Professional Documents
Culture Documents
2014
over the study period. Therefore, the original frequency in the adequate for the assessments of production costs. In order to
5600MW load level is 1/24. Similarly, the whole corresponding reflect more chronological load characteristics and get a more
load frequency curve can be induced shown in figure 2. The FD reasonable result, the load frequency curve is extended to the
method reflects part of timing information through load interval frequency distribution and interval frequency
frequency curve and evaluates the relationship between distribution series in this paper, which involves both the
conventional unit operation and this frequency information. frequency information and timing distribution of load
For instance, if the loading position of the thermal unit is in the fluctuation.
very load level of 5600MW. Before 8h, this generator is in
B. Interval Frequency Distribution
offline state or hot standby, and it turns into working mode after
8h, which indicates that one upward transfer corresponds to one When scanning the load curve, not only the number of
start-up operation. Consequently, the frequency information is upward transfers is accumulated, but also every transfer
the important basis to judge the operation of conventional moment is recorded including both upward and downward.
generators. By subtracting the original load from the wind Set the time interval between two adjacent upward transfers
power output, the net load curve can be obtained as the as one time unit and then calculate the corresponding
consideration of effects of intermittent wind energy. It can be downward interval and upward interval, respectively noted as n
seen easily that the net load fluctuates more wildly than the and m. m represents the upward duration in that time unit, and n
original one and the frequency curve also varies greatly in the means the downward duration.
quantity and load distribution area. For the discretization, assume that the time step is 1h and the
load step is 1MW, the interval-frequency distribution for the
7000
load level k can be illustrated as two-dimensional array.
6000
k
x[k][m][ n ] a mn (2.1)
5000 M N
k
4000
amn indicates the time unit of k load level, which upward
3000 original load
wind power
interval is m and downward interval is n. It reflects the time
2000
net load
interval frequency distribution of the load level k in the study
1000 period T. Dimension M is the maximum downward interval and
0
the dimension N is the maximum upward interval. For every
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
t /h load level in the study period, the last transfer is dealt with the
Fig.1 Chronological original load, net load and wind output curve first one to be included in the array.
All the load level within the scope of study can form the
0.16
net load corresponding interval-frequency distribution. Hence the whole
0.14 original load
interval-frequency distribution series can be expressed as a
0.12 three dimensional matrix composed of the two-dimensional
0.1 arrays of each load level:
0.08 X xk mn K M N
(2.2)
0.06
Plotted in dimensional coordinate, each time unit is
represented by (m, n, xk mn ) to be more visual. Figure 3
0.04
0.02
illustrates the interval frequency distribution series for load
level x.
0
0 1000 2000 3000 4000 5000 6000 7000 8000
x /M W
Without doubts, the sum of xk mn in all time units in each Where X [iK 1][ M ][N] xik mn1 is the i 1th effective
load level is exactly equal to the corresponding value in the K M N
frequency curve and the whole interval is the same as the study interval frequency distribution series.
time period T. In other words, this two-dimensional array After convolution, equivalent time unit of each load level
should be satisfied with the following conditions: which contains both the frequency information and time
M N distribution of load fluctuation can be derived. Depending on
k
amn f (k) this information, production costs and reliability analysis can
m 1 n 1 be evaluated more precisely.
(2.3)
M N
B. Frequency of Start-up operation
(m n) a k
mn T
m 1 n 1 Load transition can reflect the demand for generator unit
The interval frequency distribution series are just an start-up and shut-down, but due to the actual operation which is
extension of load frequency curve. It will not only contain all constrained by minimum up-time time or minimum down-time
the information of load frequency curve, but also reflect the time limits, ramping rate restriction, generator scheduling, and
temporal fluctuation time distribution information to a certain other factors [11-15], it is an extremely complex decisions for
extent. Therefore, the interval frequency distribution series can the times of start-up and shut-down operation. This paper just
restore into the original frequency curve. refers to the timing distribution information of each time unit to
make an overall evaluation.
