Professional Documents
Culture Documents
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2019.2892598, IEEE
Transactions on Power Systems
0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2019.2892598, IEEE
Transactions on Power Systems
coincides with the nose point of the PV curve (as shown in Fig. Voltage instability in cases 3 and 4 occurs due to exiting
2). Fig. 3 shows the voltage response of buses 3 and 5 when from the attraction region of the steady state power at bus 5.
voltage instability occurs. In all figures, the solid and dotted Exiting from the attraction region and the rule of the tap changer
curves are related to buses 3 and 5, respectively. As it can be of transmission transformers at voltage instability in
observed, initially, voltage instability at bus 3 occurs. Then, distribution network are the most important reasons for
along with voltage decrease at bus 3, the voltage of bus 5 also necessity to whole system modelling. They can be explained
becomes unstable. In this case, voltage stability assessment can using Fig. 5. To more illustration, the PV curves have been
be done using static analysis with replacement of distribution drawn for the primary side of the distribution transformer (bus
network by a suitable load model. 4). These curves are related to before and after contingency. In
this Fig., the x-axis is the active power following through the
TABLE I distribution transformer and the y-axis is the voltage magnitude
The Impedance of Lines and Transformers
at bus 4. It is assumed that the distribution transformer is ideal
Impedance (p.u.) and its impedance has been added to the distribution network.
Case Transmission Distribution Transmission Distribution This causes that two sides of distribution transformer have the
Number Line Line Transformer Transformer
same loadability limits. Due to tap changer operation, the load
1 0.005+j0.025 0.01+j0.02 j0.03 j0.04
2 0.004+j0.02 0.03+j0.07 j0.0358 j0.08 seen from the primary side of the distribution transformer is of
3 0.003+j0.02 0.02+j0.05 j0.03 j0.08 constant power type that has shown by the vertical line P0. It is
4 0.003+j0.02 0.021+j0.05 j0.03 j0.08 assumed that the variable tap is on the low voltage side. Point
5 0.005+j0.025 0.01+j0.02 j0.03 j0.04 A indicates the steady state operating point before contingency.
Dashed curves show the load transient characteristics seen from
the primary of the distribution transformer. These
characteristics vary when the tap ratio changes.
The first condition of stability is that the steady state load
power be within the post-contingency loadability limit. The
second condition is to lie the post-contingency system
trajectory in the attraction region of the steady state operating
point. This region has been shown in bold in Fig. 5 (the region
Fig. 2. The PV curves in different cases. specified by OAB in the PV curve named by Pre-contingency).
If the load characteristic intersects with the PV curves at the
attraction region, the intersection point moves to the steady
state operating point and the system becomes stable, otherwise
the voltage will collapse.
0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2019.2892598, IEEE
Transactions on Power Systems
IV. REFERENCES
[1] Andersson, Göran, Peter Donalek, Richard Farmer, Nikos Hatziargyriou,
Innocent Kamwa, Prabhashankar Kundur, Nelson Martins et al. "Causes
of the 2003 major grid blackouts in North America and Europe, and
recommended means to improve system dynamic performance." IEEE
Fig. 7. The voltage response of buses 3 and 5 in case 4. Transactions on Power Systems 20, no. 4 (2005): 1922-1928.
[2] Singhal, Ankit, and Venkataramana Ajjarapu. "Long-term voltage
Case 5 compares voltage responses when the permissible stability assessment of an integrated transmission distribution system."
range for tap values is changed from a limited range (from 0.907 In Power Symposium (NAPS), 2017 North American, pp. 1-6. IEEE,
2017.
to 1.093 p.u.) to an extended range (from 0.8 to 1.2p.u.). As [3] Li, Zhengshuo, Qinglai Guo, Hongbin Sun, and Jianhui Wang. "Impact of
shown in Fig. 8, in this case, limitation on tap changes causes coupled transmission-distribution on static voltage stability
voltage instability. Because, in this case, the tap value in the assessment." IEEE Transactions on Power Systems 32, no. 4 (2017):
3311-3312.
transmission transformer reaches its limits sooner than that in [4] Karbalaei, Farid, Ataollah Abedinzadeh, and Mehran Kavyani. "The
the distribution one. In this condition, the voltage at bus 3 Necessity for Considering Distribution Systems in Voltage Stability
cannot be controlled any more. This causes the loadability limit Studies." International Journal of Electronics Communications and
Electrical Engineering 3, (2013): 85-95.
at bus 5 to decrease. Detecting which taps first reach their limits
needs time-domain simulation with simultaneous modelling of
transmission and distribution networks.
0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.