You are on page 1of 8

DIAGNOSIS

Acoustic localisation
of partial discharge in
power transformers
Practical experiences with and without the help of UHF measurement technology
Introduction
ABSTRACT
Detecting partial discharges in the insulation system of a power transformer The localisation of Partial Discharge (PD)
at an early stage reduces the risk of total breakdown. One method to detect faults in transformers is often necessary
partial discharges is acoustic measurement. With this technique detection and when such incipient faults are identified.
localisation of partial discharge is possible by placing acoustic sensors on the The measurement of partial dischar-
surface of the transformer tank. The low impact of electrical interferences from ge level in accordance with IEC 60270
outside the measurement set-up constitutes one of the strengths of the acous­ [1] is a procedure established throug-
tic method. A further advantage is the ability to identify the position of the par- hout the world for quality assurance of
tial discharge source, which is needed to estimate the risk and to enable a fast transformers and is performed as part of
and effective repair. The sensitivity and accuracy of the PD localisation can be the today routine measurements at the
improved with a combination with conventional electrical measurement or with manufacturer‘s factory. If the occurrence
Ultra High Frequency (UHF) measurement method. Since the UHF measure- of PD in the transformer has been deter-
ment method is more advantageous for measurement environments with heavy mined during such a measurement, it is
interferences in the field, the combination with acoustic localisation proves to a matter of urgency to localize the fault,
be useful even in challenging field situations. This article describes the applica- which is often very small, as quickly and
tion of this procedure illustrating it with different practical examples. accurately as possible. Similar applies to
transformers in the field. Here, PD detec-
tion and localisation procedures are gene-
KEYWORDS rally initiated as a result of corresponding
power transformer, partial discharge, acoustic localisation, electrical trigger, indications obtained from the Dissolved
UHF range Gas-in-oil Analysis (DGA) as well as from

88 TRANSFORMERS MAGAZINE | Volume 2, Issue 4



Stefan HOEK, Udo RANNINGER

PD monitoring. A precise localisation can


help to optimize the production of powe­r Detecting partial discharges in the in­
transformer or can help by an effective sulation system of a power transformer at an
maintenance during operation.
early stage reduces the risks of harm to the
An established procedure for localisatio­n insulation and transformer failure
of PD faults in transformers involves
acoustic localisation of the PD signals
using several piezoelectric sensors that are PD signals are very often superposed by wood, paper, steel, oil, etc). The sound
attached to the outside of the tank wall. A noise pulses, a fact that makes a PD data signal may reach the sensor from the
combination with conventional electrical analysis more difficult. The handling of PD source along various paths – of dif-
measurement or with UHF measurement disturbances on-site is one of the main ferent transmission speeds – as a result
method can improve the sensitivity and challenges when measuring PD. of reflection and refraction phenomena.
the accuracy of the PD localisation. Since Depending on sensor and PD location,
the Ultra High Frequency (UHF) measu- The propagation of acoustic multiple acoustic wave components of
rement method is more advantageous for signals in transformers the same PD event are potentially detec-
measurement environments with heavy ted by one sensor and overlay the signal
interferences in the field, the combinati- Partial discharges inside or on the sur- directly propagated through the oil as
on with acoustic localisation proves to be face of an insulation medium emit part illustrated in Figure 1.
useful even in challenging field situations. of the energy that they release as a sound
The application of this procedure is de- wave. At first, the sound wave propaga- The measurable signal directly propaga-
scribed in this article, also using different tes equally in energy in all directions, ted through the oil, which contains the
practical examples. while the propagation speed depends searched runtime information, depends
on the transmission medium and its re- on the intensity of the causative PD event
Partial discharge in spective temperature, as well as on the and on the damping on the propagation
high-voltage equipment sonic frequency in it. The amount of path. Therefore, the attenuation by inter-
the acoustic signal energy that is able nal parts like core, winding, transformer
Partial Discharges (PD), as defined by to reach the tank wall is determined to board, flux shielding, etc. should be as
IEC 60270 [1], are localized dielectric a large extent by the propagation paths low as possible. In this case the propaga-
discharges in a partial area of an electri- of the wave. The constructional structu- tion speed can be estimated close to the
cal insulation system under high electric res inside the transformer attenuate the speed of sound in oil (25 °C, 1400 m/s),
field intensity. PD are generally measured sound (low-pass); however, the attenu- so the search for sensor positions which
in picoCoulombs (pC). These discharges ation degree differs considerably bet- ensure that the propagation path is main-


