudden breakdown and
carry out pre-emptive repairs, PD can be
measured and evaluated.
The combination of UHF measurement
with acoustic localisation proves to be useful
PD measurements are a worldwide accept
ed tool for quality control of high voltage
even in environments with heavy interfer
apparatus. Outside screened laboratories ences in the field
Figure 1. Possible propagation paths of the acoustic PD signal (direct oil-path, steel-wave path and reflection path)
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 89
DIAGNOSIS
„
Figure 2. Principle of acoustic PD localisation with external sensors reference for the acoustic measurement
since the electrical propagation speed is
significantly higher (by a factor of about
Searching for sensor positions which en 100,000). Naturally, this requires a precise
synchronisation between a PD detector
sure that the propagation path is mainly and the localisation system. In such a case,
through oil and a good signal quality are es the equation system used for localisation
sential during the measurement procedure is based on the absolute time approach.
Figure 3 represents the available times for
both procedures respectively; however,
for the sake of simplicity only two acoustic
essential during the measurement proce- signal runtimes measured, using the speed sensors are shown.
dure. The knowledge of the transformer of sound and the known geometrical posi-
inner structure could be helpful for good tions of the sensors on the tank wall. The runtime t1 of a single, electrically trig-
positioning and repositioning of the sen- gered sensor (see Figure 4, left) produces
sors. Exact determination of the signal start a sphere around the sensor position. The
time is particularly important. Reliable spherical radius can be derived from the
Runtime-based localisation determination of the starting point of the product of the sound velocity and the
of PD sources signal is usually only possible if there is measured runtime. Every point on the
an adequate signal quality. Positioning of surface of the spherical surface may repre-
The localisation of PD sources is perfor- the sensors with good contact is therefore sent a theoretical PD fault location inside
med by means of the differences in the very important in choosing locations on the tank.
runtime of the acoustic signal between the the wall at which the measurements can
fault location and various sensors. Possi- be taken with a good signal-to-noise ra- In case of a purely acoustic measurement,
„
ble fault locations are calculated from the tio and low signal attenuation. Familiarity the signal of a single sensor provides too
Figure 3. Absolute and relative time values for the acoustic sensors
little information for a reliable detection. ing previously, and subsequently form Since the above-described method is
Only when a second sensor is used, the circular lines, as an example. based on the assumption of a direct
time difference Δt1,2 can be calculated. In acoustic propagation path with a defined
this case the PD source can be located on The spatial coordinates of the PD source sound velocity between the PD source
a hyperbolic plane between the sensors, as can be estimated, if the ring-shaped lines and the sensor, it is not always possible to
shown in the right-hand section of Figure 4. intersect in one point, as shown in Figure localise precisely the source in practice.
5, by using three acoustic sensors and an The model assumption must be conside-
The significance of the results generally electrical trigger. In the case of pure acou- red as a highly simplified image of the real
increases with the increasing number of stic measurement, additional surfaces, conditions inside a transformer and as a
sensors, as the number of possible solu- which overlap each other, are analogous- result, inaccuracies during the localisa-
tions is reduced. This is based on the fact ly formed, and their intersections may in tion may occur. It has therefore become
„
that the surfaces respectively related to ad- turn be potential locations of the acoustic common practice to optimise the position
ditional sensors overlap with those exist source and thus of the PD fault. of the sensors on the tank wall iteratively.
Here, the aim of positioning the sensors is
to find the optimal sound path between
The significance of the results generally the source and sensor.
increases with the increasing number of Currently utilized UHF pro-
sensors, as the number of possible solu cedures for PD measure-
tions is reduced ment
Mainly two different types of UHF
methods are applied:
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 91
DIAGNOSIS
„ Combination of
different detection
methods provides a
system adaptable to
the respective require
ments.
In Figure 7, the display of a spectrum feed an impulse via a second UHF sen- Figure 8 shows a schematic depiction of
analyser for the measurement range from sor prior to the measurement in order to PD signal spectrum that has been measur
0.1 GHz to 1.8 GHz is shown. The lower identify frequency ranges that are suitable ed across a bandwidth of several hundred
trace of the spectrum shows the noise for a highly sensitive measurement. MHz.
floor including the constantly active ex-
ternal signals. The upper trace shows the When this range has been established, the The envelope curve of the amplitude sig-
combination of PD signals and sporadic centre frequency is adjusted accordingly nal of the broad band measurement with
external interferences. With the frequen- and the bandwidth of e.g. 3 MHz (tuned fixed bandwidth is transferred directly
cy linearly depicted, the amplitude is dis- narrow band) or higher (tuned medium to the PD measurement system and dis-
played on a logarithmic scale. The shown band) is selected. This signal can subse- played as a correlated PD pattern.
frequency spectrum was created over a quently be displayed as a phase correlated
period of 1 minute, considering the maxi- pattern on a conventional PD measure- A disadvantage of this broadband measu-
mum value. The largest distance between ment system that has been synchronised rement procedure is the often low distance
the upper and lower traces represents the with the test voltage. between the signal and noise because in
ideal test frequency. It might be helpful to the case of such measurement systems,
„
even narrow banded noises in the mea-
surement range result in a reduced sensi-
tivity. The advantages of the procedure are
The model assumption must be considered a comparatively easy technical feasibility
and the minimal set-up effort in compa-
as a highly simplified image of the real condi rison to the previously described narrow
tions inside a transformer, which may lead to band procedures.