Only both when the duration of the load upward transfer is
III. THEORY greater than the minimum up-time limit, and when the duration
of the load downward transfer is greater than the minimum
A. EIFDs with Two State Unit
down-time limit, the demand of relative operations can be
In a manner analogous to the derivation of Effective Load responded.
Duration Curve (ELDCs) in Baleriaux-Both costing [3], the FD The EIFDs can then be integrated in the loading point to
method, is considering the effect of the generator random
failure as recursive frequency curve. The equivalent transition derive the expected times of start-up operation. Since X [ik ][ m ][ n ]
frequency [18] is made up of two independent contributions, is an effective interval frequency distribution series, it must be
the first one due to transition of load, and second one due to a premultiplied by the availability pi , we have:
unit switching between states. M N
Fi start pi xJi i 11mn (3.3)
( i 1) ( i 1)
F ( x Ci ) F ( x) m i
mmin n i
nmin
fi (x) pi fi 1 (x) qi fi 1 (x Ci ) i i
i
Where m min and n min is respectively the minimum up-time
(3.1) and minimum down-time time limits for the i th unit.
Where fi (x) is the i th
effective load frequency curve, qi For the base-load units than which the load always stays
and pi are respectively the availability and the FOR of the ith greater, there is no upward load transition at their loading point.
Hence the load transition component of the expected start-up
unit, pi 1 qi . i is the mean cycle time and 1 i represents frequency would be zero.
the frequency the units switch between up and down state. To give a comprehensive evaluation of the impact of wind
F (i 1) ( x Ci ) F (i 1) ( x ) power to the conventional generating units, the frequency of
The second term may be negligible generator start-up of unit capacity (FGSUC) [17] is adopted to
i
reflect the frequency of start-up operation per unit capacity.
if units are quite reliable [6]. Data from the IAEA database on
thermal unit reliability suggests that the mean time between n
1 start
n
1 M N
Ci Fi Ci pi xJi i 11mn
unexpected failures of modern thermal units is of the order of T i 1 T m mmin
i
nimin
I FGSUC i 1 n
(3.4)
2000hrs. If all units have a similar failure rate, the total cycling n n
costs of bringing the station to its operating temperature. In induced to explore the proportion of the dynamic costs of
addition, costs are incurred if units are kept on hot standby unsatisfied time units in the whole dynamic costs.
[6-9]. Cd ' Cd
Cd CTSU CBSU (3.5) I STIDC (3.9)
Cd '
Where CTSU is turbine start-up cost and CBSU is boiler '
Where Cd is the dynamic cost considering all the time units,
start-up cost.
The costs for the first part are more or less constant between that is to say the times of star-up and
M N
different start-up conditions. For models which represent
thermal units individually, the total turbine start-up costs
shut-down Fi
start
pi xJi i 11mn , which is equal to one in
m 1n 1
associated with the ith unit over a period T is just the multiply FD method theoretically.
of the unit start-up cost and the corresponding times of start-up Similarly, the short time interval proportion of unit capacity
operation. (STIPUC) is proposed to reflect the proportion of short time
I
interval per unit capacity.
CTSU i
pi Ci cTSU Fi start (3.6) i i
i 1 n
1 start
n
1 mmin nmin i 1
Ci Fi Ci p x
i
Where cTSU is start-up cost per unit capacity per start-up of 1 T i 1 T i m 1 n 1 Ji 1mn
I STIPUC i
(3.10)
ith unit start-up, I is total number of generating units. n n
Ci Ci
The second component of plant start-up costs is that i 1 i 1
associated with bringing units to operating temperature. The
cost will depend upon the time for which units have been
offline. If the unit is allowed to cool after off-loading, the heat IV. SAMPLE COMPUTATION
will decay approximately exponentially with a time constant i .
b
1 1200 2 0.132
2 600 2 0.153 35 10 12 7 5
3 400 3 0.119 35 10 12 7 5
4 200 4 0.082 30 10 8 5 3
5 800 2 0.171 35 10 12 7 5
6 200 3 0.082 30 10 8 5 3
7 50 20 0.120 20 3 3 2 1
capacity of wind power is shown in figure 5. According to the
A. Interval Frequency Distribution and Restored Frequency
proposed method in section 2.2, take 50 MW as the load step
Curve
and scan the whole net load sequence to get the original interval
Based on the principle of priority acceptance of wind power, frequency distribution series.