can harm the insulation and might lead to ween the various materials (pressboard, ly through oil and a good signal quality is
a total destruction of the asset over time.
To prevent such a sudden breakdown and
carry out pre-emptive repairs, PD can be
measured and evaluated.
The combination of UHF measurement
with acoustic localisation proves to be useful
PD measurements are a worldwide accept­
ed tool for quality control of high voltage
even in environments with heavy interfer­
apparatus. Outside screened laboratories ences in the field

Figure 1. Possible propagation paths of the acoustic PD signal (direct oil-path, steel-wave path and reflection path)

w w w . t ra n sfo r m e r s - m a g a z i n e . co m 89
DIAGNOSIS

with the internal structure of the transfor-


mer and experience in performing such
measurements are advantages here.

With regard to the localisation and the


visualisation of the obtained results, a di-
stinction can be made between measure-
ments with an acoustic and with an electric
trigger. In the first case, an acoustic sensor
is used to determine the reference point in
time. In such a case, only the time offset
(Δt1,2,n) between the sensors is available
for calculation, which leads to an equa-
tion system based on the time difference
approach. In addition to the pure acoustic
method, the information on the electrical
detected PD impulse can be used as time


Figure 2. Principle of acoustic PD localisation with external sensors reference for the acoustic measurement
since the electrical propagation speed is
significantly higher (by a factor of about
Searching for sensor positions which en­ 100,000). Naturally, this requires a precise
synchronisation between a PD detector
sure that the propagation path is mainly and the localisation system. In such a case,
through oil and a good signal quality are es­ the equation system used for localisation
sential during the measurement procedure is based on the absolute time approach.
Figure 3 represents the available times for
both procedures respectively; however,
for the sake of simplicity only two acoustic
essential during the measurement proce- signal runtimes measured, using the speed sensors are shown.
dure. The knowledge of the transformer of sound and the known geometrical posi-
inner structure could be helpful for good tions of the sensors on the tank wall. The runtime t1 of a single, electrically trig-
positioning and repositioning of the sen- gered sensor (see Figure 4, left) produces
sors. Exact determination of the signal start a sphere around the sensor position. The
time is particularly important. Reliable spherical radius can be derived from the
Runtime-based localisation determination of the starting point of the product of the sound velocity and the
of PD sources signal is usually only possible if there is measured runtime. Every point on the
an adequate signal quality. Positioning of surface of the spherical surface may repre-
The localisation of PD sources is perfor- the sensors with good contact is therefore sent a theoretical PD fault location inside
med by means of the differences in the very important in choosing locations on the tank.
runtime of the acoustic signal between the the wall at which the measurements can
fault location and various sensors. Possi- be taken with a good signal-to-noise ra- In case of a purely acoustic measurement,


ble fault locations are calculated from the tio and low signal attenuation. Familiarity the signal of a single sensor provides too

Possible fault loca­


tions are calculated
from the measured
sig­nal runtimes, using
the sound speed and
the established geo­
metrical positions of
the sensors on the
tank wall

Figure 3. Absolute and relative time values for the acoustic sensors

90 TRANSFORMERS MAGAZINE | Volume 2, Issue 4


Figure 4. Possible positions of a PD source for an electrically triggered sensor (left) and with a purely acoustic measurement using two sensors (right)

littl­e information for a reliable detection. ing previously, and subsequently form Since the above-described method is
Only when a second sensor is used, the circular lines, as an example. based on the assumption of a direct
time difference Δt1,2 can be calculated. In acoustic propagation path with a defined
this case the PD source can be located on The spatial coordinates of the PD source sound velocity between the PD source
a hyperbolic plane between the sensors, as can be estimated, if the ring-shaped lines and the sensor, it is not always possible to
shown in the right-hand section of Figure 4. intersect in one point, as shown in Figure localise precisely the source in practice.
5, by using three acoustic sensors and an The model assumption must be conside-
The significance of the results generally electrical trigger. In the case of pure acou- red as a highly simplified image of the real
increases with the increasing number of stic measurement, additional surfaces, conditions inside a transformer and as a
sensors, as the number of possible solu- which overlap each other, are analogous- result, inaccuracies during the localisa-
tions is reduced. This is based on the fact ly formed, and their intersections may in tion may occur. It has therefore become


