Professional Documents
Culture Documents
Source: https://www.contractormag.com
The AVB must be installed with its critical level a minimum of six inches above
the highest downstream usage; and
An AVB must not be subjected to backpressure. This valve allows air into the
system to stop a siphon with a water pressure loss. The device cannot determine
the water's direction of flow, as long as water pressure holds the valve closed to
atmosphere. Therefore, elevated piping, auxiliary sources of water and pressure
pumps, for example, are not permitted downstream; and
AVBs must be installed upright. The valve that allows air into the downstream
piping relies on gravity to function properly. If the device is installed out of plumb,
the valve may not fully open.
Source: http://forms.iapmo.org
The spring-loaded check valve does not allow drainage of water from between
the hose bibb and the upper part of the HVB; thus, freeze protection must be provided,
just as all outdoor plumbing would need to be protected under freezing conditions.
HVBs should be inspected and tested periodically to ensure they are working
properly. Fortunately, their mode of operation permits inspections to be easily made.
Verify the check valve closes and the atmospheric vent opens reliably whenever the
water supply is shut off. It is very simple to do this if a nozzle that can be shut off is used
on the end of the hose. When the nozzle shuts off, turn on the faucet and allow the hose
to pressurize. Then, shut off the faucet while the hose is pressurized. After a few
seconds, the hose pressure should be released in a small spray as the atmospheric
vent suddenly opens.
Double Check Valve Assembly
Source: http://forms.iapmo.org
The double check valve assembly is suitable for prevention of back pressure and
back siphonage, but is not suitable for high hazard applications. It is commonly used on
lawn irrigation, fire sprinkler and combi-boiler systems. If the hazard is higher, even a
relatively low hazard such as using antifreeze in the fire sprinkler system, then a more
reliable check valve such as a reduced pressure zone device may be mandated.
The pressure type vacuum breaker evolved from the AVB. There are a number of
AVB installation restrictions due to the limits of the design. One of the AVB's limitations
is the restriction of no continuous water pressure. The concern of the inlet valve sticking
closed is a serious one, as it would render the AVB useless. The PVB was designed to
overcome this problem.
Source: http://forms.iapmo.org
The AVB has one moving part that works as an air inlet or port and it serves as a
check valve to the supply piping when no water pressure is present. The PVB check
valve is similar but spring loaded. When the piping-system pressure is reduced, the
spring forces the check open to the atmosphere, allowing air into the system and
breaking the downstream siphon.
PVBs, therefore, are designed to operate under pressure for long periods of time
without becoming inoperative. The internal check valves are spring-loaded so that any
tendency for the valve to stick closed due to long periods of applied pressure and
consequent fouling will be counteracted.
The continuous pressure restriction would no longer apply and would allow
valves downstream and water pressure 24 hours per day. This type of assembly may be
used only where outlet pressure will never exceed inlet pressure and is not subject to
backpressure. This device may be installed indoors only if provisions for spillage from
the dome are provided. They must be installed a minimum of 12 inches above the
highest piping downstream of the PVB.
Source: http://forms.iapmo.org
The pressure vacuum breaker requires that both the check valve and air inlet act
independently, but the components of the SVB are not required to be independent of
each other. During operation (flow), the diaphragm at the bottom of the valve chamber
allows the poppet to close before the internal check valve opens, preventing most of the
spillage that normally occurs with a PVB. In this way, the air inlet can be closed as the
check is closed again, eliminating the spill (see Figure D). The SVB provides the same
type of protection as the PVB and can only be used where the PVB can be used.
When it comes to the potable water supply that the public utilizes, safety is the
first priority. Vacuum breakers play an important part in that effort, and understanding
when and where to use them and how they work can help maintain the highest level of
safety.
Source: http://forms.iapmo.org
The name of this assembly is derived from a zone of reduced pressure needed
for the operation of the relief or vent valve. This device is an assembly of two internally
loaded, specially designed and independently operating check valves that have a relief
valve installed between the primary valves, specifically designed to maintain a zone of
relative differential pressure between the two check valves unless one or both of the
check valves are fouled. This assembly has a tightly closing upstream and a tightly
closing downstream shutoff valve.
As water flows through the first check valve, a pressure drop is created. The
assembly's relief valve determines if the supply pressure is greater and will remain
closed; if the difference in pressure between the supply and zone is reduced, the relief
valve will open. With a loss of supply pressure and both checks closing, the relief valve
will open to maintain a minimum pressure of two psi less than the supply pressure of the
fluid in the zone and downstream line. If there is a complete loss of supply pressure, the
pressure between the two check valves will become atmospheric because the spring
has opened the relief valve.
An RP's relief valve has the potential to discharge a significant amount of water.
Care should be taken as to its location and provision for indirect drainage. The drainage
piping should be sized adequately to take the full discharge of the system. Always refer
to the manufacturer's installation requirements.