the forecast of wind power output is regarded as a negative load
adding to the original load. The net load with 1000MW
8000 0.06
The FD method
The proposed method
7000 0.05
0.04
6000
0.03
5000
0.02
4000 X: 61
Y: 0.01111
0.01
3000
0
0 50 100 150 200 250 300 350
2000
0 100 200 300 400 500 600 700 x /MW
t /h
Fig. 7 The original frequency curve
Fig. 5 The net load with 1000MW capacity wind power
Figure 8 presents the final frequency curve together with the
Take the example in the 3050MW load level shown in figure one through FD method. The final frequency which is restored
6. The interval frequency distribution contains 8 time units from the interval frequency distribution series coincides exactly
k
amn , (19,2,1), (19,5,1), (21,4,1), (22,4,1), (69,2,1) , (70,2,1), with the results in FD method once again. In conclusion, the
(117,6,1) and (354,4,1). The transition frequency is interval frequency distribution series contains all the frequency
8 information and can be restored accurately to the frequency
0.0111 .
720 curve.
Restore the distribution series into the frequency curve and 0.045
compare with the one in FD method. Figure 7 gives the original The FD method
0.04 The proposed method
frequency curve using these two methods. It can be seen that
these two curves are overlapped exactly. And for the 3050MW 0.035
load point, the times of upward transfer is also equal to 0.0111. 0.03
0.025
0.02
0.015
1.5 0.01
0.005
1
0
0 50 100 150 200 250 300 350
x /MW
Take the example of the 6th generator unit. The generator unit
0 starts with the load at 4000MW load level and the minimum
10
9
8 400
up-time and down-time limit for this generator unit are 7hrs and
7
6
5 250
300
350
5 hrs. Figure 9 gives the equivalent interval frequency
4 200
3
2 100
150 distribution series at 4000MW load level after loading the form
1 50
Downward intervel n /h 0 0
Upward intervel m /h 5 generator units. Without doubts, the total interval frequency
distribution series are increasing dramatically after
Fig. 6 The interval frequency distribution for load level 3050MW
implementing wind power. At the same time, the number of
unsatisfied time units is also growing. This suggests that the
volatility of wind power brings both more demands for
operations and a lot of impractical situations. Thus it’s quiet
necessary to eliminate the influence of the demand for this part
of the start-up and shut-down in the assessment of dynamic
costs.
0.5
0
24
22
20
18 680720
16 600 640
14 520560
12
10 400440480
360
8
6 280320
4 200240
2 120160
0 0 40 80
Downward intervel n /h Upward intervel m /h
Fig.9 Equivalent interval frequency distribution at 4000MW with and without wind power
Method Scenario Turbine cost/(105$) Boiler cost/(106$) Total dynamic cost/(106$) IFGSUC ISTIPUC
Case 1 4.39591 1.05073 1.49032 6.168 0.798
The EIFDs method
Case 0 4.26236 1.06736 1.49359 6.358 0.275
Case 1 8.17011 2.17086 2.95787 11.183
The FD method
Case 0 6.84833 1.85684 2.54167 9.725
Considering all the time units Case 1 8.17011 1.64924 2.46625 11.183
Eliminating the short time interval means that some
corresponding generating units in the short time unit need to V. CONCLUSION
keep on hot standby, which will produce some more costs. The This paper extends the load frequency curve into the interval
short time interval dynamic cost (STIDC) is induced to reflect frequency distribution series which contains both the load
this part information. fluctuation frequency information and timing distribution
Cd ' Cd 2.46625 1.49032 information. Based on this series, the EIFDs method has been
ISTIDC = =39.57% (4.1)
Cd ' 2.46625 described to evaluate the frequency of start-up and shut-down
operation and get a more reasonable assessment of dynamic