that the surfaces respectively related to ad- turn be potential locations of the acoustic common practice to optimise the position
ditional sensors overlap with those exist­ source and thus of the PD fault. of the sensors on the tank wall iteratively.
Here, the aim of positioning the sensors is
to find the optimal sound path between
The significance of the results generally the source and sensor.
increases with the increasing number of Currently utilized UHF pro-
sensors, as the number of possible solu­ cedures for PD measure-
tions is reduced ment
Mainly two different types of UHF
m­ethods are applied:

• Tuned UHF measurement with variable


centre frequency
• UHF broad band measurement with
fixed bandwidth

UHF measurement with


tuned test frequency
The principle of the tuned UHF narrow
band measurement with variable centre
frequency is shown in Figure 6. The UHF
signal, which is measured by an anten-
na type sensor, gets amplified and is dis-
played on a spectrum analyser.

Figure 5. Pinpoint localisation of the PD location by intersection of three ring-shaped lines

w w w . t ra n sfo r m e r s - m a g a z i n e . co m 91
DIAGNOSIS

„ Combination of
different detection
met­hods provides a
system adaptable to
the respective require­
ments.

UHF broadband measure-


ment
Figure 6. Example of a tuned UHF narrow band measurement with variable centre frequency The UHF broadband measurement with
fixed band width is often used in monitor­
ing systems.

In Figure 7, the display of a spectrum feed an impulse via a second UHF sen- Figure 8 shows a schematic depiction of
analyser for the measurement range from sor prior to the measurement in order to PD signal spectrum that has been measur­
0.1 GHz to 1.8 GHz is shown. The lower identify frequency ranges that are suitable ed across a bandwidth of several hundred
trace of the spectrum shows the noise for a highly sensitive measurement. MHz.
floor including the constantly active ex-
ternal signals. The upper trace shows the When this range has been established, the The envelope curve of the amplitude sig-
combination of PD signals and sporadic centre frequency is adjusted accordingly nal of the broad band measurement with
external interferences. With the frequen- and the bandwidth of e.g. 3 MHz (tuned fixed bandwidth is transferred directly
cy linearly depicted, the amplitude is dis- narrow band) or higher (tuned medium to the PD measurement system and dis-
played on a logarithmic scale. The shown band) is selected. This signal can subse- played as a correlated PD pattern.
frequency spectrum was created over a quently be displayed as a phase correlated
period of 1 minute, considering the maxi- pattern on a conventional PD measure- A disadvantage of this broadband measu-
mum value. The largest distance between ment system that has been synchronised rement procedure is the often low distance
the upper and lower traces represents the with the test voltage. between the signal and noise because in
ideal test frequency. It might be helpful to the case of such measurement systems,


even narrow banded noises in the mea-
surement range result in a reduced sensi-
tivity. The advantages of the procedure are
The model assumption must be considered a comparatively easy technical feasibility
and the minimal set-up effort in compa-
as a highly simplified image of the real condi­ rison to the previously described narrow
t­ions inside a transformer, which may lead to band procedures.

inaccur­acies during the localisation Combination of different detection


m­ethods provides a system adaptable to
the respective requirements. On the one
hand, it allows an easy and fast perfor-
mance of measurement under basic con-
ditions with a relatively low set-up effort.
In the environment with interferences, the
adjustable test frequency can ensure high-
ly sensitive measurements.