Figure 8. UHF broad band measurement with fixed bandwidth (sample schematic depiction)
Figure 9. The unit under test and its representation in the localisation software, with sensors visible at the top and the three tap changer com-
partments highlighted in brown
Figure 10: Results obtained with initial sensor position (left) and after sensor rearrangement (middle - in hyperbolic view; right - in line view)
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 93
DIAGNOSIS
„ Received sensor
signals are processed
in order to obtain the
difference between the
signal arrival times at
each sensor
with modern analysis tools such as visual using the PDL 650, OMICRON electro-
isation of a 3D power transformer model. nics, Application Note ANP_12004_ENG,
www.omicron.at, 2013
[6] T. Bengtsson, M. Leijon, L. Ming, Acoustic
Bibliography Frequencies Emitted by Partial Discharges
in Oil, 8th International Symposium on High
[1] IEC 60270 (2000), High-voltage test Voltage Engineering, 1993, p.113-116
Figure 14: Detected PD sources with the trans- techniques - Partial discharge measu- [7] C.U. Große, H.W. Reinhardt, Schalle-
former in plain view rements, International Electrotechnical missionsquellen automatisch lokalisieren,
Commission, Publication 60270, 2000 MP Materialprüfung, Jahrg. 41, pp.342, Carl
[2] C57.127 (2007), IEEE Guide for the Hanser Verlag, München, Germany, 1999
Detection and Location of Acoustic Emis- [8] Wagenaars, P.A.A.F. Wouters, P.C.J.M.
Conclusion sions from Partial Discharges in Oil-Im- van der Wielen, E.F. Steennis, Algorithms
mersed Power Transformers and Reactors, for Arrival Time Estimation of Partial
This article describes the basic idea of the
The Institute of Electrical and Electronics Discharge Pulses in Cable Systems, IEEE
time based acoustical localisation of PD
Engineers, Inc. New York, USA, 2007 Vancouver, Canada, 2008
faults in power transformers and similar [3] E. Howells, E.T. Norton, Parameters [9] S. Coenen, S. Tenbohlen, S.M. Marka-
equipment. The PD signals are captured affecting the velocity of sound in trans- lous, T. Strehl, Sensitivity of UHF PD Mea-
using three or more piezoelectric acoustic former oil, IEEE Transactions on Power surements in Power Transformers, IEEE
sensors, which are magnetically mounted Apparatus and Systems, 1984 Trans. on Dielectrics and Electrical Insula-
on the tank. To localise the source, time [4] L.E. Lundgaard, Partial Discharge – tion, Vol 15, No. 6, pp. 1553-1558, 2008
delays between the recorded acoustic si- Part XIV: Acoustic Partial Discharge Detec- [10] A. Kraetge, K. Rethmeier, S.M. Hoek,
gnals or between an electrical signal and tion – Practical Application, IEEE El. Insu- M. Krueger, Modern de-noising strategies
the acoustic signals are used to obtain lation Magazine, Sep 1992, Vol 8, No. 5 for PD measurements on transformers
information about the propagation of [5] S.M. Hoek, B. Kästner, A. Kraetge, Int- under challenging on-site conditions,
the acoustic signal inside the transformer roduction to performing acoustic partial CIGRE SC A2&D1 Colloquium 2011,
tank and the distances between the signal discharge measurements and localisations Kyoto, Japan, Paper # PS1-O-14
source and sensors. The received sensor
signals are processed in order to obtain
the difference between the signal arrival
times at each sensor.
Authors
In addition to the acoustical measure- Stefan Hoek is Product Manager for partial discharge measu-
ment, a parallel electrical PD measure- rement system and he joined OMICRON electronics in 2008.
ment can be used to obtain an electrical He studied electrical engineering at the University of Stuttgart,
trigger signal. The combination of electri- Germany and received his PhD degree (Dr.-Ing.) form the In-
cal and acoustic measurement can impro- stitute of Energy Transmission and High Voltage Technology
ve the quality ensuring higher reliability, (IEH) in Stuttgart. His main research interests are detection and
accuracy and sensitivity of the measure- localisation of partial discharge in GIS, transformer or other as-
ment. This can be essential for the success sets with the help of measurements in the UHF range or with vibrio acoustic sensors.
of an accurate localisation. Alternative to He is member of VDE, ETG and the CIGRE working group B3.24 and joint working
the electrical measurement through the group A2/D1.51. He has published several papers regarding PD measurement, loca-
bushing taps or with external coupling lisation and noise suppression.
capacitors, unconventional measurement
techniques such as the UHF range can be Udo Ranninger started working for OMICRON electronics in
used to gain a trigger source for an acous 2007. Having held different positions, he now works as an Ap-
tic measurement. plication Engineer focusing on partial discharge measurements.
He graduated from the Institution of Higher Technical Educa-
The described case studies show that both tion in Rankweil, Austria in 2006, specialising on telecommuni-
approaches can lead to a successful PD cations and high frequency technology.
fault localisation, which is also facilitated
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 95