Example 1: Measuring ex-


ample of a pure acoustic PD
location
A 500 MVA power transformer showed a
sig­nificant increase of hydrogen (H2) and
methane (CH4) a few months after instal-
lation, which are typical key gasses for PD
Figure 7. Spectrum of the measured signal at the UHF sensor (exemplary schematic depiction) activity. A pure acoustic measurement was

92 TRANSFORMERS MAGAZINE | Volume 2, Issue 4


„ Detection of acous­
tic signals on the
tank wall can be im­
peded by magnet­
ic shunts which are
known to have a sig­
nificant sound damp­
ing effect

Figure 8. UHF broad band measurement with fixed bandwidth (sample schematic depiction)

Figure 9. The unit under test and its representation in the localisation software, with sensors visible at the top and the three tap changer com-
partments highlighted in brown

Figure 10: Results obtained with initial sensor position (left) and after sensor rearrangement (middle - in hyperbolic view; right - in line view)

w w w . t ra n sfo r m e r s - m a g a z i n e . co m 93
DIAGNOSIS

„ Received sensor
sig­nals are processed
in order to obtain the
difference between the
signal arrival times at
each sensor

fre­quency was selected based on the eva-


luation of the frequency spectrum, so the
Figure 11: Synchronous UHF (above) and conventional (below) measurement on the UHF measurement was performed with a
defect transformer with the MPD-System narrow band filter, using a bandwidth of 1.5
MHz and a centre frequency of 159.5 MHz.

The 3D transformer model (including


windings, bushings and the tap changer)
and the acoustic sensors of the PD lo-
cation system can be seen in Figure 13,
which also illustrates the position of the
UHF sensor and the conventional measu-
rement at the bushing tap.

The UHF signals were used as an electrical


trigger for the acoustic fault localisation.
The measured values of the acoustic system
Figure 12: UHF frequency sweep of the measurement signal at the UHF sensor with the showed a potential fault between the tap
MPD 600 together with the UHF 620. Measurement frequency at 159.5 MHz (see grey bar) changer and its close winding (Figure 14).

After opening the transformer, the mea-



erformed, using PD localisation system sulation elements which have been repla- sured source location could be confirmed
PDL 650. Figure 9 shows the transformer ced. The transformer has been put back and repaired.
and its modelling in the localisation software. into service and is now operating without
any indication of remaining PD activity.
During the initial PD location, electrical The gas concentration remains stable.
triggering could not be utilised. Further-
more, detection of acoustic signals on Example 2: Measuring ex-
the tank wall was not possible, presuma- ample of an acoustic PD
bly due to the magnetic shunts which are localisation with UHF trig-
known to have a significant sound dam-
ping effect. Thus, the acoustic sensors had
gering
to be attached on top of the transformer.
The second measurement was performed
The measured results with the initial at a 230 kV/20 kV transformer with a no-
sensor arrangement indicated a PD loca- minal power of 100 MVA. In this case, the
tion at the middle phase, close to the tap UHF measurement and the conventional
changer and 220 kV bushing (see Figure electric measurement were performed pa-
10, left). After the rearrangement of the rallel with an MPD 600 and an UHF 620
sensors closer to the expected PD spot, an converter. The phase-separated discharge
improved signal quality and higher sound pattern of both signals is shown in Figure
levels were achieved. The resulting sur- 11. Here, the signals of both electric and
faces representing the mathematical so- UHF measurement would be suitable as
lutions of the localising equations can be the trigger signal.
seen on the right-hand side of Figure 10,
confirming the initial expectation about The frequency spectrum (Figure 12)
the PD location. An internal inspection shows potentially good measuring ran- Figure 13: Measurement set-up, including UHF
of the tap changer connection through a ges from 130  MHz to 160  MHz and sensor, electric coupling at the bushing tap,
man-hole revealed defects of different in- from 300  MHz to 450  MHz. The centre and acoustic PD localisation system

94 TRANSFORMERS MAGAZINE | Volume 2, Issue 4


„ Both described approaches can lead
to a successful PD fault localisation while
modern analysis tools, such as visual­
isation of a 3D power transformer model,
facilitate the localisation of PD faults

with modern analysis tools such as visual­ using the PDL  650, OMICRON electro-
isation of a 3D power transformer model. nics, Application Note ANP_12004_ENG,
www.omicron.at, 2013
[6] T. Bengtsson, M. Leijon, L. Ming, Acoustic
Bibliography Frequencies Emitted by Partial Discharges
in Oil, 8th International Symposium on High
[1] IEC  60270 (2000), High-voltage test Voltage Engineering, 1993, p.113-116
Figure 14: Detected PD sources with the trans- techniques - Partial discharge measu- [7] C.U. Große, H.W. Reinhardt, Schalle-
former in plain view rements, International Electrotechnical missionsquellen automatisch lokalisieren,
Commission, Publication 60270, 2000 MP Materialprüfung, Jahrg. 41, pp.342, Carl
[2] C57.127 (2007), IEEE Guide for the Hanser Verlag, München, Germany, 1999
Detection and Location of Acoustic Emis- [8] Wagenaars, P.A.A.F. Wouters, P.C.J.M.
Conclusion sions from Partial Discharges in Oil-Im- van der Wielen, E.F. Steennis,  Algorithms
mersed Power Transformers and Reactors, for Arrival Time Estimation of Partial
This article describes the basic idea of the
The Institute of Electrical and Electronics Discharge Pulses in Cable Systems, IEEE
time based acoustical localisation of PD
Engineers, Inc. New York, USA, 2007 Vancouver, Canada, 2008
faults in power transformers and similar [3] E. Howells,  E.T. Norton, Parameters [9] S. Coenen, S. Tenbohlen, S.M. Marka-
equipment. The PD signals are captured affecting the velocity of sound in trans- lous, T. Strehl, Sensitivity of UHF PD Mea-
using three or more piezoelectric acoustic former oil, IEEE Transactions on Power surements in Power Transformers, IEEE
sensors, which are magnetically mounted Apparatus and Systems, 1984 Trans. on Dielectrics and Electrical Insula-
on the tank. To localise the source, time [4] L.E. Lundgaard,  Partial Discharge – tion, Vol 15, No. 6, pp. 1553-1558, 2008
delays between the recorded acoustic si- Part XIV: Acoustic Partial Discharge Detec- [10] A. Kraetge, K. Rethmeier, S.M. Hoek,
gnals or between an electrical signal and tion – Practical Application, IEEE El. Insu- M. Krueger, Modern de-noising strategies
the acoustic signals are used to obtain lation Magazine, Sep 1992, Vol 8, No. 5 for PD measurements on transformers
information about the propagation of [5] S.M. Hoek, B. Kästner, A. Kraetge, Int- under challenging on-site conditions,
the acoustic signal inside the transformer roduction to performing acoustic partial CIGRE SC A2&D1 Colloquium 2011,
tank and the distances between the signal discharge measurements and localisations Kyoto, Japan, Paper # PS1-O-14
source and sensors. The received sensor
signals are processed in order to obtain
the difference between the signal arrival
times at each sensor.
Authors
In addition to the acoustical measure- Stefan Hoek is Product Manager for partial discharge measu-
ment, a parallel electrical PD measure- rement system and he joined OMICRON electronics in 2008.
ment can be used to obtain an electrical He studied electrical engineering at the University of Stuttgart,
trigger signal. The combination of electri- Germany and received his PhD degree (Dr.-Ing.) form the In-
cal and acoustic measurement can impro- stitute of Energy Transmission and High Voltage Technology
ve the quality ensuring higher reliability, (IEH) in Stuttgart. His main research interests are detection and
accuracy and sensitivity of the measure- localisation of partial discharge in GIS, transformer or other as-
ment. This can be essential for the success sets with the help of measurements in the UHF range or with vibrio acoustic sensors.
of an accurate localisation. Alternative to He is member of VDE, ETG and the CIGRE working group B3.24 and joint working
the electrical measurement through the group A2/D1.51. He has published several papers regarding PD measurement, loca-
bushing taps or with external coupling lisation and noise suppression.
capacitors, unconventional measurement
techniques such as the UHF range can be Udo Ranninger started working for OMICRON electronics in
used to gain a trigger source for an acous­ 2007. Having held different positions, he now works as an Ap-
tic measurement. plication Engineer focusing on partial discharge measurements.
He graduated from the Institution of Higher Technical Educa-
The described case studies show that both tion in Rankweil, Austria in 2006, specialising on telecommuni-
approaches can lead to a successful PD cations and high frequency technology.
fault localisation, which is also facilitated

w w w . t ra n sfo r m e r s - m a g a z i n e . co m 95

You might also like